1*150mm2 Single Core Copper Wire XLPE Insulation PVC Sheath For Construction Wiring
Basic Properties
Trading Properties
Product Summary
Product Details
1*150mm2 single core copper wire
,single core copper wire XLPE Insulation
,Construction single core thin wall cable
Product Description
ZR-YJV 1*150mm² Flame Retardant Copper Cable,0.6/1kV XLPE Insulation PVC Sheath for Construction Wiring
Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed.
1. Identity & Standards. The ZR-YJV 1×150 is a single-conductor, flame-retarded power cable with a CU/XLPE/PVC make-up, rated 0.6/1 kV (Um = 1.2 kV) at 50 Hz. It is manufactured and type-tested to GB/T 12706.1 / IEC 60502-1; the conductor complies with GB/T 3956 / IEC 60228; the "ZR" fire-retardant property follows GB/T 19666 and GB/T 18380. Default fire class is ZC unless ZA/ZB is ordered.

2. Construction Detail. Cross-section, inside out:
| Layer | Composition | Thickness | Diameter |
|---|---|---|---|
| Conductor | Annealed copper, Class 2, 30 × 2.52 mm (30/2.52) stranded, 150 mm² | — | ≈ 13.8 mm (compacted; up to ≈ 15.3 mm round-lay) |
| Insulation | Cross-linked polyethylene (XLPE) | 1.4 mm | ≈ 16.6 mm over insulation |
| Sheath | Flame-retarded PVC, ST2, black | 2.0 mm | ≈ 20.6 mm overall |
Mass ≈ 1590 kg/km (copper alone ≈ 1333 kg/km); overall diameter 20.6–21 mm (some makers quote up to 23 mm including tolerance).

3. Electrical Characteristics. Max DC resistance ≤ 0.124 Ω/km at 20 °C; routine withstand 3.5 kV AC / 5 min; XLPE volume resistivity ≥ 1×10¹² Ω·cm; finished-cable insulation resistance typically ≥ 36.7 MΩ·km; capacitance ≤ 0.45 μF/km. Reference ampacity ≈ 460 A in air (30 °C, single core) and ≈ 425 A direct-buried — derate for grouping, ambient and method (GB/T 16895 / IEC 60364).
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine |
|
Type-test voltage |
4.0 kV |
IEC 60502 |
|
DC resistance @20 °C (Class 2 Cu) |
≤ 0.124 Ω/km |
GB/T 3956 / IEC 60228 max |
|
AC resistance @90 °C (est.) |
≈ 0.161 Ω/km |
copper temp. coefficient |
|
Current rating in air (30–40 °C, single circuit, single-core) |
≈ 440 – 455 A |
PVC sheath; design ≈ 440 A |
|
Direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) |
≈ 400 – 415 A |
design ≈ 400 A |
|
Short-circuit current (1 s adiabatic, Cu, 250 °C) |
≈ 17.32 kA |
reference |
|
Frequency |
50/60 Hz AC (DC usable) |
— |
4. Thermal & Physical Data. Continuous conductor rating 90 °C; short-circuit ceiling 250 °C (≤ 5 s); ambient −20 to +45 °C; installation not below 0 °C without pre-warming; minimum bending radius 20 × OD for single-core runs.
