logo
Anhui Tongdu International Trade Co., Ltd.
Online Service

Online Service

Contact Person
+86 19056002718
WeChat QR Code
Follow Us

Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant

Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZR-YJV 4x240mm²+1x120mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath — ...

Product Details

Phase/Neutral conductor (×4):
Bare Annealed Copper, Class 2 Stranded, 61×∅2.25 Mm, Conductor Ø ≈ 20.2–21.5 Mm Depending On Compaction
PE conductor (×1):
Bare Annealed Copper, Class 2 Stranded, 37×∅2.03 Mm, Conductor Ø ≈ 14.2–15.1 Mm Depending On Compaction
Phase/Neutral conductor nominal area:
240 Mm²
PE conductor nominal area:
120 Mm²
Number of cores:
5 (4+1)
Phase/Neutral conductor construction:
Class 2, 61×∅2.25 Mm
PE conductor construction:
Class 2, 37×∅2.03 Mm
Phase/Neutral conductor diameter (approx.):
20.2–21.5 Mm
PE conductor diameter (approx.):
14.2–15.1 Mm
Insulation (×5):
XLPE, Colours: Brown/black/grey (L1/L2/L3), Blue (N), Yellow/green Striped (PE)
Phase/Neutral insulation thickness:
1.7 Mm (240 Mm² Class)
PE insulation thickness:
1.2 Mm (120 Mm² Class)
Diameter over phase/neutral insulated core:
23.6–24.9 Mm
Diameter over PE insulated core:
16.6–17.5 Mm
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
2.2 Mm (GB/T 12706 Multi-core 185–300 Mm² Range)
Overall cable diameter:
51.0 – 60.0 Mm
Design outer diameter:
≈ 54.5 Mm
Approx. weight:
5200 – 6200 Kg/km
Design weight:
≈ 5650 Kg/km
Cable shape:
Round

Product Description

Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


Cable Designation & Meaning


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×240+1×120 mm²

Four equal phase/neutral cores of 240 mm² copper + one reduced protective earth (PE) core of 120 mm² copper


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


ZR-YJV 4×240+1×120 mm² — Cable Specification & Engineering Data

1. Product Overview & Rating Summary. ZR-YJV 4×240+1×120 is a top-tier 4+1-core flame-retardant cable engineered for the most demanding high-current low-voltage distribution: four 240 mm² annealed copper phase conductors surround a central 120 mm² copper neutral/PE core, each separately insulated with XLPE and then collectively enclosed in one ST2 PVC oversheath for 0.6/1 kV, 50 Hz duty. Manufacture, routine testing and type approval follow GB/T 12706.1 / IEC 60502-1; conductor stranding conforms to GB/T 3956; the ZR marking denotes class ZC flame retardance to GB/T 19666. The finished outer diameter is about 68 mm and the nominal mass is roughly 10400 kg per kilometre in copper (4700 kg/km in the aluminium YJLV variant), supplied on 100 m coils or wooden drums with flanges of at least Ø 2000 mm — approximately 1040 kg per 100 m.


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


2. Layer-by-Layer Construction (Conductor to Jacket).

Layer Construction Wall Diameter
Phase conductor (×4) Annealed Cu, Class 2 stranded, 61 × 2.25 mm (1+6+12+18+24) each — ≈ 20.0 mm
Neutral conductor (×1) Annealed Cu, Class 2 stranded, 37 × 2.02 mm (1+6+12+18) — ≈ 14.0 mm
Phase insulation (×4) XLPE 1.8 mm ≈ 23.6 mm
Neutral insulation (×1) XLPE 1.8 mm ≈ 17.6 mm
Core assembly Central neutral + 4 phase cores cabled around + PP filler + polyester binder — ≈ 64.4 mm (derived)
Outer jacket Flame-retarded PVC, ST2 compound, black 1.8 mm ≈ 68.0 mm (finished)


3. Electrical Characteristics. Each 240 mm² phase conductor is held to a maximum DC resistance of 0.0754 Ω/km at 20 °C, rising to around 0.096 Ω/km at the 90 °C operating point; the 120 mm² neutral/PE is capped at 0.153 Ω/km. Every length survives the routine 3.5 kV AC power-frequency proof held for five minutes. Finished-cable insulation resistance remains above 36.7 MΩ·km, XLPE volume resistivity exceeds 1×10¹² Ω·cm, and typical figures include capacitance ≤ 0.52 μF/km, inductance ≈ 0.26 mH/km and 50 Hz AC impedance ≈ 0.08 Ω/km. On a one-second short circuit each 240 mm² phase withstands about 27.6 kA (the 120 mm² neutral on a 13.8 kA basis), using I = k·A/√t with k = 115 for copper/XLPE. With all four phase cores energised, reference loading is 460 A in free air at 25 °C and 380 A directly buried at 25 °C — engineering estimates to be confirmed against the factory test certificate.


