XLPE Insulated 4 Core Shielded Cable Copper Power ZR-YJV 4x300mm2 For Power Transmission

XLPE Insulated 4 Core Shielded Cable Copper Power ZR-YJV 4x300mm2 For Power Transmission

Basic Properties

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

XLPE Insulated Flame Retardant Copper Cable ZR-YJV 4*300mm² for Power Transmission Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath — ...

Product Details

Highlight:

XLPE Insulated 4 core shielded cable

,

4 core shielded cable 4x300mm2

,

Power Transmission copper power cable

Conductor (×4):
Bare Annealed Copper, Class 2 Stranded, Commonly 61×∅2.52 Mm (also 37×∅3.20 Mm Compact / 48×2.82 Mm), Conductor Ø ≈ 21.5–23.5 Mm Depending On Compaction
Conductor nominal area (per core):
300 Mm²
Number of cores:
4
Conductor construction:
Class 2, 61×∅2.52 Mm,IEC 60228 / GB/T 3956, Min. 15 Wires
Conductor diameter (approx.):
21.5–23.5 Mm
Insulation (×4):
XLPE
Insulation thickness:
1.8 Mm (300 Mm² Class)
Diameter over insulated core:
24.9–26.9 Mm,conductor + 2×1.8
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
2.6 Mm
Overall cable diameter:
55.0 – 64.0 Mm
Design outer diameter:
≈ 59.0 Mm
Approx. weight:
9400 – 11500 Kg/km
Design weight:
≈ 10000 Kg/km
Cable shape:
Round

Product Description

XLPE Insulated Flame Retardant Copper Cable ZR-YJV 4*300mm² for Power Transmission


Cable Designation & Meaning


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×300 mm²

Four cores, nominal copper conductor area 300 mm² per core


XLPE Insulated 4 Core Shielded Cable Copper Power ZR-YJV 4x300mm2 For Power Transmission

ZC-YJV 4×300 mm² — LV Flame-Retardant 4-Core Power Cable — Specification

1. Overview & Ratings. ZC-YJV 4×300 is a heavy four-core LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant heavy PVC sheath: four equal 300 mm² compacted copper cores (L1/L2/L3/N) laid 2+2, thick dry-cured XLPE, unarmored (armor optional). OD ≈ 42 mm, ≈ 9800 kg/km (est.), ≈ 510 A per core free air at 30 °C (est.). Scope: 380/400 V heavy main feeders, busbar risers and high-current panel supply — not 950°C fire duty.


2. Construction Stack (Inner → Outer, expanded).


Layer / Feature Build Function
Conductors L1/L2/L3/N 4×300 compacted Cu, Class 2, ≈61 strands Equal cores, R ≤0.0601 Ω/km
Strand compaction Concentric layers rolled compact per core Round heavy bundles, clean lug entry
XLPE insulation (all cores) Dry-cured PE, ≈2.8 mm Balanced thick 90°C dielectric
2+2 core laying Four equal cores in two rows of two Stable heavy round bundle
Core identification L1/L2/L3/N color code Phase sequence + full-size neutral
Heavy PVC ZC sheath Class C, ≈2.6 mm overall Binds bundle, self-extinguishes
Jacket print Continuous type/size/voltage/length On-site readable spec


3. Electrical Characteristics. R ≤ 0.0601 Ω/km on all four equal cores @20 °C. Test 3.5 kV AC / 5 min; ≈ 510 A per core (est., air 30 °C); short-circuit ≈ 26 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.

Insulation & Sheath Data

Property

Value

Insulation material

XLPE (cross-linked polyethylene)

Outer sheath material

PVC (ST₂)

Long-term service temp.

90 °C (continuous)

Max. conductor temp. (normal)

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Test voltage AC (5 min)

3.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹⁴ Ω·cm

Shield

None as standard (can be added)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage

1.2 kV AC

—

Test voltage AC (5 min)

3.5 kV

Routine test

DC resistance @20 °C

≤ 0.0601 Ω/km per core

GB/T 3956 Class 2 Cu max (300 mm²)

AC resistance @90 °C (est.)

