ZR-YJV 3x240mm²+1x120mm² XLPE Copper Cable 0.6/1kV Flame Retardant
Product Summary
Product Details
zr-yjv copper xlpe cable
,zr-yjv xlpe copper cable
,1kv copper xlpe cable
Product Description
ZR-YJV 3x240mm²+1x120mm² XLPE Copper Cable 0.6/1kV Flame Retardant
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
3×240 mm² + 1×120 mm² |
Three phase cores of 240 mm² + one neutral core of 120 mm² copper conductor |
Construction: Three 240 mm² copper conductors (phase) + one 120 mm² copper conductor (neutral), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).
ZR-YJV 3×240+1×120 mm² — Cable Specification & Engineering Data
1. Product Identity & Ratings. A heavy-duty flame-retardant 3+1-core low-voltage cable, ZR-YJV 3×240+1×120 pairs three 240 mm² copper phase conductors with a single 120 mm² copper neutral, all insulated in XLPE and protected by one ST2 PVC jacket. It is rated 0.6/1 kV (Um = 1.2 kV) at 50 Hz, produced and proof-tested in line with GB/T 12706.1 / IEC 60502-1, stranded per GB/T 3956, and classified ZC under GB/T 19666. Overall diameter is about 53 mm (Tianjin Cable Works 3+1 sample), approximate weight 8950 kg/km for copper (≈ 3720 kg/km for the aluminium YJLV equivalent); standard supply is 100 m coils or wooden drums with ≥ Ø 2000 mm flanges (≈ 895 kg per 100 m).
2. Build-Up from Conductor to Jacket. Layer by layer:
| Layer | Build | Wall | Diameter |
|---|---|---|---|
| Phase conductor (×3) | Annealed Cu, Class 2 compact, 61 × 2.25 mm (1+6+12+18+24) each | — | ≈ 20.2 mm |
| Neutral conductor (×1) | Annealed Cu, Class 2 compact, 19 × 2.83 mm (1+6+12) | — | ≈ 14.2 mm |
| Phase insulation (×3) | XLPE | 1.7 mm | ≈ 23.6 mm |
| Neutral insulation (×1) | XLPE | 1.1 mm | ≈ 16.4 mm |
| Core assembly | Central neutral + 3 phase cores around + PP filler + polyester binder | — | ≈ 47.0 mm (derived) |
| Outer jacket | Flame-retarded PVC, ST2 compound, black | 3.0 mm | ≈ 53.0 mm (finished) |
3. Electrical Performance. Phase resistance is capped at 0.0754 Ω/km at 20 °C (rising to ≈ 0.096 Ω/km at the 90 °C operating point), while the 120 mm² neutral is capped at 0.153 Ω/km. Routine factory proof is 3.5 kV AC for 5 min with no breakdown; finished-cable insulation resistance ≥ 36.7 MΩ·km and XLPE volume resistivity ≥ 1×10¹² Ω·cm. Typical capacitance ≤ 0.38 μF/km, inductance ≈ 0.23 mH/km, and AC impedance at 50 Hz ≈ 0.12 Ω/km. The 240 mm² phase withstands ≈ 27.6 kA for 1 s (the 120 mm² neutral on a ≈ 13.8 kA basis). Reference loading, with all three phases energised, is ≈ 560 A in free air at 30 °C and ≈ 470 A buried at 25 °C — a 3+1-series estimate carried forward from the Zhongce basis; note that published 3-core 240 tables cluster around 480–500 A in air, so the factory test certificate should always be consulted for the actual figure.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine |
|
Type-test voltage |
4.0 kV |
IEC 60502-1 |
|
DC resistance @20 °C (phase, per core) |
≤ 0.0754 Ω/km |
GB/T 3956 max, 240 mm² |
|
DC resistance @20 °C (neutral, per core) |
≤ 0.153 Ω/km |
GB/T 3956 max, 120 mm² |
|
AC resistance @90 °C (est., phase) |
≈ 0.098 Ω/km |
per core |
|
AC resistance @90 °C (est., neutral) |
≈ 0.199 Ω/km |
per core |
|
Current rating in air (30 °C, single circuit, 3-core+1) |
≈ 415–460 A |
based on 240 mm² phase |
|
Current rating in air (design) |
≈ 435 A |
apply grouping + ambient correction |
|
Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) |
≈ 460–500 A |
common catalogue 470–485 A |
|
Design buried rating |
≈ 478 A |
