ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 4*185mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

ZR-YJV 4*185mm² Flame Retardant 4 Core Copper Power Distribution Cable Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath — flame-retardant grade, contains halogen ...

Product Details

Highlight:

ZR-YJV 4 core electrical cable

,

4 core electrical cable 4x185mm2

,

copper power wire 300mm2

Conductor (×4):
Bare Annealed Copper, Class 2 Stranded, Commonly 37×∅2.52 Mm (also 19×∅3.55 Mm Compact / 36×2.55 Mm), Conductor Ø ≈ 16.8–18.5 Mm Depending On Compaction
Conductor nominal area:
185 Mm²
Number of cores:
4
Conductor construction:
Class 2, 37×∅2.52 Mm,IEC 60228 / GB/T 3956, Min. 15 Wires
Conductor diameter:
16.8–18.5 Mm
Insulation (×4):
XLPE
Insulation thickness:
1.6 Mm (185 Mm² Class)
Diameter over insulated core:
20.0–21.7 Mm,conductor + 2×1.6
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
2.4 Mm (GB/T 12706 Multi-core 150–300 Mm² Range)
Overall cable diameter:
45.0 – 52.0 Mm
Design outer diameter:
≈ 48.0 Mm
Approx. weight:
6200 – 7800 Kg/km
Design weight:
≈ 6700 Kg/km
Cable shape:
Round

Product Description

ZR-YJV 4*185mm² Flame Retardant 4 Core Copper Power Distribution Cable

 

Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×185 mm²

Four cores, nominal copper conductor area 185 mm² per core

ZR-YJV 4×185 mm² — Cable Engineering Data

1. Product Scope & Ratings. ZR-YJV 4×185 — flame-retarding four-core cable, four 185 mm² Cu conductors, XLPE insulation, one ST2 PVC sheath, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; manufactured and tested per GB/T 12706.1 / IEC 60502-1, conductor grading per GB/T 3956, ZC flame class per GB/T 19666. ≈ 56.8 mm, ≈ 8034 kg/km (Al ≈ 3310), 100 m coils/drums.

 

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

 

2. Construction Stack. Conductor → outer sheath:

 

Layer Build Wall Diameter
Conductor (×4) Annealed Cu, Class 2, 37 × 2.52 mm (1+6+12+18) each — ≈ 17.60 mm
Insulation (×4) XLPE 1.6 mm ≈ 20.80 mm
Lay-up Four cores + central filler + binder tape — ≈ 50.2 mm (calc.)
Sheath Flame-retarded PVC, ST2, black 2.4 mm ≈ 56.8 mm

 

 

3. Electrical Ratings. R ≤ 0.0991 Ω/km @ 20 °C; routine 3.5 kV / 5 min; insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km. Reference ampacity (four cores loaded) ≈ 375 A air / 390 A buried @ 25 °C — Mingda 4×185, cross-checked with 3×185 (identical per-core values).

 

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.0991 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.129 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core)

≈ 390–420 A

common catalogue value

Current rating in air (design)

≈ 400 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 410–460 A

common catalogue 420–450 A

Design buried rating

≈ 435 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 18.5 kA

reference

Frequency

50/60 Hz AC

—

 

4. Thermal & Fire. 90 °C continuous, 250 °C short-circuit (≤ 5 s); −20~+45 °C ambient, ≥ 0 °C laying; ZC per GB/T 19666 — GB/T 18380.12 single-burn + GB/T 18380.35 class-C bunched (char ≤ 2.5 m); PVC is halogen-bearing → WDZ-YJY for LSZH.

 

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

 

ZR-YJV 4×185 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.0991 Ω/km @ 20 °C (per core) Every production length
Routine Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor-to-earth/water
Routine Construction check GB/T 2951 Ins. ≥ 1.6 mm; sheath ≥ 2.4 mm; OD within tolerance Thickness & diameter
Sample Hot set test — XLPE GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking degree
Sample Conductor construction & diameter GB/T 3956 Class 2; 37 × 2.52 mm; Ø ≈ 17.60 mm Per batch
Type Single-cable flame test GB/T 18380.12 No flame spread to top reference ZR property
Type Bunched flame test — class C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m ZC class
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core rule
Post-install DC withstand test Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown New installations
Optional Insulation resistance @ 20 °C Factory method ≥ 36.7 MΩ·km Not routine in GB/T 12706.1
Optional XLPE volume resistivity Material test ≥ 1 × 10¹² Ω·cm Material reference

 

5. Installation & Care. Bend ≥ 15 × OD; DC site test 4U0 = 2.4 kV / 15 min before energising (Q/GDW 13244.1-2018); pre-heat drums below 0 °C; de-rate 375/390 A for ambient, grouping, burial; lugs/glands for the 17.60 mm core.

