Copper Conductor 4 Cores Cable ZR-YJV 4x240mm2 Flame Retardant Cable For Industrial
Product Summary
Product Details
Copper Conductor 4 Cores Cable
,4 Cores Cable ZR-YJV
,4x240mm2 Flame Retardant Cable
Product Description
Copper Conductor 4 Cores Cable ZR-YJV 4x240mm2 Flame Retardant Cable For Industrial
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
4×240 mm² |
Four cores of 240 mm² copper conductor each |
Construction: Four copper conductors, XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).
ZC-YJV 4×240 mm² — LV Flame-Retardant 4-Core Power Cable — Specification
1. Overview & Ratings. ZC-YJV 4×240 is a four-core (L1/L2/L3/N) LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant heavy PVC sheath. Four matched compacted 240 mm² copper cores laid 2+2, dry-cured XLPE, unarmored (armor optional). OD ≈ 38 mm, ≈ 7600 kg/km (est.), ≈ 460 A per core free air at 30 °C (est.). Scope: 380/400 V main feeders, busbar risers, large panel supply — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor L1/L2/L3 | 3×240 compacted Cu, Class 2, ≈61 strands | Phases, R ≤0.0754 Ω/km |
| Conductor N | 1×240 compacted Cu, Class 2, ≈61 strands | Equal-size neutral |
| Strand compaction | Concentric layers rolled compact per core | Round bundle, clean lug entry |
| XLPE insulation (4 cores) | Dry-cured PE, ≈2.6 mm each | 90°C dielectric |
| Core identification | L1/L2/L3/N color code | Phase sequence + neutral at panel |
| 2+2 core laying | Four cores rounded 2+2 | Stable heavy bundle |
| Heavy PVC ZC sheath | Class C, ≈2.4 mm overall | Binds cores, self-extinguishes |
| Jacket print | Continuous type/size/voltage/length | On-site readable spec |
3. Electrical Characteristics. Per-core R ≤ 0.0754 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 460 A per core (est., air 30 °C); short-circuit ≈ 21 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 0.0754 Ω/km per core |
GB/T 3956 Class 2 Cu max |
|
AC resistance @90 °C (est.) |
≈ 0.0967 Ω/km per core |
— |
|
Current rating in air (30 °C) |
4-core: 415 A |
four-core, touching, in free air |
|
Current rating in tray (30 °C) |
4-core: 455 A |
four-core, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
4-core: 435 A |
direct buried |
|
Current rating in conduit (30 °C) |
4-core: 375 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 26.6 kA (26,600 A) per core |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.24 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.09 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 4×240 at 415 A three-phase, 400 V → max load ≈ 288 kW (cos φ = 0.8). Suitable for main power distribution, large transformer connections, and heavy industrial feeders.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. 240 mm² Cu compression lugs, large glands, hydraulic crimp/torque per table; bend ≥ 15×OD ≈ 570 mm; use rollers and winch; derate bundled/duct runs; continuity, phase sequence, neutral + insulation after pulling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 825 mm at Ø55.0 mm |
four-core unarmoured |
|
Max. pulling tension |
3,600 N per core (240 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Cable tray, ladder, heavy-duty cleats |
— |
|
Conduit ID |
≥ 125 mm |
— |
|
Fixing |
heavy-duty cleats, cable ties |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Fair (Class 2 stranded, large conductor) |
fixed installation |
|
Termination note |
Heavy-duty compression lugs or mechanical connectors |
— |
6. Typical Service Applications. 380/400 V main switchboard feeders, vertical busbar risers, large distribution panel inputs, plant power mains and high-current panel supply in commercial and industrial buildings.

7. Testing & QA Regime (16 items). Routine: DC resistance L1/L2/L3/N, 3.5 kV withstand, insulation resistance, continuity, heavy sheath/thick insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass. Type: ZC flame test, short-circuit rating, sheath mechanical, 0~90°C cycle.
