ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 4*185mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

ZR-YJV 4*185mm² Flame Retardant 4 Core Copper Power Distribution Cable Cable Designation & Meaning Code Meaning ZC Flame retardant Class C YJ Cross-linked polyethylene (XLPE) insulation V Polyvinyl chloride (PVC) sheath 4×185 mm² Four cores of 185 mm² copper conductor each (3 phase + 1 neutral, ...

Product Details

Highlight:

ZR-YJV 4 core electrical cable

,

4 core electrical cable 4x185mm2

,

copper power wire 300mm2

Conductor (×4):
Bare Annealed Copper, Class 2 Stranded, Commonly 37×∅2.52 Mm (also 19×∅3.55 Mm Compact / 36×2.55 Mm), Conductor Ø ≈ 16.8–18.5 Mm Depending On Compaction
Conductor nominal area:
185 Mm²
Number of cores:
4
Conductor construction:
Class 2, 37×∅2.52 Mm,IEC 60228 / GB/T 3956, Min. 15 Wires
Conductor diameter:
16.8–18.5 Mm
Insulation (×4):
XLPE
Insulation thickness:
1.6 Mm (185 Mm² Class)
Diameter over insulated core:
20.0–21.7 Mm,conductor + 2×1.6
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
2.4 Mm (GB/T 12706 Multi-core 150–300 Mm² Range)
Overall cable diameter:
45.0 – 52.0 Mm
Design outer diameter:
≈ 48.0 Mm
Approx. weight:
6200 – 7800 Kg/km
Design weight:
≈ 6700 Kg/km
Cable shape:
Round

Product Description

ZR-YJV 4*185mm² Flame Retardant 4 Core Copper Power Distribution Cable

Cable Designation & Meaning

Code

Meaning

ZC

Flame retardant Class C 

YJ

Cross-linked polyethylene (XLPE) insulation 

V

Polyvinyl chloride (PVC) sheath 

4×185 mm²

Four cores of 185 mm² copper conductor each (3 phase + 1 neutral, equal size)


Construction: Four 185 mm² copper conductors (3 phase + 1 neutral), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

ZC-YJV 4×185 mm² — LV Flame-Retardant 4-Core Power Cable — Specification

1. Overview & Ratings. ZC-YJV 4×185 (v2) is a medium-heavy four-core LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant PVC sheath: four equal 185 mm² compacted copper cores (L1/L2/L3/N) laid 2+2, dry-cured XLPE, unarmored (armor optional). OD ≈ 33.5 mm, ≈ 6200 kg/km (est.), ≈ 370 A per core free air at 30 °C (est.). Scope: 380/400 V building floor feeders, riser branches and balanced three-phase loads (elevators, HVAC, pumps) — not 950°C fire duty.


2. Construction Stack (Inner → Outer, expanded).


Layer / Feature Build Function
Conductors L1/L2/L3/N 4×185 compacted Cu, Class 2, ≈37 strands Equal cores, R ≤0.0991 Ω/km
Strand compaction Concentric layers rolled compact per core Round bundles, tidy OD, uniform crimp
XLPE insulation (all cores) Dry-cured PE, ≈2.3 mm Balanced 90°C dielectric, low loss
2+2 core laying Four equal cores in two rows of two Stable round bundle before jacketing
Core identification L1/L2/L3/N color code Phase sequence + full-size neutral
PVC ZC sheath Class C, ≈2.3 mm overall Binds bundle, self-extinguishes
Jacket print Continuous type/section/voltage/length On-site readable spec


3. Electrical Characteristics. R ≤ 0.0991 Ω/km on all four equal cores @20 °C. Test 3.5 kV AC / 5 min; ≈ 370 A per core (est., air 30 °C); short-circuit ≈ 15 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.

Insulation & Sheath Data

Property

Value

Insulation material

XLPE (cross-linked polyethylene)

Outer sheath material

PVC (ST₂)

Long-term service temp.

90 °C (continuous)

Max. conductor temp. (normal)

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Test voltage AC (5 min)

3.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹⁴ Ω·cm

Shield

None as standard (can be added)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage

1.2 kV AC

—

Test voltage AC (5 min)

3.5 kV

Routine test

DC resistance @20 °C

≤ 0.0991 Ω/km per core

GB/T 3956 Class 2 Cu max (185 mm²)

AC resistance @90 °C (est.)