≈ 0.077 Ω/km per core

—

Current rating in air (30 °C)

3-phase: 500 A​

4×300, touching, in free air

Current rating in tray (30 °C)

3-phase: 555 A​

4×300, spaced 2×OD

Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W)

3-phase: 520 A​

direct buried

Current rating in conduit (30 °C)

3-phase: 450 A​

—

Short-circuit current (1 s, Cu, 250 °C)

≈ 33.3 kA (33,300 A) per core

—

Capacitance (core-to-sheath, approx.)

≈ 0.26 µF/km

XLPE

Inductive reactance (approx.)

≈ 0.10 Ω/km

at 50 Hz

Frequency

50/60 Hz AC

—


Reference values: 4×300 at 500 A three-phase, 400 V → max load ≈ 300 kW​ (cos φ = 0.8). Suitable for heavy-duty main distribution, large transformers, and high-current three-phase + neutral circuits.


4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Min. installation ambient temp.

0 °C (below 0 °C requires preheating)

Service ambient range

−20 °C to +90 °C

Flexing temp. range

0 °C to +90 °C

Fire Performance (ZC-YJV — Flame Retardant C)

Property

Value / Requirement

Flame retardant

GB/T 18380.12 / IEC 60332-1-2​ (single cable, self-extinguishing)

Flame retardant class

Class C​ (ZC) per GB/T 19666

Halogen content

Contains halogen (PVC sheath)

Smoke density

Not low-smoke (PVC)

Corrosivity

Corrosive (PVC)

Toxicity

Toxic fumes when burned (PVC)

EMI shielding

None (no metallic screen/armour)


5. Installation Practice & Handling. 300 mm² lugs on all four cores, large glands to 42 mm OD, hydraulic crimp/torque per table; bend ≥ 15×OD ≈ 630 mm with rollers/winch; strong derating in bundles/ducts; keep the 2+2 bundle round; four-core continuity, phase sequence, neutral + insulation after pulling.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 915 mm at Ø61.0 mm

four-core unarmoured

Max. pulling tension

4,500 N per core (300 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Suitable (with sand bedding)

—

Surface mounting

Heavy-duty cable tray, ladder, cleats

—

Conduit ID

≥ 120 mm

—

Fixing

heavy-duty cleats, cable ties

—

Impact resistance

Moderate

—

Water resistance

Good (PVC sheath)

—

UV resistance

Fair (PVC degrades outdoors, use UV-resistant PVC or conduit)

—

Flex life

Fair (Class 2 stranded, large conductor)

fixed installation

Termination note

Heavy-duty compression lugs or mechanical connectors

—


6. Typical Service Applications. 380/400 V incoming-to-main-switchboard feeders and vertical busbar risers, high-current panel supply, plant main mains serving large non-linear loads such as VFD banks and UPS systems.

XLPE Insulated 4 Core Shielded Cable Copper Power ZR-YJV 4x300mm2 For Power Transmission


7. Testing & QA Regime (16 items). Routine: all-core DC resistance (300), 3.5 kV withstand, insulation resistance, four-core continuity, thick sheath/insulation thickness, dimensional check, strand construction, core balance, eccentricity, print legibility, mass, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.