Cable Parameters
| ZC-YJV 4×240 mm² — LV Flame-Retardant 4-Core Power Cable — Full Parameter Sheet | |||
| 4×Cu / XLPE / PVC · ZC class C · 0.6/1 kV · ≈38 mm · four-core (L1/L2/L3/N) for 380/400V main feeds, busbar risers and large panel supply | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — Cu/XLPE/PVC, flame-retardant class C | — | ZC-YJV denotes a copper-conductor cable with cross-linked polyethylene insulation and a PVC outer sheath; the leading ZC marks a Chinese flame-retardant class C compound that self-extinguishes after the ignition source is removed. |
| Rated voltage (U0/U) | 0.6/1 | kV | 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines this as a general low-voltage power cable suited to 380/400 V main distribution. |
| Maximum operating voltage (Um) | 1.2 | kV | The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service. |
| Core configuration | 4×240 (L1 / L2 / L3 / N) | — | Four equal 240 mm² compacted copper cores laid 2+2: three phases and one neutral for heavy three-phase main feeds and panel supply. |
| Conductor material | Compacted stranded annealed copper | — | Soft annealed copper strands are layer-compacted into a large round bundle to lower skin effect, reduce diameter and give a clean entry into a 240 mm² lug. |
| Insulation | XLPE cross-linked polyethylene | — | Chemically cross-linked polyethylene bonds into a heat-resistant dielectric that keeps its properties at the 90 °C operating temperature. |
| Sheath | PVC, flame-retardant class C (ZC) | — | A heavy overall PVC jacket binds the 2+2 core bundle and carries the class C flame-retardant formulation; deep olive bronze-green finish. |
| Flame retardancy | ZC class C (self-extinguishing, not fire-rated) | — | On removal of a flame the cable stops propagating fire; this is flame-retardancy, not 950 °C/180 min circuit-integrity fire resistance. |
| Suitable for | Fixed indoor tray, duct, main distribution | — | Designed for fixed high-current three-phase wiring: main feeders, risers and large panel inputs. |
| Application | 380V main feeder / busbar riser | — | Typically runs three phases plus neutral from a main switchboard to a distribution panel or busbar riser. |
| Application note | Not for 950°C circuit-integrity fire duty | — | Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire. |
| 02 · Conductors | |||
| Power core count / area | 4 × 240 | mm² | Three phase cores plus one neutral, each 240 mm², carry heavy balanced 400 V feeder current. |
| Conductor type | Compacted stranded Cu, Class 2 | — | Class 2 stranded compacted construction gives a fixed-wiring large conductor that rounds into a stable bundle for clean lug termination. |
| DC resistance (240) @ 20°C | ≤ 0.0754 | Ω/km | Maximum permitted DC resistance of a 240 mm² copper conductor at 20 °C; low drop over long main feeder runs. |
| Stranding | Layer-compacted concentric bundle | — | Many concentric strand layers are compacted radially to reduce gaps, tighten the bundle and present a clean round entry into the lug. |
| Strands (nom., est.) | ≈ 61 compacted | — | Approximate number of compacted strands in a 240 mm² Class 2 bundle; exact count follows the conductor standard and factory drawing. |
| Surface | Bare copper; tinned optional | — | Bare copper suits most indoor main use; optional tinned plating improves corrosion resistance in damp or humid plant sites. |
| Core identification | L1 / L2 / L3 / N by color | — | The four cores are distinguished by insulation color so phase sequence and neutral match at the panel. |
| Nominal area tolerance | Within conductor class 2 band | — | Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count. |
| 03 · Insulation | |||
| Insulation material | XLPE (cross-linked polyethylene) | — | Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than ordinary PVC insulation for the same size. |
| Insulation thickness (nom.) | ≈ 2.6 | mm | Nominal radial insulation wall on each core; gauged to withstand the 3.5 kV routine test and the 90 °C heat load on a large feeder. |
| Working conductor temp. | 90 | °C | Maximum continuous conductor temperature under rated current without shortening insulation life. |
| Short-circuit temp. | 250 | °C | Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs. |
| Insulation resistance | High and stable | MΩ·km | XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on heavy feeders. |
| Color | L1/L2/L3/N color on request | — | Insulation colors are matched to local 3-phase convention (e.g. yellow/green/red/blue) or supplied natural with printed marking. |
