Class 2 1*95mm2 Wire Single Core Shielded Cable PVC Jacket For Building Power

Class 2 1*95mm2 Wire Single Core Shielded Cable PVC Jacket For Building Power

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 1*95mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

ZR-YJV 1*95mm² Single Core Cable, 0.6/1kV Solid Copper, XLPE Insulation PVC Jacket for Building Power Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed ZR-YJV 1×95 mm² — Product Data Sheet Executive summary — ZR-YJV 1×95 is a single-core, fire-retardant, copper/XLPE/PVC power ...

Product Details

Highlight:

Class 2 single core shielded cable

,

1*95mm2 single core shielded cable

,

Building Power wire single core

Conductor:
Bare Annealed Copper, Class 2 Stranded Circular, 19×∅2.59 Mm​ (typical), Conductor Ø ≈ 12.9 Mm
Conductor nominal area:
95 Mm²
Conductor construction:
Class 2, 19×∅2.59 Mm​ Min. 19 Wires Per GB/T 3956 (>35 Mm²)
Conductor diameter (approx.):
12.9 Mm
Insulation:
XLPE Compound, Extruded
Insulation thickness:
1.1 Mm​ (GB/T 12706.1, 70–95–120 Mm² Class)
Diameter over insulation (approx.):
15.1 Mm(12.9 + 2×1.1)
Filler / binder:
Flame-retardant (FR) Non-hygroscopic Tape / PP Mesh​
Outer sheath​:
Flame-retardant PVC Compound (ZR Grade)​ — Contains Halogen, Not Low-smoke
Sheath nominal thickness:
1.4 Mm​ Single-core PVC
Overall cable diameter:
19.5 – 20.5 Mm​ PVC Density; Use 20.0 Mm For Design
Approx. weight:
930 – 980 Kg/km
Long-term service temperature:
90 °C
Short-circuit temperature (≤5 s):
250 °C
Emergency overload:
105–130 °C (limited Duration)
Routine test:
3.5 KV AC / 5 Min; Type Test 4.0 KV
Volume resistivity @90 °C:
≥ 10¹² Ω·cm

Product Description

ZR-YJV 1*95mm² Single Core Cable, 0.6/1kV Solid Copper, XLPE Insulation PVC Jacket for Building Power

 

Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed

 

ZR-YJV 1×95 mm² — Product Data Sheet

Executive summary — ZR-YJV 1×95 is a single-core, fire-retardant, copper/XLPE/PVC power cable rated 0.6/1 kV, engineered to GB/T 12706.1 / IEC 60502-1 for dependable low-voltage energy delivery where flame-spread limitation matters. With a 95 mm² copper path, it is the natural choice for heavy feeders, motor circuits and substation auxiliary supplies.

Design & Construction, Layer by Layer

The cable is a coaxial build of three functional shells:

 

Shell Material & build Key figures
Core (conductor) Plain annealed copper, Class 2, 19 × 2.52 mm (19/2.52, lay-up 1+6+12) Ø ≈ 12.1 mm (up to 12.6 mm non-compact); DC resistance ≤ 0.193 Ω/km @ 20 °C
Dielectric (insulation) Cross-linked polyethylene (XLPE), thermoset 1.1 mm wall; Ø over insulation ≈ 14.3 mm
Jacket (outer sheath) Flame-retardant PVC, ST2, black 1.5 mm wall; overall Ø ≈ 17.6 mm (17.3–17.6 mm)

Cable weight ≈ 747 kg/km (740–747 kg/km) and rated voltage 0.6/1 kV (Um = 1.2 kV), 50 Hz.

2.Performance Profile

  • Conductivity: 19-wire stranding keeps ohmic loss low (≤ 0.193 Ω/km), easing voltage-drop compliance on long runs.
  • Dielectric strength: the cross-linked wall passes a 3.5 kV / 5 min AC routine test; material volume resistivity ≥ 1×10¹² Ω·cm; finished-cable insulation resistance ≥ 36.7 MΩ·km @ 20 °C (typical).
  • Thermal rating: 90 °C continuous, 250 °C short-circuit (≤ 5 s); service ambient −20…+45 °C; laying ≥ 0 °C.
  • Fire behaviour: "ZR" = class ZC per GB/T 19666; passes GB/T 18380.12 single test and class-C bunched test (GB/T 18380.35, char ≤ 2.5 m, ≥ 1.5 L/m non-metallic content).
  • Current-carrying capacity (reference): ≈ 345 A in air (single core, 30 °C); direct burial ≈ 335–350 A, subject to derating per GB/T 16895 / IEC 60364.
  • Laying flexibility: minimum bending radius 20 × OD for single-core runs; post-install site test DC 4U0 = 2.4 kV / 15 min (Q/GDW 13244.1-2018 practice).

