Class 2 1*95mm2 Wire Single Core Shielded Cable PVC Jacket For Building Power
Product Summary
Product Details
Class 2 single core shielded cable
,1*95mm2 single core shielded cable
,Building Power wire single core
Product Description
ZR-YJV 1*95mm² Single Core Cable, 0.6/1kV Solid Copper, XLPE Insulation PVC Jacket for Building Power
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant C — IEC 60332-3-24, Category C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
PVC sheath |
|
1×95 mm² |
Single core, 95 mm² copper conductor |
Construction: Single Class 2 stranded copper conductor, XLPE insulation, PVC outer sheath (no armour, no shield).
Applicable Standards
- GB/T 12706.1-2020 / IEC 60502-1 — Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) — Part 1: Cables for rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV)
- GB/T 19666-2019 — Flame retardant and fire resistant wires and cables
- GB/T 18380.12 / IEC 60332-1-2 — Flame propagation test for a single vertical insulated wire
- GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables
- GB/T 2951-2008 / IEC 60811 — Common test methods for insulating and sheathing materials

ZC-YJV 1×95 mm² — LV Flame-Retardant Power Cable — Specification
1. Overview & Ratings. ZC-YJV 1×95 is a single-core LV power cable rated 0.6/1 kV, 90 °C working, with a ZC class C flame-retardant PVC sheath. One compacted 95 mm² copper core, XLPE insulation, unscreened. OD ≈ 18.5 mm, ≈ 1150 kg/km, ≈ 260 A — a general feeder and motor-supply cable, not a fire-rated circuit.
2. Construction Stack (Inner → Outer).
| Layer | Build | Function |
|---|---|---|
| Conductor | 1×95 compacted Cu, Class 2 | Power core |
| XLPE insulation | Cross-linked PE, ≈1.6 mm | 90 °C dielectric |
| PVC ZC sheath | Flame-retardant class C, ≈1.8 mm | Protection, self-extinguish |
3. Electrical Characteristics. Core R ≤ 0.193 Ω/km @20 °C. Test 3.5 kV AC / 5 min; nominal ≈ 260 A (air, 30 °C); short-circuit ≈ 8.4 kA / 1 s; unscreened.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 0.193 Ω/km |
GB/T 3956 Class 2 Cu max |
|
AC resistance @90 °C (est.) |
≈ 0.248 Ω/km |
— |
|
Current rating in air (30 °C) |
Phase: 275 A |
single-core, touching, in free air |
|
Current rating in tray (30 °C) |
Phase: 305 A |
single-core, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
Phase: 285 A |
direct buried |
|
Current rating in conduit (30 °C) |
Phase: 240 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 10.5 kA (10,500 A) |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.20 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 1×95 at 275 A, single-phase 230 V → max load ≈ 63 kW (cos φ = 0.8). Suitable for power distribution, transformer connections, and panel feeders.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing on removal of flame — this is flame retardancy, not 950°C circuit-integrity fire rating.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. Standard Cu lugs and glands; bend ≥ 15×OD ≈ 278 mm; indoor/tray preferred (use UV grade if exposed); continuity and insulation after laying.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 278 mm at Ø18.5 mm |
single-core unarmoured |
|
Max. pulling tension |
1,425 N (95 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Excellent (cable tray, ladder, cleats) |
— |
|
Conduit ID |
≥ 32 mm |
— |
|
Fixing |
cable ties, cleats |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. Panel feeders, motor supply, distribution mains, lighting trunk, general LV power runs.