≈ 0.127 Ω/km per core

—

Current rating in air (30 °C)

3-phase: 360 A​

4×185, touching, in free air

Current rating in tray (30 °C)

3-phase: 400 A​

4×185, spaced 2×OD

Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W)

3-phase: 375 A​

direct buried

Current rating in conduit (30 °C)

3-phase: 320 A​

—

Short-circuit current (1 s, Cu, 250 °C)

≈ 20.5 kA (20,500 A) per core

—

Capacitance (core-to-sheath, approx.)

≈ 0.23 µF/km

XLPE

Inductive reactance (approx.)

≈ 0.09 Ω/km

at 50 Hz

Frequency

50/60 Hz AC

—


Reference values: 4×185 at 360 A three-phase, 400 V → max load ≈ 216 kW​ (cos φ = 0.8). Suitable for medium-to-heavy distribution, large motors, and building main feeders.


4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame spread control, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Min. installation ambient temp.

0 °C (below 0 °C requires preheating)

Service ambient range

−20 °C to +90 °C

Flexing temp. range

0 °C to +90 °C

Fire Performance (ZC-YJV — Flame Retardant C)

Property

Value / Requirement

Flame retardant

GB/T 18380.12 / IEC 60332-1-2​ (single cable, self-extinguishing)

Flame retardant class

Class C​ (ZC) per GB/T 19666

Halogen content

Contains halogen (PVC sheath)

Smoke density

Not low-smoke (PVC)

Corrosivity

Corrosive (PVC)

Toxicity

Toxic fumes when burned (PVC)

EMI shielding

None (no metallic screen/armour)


5. Installation Practice & Handling. 185 mm² lugs on four cores, glands to ≈33.5 mm OD, hydraulic crimp/torque per table; bend ≥ 15×OD ≈ 500 mm with rollers; apply bundle derating; keep the 2+2 bundle round; four-core continuity, phase sequence, neutral + insulation after pulling.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 698 mm at Ø46.5 mm

four-core unarmoured

Max. pulling tension

2,775 N per core (185 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Suitable (with sand bedding)

—

Surface mounting

Heavy-duty cable tray, ladder, cleats

—

Conduit ID

≥ 90 mm

—

Fixing

heavy-duty cleats, cable ties

—

Impact resistance

Moderate

—

Water resistance

Good (PVC sheath)

—

UV resistance

Fair (PVC degrades outdoors, use UV-resistant PVC or conduit)

—

Flex life

Fair (Class 2 stranded, large conductor)

fixed installation

Termination note

Heavy-duty compression lugs or mechanical connectors

—


6. Typical Service Applications. Building main-to-floor-cabinet feeders and riser branches, elevator and HVAC compressor circuits, pump groups, and balanced three-phase distribution branches.


ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution


7. Testing & QA Regime (16 items). Routine: all-core DC resistance (185), 3.5 kV withstand, insulation resistance, four-core continuity, sheath/insulation thickness, dimensional check, strand construction, core balance, eccentricity, print legibility, mass, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.


