1x120mm2 Single Core Cable Full Gauge Pure Copper Anti Aging Flame Retardant Power
Product Summary
Product Details
Single Core Cable
,Single Core Cable Pure Copper
,Anti Aging Flame Retardant Power Cable
Product Description
ZR-YJV 1*120mm² Flame Retardant Power Cable, 0.6/1kV Full Gauge Pure Copper, XLPE Insulation Anti-Aging PVC Sheath for Engineering Projects
Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed
ZR-YJV 1×120 mm² — Technical Dossier
1. Scope & Certification. This dossier covers the ZR-YJV 1×120, a single-core, flame-retarded power cable built to the CU/XLPE/PVC formula and rated 0.6/1 kV (Um = 1.2 kV), 50 Hz. Compliance basis: GB/T 12706.1 / IEC 60502-1 for construction and testing, GB/T 3956 / IEC 60228 for the conductor, and GB/T 19666 together with GB/T 18380 for fire performance. "ZR" marks the cable as flame-retardant; unless an A/B class is ordered, class ZC applies.
2. Bill of Materials (Layer Stack). The cross-section, moving outward, comprises:
| Layer | Material & make-up | Thickness | Diameter |
|---|---|---|---|
| Core | Plain annealed copper, Class 2, 24 × 2.52 mm (24/2.52) concentric stranding, nominal 120 mm² | — | ≈ 12.4 mm (compact) / 12.6 mm (round-lay) |
| Dielectric | Cross-linked polyethylene (XLPE) | 1.2 mm | ≈ 15.0 mm over insulation |
| Jacket | Flame-retarded PVC, ST2, black | 1.5 mm | ≈ 17.8 mm overall |
Unit weight ≈ 1290 kg/km (the copper core alone accounts for ≈ 1067 kg/km), with the overall diameter spanning 17.8–19.1 mm depending on the maker's stranding practice.

3. Electrical Design Values. DC conductor resistance is capped at 0.153 Ω/km at 20 °C; the routine high-voltage check is 3.5 kV AC for 5 minutes with no breakdown. On the dielectric side, XLPE volume resistivity holds at ≥ 1×10¹² Ω·cm and finished-cable insulation resistance is typically ≥ 36.7 MΩ·km at 20 °C; single-core capacitance stays ≤ 0.45 μF/km. Reference ampacity reaches ≈ 400 A in free air (30 °C, single core) and ≈ 380 A direct-buried, both subject to grouping, ambient and installation derating per GB/T 16895 / IEC 60364.
4. Thermal & Mechanical Data. The thermoset XLPE permits a continuous conductor temperature of 90 °C and a short-circuit ceiling of 250 °C for up to 5 s. Service ambient spans −20 to +45 °C, and laying must not start below 0 °C unless the drum is pre-warmed. For single-core runs, keep the bending radius no tighter than 20 × OD.
| ZR-YJV 1×120 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV) | |||||
| Construction: CU / XLPE / PVC • Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance) • Nominal values for reference — confirm against factory test certificate | |||||
| No. | Category | Parameter | Value | Unit | Notes / Standard Reference |
| A. Product Identification | |||||
| 1 | Identification | Product name | Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable | — | Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing) |
| 2 | Identification | Model designation | ZR-YJV 1×120 | — | Cu / XLPE / PVC |
| 3 | Identification | Design standards | GB/T 12706.1; IEC 60502-1 | — | Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence |
| 4 | Identification | Rated voltage U0/U | 0.6/1 | kV | Max system voltage Um = 1.2 kV |
| 5 | Identification | Rated frequency | 50 | Hz | AC power distribution |
| 6 | Identification | Number of cores | 1 | — | Single-core cable |
| 7 | Identification | Nominal cross-sectional area | 120 | mm² | Nominal conductor cross-section per GB/T 3956 |
| B. Cable Construction (from conductor to outer sheath) | |||||
| 8 | Conductor | Material | Plain annealed copper (Cu) | — | High-conductivity electrolytic / oxygen-free copper |
| 9 | Conductor | Conductor class | Class 1 or Class 2 (typical: Class 2, stranded) | — | GB/T 3956 / IEC 60228 |
| 10 | Conductor | Typical stranding construction | 24 wires × 2.52 mm (24/2.52); some manufacturers use 37 × 2.03 | — | Class 2 round stranded; nominal section ≈ 120 mm² |
| 11 | Conductor | Conductor diameter | ≈ 12.4 | mm | ≈ 12.4 mm compact (12.4–12.6 mm; 24/2.52 → ≈ 12.6 mm regular stranding) |
| 12 | Conductor | Max. DC resistance of conductor at 20 °C | 0.153 | Ω/km | GB/T 3956, Class 2 copper; acceptance criterion for 120 mm² |