Cable Parameters


ZC-YJV 4×300 mm² — LV Flame-Retardant 4-Core Power Cable — Full Parameter Sheet 
4×300 Cu equal cores (L1/L2/L3/N) · XLPE / PVC ZC · 0.6/1 kV · ≈42 mm · 2+2 lay · 380/400 V heavy main feeder, busbar riser and high-current panel supply
Parameter Value Unit Remarks / Standard
01 · Identification
Cable type ZC-YJV — Cu/XLPE/PVC, flame-retardant class C — ZC-YJV denotes a copper conductor with cross-linked polyethylene insulation and a PVC outer sheath; ZC marks a class C flame-retardant PVC compound that self-extinguishes after the ignition source is removed.
Rated voltage (U0/U) 0.6/1 kV 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines a general low-voltage cable suited to 380/400 V heavy distribution.
Maximum operating voltage (Um) 1.2 kV The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service.
Core configuration 4×300 (L1 / L2 / L3 / N), equal size, 2+2 lay — Four equal 300 mm² compacted copper cores — three phases plus a full-size neutral — laid 2+2 for heavy balanced and non-linear main loads.
Conductor material Compacted stranded annealed copper — Soft annealed copper strands are layer-compacted into equal round 300 mm² bundles for heavy lug entry.
Insulation XLPE cross-linked polyethylene — Chemically cross-linked polyethylene bonds into a heat-resistant dielectric retaining properties at the 90 °C operating temperature.
Sheath PVC, flame-retardant class C (ZC) — A heavy overall PVC jacket binds the four-core bundle and carries the class C flame-retardant formulation; deep plum burgundy finish.
Flame retardancy ZC class C (self-extinguishing, not fire-rated) — On removal of a flame the cable stops propagating fire; this is flame retardancy, not 950 °C/180 min circuit-integrity fire resistance.
Suitable for Fixed heavy tray, riser, duct, 3-phase+full neutral — Designed for fixed heavy three-phase-plus-neutral main feeders serving large switchboards and high-current panels.
Application 380V heavy main feeder / busbar riser — Typically runs four equal cores from the incoming switchboard to a main distribution busbar riser or high-current panel.
Application note Not for 950°C circuit-integrity fire duty — Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire.
02 · Conductors
Cores count / area 4 × 300 (L1/L2/L3/N) mm² Four equal 300 mm² conductors: three phases and a full-size neutral for heavy unbalanced and harmonic current.
Conductor type Compacted stranded Cu, Class 2 — Class 2 stranded compacted construction gives fixed-wiring conductors that round into stable heavy bundles for lug termination.
DC resistance (300) @ 20°C ≤ 0.0601 Ω/km Maximum permitted DC resistance of a 300 mm² copper conductor at 20 °C, identical for all four equal cores.
Stranding Layer-compacted concentric bundle — Concentric layers of strands are compacted radially per core to reduce gaps, tighten the bundle and present a clean round heavy-lug entry.
Strands (nom., est.) ≈61 strands per core — Approximate strand count around 61 compacted strands in a 300 mm² core; exact count follows the conductor standard.
Surface Bare copper; tinned optional — Bare copper suits most indoor use; optional tinned plating improves corrosion resistance in damp or chemically mild sites.
Core identification L1/L2/L3/N color code, equal size — All four cores share the same 300 mm² section and are color-coded so phase sequence and neutral match at the busbar.
Nominal area tolerance Within conductor class 2 band — Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count.
Neutral sizing Full-size 300 mm² (equal to phases) — The equal-size neutral protects against high third-harmonic and unbalanced heating on heavy non-linear loads.
Compaction benefit Round bundle, lower OD, clean crimp — Radial compaction reduces overall diameter versus loose stranding and gives a flat, even lug crimp.
03 · Insulation
Insulation material XLPE (cross-linked polyethylene) — Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than PVC insulation for the same size.
Insulation thickness (nom.) ≈ 2.8 mm Thick nominal radial insulation wall on each equal 300 mm² core; gauged to withstand the 3.5 kV routine test.
Working conductor temp. 90 °C Maximum continuous conductor temperature under rated current without shortening insulation life.
Short-circuit temp. 250 °C Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs.
Insulation resistance High and stable MΩ·km XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on heavy feeders.
Color L1/L2/L3/N color on request — Insulation colors are matched to local 3-phase convention or supplied natural with printed marking.
Cure type Chemical / dry-cured XLPE — A controlled cross-linking cure locks the polymer network so the thick insulation stays elastic rather than melting under heat.
Insulation symmetry Equal wall on all four cores — Uniform insulation thickness keeps the four equal cores electrically balanced.
04 · Sheath & Flame Retardancy
Sheath material PVC, flame-retardant ZC — The heavy class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface.
Sheath thickness (nom.) ≈ 2.6 mm Thick nominal overall jacket wall sized to shield the four large cores from abrasion, mechanical handling and duct damage.
Finished outer diameter ≈ 42 mm Overall four-core heavy finished diameter used to size large ducts, trunking and glands.
Flame behavior Self-extinguishing, class C — After the test flame is removed the sample extinguishes without propagating; it is not 950°C fire-rated.
Sheath color Deep plum burgundy (black/gray on request) — Standard deep plum burgundy; black or dark gray jackets are supplied for industrial aesthetics on request.
Surface finish Smooth, continuous print — A smooth heavy jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length.
05 · Electrical
Rated voltage (U0/U) 0.6/1 kV Low-voltage rating matching 380/400 V heavy distribution systems.