Cable Parameters


ZC-YJV 4×185 mm² — LV Flame-Retardant 4-Core Power Cable — Full Parameter Sheet
4×185 Cu equal cores (L1/L2/L3/N) · XLPE insulation / PVC sheath · ZC · 0.6/1 kV · ≈34 mm · 2+2 lay · 380/400 V secondary feeder, sub-main riser and motor circuit supply
Parameter Value Unit Remarks / Standard
01 · Identification
Cable type ZC-YJV — Cu/XLPE/PVC, flame-retardant class C — ZC-YJV denotes a copper conductor with cross-linked polyethylene insulation and a PVC outer sheath; ZC marks a class C flame-retardant PVC compound that self-extinguishes after the ignition source is removed.
Rated voltage (U0/U) 0.6/1 kV 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines a general low-voltage cable suited to 380/400 V sub-main distribution.
Maximum operating voltage (Um) 1.2 kV The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service.
Core configuration 4×185 (L1 / L2 / L3 / N), equal size, 2+2 lay — Four equal 185 mm² compacted copper cores — three phases plus a full-size neutral — laid 2+2 for balanced and non-linear sub-main loads.
Conductor material Compacted stranded annealed copper — Soft annealed copper strands are layer-compacted into equal round 185 mm² bundles for medium-large lug entry.
Insulation XLPE cross-linked polyethylene — Chemically cross-linked polyethylene bonds into a heat-resistant dielectric retaining properties at the 90 °C operating temperature.
Sheath PVC, flame-retardant class C (ZC) — A heavy overall PVC jacket binds the four-core bundle and carries the class C flame-retardant formulation; deep slate blue finish.
Flame retardancy ZC class C (self-extinguishing, not fire-rated) — On removal of a flame the cable stops propagating fire; this is flame retardancy, not 950 °C/180 min circuit-integrity fire resistance.
Suitable for Fixed sub-main tray, riser, duct, 3-phase+full neutral — Designed for fixed three-phase-plus-neutral sub-main feeders serving distribution panels and motor groups.
Application 380V sub-main feeder / sub-distribution riser — Typically runs four equal cores from a main board to a sub-distribution riser, large motor feeder or panel group.
Application note Not for 950°C circuit-integrity fire duty — Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire.
02 · Conductors
Cores count / area 4 × 185 (L1/L2/L3/N) mm² Four equal 185 mm² conductors: three phases and a full-size neutral for moderate-heavy unbalanced and harmonic current.
Conductor type Compacted stranded Cu, Class 2 — Class 2 stranded compacted construction gives fixed-wiring conductors that round into stable bundles for lug termination.
DC resistance (185) @ 20°C ≤ 0.0991 Ω/km Maximum permitted DC resistance of an 185 mm² copper conductor at 20 °C, identical for all four equal cores.
Stranding Layer-compacted concentric bundle — Concentric layers of strands are compacted radially per core to reduce gaps, tighten the bundle and present a clean round lug entry.
Strands (nom., est.) ≈37 strands per core — Approximate strand count around 37 compacted strands in an 185 mm² core; exact count follows the conductor standard.
Surface Bare copper; tinned optional — Bare copper suits most indoor use; optional tinned plating improves corrosion resistance in damp or chemically mild sites.
Core identification L1/L2/L3/N color code, equal size — All four cores share the same 185 mm² section and are color-coded so phase sequence and neutral match at the panel.
Nominal area tolerance Within conductor class 2 band — Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count.
Neutral sizing Full-size 185 mm² (equal to phases) — The equal-size neutral protects against third-harmonic and unbalanced heating on sub-main motor and non-linear loads.
Compaction benefit Round bundle, lower OD, clean crimp — Radial compaction reduces overall diameter versus loose stranding and gives a flat, even lug crimp.
03 · Insulation
Insulation material XLPE (cross-linked polyethylene) — Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than PVC insulation for the same size.
Insulation thickness (nom.) ≈ 2.4 mm Thick nominal radial insulation wall on each equal 185 mm² core; gauged to withstand the 3.5 kV routine test.
Working conductor temp. 90 °C Maximum continuous conductor temperature under rated current without shortening insulation life.
Short-circuit temp. 250 °C Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs.
Insulation resistance High and stable MΩ·km XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on sub-main feeders.
Color L1/L2/L3/N color on request — Insulation colors are matched to local 3-phase convention or supplied natural with printed marking.
Cure type Chemical / dry-cured XLPE — A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat.
Insulation symmetry Equal wall on all four cores — Uniform insulation thickness keeps the four equal cores electrically balanced.
04 · Sheath & Flame Retardancy
Sheath material PVC, flame-retardant ZC — The heavy class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface.
Sheath thickness (nom.) ≈ 2.4 mm Nominal overall jacket wall sized to shield the four medium-large cores from abrasion, mechanical handling and duct damage.
Finished outer diameter ≈ 34 mm Overall four-core medium-heavy finished diameter used to size ducts, trunking and glands.
Flame behavior Self-extinguishing, class C — After the test flame is removed the sample extinguishes without propagating; it is not 950°C fire-rated.
Sheath color Deep slate blue (black/gray on request) — Standard deep slate blue; black or dark gray jackets are supplied for industrial aesthetics on request.
Surface finish Smooth, continuous print — A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length.
05 · Electrical
