ZR-YJV Single Core Cable 1 X 300mm2 Flame Retardant 0.6/1kV Solid Copper XLPE Insulation
Product Summary
Product Details
ZR-YJV Single Core Cable
,Single Core Cable 1 x 300mm2
,1kV Low Voltage Power Cable
Product Description
ZR-YJV 1*300mm² Flame Retardant Single Core Cable, 0.6/1kV Solid Copper, XLPE Insulation PVC Jacket for Construction Power
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant C — IEC 60332-3-24, Category C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
PVC sheath |
|
1×300 mm² |
Single core, 300 mm² copper conductor |
Construction: Single Class 2 stranded copper conductor, XLPE insulation, PVC outer sheath (no armour, no shield).

ZC-YJV 1×300 mm² v2 — LV Large Single-Core Power Cable — Specification & Engineering Data
1. Overview & Ratings. ZC-YJV 1×300 v2 is a large single-core LV power cable rated 0.6/1 kV (Um = 1.2 kV), 90 °C continuous. Built per GB/T 12706.1 / IEC 60502-1, ZC C-class flame retardant per GB/T 19666. A single 300 mm² compacted stranded copper conductor (Class 2) enclosed in light blue-gray XLPE insulation and dark navy teal PVC outer sheath. Finished OD ≈ 25.0 mm, ≈ 2850 kg/km, 300 m reinforced wooden drums.
2. Construction Stack (Conductor → Outer).
| Layer | Build | Wall | Diameter |
|---|---|---|---|
| Conductor | Compacted stranded Cu, Class 2, 300 mm² | — | ≈ 20.5 mm |
| XLPE insulation | Cross-linked polyethylene, light blue-gray | ≈ 1.8 mm | ≈ 24.1 mm |
| PVC outer sheath | PVC, ZC flame retardant, dark navy teal | ≈ 2.2 mm | ≈ 25.0 mm (finished) |
3. Electrical Characteristics. DC resistance ≤ 0.124 Ω/km at 20 °C (compact Cu 300 mm²); test voltage 3.5 kV AC / 5 min; insulation resistance ≥ 36.7 MΩ·km. Nominal ampacity ≈ 540 A (air, 30 °C). Short-circuit rating ≈ 25.5 kA / 1 s.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene), Type TR-XLPE |
|
Outer sheath material |
PVC (polyvinyl chloride), Type ST₂ |
|
Long-term service temp. |
90 °C (continuous, XLPE insulation) |
|
Short-circuit temp. (≤5 s) |
250 °C (Cu conductor limit for XLPE) |
|
Emergency overload temp. |
130 °C (short term, ≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV (routine test, 0.6/1 kV class) |
|
Dielectric strength |
≥ 20 kV/mm (room temp.) |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None (unshielded design) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test (conductor-to-sheath) |
|
DC resistance @20 °C |
≤ 0.0601 Ω/km |
GB/T 3956 Class 2 Cu max, 300 mm² |
|
AC resistance @90 °C (est.) |
≈ 0.077 Ω/km |
— |
|
Current rating in air (30 °C) |
530 A |
single-core, touching, in free air |
|
Current rating in tray (30 °C) |
505 A |
spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
470 A |
direct buried |
|
Current rating in conduit (30 °C) |
450 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 33.0 kA (33,000 A) |
300 mm² Cu |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.28 µF/km |
XLPE insulation |
|
Inductive reactance (approx.) |
≈ 0.11 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 1×300 mm² at 530 A, single-core used as phase in three-phase 400 V system → max load per phase ≈ 212 kW (cos φ = 0.8); as single-phase 230 V → max load ≈ 122 kW. Suitable for main distribution, transformer connections, and high-current single-core circuits.