 

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

 

6. Flame Retardant Test Parameters

 

Technical Datasheet — Flame-Retardant (FR) Characteristics
ZR-YJV  0.6/1 kV  4 × 185 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Code / Item Meaning / Value Standard / Note
ZR Flame Retardant (legacy prefix); under GB/T 19666-2019 defaults to Class C; modern equivalent = ZC GB/T 19666-2019
YJ XLPE — cross-linked polyethylene insulation —
V PVC outer sheath — flame-retardant grade, contains halogen (Cl) GB/T 19666-2019
0.6/1 kV Rated voltage U₀/U = 600/1000 V; maximum Uₘ = 1.2 kV IEC 60502-1
4 × 185 mm² Four cores, nominal copper conductor area 185 mm² per core (all cores equal) —
Construction Unarmoured, non-screened, round multi-core —
Application note Four-core → three-phase AC with neutral (L1+L2+L3+N) or with PE (L1+L2+L3+PE), equal conductor sizes —
2.  Flame-Retardant & Fire Performance  (CORE)
Property Value / Requirement Standard
Flame Retardant Class Class C (bundled cables, char length ≤ 2.5 m) GB/T 19666-2019; GB/T 18380.3 / IEC 60332-3-24
Legacy designation ZR (= ZC); modern prefix preferred: ZC GB/T 19666-2019
Test method — flame Bunched flame test (category C), char ≤ 2.5 m after flame removal GB/T 18380.3 (IEC 60332-3-24)
Halogen content Contains halogen — Cl from PVC sheath; releases HCl on burning GB/T 17650 / IEC 60754-1/-2
Smoke density Heavy dark smoke — NOT low-smoke (no LSZH certification) GB/T 17651 / IEC 61034
Corrosivity Corrosive — HCl gas generated during fire GB/T 17650 / IEC 60754-2
pH / conductivity of gases Not certified (PVC base — acidic / conductive combustion gases) GB/T 17650 / IEC 60754-2
Limited Oxygen Index (LOI) PVC typical ≈ 45–49 % O₂ (reference, design value) ASTM D2863 / GB/T 2406, reference
Max. conductor operating temp. 90 °C (long-term service) GB/T 12706.1-2020
Max. short-circuit temp. (≤5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) IEC 60502-1
Service ambient range (PVC sheath) −15 °C to +90 °C —
Min. installation ambient temp. 0 °C (pre-heat required below 0 °C) —
Note: ZR = Flame Retardant only — it does NOT imply low-smoke (LSZH) or fire-survival. PVC sheath is halogenated; upgrade to WDZ-YJY / WDZN-YJY for LSZH or NH-ZR-YJV for fire-survival circuits.
3.  Fire Test Summary
Test Requirement ZR-YJV 4×185 Verdict
Bunched flame test (Class C) Char length ≤ 2.5 m PASS (design, Class C)
Single flame test (IEC 60332-1) Self-extinguishing PASS (XLPE/PVC FR)
Smoke density (IEC 61034) Light transmittance ≥ 60 % for LSZH N/A (PVC = heavy smoke)
Halogen content (IEC 60754) ≤ 0.5 % HCl for LSZH N/A (contains Cl)
Acidity / corrosivity (IEC 60754-2) pH ≥ 4.3; conductivity ≤ 10 µS/mm for LSZH N/A (corrosive HCl)
Fire-survival (BS 6387 / IEC 60331) Circuit integrity during/after fire N/A — use NH-ZR-YJV / WDZN-YJY
4.  Key Electrical & Thermal Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.0991 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.129 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 390–420 A (design ≈ 400 A) 4-core
Current rating — direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) ≈ 410–460 A (design ≈ 435 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 18.5 kA reference
Frequency 50/60 Hz AC —
Design recommendation: ≈ 400 A in air / ≈ 435 A buried, then apply grouping & ambient + soil-thermal-resistivity correction. Buried rating often > air rating due to better heat dissipation under reference conditions. Catalogue values vary by maker — confirm before specification.
5.  Construction & Material Specification
Layer (inside → out) Description / Specification FR Contribution
Conductor (×4) Bare annealed copper, Class 2 stranded, 37×∅2.52 mm, conductor Ø ≈ 16.8–18.5 mm None (Cu non-combustible)
Conductor screen Omitted (not required for 0.6/1 kV) —
Insulation (×4) XLPE, colours: brown/black/grey/blue etc., 1.6 mm nominal XLPE — low flame spread
Filler Flame-retardant PP / PE to form round assembly FR additive
Binder Flame-retardant tape over laid-up cores FR barrier
Outer sheath Flame-retardant PVC (ZR grade), 2.4 mm nominal, black Primary FR layer (halogenated)
Armour None —
Metallic screen None —
6.  Dimensional Data
Item Typical Value Remarks
Conductor nominal area (per core) 185 mm² —
Number of cores 4 —
Conductor construction Class 2, 37×∅2.52 mm IEC 60228 / GB/T 3956, min. 15 wires
Conductor diameter (approx.) 16.8–18.5 mm compact vs solid-round
Insulation thickness 1.6 mm 185 mm² class
Diameter over insulated core 20.0–21.7 mm conductor + 2×1.6
Sheath thickness 2.4 mm GB/T 12706, 150–300 mm² range
Overall cable diameter ≈ 46.0–50.0 mm (catalogue range 45.0–52.0 mm) plain-round design
Design outer diameter ≈ 48.0 mm common Chinese maker value
Approx. weight 6200 – 7800 kg/km (plain YJV Cu ≈ 6400–7000) design ≈ 6700 kg/km
Cable shape Round —
     