| Cure type | Chemical / dry-cured XLPE | — | A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat. |
| 04 · Sheath & Flame Retardancy | |||
| Sheath material | PVC, flame-retardant ZC | — | The class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface. |
| Sheath thickness (nom.) | ≈ 2.4 | mm | Heavy nominal overall jacket wall sized to protect the four large cores from abrasion, crushing and mechanical handling. |
| Finished outer diameter | ≈ 38 | mm | Overall four-core finished diameter used to size heavy trunking, duct fill and large gland entry. |
| Flame behavior | Self-extinguishing, class C | — | After the test flame is removed the sample extinguishes without propagating along the cable; it is not 950°C fire-rated. |
| Sheath color | Deep olive bronze-green (black/gray on request) | — | Standard deep olive bronze-green; black or dark gray jackets are supplied for industrial plant aesthetics on request. |
| Surface finish | Smooth, continuous print | — | A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length. |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | Low-voltage rating matching 380/400 V main distribution systems. |
| Max voltage (Um) | 1.2 | kV | Continuous upper system voltage for phase-to-earth insulation stress. |
| Nominal current (per 240 core, est.) | ≈ 460 | A | Approximate ampacity of a single 240 mm² core in free air at 30 °C; reduce for bundling, duct fill and high ambient. |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine dielectric withstand applied between each conductor and sheath for five minutes without breakdown. |
| Insulation resistance | High, XLPE | MΩ·km | Measured after conditioning; confirms no void, crack or contamination in the cured large-core insulation. |
| Short-circuit current (240, 1s, est.) | ≈ 21 | kA | Approximate 1-second copper short-time withstand; the main feeder handles a substantial panel fault duty. |
| Frequency | 50 / 60 | Hz | Compatible with both 50 Hz and 60 Hz three-phase power systems. |
| Dielectric | XLPE, low loss | — | Low dielectric loss keeps heating down under continuous heavy feeder load. |
| 06 · Thermal & Environment | |||
| Normal conductor temp. | 90 | °C | Sustained operating temperature the XLPE insulation is rated for under full main load. |
| Installed ambient | 0 ~ +40 | °C | Recommended continuous ambient around the cable; high plant rooms require ampacity derating. |
| Min install temp. | 0 | °C | Avoid cold bending below 0 °C where the heavy PVC jacket and insulation may stiffen and crack. |
| Burning | Self-extinguishing, ZC class C | — | Class C vertical flame test behavior: flame stops once the external burner is removed. |
| Outdoor / UV | Indoor preferred; UV-grade jacket optional | — | Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor risers. |
| Oil / chemicals | Resistant to common oils; check aggressive media | — | Withstands typical plant oils; verify against specific solvents, alkalis or chemical fumes before use. |
| Temperature cycle | Withstands repeated 0~90°C duty | — | The insulation and heavy jacket survive repeated heating/cooling cycles without cracking or delamination. |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 570 | mm | Fixed-installation minimum bend radius for the heavy four-core cable; large radii protect the big cores and insulation. |
| Flexibility | Stranded, pulled with large drum gear | — | Compacted strands allow controlled pulling; large feeder runs require winches and proper rollers. |
| Shielding / Armor | None / unarmored (armor optional) | — | No copper braid screen and no armor as standard; add steel-tape/galvanized-wire armor where ground crushing risk exists. |
| Cable weight per km (est.) | ≈ 7600 | kg/km | Approximate heavy mass per kilometer; plan tray loading, drum capacity and lifting equipment. |
| Circularity | 2+2 core bundle, rounded under sheath | — | The four cores lay into a rounded 2+2 bundle so the finished OD stays consistent along the feeder. |
| Tensile / elongation | Heavy jacket meets PVC grade | — | Sheath tensile strength and elongation satisfy the heavy PVC compound grade for repeated handling. |
| 08 · Factory Advantages | |||
| Heavy balanced feeder | L1/L2/L3/N built to the same 240 mm² spec | — | Four equal cores keep phase and neutral impedance balanced on the main feeder. |
| Stable XLPE cure | Even cross-linking keeps the 90°C dielectric consistent lot to lot | — | Controlled cure on thick insulation removes soft spots that would age faster under continuous load. |
