ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution
Product Summary
Product Details
ZR-YJV 4 core electrical cable
,4 core electrical cable 4x185mm2
,copper power wire 300mm2
Product Description
ZR-YJV 4*185mm² Flame Retardant 4 Core Copper Power Distribution Cable
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
4×185 mm² |
Four cores of 185 mm² copper conductor each (3 phase + 1 neutral, equal size) |
Construction: Four 185 mm² copper conductors (3 phase + 1 neutral), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).
ZC-YJV 4×185 mm² — LV Flame-Retardant 4-Core Power Cable — Specification
1. Overview & Ratings. ZC-YJV 4×185 (v2) is a medium-heavy four-core LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant PVC sheath: four equal 185 mm² compacted copper cores (L1/L2/L3/N) laid 2+2, dry-cured XLPE, unarmored (armor optional). OD ≈ 33.5 mm, ≈ 6200 kg/km (est.), ≈ 370 A per core free air at 30 °C (est.). Scope: 380/400 V building floor feeders, riser branches and balanced three-phase loads (elevators, HVAC, pumps) — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Conductors L1/L2/L3/N | 4×185 compacted Cu, Class 2, ≈37 strands | Equal cores, R ≤0.0991 Ω/km |
| Strand compaction | Concentric layers rolled compact per core | Round bundles, tidy OD, uniform crimp |
| XLPE insulation (all cores) | Dry-cured PE, ≈2.3 mm | Balanced 90°C dielectric, low loss |
| 2+2 core laying | Four equal cores in two rows of two | Stable round bundle before jacketing |
| Core identification | L1/L2/L3/N color code | Phase sequence + full-size neutral |
| PVC ZC sheath | Class C, ≈2.3 mm overall | Binds bundle, self-extinguishes |
| Jacket print | Continuous type/section/voltage/length | On-site readable spec |
3. Electrical Characteristics. R ≤ 0.0991 Ω/km on all four equal cores @20 °C. Test 3.5 kV AC / 5 min; ≈ 370 A per core (est., air 30 °C); short-circuit ≈ 15 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 0.0991 Ω/km per core |
GB/T 3956 Class 2 Cu max (185 mm²) |
|
AC resistance @90 °C (est.) |
≈ 0.127 Ω/km per core |
— |
|
Current rating in air (30 °C) |
3-phase: 360 A |
4×185, touching, in free air |
|
Current rating in tray (30 °C) |
3-phase: 400 A |
4×185, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
3-phase: 375 A |
direct buried |
|
Current rating in conduit (30 °C) |
3-phase: 320 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 20.5 kA (20,500 A) per core |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.23 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.09 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 4×185 at 360 A three-phase, 400 V → max load ≈ 216 kW (cos φ = 0.8). Suitable for medium-to-heavy distribution, large motors, and building main feeders.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame spread control, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. 185 mm² lugs on four cores, glands to ≈33.5 mm OD, hydraulic crimp/torque per table; bend ≥ 15×OD ≈ 500 mm with rollers; apply bundle derating; keep the 2+2 bundle round; four-core continuity, phase sequence, neutral + insulation after pulling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 698 mm at Ø46.5 mm |
four-core unarmoured |
|
Max. pulling tension |
2,775 N per core (185 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Heavy-duty cable tray, ladder, cleats |
— |
|
Conduit ID |
≥ 90 mm |
— |
|
Fixing |
heavy-duty cleats, cable ties |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Fair (Class 2 stranded, large conductor) |
fixed installation |
|
Termination note |
Heavy-duty compression lugs or mechanical connectors |
— |
6. Typical Service Applications. Building main-to-floor-cabinet feeders and riser branches, elevator and HVAC compressor circuits, pump groups, and balanced three-phase distribution branches.

7. Testing & QA Regime (16 items). Routine: all-core DC resistance (185), 3.5 kV withstand, insulation resistance, four-core continuity, sheath/insulation thickness, dimensional check, strand construction, core balance, eccentricity, print legibility, mass, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.