Max voltage (Um) 1.2 kV Continuous upper system voltage for phase-to-earth insulation stress.
Nominal current (per 300 core, est.) ≈ 510 A Approximate ampacity of a single 300 mm² core in free air at 30 °C; reduce strongly for bundling, duct fill and high ambient.
Test voltage (AC) 3.5 kV / 5 min — Routine dielectric withstand applied between each conductor and sheath for five minutes without breakdown.
Insulation resistance High, XLPE MΩ·km Measured after conditioning; confirms no void, crack or contamination in the thick cured insulation.
Short-circuit current (300, 1s, est.) ≈ 26 kA Approximate 1-second copper short-time withstand on the 300 mm² core; heavy main fault duty.
Frequency 50 / 60 Hz Compatible with both 50 Hz and 60 Hz three-phase power systems.
Dielectric XLPE, low loss — Low dielectric loss keeps heating down under continuous heavy feeder and busbar riser load.
06 · Thermal & Environment
Normal conductor temp. 90 °C Sustained operating temperature the thick XLPE insulation is rated for under full load.
Installed ambient 0 ~ +40 °C Recommended continuous ambient around the cable; high rooms and crowded trays require ampacity derating.
Min install temp. 0 °C Avoid cold bending below 0 °C where the thick PVC jacket and insulation may stiffen and crack.
Burning Self-extinguishing, ZC class C — Class C vertical flame test behavior: flame stops once the external burner is removed.
Outdoor / UV Indoor preferred; UV-grade jacket optional — Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor risers.
Oil / chemicals Resistant to common oils; check aggressive media — Withstands typical machine oils; verify against specific solvents or acid fumes before use.
Temperature cycle Withstands repeated 0~90°C duty — The thick insulation and jacket survive repeated heating/cooling cycles without cracking or delamination.
07 · Mechanical & Construction
Min bending radius (fixed) ≥ 15 × OD ≈ 630 mm Fixed-installation minimum bend radius for the heavy four-core cable; tight bends risk insulation and jacket damage.
Flexibility Stranded, handled with rollers and winch — Compacted strands remain manageable but large cores require rollers, supports and lifting equipment on site.
Shielding / Armor None / unarmored (armor optional) — No copper braid screen and no armor as standard; add steel-tape or wire armor where ground crushing or EMI exists.
Cable weight per km (est.) ≈ 9800 kg/km Very heavy mass per kilometer used for structural tray loading and extra-large drum sizing.
Circularity 2+2 four-core bundle, stable heavy OD — Four equal cores laid 2+2 form a round bundle so the finished OD stays consistent.
Tensile / elongation Heavy jacket meets PVC grade — Thick sheath tensile strength and elongation satisfy the PVC compound grade for rugged pulling.
08 · Factory Advantages
Equal-size 4-core build L1/L2/L3/N all 300 mm² for heavy harmonic load — Full-size neutral handles third harmonics and unbalance without overheating.
Thick stable XLPE cure Even cross-linking on thick insulation keeps the 90°C dielectric consistent — Controlled cure prevents soft spots in thick insulation under sustained main load.
Heavy dosed ZC compound Thick flame-retardant PVC self-extinguishes to class C — Dosed flame inhibitors protect switchboard rooms and main wiring spaces.
Length-on-demand Cut to exact riser/feeder meter, sealed ends — Custom cut lengths match the measured vertical riser and horizontal feeder route.
Batch resistance log All four core R logged against lot — Every equal-core resistance is recorded against batch ID for full traceability.
Continuous print line Type, size, ZC, voltage and length along heavy jacket — Clear continuous marking lets installers read the spec on thick, long heavy cables.
Phase-color option L1/L2/L3/N insulation colors matched to convention — Pre-colored equal cores remove wiring guesswork at busbar terminals.
Extra-heavy drum pack Large industrial drum with lifting cleats and sealed ends — Heavy main cable wound on reinforced drums suitable for winch pulling.
Certified QA pack Routine + type test record shipped per batch — A complete QA packet supports buyer audit, inspection and commissioning sign-off.
09 · Installation
Laying Heavy main tray, riser, duct, 3-phase+N — Route on rated heavy trays or vertical risers; keep the 2+2 bundle round and bending above 15×OD.
Connectors 300 mm² lugs on all four cores — Crimp matched heavy 300 mm² lugs on phases and neutral; select large glands sized to 42 mm OD.
Bend radius ≥ 15×OD ≈ 630 mm — Maintain the large minimum radius around riser bends to prevent insulation cold-working.
Parallel runs Strong derating in bundles and ducts — Adjacent heavy cores share heat; apply bundle derating before sizing the main breaker.
Site test Continuity + insulation post-laying — After pulling, verify four-core continuity, phase sequence, neutral and insulation resistance.
Termination Strip, hydraulic crimp lug, torque per table — Strip thick insulation without nicking strands, use a large hydraulic press on each lug, and torque per the lug table.
10 · Packing & Applications
Supply length Custom / extra-heavy wooden drum m Cut to the measured main riser/feeder length on a reinforced drum.
Length tolerance Per trade standard for cut lengths — Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise.
Reel type Extra-large wooden drum — Industrial drum for very heavy main lengths; sealed ends prevent moisture ingress.
Surface marking ZC-YJV, 4×300, 0.6/1kV, ZC, length — Heavy jacket prints type, core size, voltage, flame class and cumulative meter length.
Typical use Heavy main feeder, busbar riser, high-current panel — Runs four equal cores to main switchboards and high-current distribution.
Storage Dry indoor on drum supports, avoid UV — Store the drum horizontally on strong timber supports, dry and shaded, avoiding direct sunlight.