Class 2 1*95mm2 Wire  Single Core Shielded Cable PVC Jacket For Building Power

3.Parameter Highlights 

  • Core: 95 mm²; 19/2.52; Ø ≈ 12.1 mm — Insulation: 1.1 mm — Jacket: 1.5 mm — OD 17.3–17.6 mm — Weight ≈ 747 kg/km — Standard drum length 100 m.
ZR-YJV 1×95 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV)
Construction: CU / XLPE / PVC  •  Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance)  •  Nominal values for reference — confirm against factory test certificate
No. Category Parameter Value Unit Notes / Standard Reference
A. Product Identification
1 Identification Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable — Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing)
2 Identification Model designation ZR-YJV 1×95 — Cu / XLPE / PVC
3 Identification Design standards GB/T 12706.1; IEC 60502-1 — Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence
4 Identification Rated voltage U0/U 0.6/1 kV Max system voltage Um = 1.2 kV
5 Identification Rated frequency 50 Hz AC power distribution
6 Identification Number of cores 1 — Single-core cable
7 Identification Nominal cross-sectional area 95 mm² Nominal conductor cross-section per GB/T 3956
B. Cable Construction (from conductor to outer sheath)
8 Conductor Material Plain annealed copper (Cu) — High-conductivity electrolytic / oxygen-free copper
9 Conductor Conductor class Class 1 or Class 2 (typical: Class 2, stranded) — GB/T 3956 / IEC 60228
10 Conductor Typical stranding construction 19 wires × 2.52 mm (19/2.52, lay-up 1+6+12) — Class 2 round stranded; nominal section ≈ 95 mm²
11 Conductor Conductor diameter ≈ 12.1 mm ≈ 12.1 mm compact (12.1–12.6 mm; 19/2.52 → ≈ 12.6 mm regular stranding)
12 Conductor Max. DC resistance of conductor at 20 °C 0.193 Ω/km GB/T 3956, Class 2 copper; acceptance criterion for 95 mm²
13 Insulation Material Cross-linked polyethylene (XLPE) — Thermally cross-linked; natural/transparent colour
14 Insulation Nominal insulation thickness 1.1 mm GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 95 mm²)
15 Insulation Diameter over insulation ≈ 14.3 mm ≈ 12.1 + 2 × 1.1 (calculated)
16 Sheath Material Flame-retardant polyvinyl chloride (PVC, ST2 type) — Colour: black (or as ordered)
17 Sheath Nominal sheath thickness 1.5 mm GB/T 12706.1 / IEC 60502-1
18 Dimensions Approx. overall diameter 17.3–17.6 mm Qifan 17.6 mm; Weiguang 17.3 mm
19 Dimensions Approx. cable weight ≈ 747 kg/km Range 740–747 kg/km across manufacturers (Qifan 747; Weiguang 740)
C. Electrical Performance
20 Electrical Max. DC conductor resistance at 20 °C 0.193 Ω/km GB/T 3956; routine measurement
21 Electrical Power-frequency withstand voltage (routine test) 3.5 kV / 5 min, no breakdown — AC 50 Hz; per GB/T 12706.1 / IEC 60502-1
22 Electrical Insulation resistance (finished cable, 20 °C) ≥ 36.7 MΩ·km Typical finished-cable requirement for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method
23 Electrical XLPE volume resistivity at 20 °C ≥ 1 × 10¹² Ω·cm Material-level requirement (manufacturer reference)
24 Electrical Capacitance (single-core, approx.) ≤ 0.45 μF/km Manufacturer reference value
25 Electrical Reference ampacity — in air, 30 °C, single core ≈ 345 A Reference value (Guangheng); depends on laying, grouping, ambient — apply correction factors per GB/T 16895 / IEC 60364
26 Electrical Reference ampacity — direct burial, 25 °C ≈ 335–350 A Reference value; depends on soil thermal resistivity and depth (reference range)
D. Thermal Performance
27 Thermal Max. continuous conductor temperature 90 °C XLPE insulation temperature class
28 Thermal Max. conductor temperature under short-circuit (≤ 5 s) 250 °C Per GB/T 12706.1 / IEC 60502-1
29 Thermal Ambient service temperature range -20 to +45 °C Per Qifan datasheet; check project specification
30 Thermal Min. installation (laying) temperature 0 °C Pre-heat the cable if ambient is below 0 °C
E. Flame Retardance (ZR)
31 Flame retardance Flame-retardant class ZC (class C) by default for "ZR" — GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH)
32 Flame retardance Single-cable vertical flame-spread test Pass — GB/T 18380.12
33 Flame retardance Bunched flame-spread test (class C) Char extent ≤ 2.5 m above burner bottom edge — GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min
34 Flame retardance Halogen content Halogen-containing (PVC) — For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type
F. Installation
35 Installation Min. bending radius — single-core cable 20 × OD — Qifan & Huaneng datasheets; some manufacturers specify 15 × OD; OD = actual cable diameter
36 Installation Laying methods Conduit, tray, cable trench, tunnel, duct, supported/suspended aerial — Also direct burial with mechanical protection where permitted
37 Installation Site withstand test after installation DC 4U0 = 2.4 kV, 15 min (recommended) — Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project
G. Packing & Delivery
38 Packing Standard delivery length 100 m per coil/drum (or as ordered) — Typical industry practice; custom lengths available
39 Packing Cable marking Model, rated voltage, manufacturer, year of manufacture, sequential length marks — Per GB/T 6995 / project specification
40 Packing Packing form Wooden drum / coil / export packing — As per customer requirement