Cable Parameters
| ZC-YJV 4×185 mm² — LV Flame-Retardant 4-Core Power Cable — Full Parameter Sheet | |||
| 4×185 Cu equal cores (L1/L2/L3/N) · XLPE insulation / PVC sheath · ZC · 0.6/1 kV · ≈34 mm · 2+2 lay · 380/400 V secondary feeder, sub-main riser and motor circuit supply | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — Cu/XLPE/PVC, flame-retardant class C | — | ZC-YJV denotes a copper conductor with cross-linked polyethylene insulation and a PVC outer sheath; ZC marks a class C flame-retardant PVC compound that self-extinguishes after the ignition source is removed. |
| Rated voltage (U0/U) | 0.6/1 | kV | 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines a general low-voltage cable suited to 380/400 V sub-main distribution. |
| Maximum operating voltage (Um) | 1.2 | kV | The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service. |
| Core configuration | 4×185 (L1 / L2 / L3 / N), equal size, 2+2 lay | — | Four equal 185 mm² compacted copper cores — three phases plus a full-size neutral — laid 2+2 for balanced and non-linear sub-main loads. |
| Conductor material | Compacted stranded annealed copper | — | Soft annealed copper strands are layer-compacted into equal round 185 mm² bundles for medium-large lug entry. |
| Insulation | XLPE cross-linked polyethylene | — | Chemically cross-linked polyethylene bonds into a heat-resistant dielectric retaining properties at the 90 °C operating temperature. |
| Sheath | PVC, flame-retardant class C (ZC) | — | A heavy overall PVC jacket binds the four-core bundle and carries the class C flame-retardant formulation; deep slate blue finish. |
| Flame retardancy | ZC class C (self-extinguishing, not fire-rated) | — | On removal of a flame the cable stops propagating fire; this is flame retardancy, not 950 °C/180 min circuit-integrity fire resistance. |
| Suitable for | Fixed sub-main tray, riser, duct, 3-phase+full neutral | — | Designed for fixed three-phase-plus-neutral sub-main feeders serving distribution panels and motor groups. |
| Application | 380V sub-main feeder / sub-distribution riser | — | Typically runs four equal cores from a main board to a sub-distribution riser, large motor feeder or panel group. |
| Application note | Not for 950°C circuit-integrity fire duty | — | Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire. |
| 02 · Conductors | |||
| Cores count / area | 4 × 185 (L1/L2/L3/N) | mm² | Four equal 185 mm² conductors: three phases and a full-size neutral for moderate-heavy unbalanced and harmonic current. |
| Conductor type | Compacted stranded Cu, Class 2 | — | Class 2 stranded compacted construction gives fixed-wiring conductors that round into stable bundles for lug termination. |
| DC resistance (185) @ 20°C | ≤ 0.0991 | Ω/km | Maximum permitted DC resistance of an 185 mm² copper conductor at 20 °C, identical for all four equal cores. |
| Stranding | Layer-compacted concentric bundle | — | Concentric layers of strands are compacted radially per core to reduce gaps, tighten the bundle and present a clean round lug entry. |
| Strands (nom., est.) | ≈37 strands per core | — | Approximate strand count around 37 compacted strands in an 185 mm² core; exact count follows the conductor standard. |
| Surface | Bare copper; tinned optional | — | Bare copper suits most indoor use; optional tinned plating improves corrosion resistance in damp or chemically mild sites. |
| Core identification | L1/L2/L3/N color code, equal size | — | All four cores share the same 185 mm² section and are color-coded so phase sequence and neutral match at the panel. |
| Nominal area tolerance | Within conductor class 2 band | — | Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count. |
| Neutral sizing | Full-size 185 mm² (equal to phases) | — | The equal-size neutral protects against third-harmonic and unbalanced heating on sub-main motor and non-linear loads. |