| Dosed ZC compound | Flame-retardant heavy PVC self-extinguishes to class C | — | Dosed flame inhibitors give a safety margin in main switchboard and riser wiring spaces. |
| Length-on-demand | Cut to exact feeder length, sealed ends | — | Custom long cuts match the measured riser or feeder route and minimize jointing. |
| Batch resistance log | Per-core DC R recorded against the lot number | — | Each core's resistance is logged against batch ID for feeder voltage-drop verification and audit. |
| Continuous print line | Type, size, ZC, voltage and length along heavy jacket | — | Clear continuous marking lets installers read the heavy feeder spec without a certificate on site. |
| Phase-color option | L1/L2/L3/N colors matched to convention | — | Pre-colored phases and neutral remove wiring guesswork at the main panel. |
| Heavy drum pack | Supplied on large timber drums for long feeders | — | Heavy-duty wooden drums suit the long, high-mass main feeder and riser pulls. |
| Certified QA pack | Routine + type test record shipped per batch | — | A complete QA packet supports main-contractor audit and energization sign-off. |
| 09 · Installation | |||
| Laying | Tray, duct, riser, main feeder | — | Route on heavy supports; use rollers and winch; keep the 2+2 bundle round and bending above 15×OD. |
| Connectors | 240 mm² Cu lugs, large glands | — | Crimp matched 240 mm² copper compression lugs on each core; select a large gland sized to the 38 mm OD. |
| Bend radius | ≥ 15×OD ≈ 570 mm | — | Maintain the large minimum radius around riser corners to prevent insulation cold-working. |
| Parallel runs | Derate when bundled in tray/duct | — | Adjacent heavy cores share heat; apply bundle derating before sizing the main feeder breaker. |
| Site test | Continuity + insulation post-laying | — | After pulling, verify four-core continuity, phase sequence, neutral and insulation resistance. |
| Termination | Strip, compress lug, torque per table | — | Strip insulation without nicking strands, use a hydraulic compressor on the lug, and torque per the lug table. |
| 10 · Packing & Applications | |||
| Supply length | Custom / large drum | m | Cut to the measured main feeder length; heavy timber drum packing. |
| Length tolerance | Per trade standard for cut lengths | — | Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise. |
| Reel type | Heavy wooden drum | — | Large drum for long high-current main feeders and busbar risers. |
| Surface marking | ZC-YJV, 4×240, 0.6/1kV, ZC, length | — | Jacket prints type, four-core size, voltage, flame class and cumulative meter length. |
| Typical use | Main feeder, riser, large panel supply | — | Runs three phases plus neutral to main panels and busbar risers. |
| Storage | Dry indoor on heavy support, avoid UV | — | Store the heavy drum horizontally on chocks, dry and shaded, to prevent jacket damage. |
Cable Test Parameters
| Test Parameters — ZC-YJV 4×240 LV Flame-Retardant 4-Core Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | 20 °C, each core L1/L2/L3/N | 240 ≤0.0754 Ω/km | Routine |
| 2 | Voltage test (AC) | 3.5 kV AC, 5 min, core-to-sheath | No breakdown | Routine |
| 3 | Insulation resistance | XLPE, 20°C, per core | High & stable | Routine |
| 4 | Continuity | Each core L1/L2/L3/N | Continuous | Routine |
| 5 | Flame retardancy | Class C vertical test | Self-extinguish | Type |
| 6 | Sheath thickness | Micrometer, cross-section | Nominal ≥2.4 mm | Routine |
| 7 | Insulation thickness | Micrometer, per core | Nominal ≥2.6 mm | Routine |
| 8 | Dimensional check | Caliper, overall OD | OD ≈ 38 mm | Routine |
| 9 | Conductor construction | Visual / strand count | Class 2 compacted | Routine |
| 10 | Short-circuit rating | Calculated / type | 21 kA / 1 s | Type |
| 11 | Insulation eccentric test | Cross-section measure per core | Within tolerance | Routine |
| 12 | Sheath appearance | Visual along length | Smooth, no flaw | Routine |
| 13 | Printing legibility | Visual | Marking readable | Routine |
| 14 | Mass per unit length | Weigh / calculate | ≈ 7600 kg/km | Routine |
| 15 | Sheath mechanical | Tensile / elongation check | Meets heavy PVC grade | Type |
| 16 | Temperature cycle | Repeated 0~90°C duty | No cracking | Type |
Cable Cross Section Structure

| ZC-YJV 4×240 — 4-Core Cross-Section Construction Diagram | |||||
| 4×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈38 mm · L1/L2/L3/N main feeders, busbar risers & large panel supply | |||||