Rated voltage (U0/U) 0.6/1 kV Low-voltage rating matching 380/400 V sub-main distribution systems.
Max voltage (Um) 1.2 kV Continuous upper system voltage for phase-to-earth insulation stress.
Nominal current (per 185 core, est.) ≈ 380 A Approximate ampacity of a single 185 mm² core in free air at 30 °C; reduce for bundling, duct fill and high ambient.
Test voltage (AC) 3.5 kV / 5 min — Routine dielectric withstand applied between each conductor and sheath for five minutes without breakdown.
Insulation resistance High, XLPE MΩ·km Measured after conditioning; confirms no void, crack or contamination in the cured insulation.
Short-circuit current (185, 1s, est.) ≈ 16 kA Approximate 1-second copper short-time withstand on the 185 mm² core; sub-main fault duty.
Frequency 50 / 60 Hz Compatible with both 50 Hz and 60 Hz three-phase power systems.
Dielectric XLPE, low loss — Low dielectric loss keeps heating down under continuous sub-main feeder and riser load.
06 · Thermal & Environment
Normal conductor temp. 90 °C Sustained operating temperature the XLPE insulation is rated for under full load.
Installed ambient 0 ~ +40 °C Recommended continuous ambient around the cable; high rooms and crowded trays require ampacity derating.
Min install temp. 0 °C Avoid cold bending below 0 °C where the PVC jacket and insulation may stiffen and crack.
Burning Self-extinguishing, ZC class C — Class C vertical flame test behavior: flame stops once the external burner is removed.
Outdoor / UV Indoor preferred; UV-grade jacket optional — Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor risers.
Oil / chemicals Resistant to common oils; check aggressive media — Withstands typical machine oils; verify against specific solvents or acid fumes before use.
Temperature cycle Withstands repeated 0~90°C duty — The insulation and jacket survive repeated heating/cooling cycles without cracking or delamination.
07 · Mechanical & Construction
Min bending radius (fixed) ≥ 15 × OD ≈ 510 mm Fixed-installation minimum bend radius for the four-core cable; tight bends risk insulation and jacket damage.
Flexibility Stranded, handled with rollers — Compacted strands remain manageable but large cores benefit from rollers and mechanical help on site.
Shielding / Armor None / unarmored (armor optional) — No copper braid screen and no armor as standard; add steel-tape or wire armor where ground crushing or EMI exists.
Cable weight per km (est.) ≈ 6400 kg/km Heavy mass per kilometer used for structural tray loading and drum sizing.
Circularity 2+2 four-core bundle, stable OD — Four equal cores laid 2+2 form a round bundle so the finished OD stays consistent.
Tensile / elongation Jacket meets PVC grade — Jacket tensile strength and elongation satisfy the PVC compound grade for rugged pulling.
08 · Factory Advantages
Equal-size 4-core build L1/L2/L3/N all 185 mm² for harmonic load — Full-size neutral handles third harmonics and sub-main unbalance without overheating.
Stable XLPE cure Even cross-linking keeps the 90°C dielectric consistent — Controlled cure prevents soft spots in insulation under sustained feeder load.
Dosed ZC compound Flame-retardant PVC self-extinguishes to class C — Dosed flame inhibitors protect panel rooms and sub-main wiring spaces.
Length-on-demand Cut to exact riser/feeder meter, sealed ends — Custom cut lengths match the measured riser and horizontal feeder route.
Batch resistance log All four core R logged against lot — Every equal-core resistance is recorded against batch ID for full traceability.
Continuous print line Type, size, ZC, voltage and length along jacket — Clear continuous marking lets installers read the spec on medium-heavy cables.
Phase-color option L1/L2/L3/N insulation colors matched to convention — Pre-colored equal cores remove wiring guesswork at panel terminals.
Reinforced drum pack Industrial wooden drum with sealed ends — Sub-main length wound on a sound drum suitable for winch or manual pulling.
Certified QA pack Routine + type test record shipped per batch — A complete QA packet supports buyer audit, inspection and commissioning sign-off.
09 · Installation
Laying Sub-main tray, riser, duct, 3-phase+N — Route on rated trays or risers; keep the 2+2 bundle round and bending above 15×OD.
Connectors 185 mm² lugs on all four cores — Crimp matched 185 mm² lugs on phases and neutral; select glands sized to 34 mm OD.
Bend radius ≥ 15×OD ≈ 510 mm — Maintain the large minimum radius around riser bends to prevent insulation cold-working.
Parallel runs Derating in bundles and ducts — Adjacent cores share heat; apply bundle derating before sizing the sub-main breaker.
Site test Continuity + insulation post-laying — After pulling, verify four-core continuity, phase sequence, neutral and insulation resistance.
Termination Strip, hydraulic crimp lug, torque per table — Strip insulation without nicking strands, use a hydraulic press on each lug, and torque per the lug table.
10 · Packing & Applications
Supply length Custom / industrial wooden drum m Cut to the measured sub-main feeder length on a sound drum.
Length tolerance Per trade standard for cut lengths — Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise.
Reel type Industrial wooden drum — Drum for heavy sub-main lengths; sealed ends prevent moisture ingress.
Surface marking ZC-YJV, 4×185, 0.6/1kV, ZC, length — Jacket prints type, core size, voltage, flame class and cumulative meter length.
Typical use Sub-main feeder, sub-riser, large motor circuit — Runs four equal cores to sub-distribution boards and motor feeders.
Storage Dry indoor on drum supports, avoid UV — Store the drum horizontally on timber supports, dry and shaded, avoiding direct sunlight.