Cable Test Parameters


Test Parameters — ZC-YJV 4×300 LV Flame-Retardant 4-Core Cable 
No. Test Item Test Condition / Method Requirement Type
1 DC resistance (all 4 cores) 20 °C, each L1/L2/L3/N (300 mm²) ≤0.0601 Ω/km Routine
2 Voltage test (AC) 3.5 kV AC, 5 min, core-to-sheath No breakdown Routine
3 Insulation resistance XLPE, 20°C, per core High & stable Routine
4 Continuity Each core L1/L2/L3/N Continuous Routine
5 Flame retardancy Class C vertical test Self-extinguish Type
6 Sheath thickness Micrometer, cross-section Nominal ≥2.6 mm Routine
7 Insulation thickness Micrometer, 300 mm² cores Nominal ≥2.8 mm Routine
8 Dimensional check Caliper, overall OD OD ≈ 42 mm Routine
9 Conductor construction Visual / strand count per core Class 2 compacted Routine
10 Short-circuit rating Calculated / type 26 kA / 1 s Type
11 Insulation eccentric test Cross-section measure per core Within tolerance Routine
12 Printing legibility Visual Marking readable Routine
13 Mass per unit length Weigh / calculate ≈ 9800 kg/km Routine
14 Core balance check Resistance compare across 4 cores Balanced within band Routine
15 Sheath mechanical Tensile / elongation check Meets PVC grade Type
16 Packing & drum inspection Visual / drum condition Sealed ends, sound drum Routine


Cable Cross Section Structure

XLPE Insulated 4 Core Shielded Cable Copper Power ZR-YJV 4x300mm2 For Power Transmission