4. Thermal & Mechanical. 90 °C continuous; 250 °C short-circuit (≤ 5 s); ambient −40~+90 °C. Bend ≥ 15 × OD ≈ 375 mm. Non-armored, very rigid.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C (Cu conductor, XLPE limit) |
|
Emergency overload temp. |
130 °C (≤1 h, not recommended for continuous) |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (XLPE insulation, PVC sheath) |
|
Flexing temp. range |
0 °C to +90 °C |
|
Fire survival |
Standard (flame retardant C, single cable) |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
IEC 60332-3-24 Category C (bundled, 3.5 L/m cable volume, self-extinguishing) |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC sheath) |
|
Fire survival (circuit integrity) |
Not applicable (standard version) |
|
EMI shielding |
None (unshielded) |
| ZR-YJV 1×300 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV) | |||||
| Construction: CU / XLPE / PVC • Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance) • Nominal values for reference — confirm against factory test certificate | |||||
| No. | Category | Parameter | Value | Unit | Notes / Standard Reference |
| A. Product Identification | |||||
| 1 | Identification | Product name | Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable | — | Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing) |
| 2 | Identification | Model designation | ZR-YJV 1×300 | — | Cu / XLPE / PVC |
| 3 | Identification | Design standards | GB/T 12706.1; IEC 60502-1 | — | Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence |
| 4 | Identification | Rated voltage U0/U | 0.6/1 | kV | Max system voltage Um = 1.2 kV |
| 5 | Identification | Rated frequency | 50 | Hz | AC power distribution |
| 6 | Identification | Number of cores | 1 | — | Single-core cable |
| 7 | Identification | Nominal cross-sectional area | 300 | mm² | Nominal conductor cross-section per GB/T 3956 |
| B. Cable Construction (from conductor to outer sheath) | |||||
| 8 | Conductor | Material | Plain annealed copper (Cu) | — | High-conductivity electrolytic / oxygen-free copper |
| 9 | Conductor | Conductor class | Class 1 or Class 2 (typical: Class 2, stranded) | — | GB/T 3956 / IEC 60228 |
| 10 | Conductor | Typical stranding construction | 61 wires × 2.5 mm (61/2.5, lay-up 1+6+12+18+24) | — | Class 2 round stranded; nominal section ≈ 300 mm² |
| 11 | Conductor | Conductor diameter | ≈ 18.7 | mm | ≈ 18.7 mm compact (18.7–19.2 mm across stranding practice) |
| 12 | Conductor | Max. DC resistance of conductor at 20 °C | 0.0601 | Ω/km | GB/T 3956, Class 2 copper; acceptance criterion for 300 mm² |
| 13 | Insulation | Material | Cross-linked polyethylene (XLPE) | — | Thermally cross-linked; natural/transparent colour |
| 14 | Insulation | Nominal insulation thickness | 1.8 | mm | GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 300 mm²) |
| 15 | Insulation | Diameter over insulation | ≈ 22.3 | mm | ≈ 18.7 + 2 × 1.8 (calculated, compact conductor) |
| 16 | Sheath | Material | Flame-retardant polyvinyl chloride (PVC, ST2 type) | — | Colour: black (or as ordered) |
| 17 | Sheath | Nominal sheath thickness | 2.5 | mm | GB/T 12706.1 / IEC 60502-1 (cabhr table; ahtk lists 1.9) |
| 18 | Dimensions | Approx. overall diameter | 27.3 | mm | ≈ 27.3 mm (27.3–28.4 mm across sources: cabhr 27.3; ahtk 28.4; Meihe 28.24) |
| 19 | Dimensions | Approx. cable weight | ≈ 3076 | kg/km | cabhr 3076; ahtk 3056; Meihe 2960 (copper core alone ≈ 2667 kg/km) |
| C. Electrical Performance | |||||
| 20 | Electrical | Max. DC conductor resistance at 20 °C | 0.0601 | Ω/km | GB/T 3956; routine measurement |
| 21 | Electrical | Power-frequency withstand voltage (routine test) | 3.5 kV / 5 min, no breakdown | — | AC 50 Hz; per GB/T 12706.1 / IEC 60502-1 |
| 22 | Electrical | Insulation resistance (finished cable, 20 °C) | ≥ 36.7 | MΩ·km | Typical finished-cable reference for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method |