| Compaction benefit | Round bundle, lower OD, clean crimp | — | Radial compaction reduces overall diameter versus loose stranding and gives a flat, even lug crimp. |
| 03 · Insulation | |||
| Insulation material | XLPE (cross-linked polyethylene) | — | Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than PVC insulation for the same size. |
| Insulation thickness (nom.) | ≈ 2.4 | mm | Thick nominal radial insulation wall on each equal 185 mm² core; gauged to withstand the 3.5 kV routine test. |
| Working conductor temp. | 90 | °C | Maximum continuous conductor temperature under rated current without shortening insulation life. |
| Short-circuit temp. | 250 | °C | Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs. |
| Insulation resistance | High and stable | MΩ·km | XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on sub-main feeders. |
| Color | L1/L2/L3/N color on request | — | Insulation colors are matched to local 3-phase convention or supplied natural with printed marking. |
| Cure type | Chemical / dry-cured XLPE | — | A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat. |
| Insulation symmetry | Equal wall on all four cores | — | Uniform insulation thickness keeps the four equal cores electrically balanced. |
| 04 · Sheath & Flame Retardancy | |||
| Sheath material | PVC, flame-retardant ZC | — | The heavy class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface. |
| Sheath thickness (nom.) | ≈ 2.4 | mm | Nominal overall jacket wall sized to shield the four medium-large cores from abrasion, mechanical handling and duct damage. |
| Finished outer diameter | ≈ 34 | mm | Overall four-core medium-heavy finished diameter used to size ducts, trunking and glands. |
| Flame behavior | Self-extinguishing, class C | — | After the test flame is removed the sample extinguishes without propagating; it is not 950°C fire-rated. |
| Sheath color | Deep slate blue (black/gray on request) | — | Standard deep slate blue; black or dark gray jackets are supplied for industrial aesthetics on request. |
| Surface finish | Smooth, continuous print | — | A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length. |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | Low-voltage rating matching 380/400 V sub-main distribution systems. |
| Max voltage (Um) | 1.2 | kV | Continuous upper system voltage for phase-to-earth insulation stress. |
| Nominal current (per 185 core, est.) | ≈ 380 | A | Approximate ampacity of a single 185 mm² core in free air at 30 °C; reduce for bundling, duct fill and high ambient. |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine dielectric withstand applied between each conductor and sheath for five minutes without breakdown. |
| Insulation resistance | High, XLPE | MΩ·km | Measured after conditioning; confirms no void, crack or contamination in the cured insulation. |
| Short-circuit current (185, 1s, est.) | ≈ 16 | kA | Approximate 1-second copper short-time withstand on the 185 mm² core; sub-main fault duty. |
| Frequency | 50 / 60 | Hz | Compatible with both 50 Hz and 60 Hz three-phase power systems. |
| Dielectric | XLPE, low loss | — | Low dielectric loss keeps heating down under continuous sub-main feeder and riser load. |
| 06 · Thermal & Environment | |||
| Normal conductor temp. | 90 | °C | Sustained operating temperature the XLPE insulation is rated for under full load. |
| Installed ambient | 0 ~ +40 | °C | Recommended continuous ambient around the cable; high rooms and crowded trays require ampacity derating. |
| Min install temp. | 0 | °C | Avoid cold bending below 0 °C where the PVC jacket and insulation may stiffen and crack. |
| Burning | Self-extinguishing, ZC class C | — | Class C vertical flame test behavior: flame stops once the external burner is removed. |