 

4.Verification & Test Regime

 

ZR-YJV 1×95 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Test Stage Test Item Method / Standard Requirement / Acceptance Criterion Notes
Routine test Conductor DC resistance measurement GB/T 3956 (IEC 60228) ≤ 0.193 Ω/km at 20 °C Measured on every production length
Routine test Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC, 5 min, no breakdown Applied between conductor and water/earth; 50 Hz
Routine test Construction check — insulation & sheath thickness, outer diameter GB/T 2951 Within GB/T 12706.1 tolerances Insulation ≥ 1.1 mm nominal; sheath ≥ 1.5 mm nominal
Sample test Hot set (thermal elongation) test — XLPE insulation GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % Verifies degree of cross-linking
Sample test Conductor construction & diameter check GB/T 3956 Class 2; 19 × 2.52 mm; Ø ≈ 12.1 mm Sampled per batch
Type test Single-cable vertical flame-spread test (flame retardance) GB/T 18380.12 No flame spread; charring does not reach top reference point ZR / ZC flame-retardant property
Type test Bunched flame-spread test, class C GB/T 18380.35 Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m Class ZC per GB/T 19666
Type test Bending test (mechanical) GB/T 12706.1 Bend around specified mandrel without insulation/sheath damage Mandrel diameter related to cable OD
Post-installation DC withstand test after installation Q/GDW 13244.1-2018 (recommended practice) 4U0 = 2.4 kV DC, 15 min, no breakdown For new installations; verify project specification
Optional Insulation resistance measurement at 20 °C Manufacturer test method ≥ 36.7 MΩ·km (typical finished-cable value) Not a routine item in GB/T 12706.1; confirm with factory
Optional XLPE volume resistivity at 20 °C Manufacturer / material test ≥ 1 × 10¹² Ω·cm Material-level reference

 

Class 2 1*95mm2 Wire  Single Core Shielded Cable PVC Jacket For Building Power

 

5.Cross Section Structure

 

Class 2 1*95mm2 Wire  Single Core Shielded Cable PVC Jacket For Building Power

ZR-YJV 1×95 mm² — Cable Cross-Section Structure (Schematic)
Layers from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
           
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) Annealed copper, Class 2 stranded — 19 × 2.52 mm (19/2.52, 1+6+12), nominal 95 mm² — ≈ 12.1 (Ø) Current-carrying element; max DC resistance ≤ 0.193 Ω/km @ 20 °C
2 Insulation (XLPE) Cross-linked polyethylene 1.1 ≈ 14.3 (Ø over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.5 ≈ 17.6 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
           