| No. | Layer / Feature | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Detailed Function / Remarks |
| 1 | Conductor L1 — phase | 1×240 compacted Cu, Class 2, ≈61 strands | — | ≈ 18.5 | Phase 1 core, DC R ≤0.0754 Ω/km @20°C; heavy feeder current. |
| 2 | Conductor L2 — phase | 1×240 compacted Cu, Class 2, ≈61 strands | — | ≈ 18.5 | Phase 2 core, same size/resistance for balanced impedance. |
| 3 | Conductor L3 — phase | 1×240 compacted Cu, Class 2, ≈61 strands | — | ≈ 18.5 | Phase 3 core, same spec; color-coded for phase sequence. |
| 4 | Conductor N — neutral | 1×240 compacted Cu, Class 2, ≈61 strands | — | ≈ 18.5 | Equal-size neutral to carry unbalanced current on the feeder. |
| 5 | Strand compaction | Concentric layers rolled compact per core | — | — | Radial compaction closes strand gaps for a round bundle and clean lug entry. |
| 6 | XLPE insulation (4 cores) | Dry-cured cross-linked PE, ≈2.6 mm each | ≈ 2.6 | ≈ 23.7 | 90°C dielectric on each core, low loss, stable insulation resistance. |
| 7 | Core identification | L1/L2/L3/N color code | — | — | Phases and neutral readable at the main panel to prevent miswiring. |
| 8 | 2+2 core laying & PVC ZC sheath | Four cores 2+2, heavy class C jacket | ≈ 2.4 | ≈ 38 | Rounded 2+2 bundle; heavy jacket binds cores, shields and self-extinguishes. |
| 9 | Jacket print | Continuous type/size/voltage/length line | — | — | Marking along the heavy jacket: ZC-YJV, 4×240, 0.6/1kV, ZC, cumulative length. |
| Key Dimensions, Electrical & Mechanical Properties (expanded) | |||||
| Finished cable diameter | ≈ 38 | mm | Heavy four-core OD for large glands and duct fill. | ||
| Approx. cable mass (est.) | ≈ 7600 | kg/km | Heavy feeder; plan drum and lifting equipment. | ||
| Nominal voltage rating | 0.6/1 | kV | Matches 380/400 V main distribution. | ||
| Max voltage (Um) | 1.2 | kV | Phase-to-earth continuous upper limit. | ||
| Normal conductor temp. | 90 | °C | Continuous load temperature of XLPE. | ||
| Short-circuit temp. | 250 | °C | Short-time fault peak before insulation damage. | ||
| DC resistance (240) | ≤ 0.0754 | Ω/km | Per core @20°C; low drop on long feeders. | ||
| Nominal current (est.) | ≈ 460 | A | Per core, free air 30°C; derate bundled. | ||
| Short-circuit rating (1s, est.) | ≈ 21 | kA | 240 Cu, main-feeder fault duty. | ||
| Flame retardancy | ZC class C, self-extinguishing | — | Not 950°C fire-rated. | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 570 | mm | Heavy 4-core install corner radius. | ||
| Frequency | 50 / 60 | Hz | Compatible with both power systems. | ||
| Insulation resistance | High & stable | MΩ·km | XLPE; supports earth-fault detection. | ||
| Dielectric loss | Low | — | XLPE keeps heating down on heavy load. | ||
| Temperature cycle | 0~90°C repeated | — | Survives heating/cooling without cracking. | ||
| Sheath mechanical | Meets heavy PVC grade | — | Tensile/elongation checked at type test. | ||
| Pack choice | Heavy wooden drum | — | Drum for long main feeders and risers. | ||
| Core configuration | 4×240 (L1/L2/L3/N) | — | Three phases + neutral. | ||
| Application | Main feeder, riser, large panel supply | — | 380/400 V heavy distribution. | ||
| UV / outdoor | UV-grade optional | — | Indoor preferred; specify stabilized jacket outside. | ||
| Schematic — not to exact scale. OD ≈38 mm, weight ≈7600 kg/km, ≈460 A per core free air at 30°C and ≈21 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 4×240 serves 380/400 V main feeders, busbar risers and large panel supply; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 4×240 LV flame-retardant 4-core cable | |||
| 4×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈38 mm · L1/L2/L3/N main feeders, busbar risers & large panel supply | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 4×240 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; four L1/L2/L3/N cores. OD ≈38 mm, ≈7600 kg/km (est.), ≈460 A per core free air at 30°C (est.), heavy drum. It is a fixed heavy main-feeder cable, not a flexible cord and not a 950°C fire-rated circuit. | |||
| 2. Copper Conductors (4×240) | |||
| Three phase cores plus one neutral, each 240 mm² compacted Class 2 Cu, ≈61 strands; DC R ≤0.0754 Ω/km @20°C; low drop on long feeders; tinned plating optional for damp plant; phase-color insulation supplied on request. | |||
| 3. Strand Compaction & 2+2 Bundle | |||
| Many concentric strand layers are rolled compact per core to close gaps and give clean compression-lug entry; the four cores lay 2+2 into a rounded bundle before the heavy jacket. | |||
| 4. XLPE Insulation | |||