Electrical Parameters


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (phase/neutral, per core)

≤ 0.0754 Ω/km

GB/T 3956 max, 240 mm²

DC resistance @20 °C (PE, per core)

≤ 0.153 Ω/km

GB/T 3956 max, 120 mm²

AC resistance @90 °C (est., phase/neutral)

≈ 0.0981 Ω/km

per core

AC resistance @90 °C (est., PE)

≈ 0.199 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core+1)

≈ 440–495 A

based on 240 mm² phase

Current rating in air (design)

≈ 460 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 510–565 A

common catalogue 525–540 A

Design buried rating

≈ 532 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, phase/neutral)

≈ 24.0 kA

240 mm² reference

Short-circuit current (1 s, Cu, 250 °C, PE)

≈ 12.0 kA

120 mm² reference

Frequency

50/60 Hz AC

—


4. Thermal Response & Flame Performance. XLPE sustains a 90 °C continuous conductor temperature and tolerates a 250 °C short-circuit peak for up to five seconds. The cable is rated for service ambients between −20 and +45 °C, must not be uncoiled below 0 °C without pre-conditioning, and uses 25 °C as the reference soil temperature for buried ratings. Flame behaviour meets class ZC of GB/T 19666, proven by both the single-cable vertical test (GB/T 18380.12) and the category-C bunched test (GB/T 18380.35) with char height limited to 2.5 m. The PVC jacket is halogenated and will emit smoke and acid gas in a fire; low-smoke zero-halogen projects must specify WDZ-YJY instead.


Cable Flame Retarmeters


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


Cable Insulation Parameters


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 1020 mm for this size. Before first energisation, apply the DC site withstand at 4U0 = 2.4 kV for 15 minutes in line with Q/GDW 13244.1-2018. Drums held below 0 °C in storage must be warmed indoors before uncoiling; pulling tension should stay within 38000 N, and for longer runs a powered winch with a proper pulling grip is advisable. The 460 A (air) and 380 A (buried) references require derating whenever ambient temperature, cable grouping or soil thermal resistivity deviates from reference conditions. Crimp lugs, glands and heat-shrink termination kits must be matched to the 20.0 mm phase core, 14.0 mm neutral core and ≈ 68 mm jacket, and both phase and neutral short-circuit withstand should be coordinated with upstream protective device settings.


6. Typical Service Applications. This cross-section serves main distribution circuits in larger commercial and industrial installations: vertical risers in high-rise buildings, transformer secondary feeders up to about 1000 kVA, motor connections in the 110–160 kW range, machine-tool and process-line power leads, factory workshop and warehouse distribution panels, elevator and escalator supply circuits, and auxiliary power in light-industrial installations. Approved installation methods include steel or PVC conduit, cable trunking, tray and indoor ducting, both indoors and in covered outdoor locations. For direct burial or mechanically exposed routing, the steel-tape armoured ZR-YJV22 variant is recommended.


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


7. Testing & Quality Assurance Regime. Routine tests on every length include phase and neutral DC resistance verification (≤ 0.0754 / 0.153 Ω/km at 20 °C), the 3.5 kV AC / 5 min withstand, conductor continuity across all five cores and dimensional inspection covering phase insulation ≥ 1.8 mm, neutral insulation ≥ 1.8 mm, sheath ≥ 1.8 mm and overall diameter ≈ 68 mm. Sample and type tests comprise the XLPE hot-set trial at 200 ± 3 °C for 15 minutes under 0.2 MPa (load elongation ≤ 175 %, permanent set ≤ 15 %), XLPE tensile ≥ 12.5 MPa with elongation ≥ 200 %, PVC sheath tensile ≥ 10 MPa with elongation ≥ 125 %, PVC thermal stability ≥ 200 minutes at 200 °C, single-cable and category-C bunched flame trials, and bending assessment. Commissioning on site requires insulation-resistance measurement, the DC 2.4 kV / 15 min withstand and positive L1/L2/L3/N/PE identification before switching. A factory test certificate accompanies each drum.


Cable Parameters


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


Test Parameters


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


Cable Cross Section Structure


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


Heavy Gauge 4+1 Core Cable ZR-YJV 4x240mm²+1x120mm² XLPE Copper Flame Retardant


8. Standards & Conformity. Design and production are governed by GB/T 12706.1 and IEC 60502-1 for 0.6/1 kV extruded-insulation power cables. Conductors satisfy GB/T 3956 / IEC 60228 Class 2 — the 240 mm² phase as sixty-one wires of 2.25 mm with R ≤ 0.0754 Ω/km, and the 120 mm² neutral as thirty-seven wires of 2.02 mm with R ≤ 0.153 Ω/km. Flame retardance is classified under GB/T 19666 (ZC as the default for the ZR marking) and proven by GB/T 18380.12 and GB/T 18380.35 category C. Installation acceptance follows Q/GDW 13244.1-2018 and GB 50168, while surface marking complies with GB/T 6995. Cables can also be supplied to IEC, BS, DIN, ICEA or JIS requirements on request. Because the ST2 PVC jacket contains halogen, tunnels, metro systems, hospitals and other confined public areas call for WDZ-YJY.