Cable Test Parameters


Test Parameters — ZC-YJV 4×185 LV Flame-Retardant 4-Core Cable 
No. Test Item Test Condition / Method Requirement Type
1 DC resistance (all 4 cores) 20 °C, each L1/L2/L3/N (185 mm²) ≤0.0991 Ω/km Routine
2 Voltage test (AC) 3.5 kV AC, 5 min, core-to-sheath No breakdown Routine
3 Insulation resistance XLPE, 20°C, per core High & stable Routine
4 Continuity Each core L1/L2/L3/N Continuous Routine
5 Flame retardancy Class C vertical test Self-extinguish Type
6 Sheath thickness Micrometer, cross-section Nominal ≈2.4 mm Routine
7 Insulation thickness Micrometer, 185 mm² cores Nominal ≈2.4 mm Routine
8 Dimensional check Caliper, overall OD OD ≈ 34 mm Routine
9 Conductor construction Visual / strand count per core Class 2 compacted Routine
10 Short-circuit rating Calculated / type 16 kA / 1 s Type
11 Insulation eccentric test Cross-section measure per core Within tolerance Routine
12 Printing legibility Visual Marking readable Routine
13 Mass per unit length Weigh / calculate ≈ 6400 kg/km Routine
14 Core balance check Resistance compare across 4 cores Balanced within band Routine
15 Sheath mechanical Tensile / elongation check Meets PVC grade Type
16 Packing & drum inspection Visual / drum condition Sealed ends, sound drum Routine