soil thermal resistivity correction required |
|
Short-circuit current (1 s, Cu, 250 °C, phase) |
≈ 24.0 kA |
240 mm² reference |
|
Short-circuit current (1 s, Cu, 250 °C, neutral) |
≈ 12.0 kA |
120 mm² reference |
|
Frequency |
50/60 Hz AC |
— |
4. Thermal & Flame Behaviour. The XLPE system permits 90 °C continuous conductor temperature and 250 °C under short-circuit (≤ 5 s). Service ambient ranges from −20 to +45 °C, with a 0 °C minimum laying temperature and 25 °C reference soil temperature for direct burial. Flame performance is class ZC per GB/T 19666, demonstrated by GB/T 18380.12 single-cable and GB/T 18380.35 category-C bunched tests (char height ≤ 2.5 m). Because the PVC jacket is halogenated and generates smoke under fire, WDZ-YJY is the correct choice where low-smoke zero-halogen performance is required.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation & Handling. Keep bends to at least 15 × OD, i.e. ≈ 795 mm for this size. Before first energisation apply the DC commissioning test at 4U0 = 2.4 kV for 15 min per Q/GDW 13244.1-2018. Drums stored below 0 °C must be warmed before pulling; maximum pulling tension is ≤ 9600 N. The 560/470 A references must be derated for ambient temperature, cable grouping and soil conditions. Terminals and glands should be selected for the 20.2 mm phase core, 14.2 mm neutral core and ≈ 53 mm jacket, and both phase and neutral short-circuit ratings should be checked against the protective device settings.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 675 mm at Ø45.0 mm |
four-core unarmoured |
|
Max. pulling tension (phase) |
3,600 N per core (240 mm² × 15 N/mm²) |
Cu conductor limit |
|
Max. pulling tension (neutral) |
1,800 N per core (120 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Heavy-duty cable tray, ladder, cleats |
— |
|
Conduit ID |
≥ 90 mm |
— |
|
Fixing |
heavy-duty cleats, cable ties |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Fields of Application. This cable is intended for the most demanding three-phase four-wire distribution duties: main switchgear incomers, LV transformer secondaries in the ~1600–2000 kVA range, vertical busbar risers in high-rise and commercial buildings, heavy industrial plant feeders, pump and compressor stations, primary feeds to data centres and municipal distribution networks where a dedicated neutral is carried in a single cable (TN-C style). Approved laying methods include conduit, tray, trench, duct, trunking and direct burial with mechanical protection, indoors or in sheltered outdoor locations. For direct burial without added protection specify the steel-tape armoured ZR-YJV22 variant (≈ 63–68 mm OD).

7. Testing & Quality Control. Routine tests on every production length cover phase and neutral DC resistance (≤ 0.0754 / 0.153 Ω/km at 20 °C), the 3.5 kV AC / 5 min power-frequency withstand, conductor continuity and dimensional checks (phase insulation ≥ 1.7 mm, neutral ≥ 1.1 mm, sheath ≥ 3.0 mm, OD ≈ 53 mm). Sample and type tests include the XLPE hot-set test at 200 ± 3 °C for 15 min under 0.2 MPa (load elongation ≤ 175 %, permanent set ≤ 15 %), XLPE tensile ≥ 12.5 MPa with elongation ≥ 200 %, PVC sheath tensile ≥ 10 MPa with elongation ≥ 125 %, PVC thermal stability ≥ 200 min at 200 °C, single-cable and category-C bunched flame tests, and bending tests. On site, insulation resistance, the DC 2.4 kV / 15 min withstand and phase/neutral identification must be completed before switching on. Each drum is accompanied by a factory test certificate.