ZC-YJV 4×300 — 4-Core 2+2 Cross-Section Construction Diagram 
4×300 equal Cu cores (L1/L2/L3/N) / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈42 mm · heavy main feeder, busbar riser & high-current panel
No. Layer / Feature Material / Construction Nominal Thickness (mm) Diameter (mm) Detailed Function / Remarks
1 Conductor L1 — phase 1×300 compacted Cu, Class 2, ≈61 strands — ≈ 15.6 Phase 1 core, DC R ≤0.0601 Ω/km @20°C; heavy main current.
2 Conductor L2 — phase 1×300 compacted Cu, Class 2, ≈61 strands — ≈ 15.6 Phase 2 core, equal size/resistance for balanced impedance.
3 Conductor L3 — phase 1×300 compacted Cu, Class 2, ≈61 strands — ≈ 15.6 Phase 3 core, equal spec; color-coded for phase sequence.
4 Conductor N — neutral 1×300 compacted Cu, Class 2, equal size — ≈ 15.6 Full-size neutral, same R as phases; handles harmonics/unbalance.
5 Strand compaction Concentric layers rolled compact per core — — Radial compaction closes gaps for round heavy bundles and clean lug entry.
6 XLPE insulation (all cores) Dry-cured cross-linked PE, ≈2.8 mm ≈ 2.8 ≈ 21.2 Thick 90°C dielectric on each equal core, low loss, balanced wall.
7 2+2 core laying Four equal cores in two rows of two — — 2+2 arrangement stabilizes the heavy bundle before sheathing.
8 PVC ZC sheath Heavy class C jacket, ≈2.6 mm ≈ 2.6 ≈ 42 Binds the four-core bundle and self-extinguishes to class C.
9 Jacket print Continuous type/size/voltage/length line — — Marking: ZC-YJV, 4×300, 0.6/1kV, ZC, cumulative length.
Key Dimensions, Electrical & Mechanical Properties (expanded)
Finished cable diameter ≈ 42 mm Heavy four-core overall OD for large ducts and glands.
Approx. cable mass (est.) ≈ 9800 kg/km Very heavy main feeder; extra-large drum.
Nominal voltage rating 0.6/1 kV Matches 380/400 V systems.
Max voltage (Um) 1.2 kV Phase-to-earth continuous upper limit.
Normal conductor temp. 90 °C Continuous load temperature of XLPE.
Short-circuit temp. 250 °C Short-time fault peak before insulation damage.
DC resistance (300, all cores) ≤ 0.0601 Ω/km Per equal core @20°C.
Neutral sizing Full 300 equal to phases — For harmonics and heavy unbalance.
Nominal core current (est.) ≈ 510 A Per 300 core, free air 30°C; strong derating bundled.
Short-circuit rating (1s, est.) ≈ 26 kA Heavy main feeder fault duty.
Flame retardancy ZC class C, self-extinguishing — Not 950°C fire-rated.
Min bending radius (fixed) ≥ 15 × OD ≈ 630 mm Heavy four-core riser bend radius.
Frequency 50 / 60 Hz Compatible with both power systems.
Insulation resistance High & stable MΩ·km XLPE; supports earth-fault detection.
Dielectric loss Low — XLPE keeps heating down on heavy load.
Temperature cycle 0~90°C repeated — Survives heating/cooling without cracking.
Sheath mechanical Heavy jacket meets PVC grade — Tensile/elongation checked at type test.
Pack choice Extra-large wooden drum — Reinforced drum with lifting cleats.
Core configuration 4×300 (L1/L2/L3/N), 2+2 — Four equal cores.
Application Heavy main feeder, busbar riser, panel — 380/400 V high-current 3-phase+N power.
Schematic — not to exact scale. OD ≈42 mm, weight ≈9800 kg/km, core ampacity ≈510 A free air at 30°C and ≈26 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 4×300 serves 380/400 V heavy main feeders, busbar risers and high-current panels; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch.


Cable Construction Description


Construction Description — ZC-YJV 4×300 LV flame-retardant 4-core cable 
4×300 equal Cu cores (L1/L2/L3/N) / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈42 mm · heavy main feeder, busbar riser & high-current panel
1. Product Identity & Ratings
ZC-YJV 4×300 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; four equal 300 mm² cores (L1/L2/L3/N) laid 2+2. OD ≈42 mm, ≈9800 kg/km (est.), ≈510 A per core free air at 30°C (est.), extra-large wooden drum. It is a fixed heavy main feeder cable, not a flexible cord and not a 950°C fire-rated circuit.
2. Copper Conductors (4 equal 300 mm² cores)
Four equal compacted Class 2 Cu cores (L1/L2/L3/N), R ≤0.0601 Ω/km @20°C; full-size neutral equals phases to carry third harmonics and heavy unbalance; tinned plating optional; phase-color insulation on request.
3. Strand Compaction & 2+2 Bundle
Concentric strands are rolled compact per core to close gaps and give clean heavy-lug entry; four equal cores lay in two rows of two (2+2) to stabilize the heavy round bundle before sheathing.
4. XLPE Insulation
Dry-cured cross-linked PE ≈2.8 mm on every equal core; stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; balanced wall keeps all cores electrically equal.
5. Core Identification
L1/L2/L3 phases and the N neutral are identified by insulation color; because all four cores are equal size, color alone separates phase from neutral at the busbar terminal.
6. PVC ZC Sheath
Heavy flame-retardant PVC ≈2.6 mm overall, self-extinguishing class C; deep plum burgundy standard (black/gray on request); smooth printable surface; binds the four-core bundle and shields from abrasion and duct damage.
7. Electrical Characteristics
0.6/1 kV, Um 1.2; R ≤0.0601 Ω/km on all four equal cores; routine 3.5 kV AC/5 min; ≈510 A per core (est., air 30°C); short-circuit ≈26 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE.
8. Factory Advantages
• Equal-size 4-core build (full-size neutral).  • Thick stable XLPE cure.  • Heavy dosed ZC self-extinguish.  • Length-on-demand.  • All-core resistance log.  • Continuous clear print.  • Phase-color option.  • Extra-heavy drum pack.  • Certified QA pack.
9. Site Handling & Installation
• Bend 15×OD (≈630 mm) with rollers/winch.  • 300 mm² lugs on all four cores, large glands, hydraulic crimp, torque per table.  • Strong derating in bundles/ducts.  • Keep 2+2 bundle round.  • Four-core continuity, phase sequence, neutral + insulation after pulling.
10. Typical Service Applications
380/400 V incoming-to-main-switchboard feeders and vertical busbar risers, high-current panel supply, plant main mains serving large non-linear loads such as VFD banks and UPS systems.
11. Testing & QA
16-item regime: routine all-core DC resistance (300), 3.5 kV withstand, insulation resistance, four-core continuity, thick sheath/insulation thickness, dimensional check, strand construction, core balance, eccentricity, print legibility, mass, packing inspection; type ZC flame, short-circuit, sheath mechanical.
12. Packaging, Storage & Notes
Cut to measured main length on an extra-large reinforced wooden drum with sealed ends; continuous marking; store dry indoor on strong drum supports, shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated.