| Outdoor / UV | Indoor preferred; UV-grade jacket optional | — | Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor risers. |
| Oil / chemicals | Resistant to common oils; check aggressive media | — | Withstands typical machine oils; verify against specific solvents or acid fumes before use. |
| Temperature cycle | Withstands repeated 0~90°C duty | — | The insulation and jacket survive repeated heating/cooling cycles without cracking or delamination. |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 510 | mm | Fixed-installation minimum bend radius for the four-core cable; tight bends risk insulation and jacket damage. |
| Flexibility | Stranded, handled with rollers | — | Compacted strands remain manageable but large cores benefit from rollers and mechanical help on site. |
| Shielding / Armor | None / unarmored (armor optional) | — | No copper braid screen and no armor as standard; add steel-tape or wire armor where ground crushing or EMI exists. |
| Cable weight per km (est.) | ≈ 6400 | kg/km | Heavy mass per kilometer used for structural tray loading and drum sizing. |
| Circularity | 2+2 four-core bundle, stable OD | — | Four equal cores laid 2+2 form a round bundle so the finished OD stays consistent. |
| Tensile / elongation | Jacket meets PVC grade | — | Jacket tensile strength and elongation satisfy the PVC compound grade for rugged pulling. |
| 08 · Factory Advantages | |||
| Equal-size 4-core build | L1/L2/L3/N all 185 mm² for harmonic load | — | Full-size neutral handles third harmonics and sub-main unbalance without overheating. |
| Stable XLPE cure | Even cross-linking keeps the 90°C dielectric consistent | — | Controlled cure prevents soft spots in insulation under sustained feeder load. |
| Dosed ZC compound | Flame-retardant PVC self-extinguishes to class C | — | Dosed flame inhibitors protect panel rooms and sub-main wiring spaces. |
| Length-on-demand | Cut to exact riser/feeder meter, sealed ends | — | Custom cut lengths match the measured riser and horizontal feeder route. |
| Batch resistance log | All four core R logged against lot | — | Every equal-core resistance is recorded against batch ID for full traceability. |
| Continuous print line | Type, size, ZC, voltage and length along jacket | — | Clear continuous marking lets installers read the spec on medium-heavy cables. |
| Phase-color option | L1/L2/L3/N insulation colors matched to convention | — | Pre-colored equal cores remove wiring guesswork at panel terminals. |
| Reinforced drum pack | Industrial wooden drum with sealed ends | — | Sub-main length wound on a sound drum suitable for winch or manual pulling. |
| Certified QA pack | Routine + type test record shipped per batch | — | A complete QA packet supports buyer audit, inspection and commissioning sign-off. |
| 09 · Installation | |||
| Laying | Sub-main tray, riser, duct, 3-phase+N | — | Route on rated trays or risers; keep the 2+2 bundle round and bending above 15×OD. |
| Connectors | 185 mm² lugs on all four cores | — | Crimp matched 185 mm² lugs on phases and neutral; select glands sized to 34 mm OD. |
| Bend radius | ≥ 15×OD ≈ 510 mm | — | Maintain the large minimum radius around riser bends to prevent insulation cold-working. |
| Parallel runs | Derating in bundles and ducts | — | Adjacent cores share heat; apply bundle derating before sizing the sub-main breaker. |
| Site test | Continuity + insulation post-laying | — | After pulling, verify four-core continuity, phase sequence, neutral and insulation resistance. |
| Termination | Strip, hydraulic crimp lug, torque per table | — | Strip insulation without nicking strands, use a hydraulic press on each lug, and torque per the lug table. |
| 10 · Packing & Applications | |||