Cable Cross Section Structure


ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

ZC-YJV 4×185 — 4-Core 2+2 Cross-Section Construction Diagram (Schematic, Expanded)
4×185 equal Cu cores (L1/L2/L3/N) / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈34 mm · sub-main feeder, sub-riser & large motor circuit
No. Layer / Feature Material / Construction Nominal Thickness (mm) Diameter (mm) Detailed Function / Remarks
1 Conductor L1 — phase 1×185 compacted Cu, Class 2, ≈37 strands — ≈ 12.4 Phase 1 core, DC R ≤0.0991 Ω/km @20°C; sub-main current.
2 Conductor L2 — phase 1×185 compacted Cu, Class 2, ≈37 strands — ≈ 12.4 Phase 2 core, equal size/resistance for balanced impedance.
3 Conductor L3 — phase 1×185 compacted Cu, Class 2, ≈37 strands — ≈ 12.4 Phase 3 core, equal spec; color-coded for phase sequence.
4 Conductor N — neutral 1×185 compacted Cu, Class 2, equal size — ≈ 12.4 Full-size neutral, same R as phases; handles harmonics/unbalance.
5 Strand compaction Concentric layers rolled compact per core — — Radial compaction closes gaps for round bundles and clean lug entry.
6 XLPE insulation (all cores) Dry-cured cross-linked PE, ≈2.4 mm ≈ 2.4 ≈ 17.2 Thick 90°C dielectric on each equal core, low loss, balanced wall.
7 2+2 core laying Four equal cores in two rows of two — — 2+2 arrangement stabilizes the bundle before sheathing.
8 PVC ZC sheath Class C jacket, ≈2.4 mm ≈ 2.4 ≈ 34 Binds the four-core bundle and self-extinguishes to class C.
9 Jacket print Continuous type/size/voltage/length line — — Marking: ZC-YJV, 4×185, 0.6/1kV, ZC, cumulative length.
Key Dimensions, Electrical & Mechanical Properties (expanded)
Finished cable diameter ≈ 34 mm Four-core medium-heavy overall OD for ducts and glands.
Approx. cable mass (est.) ≈ 6400 kg/km Heavy sub-main feeder; industrial drum.
Nominal voltage rating 0.6/1 kV Matches 380/400 V systems.
Max voltage (Um) 1.2 kV Phase-to-earth continuous upper limit.
Normal conductor temp. 90 °C Continuous load temperature of XLPE.
Short-circuit temp. 250 °C Short-time fault peak before insulation damage.
DC resistance (185, all cores) ≤ 0.0991 Ω/km Per equal core @20°C.
Neutral sizing Full 185 equal to phases — For harmonics and sub-main unbalance.
Nominal core current (est.) ≈ 380 A Per 185 core, free air 30°C; derate bundled.
Short-circuit rating (1s, est.) ≈ 16 kA Sub-main feeder fault duty.
Flame retardancy ZC class C, self-extinguishing — Not 950°C fire-rated.
Min bending radius (fixed) ≥ 15 × OD ≈ 510 mm Four-core riser bend radius.
Frequency 50 / 60 Hz Compatible with both power systems.
Insulation resistance High & stable MΩ·km XLPE; supports earth-fault detection.
Dielectric loss Low — XLPE keeps heating down on feeder load.
Temperature cycle 0~90°C repeated — Survives heating/cooling without cracking.
Sheath mechanical Jacket meets PVC grade — Tensile/elongation checked at type test.
Pack choice Industrial wooden drum — Sound drum with sealed ends.
Core configuration 4×185 (L1/L2/L3/N), 2+2 — Four equal cores.
Application Sub-main feeder, sub-riser, motor circuit — 380/400 V distribution 3-phase+N power.
Schematic — not to exact scale. OD ≈34 mm, weight ≈6400 kg/km, core ampacity ≈380 A free air at 30°C and ≈16 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 4×185 serves 380/400 V sub-main feeders, sub-risers and large motor circuits; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch.