| 23 | Electrical | XLPE volume resistivity at 20 °C | ≥ 1 × 10¹² | Ω·cm | Material-level requirement (manufacturer reference) |
| 24 | Electrical | Capacitance (single-core, approx.) | ≤ 0.45 | μF/km | Manufacturer reference value |
| 25 | Electrical | Reference ampacity — in air, 30 °C, single core | ≈ 720 | A | cabhr table (720 A); depends on laying, grouping, ambient — apply correction factors per GB/T 16895 / IEC 60364 |
| 26 | Electrical | Reference ampacity — direct burial, 25 °C | ≈ 630 | A | cabhr table; depends on soil thermal resistivity and depth |
| D. Thermal Performance | |||||
| 27 | Thermal | Max. continuous conductor temperature | 90 | °C | XLPE insulation temperature class |
| 28 | Thermal | Max. conductor temperature under short-circuit (≤ 5 s) | 250 | °C | Per GB/T 12706.1 / IEC 60502-1 |
| 29 | Thermal | Ambient service temperature range | -20 to +45 | °C | Per Qifan datasheet family; check project specification |
| 30 | Thermal | Min. installation (laying) temperature | 0 | °C | Pre-heat the cable if ambient is below 0 °C |
| E. Flame Retardance (ZR) | |||||
| 31 | Flame retardance | Flame-retardant class | ZC (class C) by default for "ZR" | — | GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH) |
| 32 | Flame retardance | Single-cable vertical flame-spread test | Pass | — | GB/T 18380.12 |
| 33 | Flame retardance | Bunched flame-spread test (class C) | Char extent ≤ 2.5 m above burner bottom edge | — | GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min |
| 34 | Flame retardance | Halogen content | Halogen-containing (PVC) | — | For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type |
| F. Installation | |||||
| 35 | Installation | Min. bending radius — single-core cable | 20 × OD | — | Qifan & Huaneng datasheets; OD = actual cable diameter |
| 36 | Installation | Laying methods | Conduit, tray, cable trench, tunnel, duct, supported/suspended aerial | — | Also direct burial with mechanical protection where permitted |
| 37 | Installation | Site withstand test after installation | DC 4U0 = 2.4 kV, 15 min (recommended) | — | Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project |
| G. Packing & Delivery | |||||
| 38 | Packing | Standard delivery length | 100 m per coil/drum (or as ordered) | — | Typical industry practice; custom lengths available |
| 39 | Packing | Cable marking | Model, rated voltage, manufacturer, year of manufacture, sequential length marks | — | Per GB/T 6995 / project specification |
| 40 | Packing | Packing form | Wooden drum / coil / export packing | — | As per customer requirement |
5. Installation Practice & Handling. Use 300 mm² Cu compression lugs. Single core — do NOT run in ferrous conduit (eddy currents). Site test 2.4 kV DC / 15 min before energizing. At 2850 kg/km, very heavy — requires drum jacks and lifting equipment.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 12 × OD → ≈ 362 mm at Ø30.2 mm |
unarmoured single-core |
|
Max. pulling tension |
4,500 N (300 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding and warning tape) |
unarmoured — protect from mechanical damage |
|
Surface mounting |
Good (cable tray, ladder, cleats) |
— |
|
Conduit ID |
≥ 40 mm |
— |
|
Fixing |
cable ties, clips, cleats |
— |
|
Impact resistance |
Low (PVC sheath only) |
protect with conduit in exposed areas |
|
Water resistance |
Moisture-resistant (XLPE + PVC) |
not waterproof |
|
UV resistance |
Poor (PVC degrades in sunlight) |
indoor or buried use; for outdoor aerial use UV-stabilised sheath or conduit |
|
Flex life |
Low (Class 2 stranded, not for repeated flexing) |
fixed installation only |
|
Termination note |
Crimp lug or compression terminal; no ferrules needed (Class 2 stranded) |
— |
6. Flame Resistance. Passes GB/T 18380.12 single burn and class-C bunched burn GB/T 18380.35 (char ≤ 2.5 m) → ZC per GB/T 19666. PVC carries halogen — choose WDZ-YJY for LSZH specs.