           
Key Dimensions & Properties
Overall diameter 17.3–17.6 mm Qifan 17.6 mm; Weiguang 17.3 mm    
Approx. cable weight ≈ 747 kg/km Range 740–747 kg/km across manufacturers    
Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV    
Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)    
Min. bending radius (single-core) 20 × OD — OD = actual cable diameter    
Flame-retardant class ZC (ZR) — GB/T 19666    

 

Product Structure Introduction — ZR-YJV 1×95 mm² 
Layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV
 
1. Cable at a Glance
ZR-YJV 1×95 is a single-conductor flame-retardant power cable for 0.6/1 kV (Um = 1.2 kV) AC networks at 50 Hz. Its cross-section is built coaxially: a stranded copper core, a cross-linked polyethylene dielectric and a fire-retardant PVC jacket. The whole design follows GB/T 12706.1 / IEC 60502-1, with the core dimensioned to GB/T 3956 / IEC 60228 and fire behaviour covered by GB/T 19666.
Typical figures: outer diameter 17.3–17.6 mm and unit weight about 740–747 kg/km (representative 747 kg/km). The cable suits fixed runs in trays, conduits, ducts, tunnels and trenches.
 
2. Conductive Core (Layer 1)
The current path is plain annealed copper, normally stranded as Class 2 with nineteen 2.52 mm wires (19/2.52, lay-up 1+6+12) for a nominal 95 mm². Multi-wire stranding keeps the bendability needed for real-site routing while holding the DC resistance at or below 0.193 Ω/km at 20 °C. The finished core measures about 12.1 mm across (up to ≈ 12.6 mm for regular, non-compact stranding).
 
3. Dielectric System (Layer 2)
A 1.1 mm wall of cross-linked polyethylene (XLPE) is extruded over the core, bringing the diameter over insulation to ≈ 14.3 mm. Because the compound is chemically cross-linked, it behaves as a thermoset: the continuous rating climbs to 90 °C and the short-circuit limit to 250 °C for up to 5 s. The layer also delivers high dielectric strength and very low dielectric loss, with a material resistivity of at least 1×10¹² Ω·cm at 20 °C; the finished cable passes a 3.5 kV / 5 min AC routine test.
 
4. Protective Jacket (Layer 3)
The outermost shell is a 1.5 mm black flame-retardant PVC (ST2) jacket, giving an overall diameter of ≈ 17.6 mm. It guards the dielectric against moisture, impact and abrasion, and it is the layer that earns the cable its “ZR” rating — flame-retardant class ZC under GB/T 19666, verified by the single vertical flame test (GB/T 18380.12) and the class-C bunched test (GB/T 18380.35, char limit 2.5 m). Being PVC, it is halogen-containing; choose WDZ-YJY when low-smoke zero-halogen performance is mandatory.
 
5. Application & Handling Notes
• Use for feeders, motor and switchboard circuits where a 95 mm² copper path is required; delivery is normally 100 m per drum or coil.  • Respect the 20 × OD minimum bending radius for single-core laying.  • Do not install below 0 °C unless the drum is warmed; service ambient is −20 to +45 °C.  • Re-verify all nominal values against the factory quality certificate and the GB/T 12706.1 / IEC 60502-1 test report.

 

6.Installation, Handling & Care

  1. Keep drums upright, protect the jacket from dragging over sharp edges.
  2. Never bend tighter than 20 × OD; plan generous slack at terminations.
  3. If ambient < 0 °C, warm the drum before paying out.
  4. PVC sheath means halogen is present — switch to WDZ-YJY where LSZH is mandated.
  5. Apply grouping/ambient correction before final rating; test insulation integrity before energising.

7.Typical Applications

Main and sub-main distribution feeders, motor and pump circuits, switchboard and panel interconnections, and industrial/commercial risers at 0.6/1 kV — installed in trays, conduits, trenches, tunnels and ducts, indoors or in protected outdoor locations (avoid direct UV exposure unless protected).

 

Class 2 1*95mm2 Wire  Single Core Shielded Cable PVC Jacket For Building Power

 

8. Package

 

Class 2 1*95mm2 Wire  Single Core Shielded Cable PVC Jacket For Building Power

 

9.Company Overview

 

Class 2 1*95mm2 Wire  Single Core Shielded Cable PVC Jacket For Building Power

 

Class 2 1*95mm2 Wire  Single Core Shielded Cable PVC Jacket For Building Power