Cable Parameters
| ZR-YJV 3×240+1×120 mm² — Flame-Retardant 3+1-Core Power Cable (0.6/1 kV) · Comprehensive Parameter Sheet | ||||
| Copper conductor · XLPE insulation · PVC sheath · 3 phase cores @ 240 mm² + 1 neutral core @ 120 mm² · conforms to GB/T 12706.1, IEC 60502-1, GB/T 3956, GB/T 19666 · OD per Tianjin Cable Works sample; weights/ampacities cross-checked against People's Electric selection manual | ||||
| Code | Parameter | Value | Unit | Remarks |
| 01 · Identification | ||||
| Ref: GB/T 12706.1 / IEC 60502-1; fire class GB/T 19666; Um = 1.2 kV; 50 Hz | ||||
| 1-A | Catalogue description | Copper-conductor XLPE-insulated PVC-sheathed flame-retardant power cable, 3+1 core | — | ZR-YJV family; PVC jacket contains halogen |
| 1-B | Model code | ZR-YJV 3×240+1×120 | — | Three 240 mm² phase cores + one 120 mm² neutral core |
| 1-C | Governing specifications | GB/T 12706.1; IEC 60502-1 | — | Conductor per GB/T 3956 |
| 1-D | Nominal system voltage | 0.6/1 | kV | Highest voltage for equipment Um = 1.2 kV; AC 50 Hz |
| 1-E | Conductor arrangement | Three phase cores (L1/L2/L3) surrounding a central neutral core (N) | — | Three-phase four-wire (TN-C) configuration |
| 1-F | Rated cross-sectional areas | 3 × 240 (phase) + 1 × 120 (neutral) | mm² | Phase cores carry line current; neutral per GB/T 12706.1 |
| 1-G | Flame-retardant category | Class C (ZC) — standard for "ZR" marking | — | ZA/ZB available on request |
| 1-H | Insulation system | XLPE insulation / PVC sheath (ST2) | — | 90 °C XLPE class; flame-retarded PVC jacket |
| 1-I | Design temperature class | XLPE 90 °C continuous / 250 °C short-circuit | °C | Per GB/T 12706.1 thermal rating |
| 02 · Conductor | ||||
| Ref: GB/T 3956 / IEC 60228 Class 2 — phase 240 mm² = 61 wires; neutral 120 mm² = 19 wires | ||||
| 2-A | Conductor material | Annealed electrolytic copper (high conductivity) | — | ≥ 97% IACS conductivity |
| 2-B | Stranding class | Class 2 (compact stranded) | — | GB/T 3956 / IEC 60228 |
| 2-C | Phase stranding (×3) | 61 × 2.25 mm (61/2.25) each | — | 1+6+12+18+24 concentric rings; nominal 240 mm² |
| 2-D | Neutral stranding (×1) | 19 × 2.83 mm (19/2.83) | — | 1+6+12 concentric rings; nominal 120 mm² |
| 2-E | Phase conductor diameter | ≈ 20.2 | mm | Per phase core (61 × 2.25, strand lay) |
| 2-F | Neutral conductor diameter | ≈ 14.2 | mm | Neutral core (19 × 2.83, strand lay) |
| 2-G | Phase DC resistance @ 20 °C | 0.0754 | Ω/km | GB/T 3956 Class 2 Cu (240 mm²) |
| 2-H | Neutral DC resistance @ 20 °C | 0.153 | Ω/km | GB/T 3956 Class 2 Cu (120 mm²) |
| 2-I | Phase DC resistance @ 90 °C | ≈ 0.096 | Ω/km | R20 × (234.5+90)/(234.5+20) (est.) |
| 2-J | Phase conductor mass | ≈ 2134 | kg/km per core | 240 mm² × 8.89 g/cm³ |
| 2-K | Neutral conductor mass | ≈ 1067 | kg/km | 120 mm² × 8.89 g/cm³ |
| 03 · Insulation | ||||
| Ref: GB/T 12706.1 — phase 1.7 mm (240 mm²); neutral 1.1 mm (120 mm²) | ||||
| 3-A | Dielectric material | Cross-linked polyethylene (XLPE) | — | Chemically cross-linked during extrusion |
| 3-B | Phase insulation thickness | 1.7 | mm | GB/T 12706.1 specified value for 240 mm² |
| 3-C | Neutral insulation thickness | 1.1 | mm | GB/T 12706.1 specified value for 120 mm² |
| 3-D | Diameter over phase insulation | ≈ 23.6 | mm | Per phase core (calculated) |
| 3-E | Diameter over neutral insulation | ≈ 16.4 | mm | Neutral core (calculated) |
| 3-F | Insulation mass (total) | ≈ 375 | kg/km | 3 phase + 1 neutral, density 0.92 g/cm³ (est.) |
| 3-G | XLPE tensile strength | ≥ 12.5 | MPa | GB/T 12706.1 / GB/T 2951 |
| 3-H | XLPE elongation at break | ≥ 200 | % | GB/T 12706.1 / GB/T 2951 |
| 04 · Assembly | ||||
| Ref: 3+1 cabling — neutral at centre, three phase cores around; round bundle | ||||