7. Testing & QA Regime. Routine: DC resistance, 3.5 kV withstand, insulation resistance, continuity, sheath/insulation thickness, dimensional check, appearance. Type: ZC class C flame test, short-circuit rating
Cable Parameters
| ZC-YJV 1×95 mm² — LV Flame-Retardant Power Cable — Full Parameter Sheet | |||
| Cu conductor / XLPE insulation / PVC sheath · ZC flame-retardant class C · 0.6/1 kV · ≈ 18.5 mm · single-core feeder & motor supply | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — Cu / XLPE / PVC, flame-retardant class C | — | LV power |
| Rated voltage (U0/U) | 0.6/1 | kV | Low voltage |
| Core configuration | 1×95 | — | Single core |
| Conductor material | Compacted stranded annealed copper | — | Class 2 |
| Insulation | XLPE cross-linked polyethylene | — | 90°C |
| Sheath | PVC, flame-retardant class C (ZC) | — | Slate blue |
| Flame retardancy | ZC class C (flame retardant, not fire-rated) | — | Self-extinguishing |
| Application | Feeder, motor supply, distribution, lighting trunk | — | Power |
| 02 · Conductors | |||
| Power core | 1 × 95 | mm² | Single |
| Conductor type | Compacted stranded Cu, Class 2 | — | Round |
| DC resistance (95) @ 20°C | ≤ 0.193 | Ω/km | Cu 95 |
| Stranding | Layer-compacted, concentric | — | Stable OD |
| 03 · Insulation | |||
| Insulation material | XLPE (cross-linked PE) | — | 90°C rated |
| Insulation thickness (nom.) | ≈ 1.6 | mm | Single-core |
| Working conductor temp. | 90 | °C | Normal |
| Short-circuit temp. | 250 | °C | Max, short time |
| 04 · Sheath & Flame Retardancy | |||
| Sheath material | PVC, flame-retardant ZC | — | Class C |
| Sheath thickness (nom.) | ≈ 1.8 | mm | Overall |
| Finished outer diameter | ≈ 18.5 | mm | Single core |
| Flame behavior | Self-extinguishing, class C | — | Not 950°C fire-rated |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | LV |
| Max voltage (Um) | 1.2 | kV | Phase-to-earth |
| Nominal current (95 core) | ≈ 260 | A | Air, 30°C |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine |
| Insulation resistance | High, XLPE | MΩ·km | Stable |
| Short-circuit current (95, 1s) | ≈ 8.4 | kA | Copper |
| 06 · Thermal & Environment | |||
| Normal conductor temp. | 90 | °C | Continuous |
| Installed ambient | 0 ~ +40 | °C | Indoor/tray |
| Burning | Self-extinguishing, ZC class C | — | Flame retardant |
| Outdoor / UV | Indoor preferred; use UV grade if exposed | — | PVC limit |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 278 | mm | Single-core |
| Flexibility | Flexible stranded, single-core | — | Easy pull |
| Shielding | None (unscreened power) | — | General |
| Cable weight per km | ≈ 1150 | kg/km | Copper core |
| 08 · Factory Advantages | |||
| Compacted round core | Press-lay keeps OD tight for clean conduit fit | — | Easy pull |
| Controlled XLPE cure | Even cross-linking, stable 90°C dielectric | — | Consistent insulation |
| ZC flame-retardant compound | Dosed PVC that self-extinguishes | — | Class C |
| Length-on-demand | Cut to exact meter, sealed ends, no offcut | — | No waste |
| Batch resistance log | Per-core DC R recorded against lot | — | Traceable |
| Clean print line | Voltage, size, ZC, length marked continuously | — | Clear ID |
| Light drum handling | Single-core reels load with standard equipment | — | Fast delivery |
| 09 · Installation | |||
| Laying | Tray, conduit, riser, motor terminal | — | Power |
| Connectors | Cu lugs, standard glands | — | General |
| Bend radius | ≥ 15×OD ≈ 278 mm | — | Single-core |
| Site test | Continuity + insulation post-laying | — | Commissioning |
| 10 · Packing & Applications | |||
| Supply length | Custom / wooden drum | m | Single-core |
| Reel type | Standard wooden drum | — | Light |
| Surface marking | ZC-YJV, 1×95, 0.6/1kV, ZC | — | Marking |
| Typical use | Feeders, motors, distribution, lighting trunk | — | Power |
Cable Test Parameters
| Test Parameters — ZC-YJV 1×95 LV Flame-Retardant Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | 20 °C, core | 95 ≤0.193 Ω/km | Routine |
| 2 | Voltage test (AC) | 3.5 kV AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | XLPE, 20°C | High & stable | Routine |
| 4 | Continuity | Core | Continuous | Routine |
| 5 | Flame retardancy | Class C vertical test | Self-extinguish | Type |
| 6 | Sheath thickness | Micrometer | Nominal ≥1.8 mm | Routine |
| 7 | Insulation thickness | Micrometer | Nominal ≥1.6 mm | Routine |
| 8 | Dimensional check | Caliper | OD ≈ 18.5 mm | Routine |
| 9 | Conductor construction | Visual / count | Class 2 compacted | Routine |
| 10 | Short-circuit rating | Calculated / type | 8.4 kA / 1 s | Type |
| 11 | Printing legibility | Visual | Marking readable | Routine |
| 12 | Appearance | Visual | Smooth sheath | Routine |
Cable Cross Section Structure