| 13 | Insulation | Material | Cross-linked polyethylene (XLPE) | — | Thermally cross-linked; natural/transparent colour |
| 14 | Insulation | Nominal insulation thickness | 1.2 | mm | GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 120 mm²) |
| 15 | Insulation | Diameter over insulation | ≈ 15.0 | mm | ≈ 12.6 + 2 × 1.2 (calculated; 15.0 for regular stranding) |
| 16 | Sheath | Material | Flame-retardant polyvinyl chloride (PVC, ST2 type) | — | Colour: black (or as ordered) |
| 17 | Sheath | Nominal sheath thickness | 1.5 | mm | GB/T 12706.1 / IEC 60502-1 |
| 18 | Dimensions | Approx. overall diameter | 17.8 | mm | ≈ 17.8 mm (17.8–19.1 mm across sources: cabhr 17.8 mm; ahtk 19.1 mm) |
| 19 | Dimensions | Approx. cable weight | ≈ 1290 | kg/km | cabhr & ahtk agree at 1290 kg/km (copper alone ≈ 1067 kg/km) |
| C. Electrical Performance | |||||
| 20 | Electrical | Max. DC conductor resistance at 20 °C | 0.153 | Ω/km | GB/T 3956; routine measurement |
| 21 | Electrical | Power-frequency withstand voltage (routine test) | 3.5 kV / 5 min, no breakdown | — | AC 50 Hz; per GB/T 12706.1 / IEC 60502-1 |
| 22 | Electrical | Insulation resistance (finished cable, 20 °C) | ≥ 36.7 | MΩ·km | Typical finished-cable reference for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method |
| 23 | Electrical | XLPE volume resistivity at 20 °C | ≥ 1 × 10¹² | Ω·cm | Material-level requirement (manufacturer reference) |
| 24 | Electrical | Capacitance (single-core, approx.) | ≤ 0.45 | μF/km | Manufacturer reference value |
| 25 | Electrical | Reference ampacity — in air, 30 °C, single core | ≈ 400 | A | cabhr table (400 A); depends on laying, grouping, ambient — apply correction factors per GB/T 16895 / IEC 60364 |
| 26 | Electrical | Reference ampacity — direct burial, 25 °C | ≈ 380 | A | cabhr table; depends on soil thermal resistivity and depth |
| D. Thermal Performance | |||||
| 27 | Thermal | Max. continuous conductor temperature | 90 | °C | XLPE insulation temperature class |
| 28 | Thermal | Max. conductor temperature under short-circuit (≤ 5 s) | 250 | °C | Per GB/T 12706.1 / IEC 60502-1 |
| 29 | Thermal | Ambient service temperature range | -20 to +45 | °C | Per Qifan datasheet family; check project specification |
| 30 | Thermal | Min. installation (laying) temperature | 0 | °C | Pre-heat the cable if ambient is below 0 °C |
| E. Flame Retardance (ZR) | |||||
| 31 | Flame retardance | Flame-retardant class | ZC (class C) by default for "ZR" | — | GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH) |
| 32 | Flame retardance | Single-cable vertical flame-spread test | Pass | — | GB/T 18380.12 |
| 33 | Flame retardance | Bunched flame-spread test (class C) | Char extent ≤ 2.5 m above burner bottom edge | — | GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min |
| 34 | Flame retardance | Halogen content | Halogen-containing (PVC) | — | For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type |
| F. Installation | |||||
| 35 | Installation | Min. bending radius — single-core cable | 20 × OD | — | Qifan & Huaneng datasheets; OD = actual cable diameter |
| 36 | Installation | Laying methods | Conduit, tray, cable trench, tunnel, duct, supported/suspended aerial | — | Also direct burial with mechanical protection where permitted |
| 37 | Installation | Site withstand test after installation | DC 4U0 = 2.4 kV, 15 min (recommended) | — | Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project |
| G. Packing & Delivery | |||||
| 38 | Packing | Standard delivery length | 100 m per coil/drum (or as ordered) | — | Typical industry practice; custom lengths available |
| 39 | Packing | Cable marking | Model, rated voltage, manufacturer, year of manufacture, sequential length marks | — | Per GB/T 6995 / project specification |
| 40 | Packing | Packing form | Wooden drum / coil / export packing | — | As per customer requirement |
5. Fire-Retardancy Proof. The PVC jacket earns the ZC rating: it passes the single-cable vertical burn (GB/T 18380.12) and the category-C bunched burn (GB/T 18380.35 — ≥ 1.5 L/m non-metallic content, 20-minute flame, char extent ≤ 2.5 m). The PVC chemistry does release halogen in fire; switch to WDZ-YJY where low-smoke zero-halogen is a hard requirement.