| 4-A | Lay-up configuration | Central neutral core + three phase cores in triangular ring + non-hygroscopic filler + binder tape | — | Forms round, stable cable bundle |
| 4-B | Filler material | Polypropylene (PP) rope / non-hygroscopic filler | — | Maintains roundness; water-resistant |
| 4-C | Binder tape | Polyester tape, single helical wrap | — | Secures cores during sheathing |
| 4-D | Lay ratio (typical) | 12 : 1 to 16 : 1 | — | Cabling pitch / assembly diameter |
| 4-E | Diameter over cabled assembly | ≈ 47.0 | mm | Derived: finished Ø 53 − 2 × 3.0 sheath |
| 05 · Sheath | ||||
| Ref: Tianjin Cable Works sample (Ø ≈ 53 mm); ST2 PVC per GB/T 12706.1 | ||||
| 5-A | Jacket material | Flame-retardant PVC, ST2 compound | — | Black standard; other colours on request |
| 5-B | Nominal sheath thickness | 3.0 | mm | Manufacturer practice (above GB/T minimum) |
| 5-C | Overall finished diameter | ≈ 53.0 | mm | Tianjin Cable Works 3+1 sample (≈ 53 mm) |
| 5-D | Approximate cable mass | ≈ 8950 | kg/km | Cu build-up from People's 3×240 = 7513 kg/km (est.) |
| 5-E | Approximate mass — aluminium build | ≈ 3720 | kg/km | YJLV equivalent (est.) |
| 5-F | Sheath colour | Black (standard) | — | Custom colours available |
| 5-G | PVC tensile strength | ≥ 10.0 | MPa | GB/T 12706.1 / GB/T 2951 |
| 5-H | PVC elongation at break | ≥ 125 | % | GB/T 12706.1 / GB/T 2951 |
| 5-I | PVC thermal stability | ≥ 200 | min | 200 °C Congo-red test (GB/T 2951) |
| 06 · Electrical | ||||
| Ref: GB/T 3956 resistance; ampacity cross-checked vs Mingda / ZW Cable 3-core 240 rows (480–500 A) | ||||
| 6-A | Phase conductor DC resistance | 0.0754 | Ω/km | GB/T 3956 @ 20 °C, each phase |
| 6-B | Neutral conductor DC resistance | 0.153 | Ω/km | GB/T 3956 @ 20 °C, neutral |
| 6-C | Phase DC resistance @ 90 °C | ≈ 0.096 | Ω/km | Operating-temperature resistance (est.) |
| 6-D | Routine voltage proof | 3.5 kV AC / 5 min | — | No breakdown; 50 Hz sine wave |
| 6-E | Insulation resistance (finished) | ≥ 36.7 | MΩ·km | @ 20 °C on completed cable |
| 6-F | XLPE volume resistivity | ≥ 1 × 10¹² | Ω·cm | Material-level property |
| 6-G | Capacitance (typical) | ≤ 0.38 | μF/km | Per phase core to earth/neutral (est.) |
| 6-H | Inductance (typical) | ≈ 0.23 | mH/km | Three-core cable, 50 Hz (est.) |
| 6-I | AC impedance @ 50 Hz | ≈ 0.12 | Ω/km | √(R² + X²); R-dominant (est.) |
| 6-J | Short-circuit current (1 s) | ≈ 27.6 | kA | I = k·A/√t, k=115 for Cu/XLPE |
| 6-K | Buried ampacity @ 25 °C | ≈ 470 | A | 3+1 series basis; Cu, 3 phase loaded (est.) |
| 6-L | Air ampacity @ 30 °C | ≈ 560 | A | 3+1 series basis; Cu, 3 phase loaded (est.) |
| 6-M | Earth-fault loop impedance | Per project calculation | — | Depends on cable length & upstream system |
| 07 · Thermal | ||||
| Ref: XLPE class per GB/T 12706.1 / IEC 60502-1 | ||||
| 7-A | Continuous conductor temperature | 90 | °C | XLPE insulation class rating |
| 7-B | Short-circuit temperature (≤ 5 s) | 250 | °C | GB/T 12706.1 / IEC 60502-1 |
| 7-C | Ambient operating range | -20 to +45 | °C | Per manufacturer datasheet family |
| 7-D | Minimum installation temperature | 0 | °C | Pre-heat drums if colder than 0 °C |
| 7-E | Maximum soil temperature (direct burial) | 25 | °C | Reference for buried ampacity |
| 7-F | Thermal resistance (insulation+sheath) | ≈ 2.7 | K·m/W | Typical for XLPE/PVC 0.6/1 kV (est.) |
| 08 · Fire (ZR) | ||||
| Ref: GB/T 19666; GB/T 18380.12; GB/T 18380.35 (20 min, ≥ 1.5 L/m) | ||||
| 8-A | Flame-retardant grade | Class C (ZC) — default for "ZR" | — | PVC sheath is halogen-containing |
| 8-B | Single-cable vertical flame test | Compliant | — | Method per GB/T 18380.12 |
| 8-C | Bunched-cable flame test — C | Char height ≤ 2.5 m | — | Method per GB/T 18380.35 |
| 8-D | Halogen status | Halogenated (not LSZH) | — | Use WDZ-YJY for low-smoke zero-halogen |