Cable Construction Description


Construction Description — ZC-YJV 4×185 LV flame-retardant 4-core cable 
4×185 equal Cu cores (L1/L2/L3/N) / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈34 mm · sub-main feeder, sub-riser & large motor circuit
1. Product Identity & Ratings
ZC-YJV 4×185 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; four equal 185 mm² cores (L1/L2/L3/N) laid 2+2. OD ≈34 mm, ≈6400 kg/km (est.), ≈380 A per core free air at 30°C (est.), industrial wooden drum. It is a fixed sub-main feeder cable, not a flexible cord and not a 950°C fire-rated circuit.
2. Copper Conductors (4 equal 185 mm² cores)
Four equal compacted Class 2 Cu cores (L1/L2/L3/N), R ≤0.0991 Ω/km @20°C; full-size neutral equals phases to carry third harmonics and sub-main unbalance; tinned plating optional; phase-color insulation on request.
3. Strand Compaction & 2+2 Bundle
Concentric strands are rolled compact per core to close gaps and give clean lug entry; four equal cores lay in two rows of two (2+2) to stabilize the round bundle before sheathing.
4. XLPE Insulation
Dry-cured cross-linked PE ≈2.4 mm on every equal core; stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; balanced wall keeps all cores electrically equal.
5. Core Identification
L1/L2/L3 phases and the N neutral are identified by insulation color; because all four cores are equal size, color alone separates phase from neutral at the panel terminal.
6. PVC ZC Sheath
Class C flame-retardant PVC ≈2.4 mm overall, self-extinguishing; deep slate blue standard (black/gray on request); smooth printable surface; binds the four-core bundle and shields from abrasion and duct damage.
7. Electrical Characteristics
0.6/1 kV, Um 1.2; R ≤0.0991 Ω/km on all four equal cores; routine 3.5 kV AC/5 min; ≈380 A per core (est., air 30°C); short-circuit ≈16 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE.
8. Factory Advantages
• Equal-size 4-core build (full-size neutral).  • Stable XLPE cure.  • Dosed ZC self-extinguish.  • Length-on-demand.  • All-core resistance log.  • Continuous clear print.  • Phase-color option.  • Reinforced drum pack.  • Certified QA pack.
9. Site Handling & Installation
• Bend 15×OD (≈510 mm) with rollers.  • 185 mm² lugs on all four cores, glands to 34 mm OD, hydraulic crimp, torque per table.  • Derating in bundles/ducts.  • Keep 2+2 bundle round.  • Four-core continuity, phase sequence, neutral + insulation after pulling.
10. Typical Service Applications
380/400 V main-board-to-sub-board feeders and sub-risers, large motor circuits, distribution panel groups and non-linear load branches such as VFD and UPS sub-circuits.
11. Testing & QA
16-item regime: routine all-core DC resistance (185), 3.5 kV withstand, insulation resistance, four-core continuity, sheath/insulation thickness, dimensional check, strand construction, core balance, eccentricity, print legibility, mass, packing inspection; type ZC flame, short-circuit, sheath mechanical.
12. Packaging, Storage & Notes
Cut to measured sub-main length on an industrial wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated.


8. Factory Advantages.

  • Balanced equal-core layout — 4×185 identical for balanced three-phase branches.
  • Dry-cured XLPE control — consistent cure batch-by-batch for stable dielectric.
  • Class C jacket compound — dosed flame inhibitor for wiring-shop safety.
  • Custom cut length — measured riser/feeder meter, sealed ends.
  • Per-core resistance certificate — L1/L2/L3/N values logged to lot.
  • Continuous line printing — type, section, ZC, voltage, length readable.
  • Color coordination option — insulation colors matched to project schedule.
  • Sound drum delivery — industrial wooden drum, sealed cable ends.
  • Full QA documentation — routine plus type-test record per batch.

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution


9. Packaging, Storage & Logistics. Cut to measured branch length on an industrial wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.


ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution


10. Procurement Specification. State "ZC-YJV 4×185 (v2)", length, class C, phase colors, armor if required, drum; note flame retardant not fire-rated; request per-core resistance certificate and 16-item QA record. Est. values confirmed against the factory certificate.


11. Cable Industry FAQ.

  • Q1: How does v2 differ from the first 4×185? Same 4×185 2+2 standard and R ≤0.0991, but a refined build: slightly slimmer OD (33.5 vs 34 mm), lighter (6200 vs 6400 kg/km), conservative ampacity (370 vs 380 A), teal-olive jacket, and a building floor-feeder application focus rather than general plant feeders.
  • Q2: Why a full-size neutral? Branch VFD, UPS and LED loads generate third harmonics; an equal neutral prevents neutral overheating at the floor cabinet.
  • Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
  • Q4: DC resistance? ≤ 0.0991 Ω/km on every 185 mm² core at 20°C.
  • Q5: Armor or screen? Unarmored standard; add steel armor for ground crushing and braid screen for EMI.
  • Q6: Current per core? ≈ 370 A (est.) free air 30°C; derate on bundled trays and ducts.
  • Q7: Bending? ≥ 500 mm (15×OD); use rollers around riser elbows.
  • Q8: Connectors? 185 mm² lugs on four cores, hydraulic press, gland to ≈33.5 mm OD.
  • Q9: Indoor or outdoor? Indoor preferred; UV-stabilized jacket for exposed routes.
  • Q10: Packing? Industrial wooden drum with sealed cable ends.
  • Q11: What proof ships? Per-core resistance certificate + 16-test record; est. values confirmed against certificate.