6. Test & Verification Programme. Routine (every length): DC resistance ≤ 0.153 Ω/km; 3.5 kV/5 min withstand; dimensional audit (insulation ≥ 1.2 mm, sheath ≥ 1.5 mm). Sample: hot-set on the XLPE (200 ± 3 °C, 15 min, 0.2 MPa — elongation under load ≤ 175 %, permanent set ≤ 15 %); stranding and diameter checks. Type: flame tests and mandrel bending. Post-installation: site DC test at 4U0 = 2.4 kV / 15 min (Q/GDW 13244.1-2018 practice).
| ZR-YJV 1×120 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1) | ||||
| Test Stage | Test Item | Method / Standard | Requirement / Acceptance Criterion | Notes |
| Routine test | Conductor DC resistance measurement | GB/T 3956 (IEC 60228) | ≤ 0.153 Ω/km at 20 °C | Measured on every production length |
| Routine test | Power-frequency withstand voltage | GB/T 12706.1 / IEC 60502-1 | 3.5 kV AC, 5 min, no breakdown | Applied between conductor and water/earth; 50 Hz |
| Routine test | Construction check — insulation & sheath thickness, outer diameter | GB/T 2951 | Within GB/T 12706.1 tolerances | Insulation ≥ 1.2 mm nominal; sheath ≥ 1.5 mm nominal |
| Sample test | Hot set (thermal elongation) test — XLPE insulation | GB/T 12706.1 §16.3.13 / GB/T 2951.11 | 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % | Verifies degree of cross-linking |
| Sample test | Conductor construction & diameter check | GB/T 3956 | Class 2; 24 × 2.52 mm; Ø ≈ 12.4 mm | Sampled per batch |
| Type test | Single-cable vertical flame-spread test (flame retardance) | GB/T 18380.12 | No flame spread; charring does not reach top reference point | ZR / ZC flame-retardant property |
| Type test | Bunched flame-spread test, class C | GB/T 18380.35 | Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m | Class ZC per GB/T 19666 |
| Type test | Bending test (mechanical) | GB/T 12706.1 | Bend around specified mandrel without insulation/sheath damage | Mandrel diameter related to cable OD |
| Post-installation | DC withstand test after installation | Q/GDW 13244.1-2018 (recommended practice) | 4U0 = 2.4 kV DC, 15 min, no breakdown | For new installations; verify project specification |
| Optional | Insulation resistance measurement at 20 °C | Manufacturer test method | ≥ 36.7 MΩ·km (typical finished-cable value) | Not a routine item in GB/T 12706.1; confirm with factory |
| Optional | XLPE volume resistivity at 20 °C | Manufacturer / material test | ≥ 1 × 10¹² Ω·cm | Material-level reference |
7.Cross Section Structure

| ZR-YJV 1×120 mm² — Cable Cross-Section Structure (Schematic) | |||||
| Layers from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Cu) | Annealed copper, Class 2 stranded — 24 × 2.52 mm (24/2.52), nominal 120 mm² | — | ≈ 12.4 (Ø) | Current-carrying element; max DC resistance ≤ 0.153 Ω/km @ 20 °C |
| 2 | Insulation (XLPE) | Cross-linked polyethylene | 1.2 | ≈ 15.0 (Ø over insulation) | Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min |
| 3 | Outer sheath (PVC) | Flame-retardant PVC, ST2 type, black | 1.5 | ≈ 17.8 (Ø overall) | Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666 |
| Key Dimensions & Properties | |||||
| Overall diameter | 17.8 | mm | 17.8–19.1 mm across sources (cabhr 17.8; ahtk 19.1) | ||
| Approx. cable weight | ≈ 1290 | kg/km | cabhr & ahtk agree; Cu core alone ≈ 1067 kg/km | ||
| Rated voltage | 0.6/1 | kV | AC 50 Hz; max system voltage Um = 1.2 kV | ||
| Max conductor temperature | 90 / 250 | °C | Continuous / short-circuit (≤ 5 s) | ||
| Min. bending radius (single-core) | 20 × OD | — | OD = actual cable diameter | ||
| Flame-retardant class | ZC (ZR) | — | GB/T 19666 | ||