| Supply length | Custom / industrial wooden drum | m | Cut to the measured sub-main feeder length on a sound drum. |
| Length tolerance | Per trade standard for cut lengths | — | Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise. |
| Reel type | Industrial wooden drum | — | Drum for heavy sub-main lengths; sealed ends prevent moisture ingress. |
| Surface marking | ZC-YJV, 4×185, 0.6/1kV, ZC, length | — | Jacket prints type, core size, voltage, flame class and cumulative meter length. |
| Typical use | Sub-main feeder, sub-riser, large motor circuit | — | Runs four equal cores to sub-distribution boards and motor feeders. |
| Storage | Dry indoor on drum supports, avoid UV | — | Store the drum horizontally on timber supports, dry and shaded, avoiding direct sunlight. |
Cable Test Parameters
| Test Parameters — ZC-YJV 4×185 LV Flame-Retardant 4-Core Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | DC resistance (all 4 cores) | 20 °C, each L1/L2/L3/N (185 mm²) | ≤0.0991 Ω/km | Routine |
| 2 | Voltage test (AC) | 3.5 kV AC, 5 min, core-to-sheath | No breakdown | Routine |
| 3 | Insulation resistance | XLPE, 20°C, per core | High & stable | Routine |
| 4 | Continuity | Each core L1/L2/L3/N | Continuous | Routine |
| 5 | Flame retardancy | Class C vertical test | Self-extinguish | Type |
| 6 | Sheath thickness | Micrometer, cross-section | Nominal ≈2.4 mm | Routine |
| 7 | Insulation thickness | Micrometer, 185 mm² cores | Nominal ≈2.4 mm | Routine |
| 8 | Dimensional check | Caliper, overall OD | OD ≈ 34 mm | Routine |
| 9 | Conductor construction | Visual / strand count per core | Class 2 compacted | Routine |
| 10 | Short-circuit rating | Calculated / type | 16 kA / 1 s | Type |
| 11 | Insulation eccentric test | Cross-section measure per core | Within tolerance | Routine |
| 12 | Printing legibility | Visual | Marking readable | Routine |
| 13 | Mass per unit length | Weigh / calculate | ≈ 6400 kg/km | Routine |
| 14 | Core balance check | Resistance compare across 4 cores | Balanced within band | Routine |
| 15 | Sheath mechanical | Tensile / elongation check | Meets PVC grade | Type |
| 16 | Packing & drum inspection | Visual / drum condition | Sealed ends, sound drum | Routine |
Cable Cross Section Structure

| ZC-YJV 4×185 — 4-Core 2+2 Cross-Section Construction Diagram (Schematic, Expanded) | |||||
| 4×185 equal Cu cores (L1/L2/L3/N) / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈34 mm · sub-main feeder, sub-riser & large motor circuit | |||||
| No. | Layer / Feature | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Detailed Function / Remarks |
| 1 | Conductor L1 — phase | 1×185 compacted Cu, Class 2, ≈37 strands | — | ≈ 12.4 | Phase 1 core, DC R ≤0.0991 Ω/km @20°C; sub-main current. |
| 2 | Conductor L2 — phase | 1×185 compacted Cu, Class 2, ≈37 strands | — | ≈ 12.4 | Phase 2 core, equal size/resistance for balanced impedance. |
| 3 | Conductor L3 — phase | 1×185 compacted Cu, Class 2, ≈37 strands | — | ≈ 12.4 | Phase 3 core, equal spec; color-coded for phase sequence. |
| 4 | Conductor N — neutral | 1×185 compacted Cu, Class 2, equal size | — | ≈ 12.4 | Full-size neutral, same R as phases; handles harmonics/unbalance. |
| 5 | Strand compaction | Concentric layers rolled compact per core | — | — | Radial compaction closes gaps for round bundles and clean lug entry. |
| 6 | XLPE insulation (all cores) | Dry-cured cross-linked PE, ≈2.4 mm | ≈ 2.4 | ≈ 17.2 | Thick 90°C dielectric on each equal core, low loss, balanced wall. |
| 7 | 2+2 core laying | Four equal cores in two rows of two | — | — | 2+2 arrangement stabilizes the bundle before sheathing. |
| 8 | PVC ZC sheath | Class C jacket, ≈2.4 mm | ≈ 2.4 | ≈ 34 | Binds the four-core bundle and self-extinguishes to class C. |
| 9 | Jacket print | Continuous type/size/voltage/length line | — | — | Marking: ZC-YJV, 4×185, 0.6/1kV, ZC, cumulative length. |