| Dry-cured cross-linked PE ≈2.6 mm on each core, stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; L1/L2/L3/N distinguished by phase color. | |||
| 5. Core Identification | |||
| The three phases and neutral are identified by insulation color so phase sequence and neutral match at the main panel; colors can be supplied to local 3-phase convention. | |||
| 6. Heavy PVC ZC Sheath | |||
| Flame-retardant PVC ≈2.4 mm overall, self-extinguishing class C; deep olive bronze-green standard (black/gray on request); smooth printable heavy surface; binds the 2+2 bundle and resists abrasion and crushing. | |||
| 7. Electrical Characteristics | |||
| 0.6/1 kV, Um 1.2; per-core R ≤0.0754 Ω/km; routine 3.5 kV AC/5 min; ≈460 A per core (est., air 30°C); short-circuit ≈21 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE. | |||
| 8. Factory Advantages | |||
| • Heavy balanced feeder (3 phases + neutral). • Stable XLPE cure on thick insulation. • Dosed ZC self-extinguish. • Length-on-demand. • Per-batch resistance log. • Continuous clear print. • Phase-color option. • Heavy drum pack. • Certified QA pack. | |||
| 9. Site Handling & Installation | |||
| • Bend 15×OD (≈570 mm). • 240 Cu compression lugs, large glands, hydraulic crimp, torque per table. • Derate bundled/duct runs. • Use rollers and winch. • Continuity, phase sequence, neutral + insulation after pulling. | |||
| 10. Typical Service Applications | |||
| 380/400 V main switchboard feeders, vertical busbar risers, large distribution panel inputs, plant power mains and high-current panel supply in commercial and industrial buildings. | |||
| 11. Testing & QA | |||
| 16-item regime: routine DC resistance L1/L2/L3/N, 3.5 kV withstand, insulation resistance, continuity, heavy sheath/thick insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass; type ZC flame, short-circuit, sheath mechanical, 0~90°C cycle. | |||
| 12. Packaging, Storage & Notes | |||
| Cut to measured feeder length on heavy wooden drum; continuous marking; store the drum horizontally on chocks, dry and shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated. |
8. Factory Advantages.
- Heavy balanced feeder — L1/L2/L3/N built to the same 240 mm² spec.
- Stable XLPE cure — even cross-linking on thick insulation keeps the 90°C dielectric consistent.
- Dosed ZC compound — heavy PVC self-extinguishes to class C.
- Length-on-demand — exact feeder length, sealed ends, minimal jointing.
- Batch resistance log — per-core DC R recorded against lot number.
- Continuous print line — type, size, ZC, voltage and length along heavy jacket.
- Phase-color option — L1/L2/L3/N colors matched to convention.
- Heavy drum pack — large timber drums suit long risers and feeders.
- Certified QA pack — routine + type test record per batch.

9. Packaging, Storage & Logistics. Cut to measured feeder length on heavy wooden drum; continuous marking; store the drum horizontally on chocks, dry and shaded, avoid direct UV; plan lifting equipment.

10. Procurement Specification. State "ZC-YJV 4×240", length, class C, phase colors, armor (if required), heavy drum; note flame retardant not fire-rated; request per-batch resistance log and 16-item QA record. Est. values confirmed against the factory certificate.
11. Cable Industry FAQ.
- Q1: How does 4×240 differ from 2×10? It is four cores (3 phases + N) vs twin L+N; vastly larger (240 vs 10 mm²), much thicker (38 vs 10.0 mm), far heavier (7600 vs 320 kg/km), much higher current (460 vs 55 A), far lower resistance (0.0754 vs 1.91 Ω/km). 2×10 runs 230V lighting; 4×240 runs heavy 400V main feeders.
- Q2: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
- Q3: Why equal-size neutral on a 4×240? It carries unbalanced and harmonic currents; matching phase size protects against neutral overheating.
- Q4: DC resistance on 240? ≤ 0.0754 Ω/km per core at 20°C — low drop on long main runs.
- Q5: Armored or screened? Unarmored as standard; add steel-tape/wire armor where ground crushing risk exists.
- Q6: Indoor or outdoor? Indoor preferred; UV-grade jacket for exposed risers.
- Q7: Current per core? ≈ 460 A (est.) free air 30°C; derate in duct/tray bundles.
- Q8: Connectors? 240 mm² Cu compression lugs, large gland to 38 mm OD, hydraulic crimp, torque per table.
- Q9: How is it pulled? Rollers, winch and proper rope grip; never exceed the 570 mm bend radius.
- Q10: Packing? Heavy wooden drum; store horizontally on chocks.
- Q11: What proof ships? Per-batch resistance log + 16-test record; est. values confirmed against certificate.