| Product Structure Introduction — ZR-YJV 1×120 mm² | |||
| Layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV | |||
| 1. Cable Architecture at a Glance | |||
| This is a one-conductor, fire-retardant feeder cable for 0.6/1 kV AC systems (Um = 1.2 kV, 50 Hz). The physical layout is strictly concentric: a round stranded copper core sits at the centre, wrapped by a cross-linked polyethylene dielectric, and finished with a halogen-bearing flame-retardant PVC jacket. Design and tests follow GB/T 12706.1 / IEC 60502-1; conductor sizing follows GB/T 3956 / IEC 60228; fire behaviour is governed by GB/T 19666. | |||
| Representative envelope: 17.8 mm overall diameter (17.8–19.1 mm per source) and ≈ 1290 kg/km unit weight. The cable is shipped on 100 m drums or coils and suits fixed industrial and utility runs. | |||
| 2. The Copper Core | |||
| Plain annealed copper, normally drawn as Class 2, is stranded into twenty-four 2.52 mm wires (24/2.52) — a classic concentric construction — to realise the nominal 120 mm² section. The multi-wire bundle provides the flexibility required for site handling while capping DC resistance at 0.153 Ω/km at 20 °C. Core diameter lands near 12.4 mm for compact stranding, rising to about 12.6 mm when fully round-lay. | |||
| 3. The XLPE Dielectric | |||
| Over the core, a 1.2 mm layer of cross-linked polyethylene is extruded, bringing the diameter over insulation to ≈ 15.0 mm. Chemical cross-linking converts the thermoplastic into a thermoset network, which lifts the continuous operating limit to 90 °C and the short-circuit limit to 250 °C (max 5 s). This layer provides the primary electrical barrier — volume resistivity ≥ 1×10¹² Ω·cm at 20 °C and a pass at 3.5 kV AC for 5 minutes on the finished length. | |||
| 4. The PVC Jacket | |||
| The outermost 1.5 mm shell is a black, flame-retarded PVC compound (ST2). It absorbs mechanical abuse, resists moisture ingress and delivers the “ZR” fire rating — class ZC per GB/T 19666, demonstrated through the single vertical burn (GB/T 18380.12) and the category-C bunched burn (GB/T 18380.35, char limit 2.5 m). Because the jacket is PVC, the cable releases halogen under fire; projects that demand low smoke and zero halogen should call for WDZ-YJY instead. | |||
| 5. Deployment Guidance | |||
| • Suitable for main feeders, motor circuits and panel supplies at the 120 mm² copper level; standard drum 100 m. • Keep the bend radius above 20 × OD when laying a single core. • Do not install at temperatures below 0 °C without pre-warming; normal service range is −20 to +45 °C. • Always reconcile nominal values with the factory certificate and the GB/T 12706.1 / IEC 60502-1 test report. |
8. Site Handling & Precautions. Keep drums upright and unroll without dragging the jacket over sharp edges; allow slack at terminations instead of over-tensioning. Protect the sheath from UV if laid outdoors long-term. Re-check insulation integrity before energising and never exceed the 3.5 kV/5 min test level during site verification unless the project spec says otherwise.
9. Fields of Use. Main and sub-main feeders, motor and pump circuits, transformer secondary tails, switchboard interconnections and industrial risers at 0.6/1 kV — in trays, conduits, trenches, tunnels and ducts, indoors and in protected outdoor locations.

10. Procurement Notes. Order as: ZR-YJV 0.6/1 kV 1×120, stating length, drum type, marking and any special sheath colour. Delivery is normally 100 m per drum/coil. Always reconcile the figures in this dossier with the factory quality certificate and the GB/T 12706.1 / IEC 60502-1 test report before installation.