| Key Dimensions, Electrical & Mechanical Properties (expanded) | |||||
| Finished cable diameter | ≈ 34 | mm | Four-core medium-heavy overall OD for ducts and glands. | ||
| Approx. cable mass (est.) | ≈ 6400 | kg/km | Heavy sub-main feeder; industrial drum. | ||
| Nominal voltage rating | 0.6/1 | kV | Matches 380/400 V systems. | ||
| Max voltage (Um) | 1.2 | kV | Phase-to-earth continuous upper limit. | ||
| Normal conductor temp. | 90 | °C | Continuous load temperature of XLPE. | ||
| Short-circuit temp. | 250 | °C | Short-time fault peak before insulation damage. | ||
| DC resistance (185, all cores) | ≤ 0.0991 | Ω/km | Per equal core @20°C. | ||
| Neutral sizing | Full 185 equal to phases | — | For harmonics and sub-main unbalance. | ||
| Nominal core current (est.) | ≈ 380 | A | Per 185 core, free air 30°C; derate bundled. | ||
| Short-circuit rating (1s, est.) | ≈ 16 | kA | Sub-main feeder fault duty. | ||
| Flame retardancy | ZC class C, self-extinguishing | — | Not 950°C fire-rated. | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 510 | mm | Four-core riser bend radius. | ||
| Frequency | 50 / 60 | Hz | Compatible with both power systems. | ||
| Insulation resistance | High & stable | MΩ·km | XLPE; supports earth-fault detection. | ||
| Dielectric loss | Low | — | XLPE keeps heating down on feeder load. | ||
| Temperature cycle | 0~90°C repeated | — | Survives heating/cooling without cracking. | ||
| Sheath mechanical | Jacket meets PVC grade | — | Tensile/elongation checked at type test. | ||
| Pack choice | Industrial wooden drum | — | Sound drum with sealed ends. | ||
| Core configuration | 4×185 (L1/L2/L3/N), 2+2 | — | Four equal cores. | ||
| Application | Sub-main feeder, sub-riser, motor circuit | — | 380/400 V distribution 3-phase+N power. | ||
| Schematic — not to exact scale. OD ≈34 mm, weight ≈6400 kg/km, core ampacity ≈380 A free air at 30°C and ≈16 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 4×185 serves 380/400 V sub-main feeders, sub-risers and large motor circuits; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 4×185 LV flame-retardant 4-core cable | |||
| 4×185 equal Cu cores (L1/L2/L3/N) / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈34 mm · sub-main feeder, sub-riser & large motor circuit | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 4×185 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; four equal 185 mm² cores (L1/L2/L3/N) laid 2+2. OD ≈34 mm, ≈6400 kg/km (est.), ≈380 A per core free air at 30°C (est.), industrial wooden drum. It is a fixed sub-main feeder cable, not a flexible cord and not a 950°C fire-rated circuit. | |||
| 2. Copper Conductors (4 equal 185 mm² cores) | |||
| Four equal compacted Class 2 Cu cores (L1/L2/L3/N), R ≤0.0991 Ω/km @20°C; full-size neutral equals phases to carry third harmonics and sub-main unbalance; tinned plating optional; phase-color insulation on request. | |||
| 3. Strand Compaction & 2+2 Bundle | |||
| Concentric strands are rolled compact per core to close gaps and give clean lug entry; four equal cores lay in two rows of two (2+2) to stabilize the round bundle before sheathing. | |||
| 4. XLPE Insulation | |||
| Dry-cured cross-linked PE ≈2.4 mm on every equal core; stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; balanced wall keeps all cores electrically equal. | |||
| 5. Core Identification | |||
| L1/L2/L3 phases and the N neutral are identified by insulation color; because all four cores are equal size, color alone separates phase from neutral at the panel terminal. | |||
| 6. PVC ZC Sheath | |||
| Class C flame-retardant PVC ≈2.4 mm overall, self-extinguishing; deep slate blue standard (black/gray on request); smooth printable surface; binds the four-core bundle and shields from abrasion and duct damage. | |||