| 8-E | Smoke density (PVC) | Higher than LSZH | — | PVC emits smoke under fire |
| 8-F | Oxygen index (FR-PVC) | ≥ 28 | % | Typical flame-retardant PVC compound (est.) |
| 09 · Installation | ||||
| Ref: Q/GDW 13244.1-2018; GB 50168 | ||||
| 9-A | Minimum bending radius (multi-core) | ≥ 15 × actual OD | — | ≈ 795 mm for Ø 53 mm |
| 9-B | Approved laying methods | Conduit, tray, trench, duct, trunking, direct burial | — | Mechanical protection required for direct burial |
| 9-C | Post-install commissioning test | DC 4U0 = 2.4 kV / 15 min | — | Per Q/GDW 13244.1-2018 |
| 9-D | Maximum pulling tension | ≤ 9600 | N | Rule of thumb: 40 N/mm² of main core area (est.) |
| 9-E | Storage conditions | Dry, covered, −20 to +45 °C | — | Avoid direct sunlight and moisture |
| 9-F | Cold-weather pre-heating | Warm to ≥ 0 °C before pulling | — | Prevents jacket cracking |
| 10 · Packing | ||||
| Ref: custom lengths; marking per GB/T 6995 / project spec | ||||
| 10-A | Standard supply length | 100 m per coil or wooden drum | — | Custom lengths available on request |
| 10-B | Cable surface marking | Type, voltage, manufacturer, year, metre marks | — | Per GB/T 6995 and project requirements |
| 10-C | Recommended drum size | ≥ Ø 2000 mm flange | — | For 100 m of Ø 53 mm cable (est.) |
| 10-D | Approx. net weight per 100 m drum | ≈ 895 | kg | 100 m × 8950 kg/km |
Cable Test Parameters
| ZR-YJV 3×240+1×120 mm² — Test & Verification Schedule (GB/T 12706.1 & IEC 60502-1) | ||||
| Stage | Test Item | Method / Standard | Acceptance Criterion | Notes |
| Routine | Phase conductor DC resistance | GB/T 3956 (IEC 60228) | ≤ 0.0754 Ω/km @ 20 °C (240 mm²) | Every production length |
| Routine | Neutral conductor DC resistance | GB/T 3956 (IEC 60228) | ≤ 0.153 Ω/km @ 20 °C (120 mm²) | Every production length |
| Routine | Power-frequency withstand | GB/T 12706.1 / IEC 60502-1 | 3.5 kV AC / 5 min, no breakdown | Conductor to earth/water bath |
| Routine | Dimensional inspection | GB/T 2951 | Phase ins. ≥ 1.7 mm; neutral ins. ≥ 1.1 mm; sheath ≥ 3.0 mm; OD ≈ 53 mm | Wall & diameter check |
| Routine | Conductor continuity | Visual / electrical | All cores continuous, no break | Every length |
| Sample | XLPE hot-set test | GB/T 12706.1 §16.3.13 / GB/T 2951.11 | 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % | Cross-linking verification |
| Sample | XLPE tensile & elongation | GB/T 2951 | Tensile ≥ 12.5 MPa; elongation ≥ 200 % | Aged and unaged |
| Sample | PVC sheath tensile & elongation | GB/T 2951 | Tensile ≥ 10.0 MPa; elongation ≥ 125 % | Aged and unaged |
| Sample | PVC thermal stability | GB/T 2951 (Congo-red) | ≥ 200 min @ 200 °C | HCl evolution test |
| Sample | Conductor geometry | GB/T 3956 | Phase: 61 × 2.25 mm Ø ≈ 20.2; neutral: 19 × 2.83 mm Ø ≈ 14.2 | Per batch |
| Type | Single-cable flame test | GB/T 18380.12 | No flame to upper reference mark | ZR property |
| Type | Bunched flame test — C | GB/T 18380.35 | Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m | Class C compliance |
| Type | Bending test | GB/T 12706.1 | No damage on specified mandrel (15 × OD) | Multi-core bending rule |
| Type | Insulation resistance | Factory method | ≥ 36.7 MΩ·km @ 20 °C | Not routine under GB/T 12706.1 |
| Post-install | DC withstand commissioning | Q/GDW 13244.1-2018 | 2.4 kV DC / 15 min, no breakdown | Required for new installations |
| Post-install | Phase identification | Visual / continuity | L1/L2/L3/N correctly labelled at both ends | Before energisation |
Cable Cross Section Structure

| ZR-YJV 3×240 mm²+1×120 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Layered 3+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 53 mm per Tianjin Cable Works sample | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Phase conductor (Cu) × 3 | Annealed copper, Class 2 compact strand — 61 wires of 2.25 mm per core (61/2.25, 1+6+12+18+24 layout), nominal area 240 mm² each | — | ≈ 20.2 (Ø each phase core) | Line-current carrying phase conductors; DC resistance capped at 0.0754 Ω/km at 20 °C |