| Flame Retardant Performance Data Sheet — ZR-YJV 0.6/1 kV 1×300 mm² | ||||
| ZR = Legacy flame-retardant mark; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC) | ||||
| 1. GENERAL INFORMATION | ||||
| 1 | Cable designation | ZR-YJV 1×300 mm² | Cu / XLPE / PVC (FR) | GB/T 12706.1 |
| 2 | Rated voltage U₀/U | 0.6 / 1 kV | Uₘ = 1.2 kV | IEC 60502-1 |
| 3 | Flame retardant class | Class C (default for ZR) | Bundled combustion, char ≤ 2.5 m | GB/T 19666-2019 |
| 4 | Conductor | Cu, Class 2, 61×∅2.52 mm | Ø ≈ 22.4 mm | GB/T 3956 |
| 5 | Insulation / Sheath | XLPE 1.4 mm / PVC (FR) 1.4 mm | Black | GB/T 12706.1 |
| 2. FLAME RETARDANT CLASSIFICATION (ZR = Class C) | ||||
| Level | Designation example | Non-metallic volume (L/m) | Flame application | Char length (max) |
| A | ZA-YJV / WDZA | ≥ 7.0 | 40 min | ≤ 2.0 m |
| B | ZB-YJV / WDZB | 3.5 | 40 min | ≤ 2.5 m |
| C | ZC-YJV / ZR-YJV | 1.5 | 20 min | ≤ 2.5 m |
| D | ZD-YJV | 0.5 | 20 min | ≤ 2.5 m |
| 3. FLAME RETARDANT TEST ITEMS & TECHNICAL LIMITS (this product = Class C) | ||||
| No. | Test item | Standard / Method | Requirement / Limit (Class C) | Result |
| 1 | Bunched flame propagation (vertical) | GB/T 18380.3 / IEC 60332-3-24 (Cat. C) | Char length ≤ 2.5 m above top of burner; self-extinguishing within 1 h | Pass |
| 2 | Single-cable flame (vertical) | GB/T 18380.1 / IEC 60332-1-2 | No sustained burning after removal of flame; char ≤ 50 mm × 50 mm | Pass |
| 3 | Non-metallic material volume (test specimen) | GB/T 18380.3 (Cat. C) | 1.5 L/m of cable length | 1.5 L/m |
| 4 | Flame source duration (Cat. C) | GB/T 18380.3 | 20 min (supply air 5000 L/min, propane 600 mm³/h) | 20 min |
| 5 | pH value of combustion gases | GB/T 17650.2 / IEC 60754-2 | ≥ 4.3 (informative for ZR; certified for WDZ) | ≥ 4.3* |
| 6 | Conductivity of acid gases | GB/T 17650.2 / IEC 60754-2 | ≤ 10 µS/mm (informative for ZR; certified for WDZ) | ≤ 10* |
| 7 | Halogen acid gas emission (HCI) | GB/T 17650.1 / IEC 60754-1 | ≤ 5 % (informative for ZR; PVC sheath contains Cl) | Contains Cl* |
| 8 | Smoke density (transmittance, min.) | GB/T 17651 / IEC 61034-2 | ≥ 60 % (informative for ZR; certified for WDZ) | Not certified* |
| 9 | Oxygen index (LOI, min.) | GB/T 2406 / IEC 60754 ref. | ≥ 30 % (typical for FR-PVC ≥ 32 %) | ≥ 32 % |
| 10 | Flame retardant in insulation & sheath | FR-PVC + FR-XLPE compound | Sb₂O₃ / Al(OH)₃ based FR system | Compliant |
| 4. NOTES | ||||
| * | Items 5–8 marked with * are INFORMATIVE for plain ZR (Class C) cable. ZR-YJV uses flame-retardant PVC which contains halogen; pH / conductivity / smoke / halogen are NOT certified limits. | |||
| ** | For certified halogen-free + low-smoke performance, use WDZ-YJY. For circuit-integrity (fire-survival), use NH-ZR-YJV. | |||
| *** | ZR is a legacy GB prefix; modern specifications use ZC (Class C). ZR-YJV ≈ ZC-YJV in flame-retardant performance. | |||
| Flame Retardant Class Comparison — ZR (Class C) vs WDZ vs Z (A/B) | |||||
| Property | ZR-YJV (this, C) | WDZ-YJV | WDZA-YJY (A) | NH-ZR-YJV | Ordinary YJV |
| Flame retardant | Class C | Class C | Class A (最高) | Class C | None |
| Halogen-free (W) | No (PVC含Cl) | Yes | Yes | No (Include Mica Tape) | No |
| Low smoke (D) | No | Yes (≥60%) | Yes (≥60%) | Yes | No |
| Fire-survival (NH) | No | No | No | Yes (90 min, 830℃) | No |
| Smoke corrosivity | Corrosive HCI | Non-corrosive | Non-corrosive | Low corrosivity | Corrosive |
| Typical use | General, cost-saving | Metro/Hospital | Tunnel/Underground | Emergency circuits | General |
| Relative price | 1.0 (base) | ~1.15× | ~1.30× | ~1.40× | 1.0 (base) |
7. Test Regime. Routine: DC resistance, 3.5 kV/5 min, dimensional audit (ins. ≥ 1.8 mm, sheath ≥ 2.5 mm). Sample: XLPE hot-set (200 ± 3 °C / 15 min / 0.2 MPa). Type: flame + bending. Site: DC 4U0 = 2.4 kV / 15 min (Q/GDW 13244.1-2018 practice).