8. Factory Advantages.

  • Equal-size 4-core build — L1/L2/L3/N all 300 mm² for heavy harmonic load.
  • Thick stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
  • Heavy dosed ZC compound — thick flame-retardant PVC self-extinguishes to class C.
  • Length-on-demand — exact riser/feeder meter, sealed ends.
  • All-core resistance log — every equal-core R recorded against lot.
  • Continuous print line — type, size, ZC, voltage and length along heavy jacket.
  • Phase-color option — L1/L2/L3/N colors matched to convention.
  • Extra-heavy drum pack — reinforced drum with lifting cleats.
  • Certified QA pack — routine + type test record per batch.

XLPE Insulated 4 Core Shielded Cable Copper Power ZR-YJV 4x300mm2 For Power Transmission

9. Packaging, Storage & Logistics. Cut to measured main length on an extra-large reinforced wooden drum with sealed ends; continuous marking; store dry indoor on strong drum supports, shaded, avoid direct UV.

XLPE Insulated 4 Core Shielded Cable Copper Power ZR-YJV 4x300mm2 For Power Transmission


10. Procurement Specification. State "ZC-YJV 4×300", length, class C, phase colors, armor if required, extra-large drum; note flame retardant not fire-rated; request all-core resistance log and 16-item QA record. Est. values confirmed against the factory certificate.


11. Cable Industry FAQ.

  • Q1: How does 4×300 differ from 2×10? Four equal heavy cores vs a twin L+N pair; vastly larger (300 vs 10 mm²), much thicker (42 vs 10.0 mm), far heavier (9800 vs 320 kg/km), far higher current (510 vs 55 A), far lower resistance (0.0601 vs 1.91 Ω/km). It runs 400 V main feeders, not 230 V lighting drops.
  • Q2: Why a full-size neutral? Heavy non-linear loads (VFDs, UPS, LED banks) generate third harmonics; an equal neutral prevents neutral overheating.
  • Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
  • Q4: DC resistance? ≤ 0.0601 Ω/km on every 300 mm² core at 20°C.
  • Q5: Armor or screen? Unarmored standard; add steel-tape/wire armor for ground crushing and braid screen for EMI.
  • Q6: Current per core? ≈ 510 A (est.) free air 30°C; derate strongly in crowded trays and ducts.
  • Q7: Bending? ≥ 630 mm (15×OD); use rollers and winch on this very heavy cable.
  • Q8: Connectors? 300 mm² lugs on all four cores, large hydraulic press, gland to 42 mm OD.
  • Q9: Indoor or outdoor? Indoor preferred; UV-grade jacket for exposed risers.
  • Q10: Packing? Extra-large reinforced wooden drum with sealed ends and lifting cleats.
  • Q11: What proof ships? All-core resistance log + 16-test record; est. values confirmed against certificate.