| 2 | Neutral conductor (Cu) × 1 | Annealed copper, Class 2 compact strand — 19 wires of 2.83 mm (19/2.83, 1+6+12 layout), nominal area 120 mm² | — | ≈ 14.2 (Ø neutral core) | Return / neutral path; DC resistance capped at 0.153 Ω/km at 20 °C |
| 3 | Phase insulation (XLPE) × 3 | Cross-linked polyethylene dielectric | 1.7 | ≈ 23.6 (Ø each phase core, incl. insulation) | Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min |
| 4 | Neutral insulation (XLPE) × 1 | Cross-linked polyethylene dielectric | 1.1 | ≈ 16.4 (Ø neutral core, incl. insulation) | Electrical isolation for the neutral conductor |
| 5 | Core assembly | Neutral core at centre + three phase cores cabled around + PP filler + polyester binder tape | — | ≈ 47.0 (Ø over assembled cores) | 3+1 configuration; derived from finished Ø 53 − 2×3.0 sheath |
| 6 | Outer jacket (PVC) | Flame-retardant PVC, ST2 compound, black | 3 | ≈ 53.0 (Ø finished cable) | Mechanical and moisture protection; ZC flame retardance per GB/T 19666 |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 53.0 | mm | Tianjin Cable Works 3+1 sample | ||
| Approximate cable mass | ≈ 8950 | kg/km | Cu build-up vs People's 3×240 = 7513 (est.) | ||
| Approximate mass, aluminium build | ≈ 3720 | kg/km | YJLV equivalent (est.) | ||
| Nominal voltage rating | 0.6/1 | kV | AC 50 Hz; maximum system voltage Um = 1.2 kV | ||
| Conductor temperature limits | 90 / 250 | °C | Continuous service / short-circuit (≤ 5 s) | ||
| Minimum bend radius (multi-core) | ≥ 15 × OD ≈ 795 | mm | OD = actual finished cable diameter | ||
| Flame-retardant classification | ZC (ZR) | — | Per GB/T 19666 | ||
| Short-circuit current, phase (1 s) | ≈ 27.6 | kA | I = k·A/√t, k=115 for Cu/XLPE | ||
| Short-circuit current, neutral (1 s) | ≈ 13.8 | kA | 120 mm² neutral, same k factor | ||
| AC impedance @ 50 Hz | ≈ 0.12 | Ω/km | √(R² + X²); R-dominant (est.) | ||
| Capacitance (typical) | ≤ 0.38 | μF/km | Per phase core (est.) | ||
| Inductance (typical) | ≈ 0.23 | mH/km | Three-core cable (est.) | ||
| Air ampacity @ 30 °C | ≈ 560 | A | 3+1 series basis; Cu, 3 phase loaded (est.) | ||
| Buried ampacity @ 25 °C | ≈ 470 | A | 3+1 series basis; Cu, 3 phase loaded (est.) | ||
| Maximum pulling tension | ≤ 9600 | N | 40 N/mm² of main core area (est.) | ||
| Schematic — not to exact scale. Finished Ø ≈ 53 mm from the Tianjin Cable Works 3+1 sample; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1; mass and ampacity are engineering estimates cross-checked against People's Electric / Mingda / ZW Cable tables. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — ZR-YJV 3×240+1×120 mm² | |||
| Layer-by-layer build-up narrative, conductor through outer jacket · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV class · finished Ø ≈ 53 mm (Tianjin Cable Works sample) | |||
| 1. Product Identity & Ratings | |||
| ZR-YJV 3×240+1×120 is the largest standard flame-retardant 3+1-core cable in the low-voltage family: it combines three 240 mm² copper phase conductors with a single 120 mm² copper neutral conductor, all insulated in XLPE and enclosed in one ST2 PVC jacket, for 0.6/1 kV service. Manufacturing and type testing follow GB/T 12706.1 / IEC 60502-1, conductor stranding follows GB/T 3956, and the ZR marking corresponds to class ZC under GB/T 19666. The finished cable measures about 53 mm across (Tianjin Cable Works sample) and weighs approximately 8950 kg per kilometre; supply is in 100 m coils or wooden drums. | |||