| ZR-YJV 1×150 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV) | |||||
| Construction: CU / XLPE / PVC • Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance) • Nominal values for reference — confirm against factory test certificate | |||||
| No. | Category | Parameter | Value | Unit | Notes / Standard Reference |
| A. Product Identification | |||||
| 1 | Identification | Product name | Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable | — | Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing) |
| 2 | Identification | Model designation | ZR-YJV 1×150 | — | Cu / XLPE / PVC |
| 3 | Identification | Design standards | GB/T 12706.1; IEC 60502-1 | — | Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence |
| 4 | Identification | Rated voltage U0/U | 0.6/1 | kV | Max system voltage Um = 1.2 kV |
| 5 | Identification | Rated frequency | 50 | Hz | AC power distribution |
| 6 | Identification | Number of cores | 1 | — | Single-core cable |
| 7 | Identification | Nominal cross-sectional area | 150 | mm² | Nominal conductor cross-section per GB/T 3956 |
| B. Cable Construction (from conductor to outer sheath) | |||||
| 8 | Conductor | Material | Plain annealed copper (Cu) | — | High-conductivity electrolytic / oxygen-free copper |
| 9 | Conductor | Conductor class | Class 1 or Class 2 (typical: Class 2, stranded) | — | GB/T 3956 / IEC 60228 |
| 10 | Conductor | Typical stranding construction | 30 wires × 2.52 mm (30/2.52) | — | Class 2 round stranded; nominal section ≈ 150 mm² |
| 11 | Conductor | Conductor diameter | ≈ 13.8 | mm | ≈ 13.8 mm compact (13.8–15.3 mm across stranding practice) |
| 12 | Conductor | Max. DC resistance of conductor at 20 °C | 0.124 | Ω/km | GB/T 3956, Class 2 copper; acceptance criterion for 150 mm² |
| 13 | Insulation | Material | Cross-linked polyethylene (XLPE) | — | Thermally cross-linked; natural/transparent colour |
| 14 | Insulation | Nominal insulation thickness | 1.4 | mm | GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 150 mm²) |
| 15 | Insulation | Diameter over insulation | ≈ 16.6 | mm | ≈ 13.8 + 2 × 1.4 (calculated, compact conductor) |
| 16 | Sheath | Material | Flame-retardant polyvinyl chloride (PVC, ST2 type) | — | Colour: black (or as ordered) |
| 17 | Sheath | Nominal sheath thickness | 2.0 | mm | GB/T 12706.1 / IEC 60502-1 (cabhr & Hongqi tables) |
| 18 | Dimensions | Approx. overall diameter | 20.6 | mm | ≈ 20.6 mm (20.6–21 mm; some makers list up to 23 mm incl. tolerance) |
| 19 | Dimensions | Approx. cable weight | ≈ 1590 | kg/km | cabhr / Hongqi / Lvbao agree at 1590 kg/km (copper core alone ≈ 1333 kg/km) |
| C. Electrical Performance | |||||
| 20 | Electrical | Max. DC conductor resistance at 20 °C | 0.124 | Ω/km | GB/T 3956; routine measurement |
| 21 | Electrical | Power-frequency withstand voltage (routine test) | 3.5 kV / 5 min, no breakdown | — | AC 50 Hz; per GB/T 12706.1 / IEC 60502-1 |
| 22 | Electrical | Insulation resistance (finished cable, 20 °C) | ≥ 36.7 | MΩ·km | Typical finished-cable reference for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method |
| 23 | Electrical | XLPE volume resistivity at 20 °C | ≥ 1 × 10¹² | Ω·cm | Material-level requirement (manufacturer reference) |
| 24 | Electrical | Capacitance (single-core, approx.) | ≤ 0.45 | μF/km | Manufacturer reference value |
| 25 | Electrical | Reference ampacity — in air, 30 °C, single core | ≈ 460 | A | cabhr table (460 A); depends on laying, grouping, ambient — apply correction factors per GB/T 16895 / IEC 60364 |
| 26 | Electrical | Reference ampacity — direct burial, 25 °C | ≈ 425 | A | cabhr table; depends on soil thermal resistivity and depth |
| D. Thermal Performance | |||||
| 27 | Thermal | Max. continuous conductor temperature | 90 | °C | XLPE insulation temperature class |
| 28 | Thermal | Max. conductor temperature under short-circuit (≤ 5 s) | 250 | °C | Per GB/T 12706.1 / IEC 60502-1 |
| 29 | Thermal | Ambient service temperature range | -20 to +45 | °C | Per Qifan datasheet family; check project specification |
| 30 | Thermal | Min. installation (laying) temperature | 0 | °C | Pre-heat the cable if ambient is below 0 °C |
| E. Flame Retardance (ZR) | |||||
| 31 | Flame retardance | Flame-retardant class | ZC (class C) by default for "ZR" | — | GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH) |
| 32 | Flame retardance | Single-cable vertical flame-spread test | Pass | — | GB/T 18380.12 |
| 33 | Flame retardance | Bunched flame-spread test (class C) | Char extent ≤ 2.5 m above burner bottom edge | — | GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min |
| 34 | Flame retardance | Halogen content | Halogen-containing (PVC) | — | For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type |
| F. Installation | |||||
| 35 | Installation | Min. bending radius — single-core cable | 20 × OD | — | Qifan & Huaneng datasheets; OD = actual cable diameter |
| 36 | Installation | Laying methods | Conduit, tray, cable trench, tunnel, duct, supported/suspended aerial | — | Also direct burial with mechanical protection where permitted |
| 37 | Installation | Site withstand test after installation | DC 4U0 = 2.4 kV, 15 min (recommended) | — | Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project |
| G. Packing & Delivery | |||||
| 38 | Packing | Standard delivery length | 100 m per coil/drum (or as ordered) | — | Typical industry practice; custom lengths available |
| 39 | Packing | Cable marking | Model, rated voltage, manufacturer, year of manufacture, sequential length marks | — | Per GB/T 6995 / project specification |
| 40 | Packing | Packing form | Wooden drum / coil / export packing | — | As per customer requirement |
5. Flame-Retardance & Environment. The ST2 PVC jacket passes the single vertical burn (GB/T 18380.12) and the class-C bunched burn (GB/T 18380.35: ≥ 1.5 L/m non-metallic content, 20 min, char ≤ 2.5 m), earning class ZC per GB/T 19666. PVC releases halogen under fire — select WDZ-YJY where low-smoke zero-halogen is specified.