7.  Mechanical & Installation Parameters
Parameter Value Note
Minimum bending radius (unarmoured multi-core) ≥ 15 × OD ≈ 675–720 mm @ Ø45–48 mm (≈ 720 mm @ 48 mm) —
Max. pulling tension (Cu only) 50 N/mm² × 185 mm² × 4 = 37,000 N = 37 kN total use conductor sock, avoid sheath grip
Direct burial Allowed in non-aggressive soil; for mechanical load / road crossing use ZR-YJV22 4×185 —
Conduit ID ≥ 1.5 × OD → ≥ 68–72 mm (use 75 mm or 90 mm conduit) —
Fixing spacing Horizontal tray ≈ 800 mm; vertical ≈ 1500 mm —
Elevation difference limit None (XLPE) —
8.  Selection Guide — When FR Matters
Scenario Recommended Cable Reason
Flame-retardant, halogenated acceptable (standard) ZR-YJV 4×185 (this cable) Class C FR, PVC sheath, cost-effective
Low-smoke halogen-free required (LSZH) WDZ-YJY 4×185 LSZH sheath — IEC 61034 / IEC 60754 compliant
Fire-survival circuit (circuit integrity) NH-ZR-YJV / WDZN-YJY 4×185 BS 6387 / IEC 60331 fire-survival grade
Heavy mechanical load / buried under roads ZR-YJV22 4×185 Steel-tape armoured version
Separate PE and N required 5-core version (e.g. 5×185 or 4×185+1×95) 4×185 has combined/shared PE-N only
Applicable standards: GB/T 12706.1-2020 (equiv. IEC 60502-1) · GB/T 3956 / IEC 60228 · GB/T 19666-2019 · GB/T 18380.3 · GB/T 17651 / IEC 61034 · GB/T 17650 / IEC 60754.  |  Packing: steel-wooden drum or coil, 100–500 m typical.  |  HS code (China): 8544 4921.
Values are typical / design reference. Plain-round 185 mm² shows maker-to-maker dimensional variance (OD 45–52 mm, weight 6200–7800 kg/km) — always confirm with manufacturer test reports & relevant local regulations before final specification.

 

 

7.Cross Section Structure

 

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

 

Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 4 Annealed copper, Class 2 stranded — 37 × 2.52 mm per core (37/2.52, 1+6+12+18), nominal 185 mm² per core — ≈ 17.60 (Ø per core) Current-carrying element; max DC resistance ≤ 0.0991 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 4 Cross-linked polyethylene 1.6 ≈ 20.80 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Four insulated cores laid up around central non-hygroscopic filler; binder tape — ≈ 50.2 (Ø over lay-up, calc.) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 2.4 ≈ 56.8 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter ≈ 56.8 mm Mingda four-core unarmored table    
Approx. cable weight ≈ 8034 kg/km Mingda 8034 (Al ≈ 3310)    
Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV    
Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)    
Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter    
Flame-retardant class ZC (ZR) — GB/T 19666    
Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.

 

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

 

8. Application. Heavy distribution risers, plant rooms, large motor and transformer circuits, industrial sub-feeds — conduit, tray, trench, duct, trunking; indoor or sheltered outdoor.

 

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

 

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distribution

 

9. Ordering. ZR-YJV 0.6/1 kV 4×185 + length/drum + marking; confirm against factory test certificate.

 