| The 3+1 build follows the conventional three-phase four-wire format: the reduced neutral core sits in the centre while the three phase cores are laid up around it. With all three phase cores energised, the cable supports a reference current of about 560 A in free air at 30 °C and 470 A when directly buried at 25 °C (3+1-series estimates; published 3-core 240 tables run 480–500 A air) — suited to main switchgear incomers, transformer secondaries and the heaviest industrial feeders. | |||
| 2. Copper Stranded Conductors | |||
| Each 240 mm² phase core is formed from sixty-one 2.25 mm annealed wires in the 1+6+12+18+24 compact arrangement (61/2.25) — the Class 2 standard for this cross-section — giving a strand-lay diameter of about 20.2 mm and a DC resistance ceiling of 0.0754 Ω/km at 20 °C (about 0.096 Ω/km at the 90 °C operating temperature). The 120 mm² neutral core uses nineteen 2.83 mm wires (19/2.83) to about 14.2 mm strand-lay Ø, with resistance capped at 0.153 Ω/km. Copper mass alone is about 2134 kg/km per phase core and 1067 kg/km for the neutral; the five-ring 61-wire phase construction keeps the large-section core compact yet flexible enough for drum handling and crimp lug termination. | |||
| 3. XLPE Dielectric Insulation | |||
| XLPE is extruded at 1.7 mm onto the phase cores (the GB/T 12706.1 specified value for 240 mm²) and at 1.1 mm onto the 120 mm² neutral core — producing approximately 23.6 mm per phase core and 16.4 mm for the neutral core over the insulation. The dielectric is rated for 90 °C continuous duty and 250 °C for five seconds, maintains volume resistivity above 1×10¹² Ω·cm, passes the routine 3.5 kV AC five-minute voltage proof, and offers tensile strength ≥ 12.5 MPa with elongation ≥ 200 %. Total XLPE mass is about 375 kg/km. | |||
| 4. Cabling & PVC Outer Jacket | |||
| After insulation, the neutral core is placed at the centre and the three phase cores are cabled around it in a triangular ring with polypropylene filler and a polyester binder tape, forming a bundle of about 47.0 mm diameter (derived from the finished size). A 3.0 mm layer of flame-retarded ST2 PVC is then extruded over the assembly to the ≈ 53 mm finish. The jacket provides ZC behaviour through GB/T 18380.12 and GB/T 18380.35, offers tensile strength ≥ 10 MPa and elongation ≥ 125 %; because PVC is halogenated, low-smoke zero-halogen projects should specify WDZ-YJY, and direct-burial projects without added protection should specify steel-tape armoured ZR-YJV22 (≈ 63–68 mm OD). | |||
| 5. Site Handling & Operational Notes | |||
| • Observe the 15 × OD minimum bending radius (≈ 795 mm). • Perform the DC 4U0 = 2.4 kV / 15 min commissioning test before first energisation. • Service ambient spans −20 to +45 °C; warm drums below 0 °C before pulling. • Derate the 560 A (air) / 470 A (buried) references for ambient temperature, grouping and soil conditions. • Maximum pulling tension ≤ 9600 N; use appropriate pulling grips and lubricant. • Select lugs and glands matched to the 20.2 mm phase core, 14.2 mm neutral core and ≈ 53 mm jacket. • Short-circuit rating ≈ 27.6 kA for 1 s on the phase (≈ 13.8 kA basis on the neutral) — verify against protective device settings. • Use drums with ≥ Ø 2000 mm flanges (≈ 895 kg per 100 m). |
9. Packaging, Storage & Logistics. Standard lengths are 100 m per coil or wooden drum, with custom cut lengths available. Each drum is marked with type, voltage, manufacturer, year of manufacture and sequential metre marks per GB/T 6995. Store in dry, covered conditions between −20 and +45 °C, away from direct sunlight, moisture, oils and sharp objects; keep drums sealed until installation and stand them on their flanges rather than lying flat. In cold weather, condition drums indoors to ≥ 0 °C before uncoiling and pulling. During transport, secure drums against rolling and impact, and never drag the cable over rough ground or sharp edges.