| ZC-YJV 1×95 — Cross-Section Construction Diagram (Schematic) | |||||
| Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C flame retardant · ≈ 18.5 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor | 1×95 compacted Cu, Class 2 | — | ≈ 13 | Power core |
| 2 | XLPE insulation | Cross-linked PE | ≈ 1.6 | ≈ 16.9 | 90°C dielectric |
| 3 | PVC sheath | ZC flame-retardant | ≈ 1.8 | ≈ 18.5 | Protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 18.5 | mm | Single core | ||
| Approx. cable mass | ≈ 1150 | kg/km | Cu core | ||
| Nominal voltage rating | 0.6/1 | kV | LV | ||
| Normal conductor temp. | 90 | °C | Continuous | ||
| Flame retardancy | ZC class C, self-extinguishing | — | Not fire-rated | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 278 | mm | Single-core | ||
| DC resistance (95) | ≤ 0.193 | Ω/km | Cu 95 | ||
| Nominal current (95 core) | ≈ 260 | A | Air, 30°C | ||
| Short-circuit rating (1s) | ≈ 8.4 | kA | 95 Cu | ||
| Core configuration | 1×95 | — | Single | ||
| Application | Feeders, motors, distribution | — | Power | ||
| Schematic — not to exact scale. OD ≈18.5 mm and weight ≈1150 kg/km from cross-referenced industry samples. ZC-YJV 1×95 is a general LV flame-retardant power cable for feeders, motor supply and distribution; ZC class C self-extinguishes but is not 950°C fire-rated. Values marked (est.) require confirmation against the factory test certificate. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 1×95 LV flame-retardant power cable | |||
| Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈18.5 mm | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 1×95 rated 0.6/1 kV, 90°C working, ZC class C flame retardant. OD ≈18.5 mm, ≈1150 kg/km, ≈260 A, standard wooden drum. | |||
| 2. Copper Conductor (1×95) | |||
| Single 95 mm² compacted Class 2 Cu core, concentric lay. DC R ≤0.193 Ω/km @20°C. | |||
| 3. XLPE Insulation | |||
| Cross-linked PE at ≈1.6 mm gives a stable 90°C dielectric; short-circuit limit 250°C. | |||
| 4. PVC ZC Sheath | |||
| Flame-retardant PVC ≈1.8 mm, self-extinguishing class C; slate blue finish. | |||
| 5. Factory Advantages | |||
| • Compacted round core, clean conduit fit. • Controlled XLPE cure. • Dosed ZC self-extinguish compound. • Cut to exact meter. • Per-batch resistance log. • Continuous clear print. • Light drum, standard handling. | |||
| 6. Site Handling Notes | |||
| • Bend 15×OD (≈278 mm). • Cu lugs, standard glands. • Indoor/tray; UV grade if exposed. • Continuity + insulation after laying. |
8. Factory Advantages.
- Compacted round core — press-lay keeps OD tight for a clean conduit fit and easy pull.
- Controlled XLPE cure — even cross-linking gives a stable 90°C dielectric lot to lot.
- ZC flame-retardant compound — dosed PVC that self-extinguishes to class C.
- Length-on-demand — cut to the exact meter with sealed ends, no offcut waste.
- Batch resistance log — per-core DC R recorded against the lot for traceability.
- Clean print line — voltage, size, ZC, and length marked continuously along the jacket.
- Light drum handling — single-core reels load with standard equipment for fast delivery.

9. Packaging, Storage & Logistics. Standard wooden drum; continuous marking (ZC-YJV, 1×95, 0.6/1kV, ZC). Store dry, indoor; lighter reels suit manual/standard handling.

10. Procurement Specification. State "ZC-YJV 1×95", length, and class C requirement; note it is flame retardant, not fire-rated, and request the resistance log per batch.