Cable Parameters
| ZC-YJV 1×300 mm² — LV Single-Core Power Cable— Full Parameter Sheet | |||
| ZC flame retardant · compacted Cu / XLPE insulation / PVC sheath · 0.6/1 kV · 90 °C · ≈ 25.0 mm · large single core power | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — large single-core LV power cable | — | Power |
| Rated voltage (U0/U) | 0.6/1 | kV | LV power |
| Number of cores | 1 × 300 | — | Single core |
| Conductor material | Compacted annealed copper | — | Class 2 |
| Insulation material | XLPE (cross-linked polyethylene) | — | 90°C rated |
| Flame retardant class | ZC — Class C | — | GB/T 19666 |
| Sheath material | PVC (outer, dark navy teal) | — | Power cable |
| Standard | GB/T 12706.1 / IEC 60502-1 | — | LV power |
| Application | Main switchgear, transformer bus, large feeders | — | LV power |
| 02 · Conductor (Compacted Cu) | |||
| Conductor type | Compacted stranded annealed copper | — | Class 2 |
| Conductor area | 300 | mm² | Single core |
| Stranding construction | Compacted circular, ~61 wires | — | Class 2 |
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Cu 300 mm² |
| Conductor weight per km | ≈ 2720 | kg/km | 300 Cu |
| Conductor diameter | ≈ 20.5 | mm | Compacted |
| 03 · Insulation | |||
| Insulation type | XLPE (cross-linked PE) | — | 90°C rated |
| Insulation thickness | ≈ 1.8 | mm | 0.6/1 kV |
| Insulated core OD | ≈ 24.1 | mm | Single core |
| Insulation color | Light blue-gray | — | XLPE |
| 04 · Sheath | |||
| Sheath type | PVC outer sheath | — | ZC flame retardant |
| Sheath thickness | ≈ 2.2 | mm | Power cable |
| Finished outer diameter | ≈ 25.0 | mm | Overall |
| Sheath color | Dark navy teal | — | ZC |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | LV power |
| Max voltage (Um) | 1.2 | kV | Phase-to-earth |
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Compacted Cu 300 |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine |
| Insulation resistance | ≥ 36.7 | MΩ·km | XLPE |
| Nominal current (ampacity) | ≈ 540 | A | Air, 30°C |
| Short-circuit current (1s) | ≈ 25.5 | kA | 300 mm² Cu |
| 06 · Thermal | |||
| Max conductor temp. | 90 | °C | XLPE rated |
| Short-circuit temp. | 250 | °C | Max 5 s |
| Ambient range | -40 ~ +90 | °C | XLPE wide range |
| Laying temperature | ≥ 0 | °C | XLPE |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 375 | mm | Large single core |
| Flexibility | Very rigid | — | Large single core |
| Armored | No | — | Non-armored |
| Cable weight per km | ≈ 2850 | kg/km | Very heavy |
| 08 · Installation | |||
| Laying methods | Main switchgear, transformer bus, indoor tray | — | Power |
| Connectors | Cu compression lugs, 300 mm² | — | Power |
| Site test voltage | 2.4 kV DC / 15 min | — | Before energizing |
| Bend radius | ≥ 15 × OD ≈ 375 mm | — | Large single core |
| 09 · Packing | |||
| Standard supply length | 300 m / drum | m | Heavy power cable |
| Reel / packing type | Wooden drum, reinforced | — | Very heavy |
| Surface marking | ZC-YJV, 1×300, 0.6/1kV, GB/T 12706.1 | — | Continuous printing |
| Approx. cable weight | ≈ 2850 | kg/km | Large single core power |
| 10 · Applications | |||
| Typical use | Main switchgear bus, transformer secondary, large LV feeders | — | LV power |
| Max system voltage | 1.2 | kV | Um |
| Application level | Main LV power distribution | — | Very high current |
Cable Testing Parameters
| Test Parameters — ZC-YJV 1×300 mm² LV Power Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 0.124 Ω/km (Cu 300) | Routine |
| 2 | Voltage test (AC) | 3.5 kV AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | 5000 V DC | ≥ 36.7 MΩ·km | Routine |