| 7. Electrical Characteristics | |||
| 0.6/1 kV, Um 1.2; R ≤0.0991 Ω/km on all four equal cores; routine 3.5 kV AC/5 min; ≈380 A per core (est., air 30°C); short-circuit ≈16 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE. | |||
| 8. Factory Advantages | |||
| • Equal-size 4-core build (full-size neutral). • Stable XLPE cure. • Dosed ZC self-extinguish. • Length-on-demand. • All-core resistance log. • Continuous clear print. • Phase-color option. • Reinforced drum pack. • Certified QA pack. | |||
| 9. Site Handling & Installation | |||
| • Bend 15×OD (≈510 mm) with rollers. • 185 mm² lugs on all four cores, glands to 34 mm OD, hydraulic crimp, torque per table. • Derating in bundles/ducts. • Keep 2+2 bundle round. • Four-core continuity, phase sequence, neutral + insulation after pulling. | |||
| 10. Typical Service Applications | |||
| 380/400 V main-board-to-sub-board feeders and sub-risers, large motor circuits, distribution panel groups and non-linear load branches such as VFD and UPS sub-circuits. | |||
| 11. Testing & QA | |||
| 16-item regime: routine all-core DC resistance (185), 3.5 kV withstand, insulation resistance, four-core continuity, sheath/insulation thickness, dimensional check, strand construction, core balance, eccentricity, print legibility, mass, packing inspection; type ZC flame, short-circuit, sheath mechanical. | |||
| 12. Packaging, Storage & Notes | |||
| Cut to measured sub-main length on an industrial wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated. |
8. Factory Advantages.
- Balanced equal-core layout — 4×185 identical for balanced three-phase branches.
- Dry-cured XLPE control — consistent cure batch-by-batch for stable dielectric.
- Class C jacket compound — dosed flame inhibitor for wiring-shop safety.
- Custom cut length — measured riser/feeder meter, sealed ends.
- Per-core resistance certificate — L1/L2/L3/N values logged to lot.
- Continuous line printing — type, section, ZC, voltage, length readable.
- Color coordination option — insulation colors matched to project schedule.
- Sound drum delivery — industrial wooden drum, sealed cable ends.
- Full QA documentation — routine plus type-test record per batch.

9. Packaging, Storage & Logistics. Cut to measured branch length on an industrial wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.

10. Procurement Specification. State "ZC-YJV 4×185 (v2)", length, class C, phase colors, armor if required, drum; note flame retardant not fire-rated; request per-core resistance certificate and 16-item QA record. Est. values confirmed against the factory certificate.
11. Cable Industry FAQ.
- Q1: How does v2 differ from the first 4×185? Same 4×185 2+2 standard and R ≤0.0991, but a refined build: slightly slimmer OD (33.5 vs 34 mm), lighter (6200 vs 6400 kg/km), conservative ampacity (370 vs 380 A), teal-olive jacket, and a building floor-feeder application focus rather than general plant feeders.
- Q2: Why a full-size neutral? Branch VFD, UPS and LED loads generate third harmonics; an equal neutral prevents neutral overheating at the floor cabinet.
- Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
- Q4: DC resistance? ≤ 0.0991 Ω/km on every 185 mm² core at 20°C.
- Q5: Armor or screen? Unarmored standard; add steel armor for ground crushing and braid screen for EMI.
- Q6: Current per core? ≈ 370 A (est.) free air 30°C; derate on bundled trays and ducts.
- Q7: Bending? ≥ 500 mm (15×OD); use rollers around riser elbows.
- Q8: Connectors? 185 mm² lugs on four cores, hydraulic press, gland to ≈33.5 mm OD.
- Q9: Indoor or outdoor? Indoor preferred; UV-stabilized jacket for exposed routes.
- Q10: Packing? Industrial wooden drum with sealed cable ends.
- Q11: What proof ships? Per-core resistance certificate + 16-test record; est. values confirmed against certificate.