9. Packaging, Storage & Logistics. Standard delivery is 100 m per coil or wooden drum, with bespoke cut lengths available on request. Each drum carries type, voltage, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +45 °C, shielded from direct sunlight, moisture, oils and sharp objects; coils and drums remain sealed until installation and are stored upright on their flanges rather than flat. In cold conditions, condition drums indoors to ≥ 0 °C before pulling. During transit, coils and drums must be secured against rolling and impact, and the cable must never be dragged across abrasive ground or sharp edges.


10. Procurement Specification. State "ZR-YJV 0.6/1 kV 4×240+1×120" together with the required length or drum arrangement and marking preferences. Specify the flame-retardant class (ZC is standard; ZA or ZB available), jacket colour and any special drum requirements. Always request the factory test certificate to confirm the actual unarmoured diameter (≈ 68 mm), weight (≈ 10400 kg/km) and ampacity for the production batch. Where low-smoke zero-halogen or armoured construction is needed, order WDZ-YJY or ZR-YJV22 respectively.


11. Cable Industry FAQ.

  • Q1: How does 4×240+1×120 differ from the smaller 4×185+1×95? The phase area grows from 185 to 240 mm² (conductor from 37×2.52 to 61×2.25 mm) and the neutral from 95 to 120 mm² (19×2.52 to 37×2.02 mm), raising the rated current from about 390/325 A to 460/380 A, increasing the finished diameter from 62 to 68 mm, and lifting the one-second phase short-circuit withstand from about 21.3 to 27.6 kA.
  • Q2: Why is the neutral/PE only 120 mm² when the phases are 240 mm²? In a balanced four-wire circuit the neutral carries mainly unbalance and harmonic current, so GB/T 12706.1 permits a reduced core in the 4+1 construction. Where the installation serves substantial single-phase or non-linear, harmonic-generating loads, an equal-section 5-core cable should be chosen.
  • Q3: What do ZA, ZB, ZC and ZD mean? These are flame-retardant classes in GB/T 19666, assessed through the bunched-cable test GB/T 18380.35 at progressively higher fuel loads — ZA is the most demanding, ZD the least. The bare "ZR" marking defaults to ZC; ZA and ZB must be requested at ordering.
  • Q4: When should a 4+1, equal 5-core, or plain 4-core cable be selected? Choose 4+1 for standard four-wire service with a reduced neutral/PE; equal 5-core (4×A+1×A) where neutral current is expected to approach phase current; plain 4-core when no separate PE conductor is required in the cable.
  • Q5: Why do air and buried ratings differ, and how are they adjusted? Published figures assume 25 °C air or 25 °C soil at 1.0 K·m/W thermal resistivity with a single circuit. Manufacturer correction factors must be applied for ambient temperature, grouping, burial depth and soil resistivity — air factors range from about 1.29 at 20 °C down to 0.91 at 45 °C, and soil factors from 1.04 at 20 °C to 0.87 at 40 °C.
  • Q6: Copper or aluminium? Copper (this cable) delivers lower resistance (0.0754 versus roughly 0.125 Ω/km at 240 mm²), higher current per mm², better mechanical strength and more dependable terminations; aluminium (YJLV, ≈ 4700 kg/km in this size) costs less and weighs less but requires larger cross-sections and anti-oxidation treatment at every joint.
  • Q7: Why can XLPE run at 90 °C while PVC insulation is limited to 70 °C? Cross-linking transforms polyethylene into a three-dimensional thermoset network, which raises the continuous conductor rating to 90 °C and the short-circuit withstand to 250 °C — directly increasing the ampacity available from a given copper area.
  • Q8: How is the conductor cross-section chosen? Selection is governed by (a) full-load current after derating, (b) permissible voltage drop (typically ≤ 5 % for branch circuits), (c) short-circuit withstand on an I²t basis (27.6 kA·s per phase here), and (d) coordination with overcurrent protective devices; the most stringent criterion controls.
  • Q9: Why does finished diameter vary between manufacturers for the same nominal size? Standards set minimum insulation and sheath thicknesses plus electrical performance, but not a precise overall diameter. Stranding compaction, filler design and sheath tolerance differ between plants — published 4×240+1×120 figures cluster around 68 mm unarmoured — so the actual measured diameter must always be used when sizing glands, trays and conduits.
  • Q10: Which tests confirm acceptability on delivery and before energisation? At delivery, verify the factory test certificate (resistance 0.0754/0.153 Ω/km, 3.5 kV/5 min withstand, dimensions ≈ 68 mm), jacket legibility and drum integrity. After installation, complete an insulation-resistance test plus the DC 4U0 = 2.4 kV / 15 min withstand per Q/GDW 13244.1-2018, then confirm L1/L2/L3/N/PE identification before closing the breaker.
  • Q11: What service life can be expected? When installed and operated within the stated temperature and voltage limits, XLPE 0.6/1 kV cables are designed for a minimum service life of 30 years; sustained overload, ultraviolet exposure, water ingress through a damaged sheath, or operation above 90 °C will materially shorten that life.