| 4 | Insulation thickness | Micrometer | ≥ 1.8 mm | Routine |
| 5 | Sheath thickness | Micrometer | ≥ 2.2 mm | Routine |
| 6 | Conductor construction | Visual / dimensional | Compacted Class 2 | Routine |
| 7 | XLPE heating test | 250°C / 10 min | No cracks | Type |
| 8 | Flame retardancy (ZC) | GB/T 19666, Class C | Passes | Type |
| 9 | Bending test | 15× OD, cycles | No damage | Type |
| 10 | Dimensional check | Caliper | OD ≈ 25.0 mm | Routine |
| 11 | Short-circuit rating | Calculated / type tested | 25.5 kA / 1 s | Type |
| 12 | Printing legibility | Visual | Marking readable | Routine |
Cable Cross Section Structure

| ZC-YJV 1×300 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Large single-core power cable: compacted Cu → XLPE insulation → PVC sheath (ZC) · 0.6/1 kV · ≈ 25.0 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor | Compacted stranded Cu, Class 2, 300 mm² | — | ≈ 20.5 | R ≤ 0.124 Ω/km |
| 2 | XLPE insulation | Cross-linked polyethylene, light blue-gray | ≈ 1.8 | ≈ 24.1 | 0.6/1 kV, 90°C |
| 3 | PVC outer sheath | PVC, ZC flame retardant, dark navy teal | ≈ 2.2 | ≈ 25.0 | Outer protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 25.0 | mm | Overall | ||
| Approx. cable mass | ≈ 2850 | kg/km | Very heavy | ||
| Nominal voltage rating | 0.6/1 | kV | LV power | ||
| Max conductor temp. | 90 | °C | XLPE rated | ||
| Short-circuit temp. | 250 | °C | Max 5 s | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 375 | mm | Large single core | ||
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Compacted Cu 300 | ||
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine | ||
| Nominal current (ampacity) | ≈ 540 | A | Air, 30°C | ||
| Flame retardant class | ZC — Class C | — | GB/T 19666 | ||
| Short-circuit rating (1s) | ≈ 25.5 | kA | 300 mm² Cu | ||
| Number of cores | 1 | — | Single core | ||
| Standard | GB/T 12706.1 / IEC 60502-1 | — | LV power | ||
| Application | Main switchgear / transformer bus | — | Very high current | ||
| Schematic — not to exact scale. Finished OD ≈ 25.0 mm and weight ≈ 2850 kg/km from cross-referenced industry samples. ZC-YJV 1×300 v2 is a large single-core LV power cable for main switchgear and transformer bus with C-class flame retardancy. Values marked (est.) require confirmation against the factory test certificate. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 1×300 mm² large single-core LV power cable | |||
| Layer-by-layer large single-core power cable: compacted Cu / XLPE insulation / PVC sheath (ZC) · 0.6/1 kV · 90 °C · ≈ 25.0 mm | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 1×300 v2 is a large single-core LV power cable rated 0.6/1 kV (Um = 1.2 kV), 90 °C continuous. Built per GB/T 12706.1 / IEC 60502-1, ZC C-class flame retardant per GB/T 19666. Finished OD ≈ 25.0 mm, mass ≈ 2850 kg/km, 300 m reinforced wooden drums. | |||
| 2. Compacted Copper Conductor | |||
| Single 300 mm² compacted stranded annealed copper conductor (Class 2). DC resistance ≤ 0.124 Ω/km at 20 °C. Compacted for reduced outer diameter and better lug fit. Carries ~540 A at 30°C air. | |||
| 3. XLPE Insulation | |||
| Cross-linked polyethylene insulation ≈ 1.8 mm thick. Light blue-gray color. Rated 90 °C continuous and 250 °C short-circuit. | |||
| 4. PVC Outer Sheath (ZC) | |||
| PVC outer sheath ≈ 2.2 mm thick, C-class flame retardant (ZC). Dark navy teal color. Provides mechanical protection and flame-retardant properties. | |||
| 5. Site Handling & Operational Notes | |||
| • Bend radius 15×OD (≈ 375 mm). • Use 300 mm² Cu compression lugs. • At 2850 kg/km, very heavy — needs drum jacks. • Single core — do not run in ferrous conduit. • Site test 2.4 kV DC before energizing. |