10. Ordering Information. Specify "ZR-YJV 0.6/1 kV 3×240+1×120" together with the required supply length or drum arrangement and surface marking. State the flame-retardant class (ZC is the default; ZA/ZB on request), jacket colour and any special drum requirements. Always request the manufacturer's factory test certificate to confirm the actual unarmoured OD (≈ 53 mm), weight (≈ 8950 kg/km) and ampacity. For low-smoke zero-halogen or armoured variants, order WDZ-YJY or ZR-YJV22 respectively.
11. Cable Industry FAQ.
- Q1: How do YJV, ZR-YJV, YJV22 and WDZ-YJY differ? YJV is the base XLPE/PVC cable; ZR-YJV adds flame-retardant behaviour (default class ZC); YJV22 adds a steel-tape armour for direct burial and mechanical protection — the 3×240+1×120 armoured build reaches ≈ 63–68 mm; WDZ-YJY replaces the PVC jacket with a halogen-free, low-smoke compound for enclosed public spaces.
- Q2: What do ZA / ZB / ZC / ZD stand for? They are flame-retardant classes under GB/T 19666, verified by the bunched-cable test GB/T 18380.35 at different fuel loads — A is the most stringent, D the least. "ZR" without a letter defaults to ZC; ZA and ZB must be explicitly stated at the order stage.
- Q3: Why is the neutral smaller (120 mm²) than the phase (240 mm²)? In a balanced three-phase circuit the neutral carries mainly unbalance and harmonic current, so GB/T 12706.1 allows a reduced neutral in the 3+1 construction. Where heavy single-phase or non-linear, harmonic-rich loads are expected, choose an equal-section 4-core cable or a larger neutral.
- Q4: When should I use 3+1, 4-core equal, or 3+2? Use 3+1 for general TN-C three-phase four-wire service with a reduced neutral; 4-core equal (3×A+1×A) when neutral current approaches phase current; 3+2 (three phases plus separate N and PE) for TN-S systems that need distinct neutral and protective conductors.
- Q5: Why do air and buried ratings differ, and how are they corrected? The figures assume 30 °C air or 25 °C soil at 1.0 K·m/W thermal resistivity with a single circuit. Apply manufacturer correction factors for ambient temperature, cable grouping, burial depth and soil resistivity — air factors run roughly from 1.29 at 20 °C down to 0.91 at 45 °C, and soil factors from 1.04 at 20 °C to 0.87 at 40 °C.
- Q6: Copper or aluminium conductor? Copper (this cable) gives lower resistance (0.0754 versus ≈ 0.125 Ω/km at 240 mm²), higher ampacity per mm², better mechanical strength and more reliable terminations; aluminium (YJLV, ≈ 3720 kg/km in this size) is cheaper and lighter but requires larger cross-sections and anti-oxidation treatment at joints.
- Q7: Why is XLPE rated 90 °C while PVC insulation is only 70 °C? Cross-linking converts polyethylene into a thermoset network, lifting the continuous conductor temperature to 90 °C and short-circuit tolerance to 250 °C — which directly raises ampacity for the same copper area.
- Q8: How is the conductor size chosen? Size against (a) full-load current with derating factors, (b) permissible voltage drop (typically ≤ 5 % for power circuits), (c) short-circuit withstand on an I²t basis (27.6 kA·s per phase here), and (d) coordination with protective devices; the most onerous requirement governs.
- Q9: Why does finished diameter vary between manufacturers for the same nominal size? Standards fix minimum insulation and sheath thickness plus electrical performance, not exact OD. Stranding compaction, filler design and sheath tolerance differ by plant — published 3×240+1×120 figures cluster around 53 mm unarmoured — so always use the actual measured OD when sizing glands, trays and conduits.
- Q10: Which tests confirm the cable is acceptable on delivery and before energisation? On delivery, verify the factory test certificate (resistance 0.0754/0.153 Ω/km, 3.5 kV/5 min withstand, dimensions ≈ 53 mm), jacket marking and drum condition. After laying, carry out an insulation-resistance test plus the DC 4U0 = 2.4 kV / 15 min withstand per Q/GDW 13244.1-2018, then confirm phase and neutral identification before switching on.
- Q11: What service life can be expected? When installed within the temperature and voltage limits, XLPE 0.6/1 kV cables are designed for ≥ 30 years of service; prolonged overload, UV exposure, water immersion through a damaged jacket, or operation above 90 °C will shorten life materially.