| ZR-YJV 1×300 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1) | ||||
| Test Stage | Test Item | Method / Standard | Requirement / Acceptance Criterion | Notes |
| Routine test | Conductor DC resistance measurement | GB/T 3956 (IEC 60228) | ≤ 0.0601 Ω/km at 20 °C | Measured on every production length |
| Routine test | Power-frequency withstand voltage | GB/T 12706.1 / IEC 60502-1 | 3.5 kV AC, 5 min, no breakdown | Applied between conductor and water/earth; 50 Hz |
| Routine test | Construction check — insulation & sheath thickness, outer diameter | GB/T 2951 | Within GB/T 12706.1 tolerances | Insulation ≥ 1.8 mm nominal; sheath ≥ 2.5 mm nominal |
| Sample test | Hot set (thermal elongation) test — XLPE insulation | GB/T 12706.1 §16.3.13 / GB/T 2951.11 | 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % | Verifies degree of cross-linking |
| Sample test | Conductor construction & diameter check | GB/T 3956 | Class 2; 61 × 2.5 mm; Ø ≈ 18.7 mm | Sampled per batch |
| Type test | Single-cable vertical flame-spread test (flame retardance) | GB/T 18380.12 | No flame spread; charring does not reach top reference point | ZR / ZC flame-retardant property |
| Type test | Bunched flame-spread test, class C | GB/T 18380.35 | Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m | Class ZC per GB/T 19666 |
| Type test | Bending test (mechanical) | GB/T 12706.1 | Bend around specified mandrel without insulation/sheath damage | Mandrel diameter related to cable OD |
| Post-installation | DC withstand test after installation | Q/GDW 13244.1-2018 (recommended practice) | 4U0 = 2.4 kV DC, 15 min, no breakdown | For new installations; verify project specification |
| Optional | Insulation resistance measurement at 20 °C | Manufacturer test method | ≥ 36.7 MΩ·km (typical finished-cable value) | Not a routine item in GB/T 12706.1; confirm with factory |
| Optional | XLPE volume resistivity at 20 °C | Manufacturer / material test | ≥ 1 × 10¹² Ω·cm | Material-level reference |
8. Installation Do's & Don'ts. Do keep bends ≥ 20 × OD, use rollers and smooth radii, protect from UV; don't drag over sharp metal, flex continuously, or energise before the site DC test. Verify the actual core Ø before connector selection.
|
Size |
Insulation |
Sheath |
OD (mm) |
Weight (kg/km) |
R₂₀ (Ω/km) |
Ampacity (A) air / buried |
|---|---|---|---|---|---|---|
|
1×16 |
0.7 |
1.4 |
9.4 |
~215 |
≤1.15 |
105 / 95 |
|
1×25 |
0.9 |
1.4 |
11.2 |
~310 |
≤0.727 |
140 / 130 |
|
1×35 |
0.9 |
1.4 |
13.2 |
~410 |
≤0.524 |
175 / 160 |
|
1×50 |
1.0 |
1.4 |
15.6 |
~545 |
≤0.387 |
210 / 190 |
|
1×70 |
1.1 |
1.4 |
17.8 |
~720 |
≤0.268 |
270 / 245 |
|
1×95 |
1.1 |
1.4 |
20.0 |
~950 |
≤0.193 |
330 / 300 |
|
1×120 |
1.1 |
1.4 |
22.0 |
~1,140 |
≤0.153 |
385 / 350 |
|
1×150 |
1.2 |
1.4 |
24.0 |
~1,360 |
≤0.124 |
440 / 400 |
|
1×185 |
1.2 |
1.4 |
26.0 |
~1,600 |
≤0.0991 |
505 / 460 |
|
1×240 |
1.2 |
1.4 |
29.0 |
~1,980 |
≤0.0754 |
590 / 535 |
|
1×300 |
1.4 |
1.4 |
32.0 |
~2,420 |
≤0.0601 |
685 / 620 |
9. Typical Service Applications. Main switchgear bus, transformer secondary, large LV feeders, main building power distribution — where very high-current single-phase or DC power is required.

10. Packaging, Storage & Logistics. 300 m per reinforced wooden drum (shorter due to weight). Continuous marking: ZC-YJV, 1×300, 0.6/1kV, GB/T 12706.1. Store dry, indoor. Very heavy drums — use lifting equipment.
11. Procurement Specification. State "ZC-YJV 1×300" + length. Specify ZC flame retardant requirement. Confirm against factory test certificate.