6. Test Regime. Routine: DC resistance ≤ 0.124 Ω/km; 3.5 kV/5 min; construction audit (insulation ≥ 1.4 mm, sheath ≥ 2.0 mm). Sample: hot-set on XLPE (200 ± 3 °C, 15 min, 0.2 MPa — elongation ≤ 175 %, permanent set ≤ 15 %); stranding/diameter check. Type: flame and bending tests. Post-install: DC 4U0 = 2.4 kV / 15 min (Q/GDW 13244.1-2018 practice).
| ZR-YJV 1×150 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1) | ||||
| Test Stage | Test Item | Method / Standard | Requirement / Acceptance Criterion | Notes |
| Routine test | Conductor DC resistance measurement | GB/T 3956 (IEC 60228) | ≤ 0.124 Ω/km at 20 °C | Measured on every production length |
| Routine test | Power-frequency withstand voltage | GB/T 12706.1 / IEC 60502-1 | 3.5 kV AC, 5 min, no breakdown | Applied between conductor and water/earth; 50 Hz |
| Routine test | Construction check — insulation & sheath thickness, outer diameter | GB/T 2951 | Within GB/T 12706.1 tolerances | Insulation ≥ 1.4 mm nominal; sheath ≥ 2.0 mm nominal |
| Sample test | Hot set (thermal elongation) test — XLPE insulation | GB/T 12706.1 §16.3.13 / GB/T 2951.11 | 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % | Verifies degree of cross-linking |
| Sample test | Conductor construction & diameter check | GB/T 3956 | Class 2; 30 × 2.52 mm; Ø ≈ 13.8 mm | Sampled per batch |
| Type test | Single-cable vertical flame-spread test (flame retardance) | GB/T 18380.12 | No flame spread; charring does not reach top reference point | ZR / ZC flame-retardant property |
| Type test | Bunched flame-spread test, class C | GB/T 18380.35 | Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m | Class ZC per GB/T 19666 |
| Type test | Bending test (mechanical) | GB/T 12706.1 | Bend around specified mandrel without insulation/sheath damage | Mandrel diameter related to cable OD |
| Post-installation | DC withstand test after installation | Q/GDW 13244.1-2018 (recommended practice) | 4U0 = 2.4 kV DC, 15 min, no breakdown | For new installations; verify project specification |
| Optional | Insulation resistance measurement at 20 °C | Manufacturer test method | ≥ 36.7 MΩ·km (typical finished-cable value) | Not a routine item in GB/T 12706.1; confirm with factory |
| Optional | XLPE volume resistivity at 20 °C | Manufacturer / material test | ≥ 1 × 10¹² Ω·cm | Material-level reference |
7.Cross Section Structure

| ZR-YJV 1×150 mm² — Cable Cross-Section Structure (Schematic) | |||||
| Layers from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Cu) | Annealed copper, Class 2 stranded — 30 × 2.52 mm (30/2.52), nominal 150 mm² | — | ≈ 13.8 (Ø) | Current-carrying element; max DC resistance ≤ 0.124 Ω/km @ 20 °C |
| 2 | Insulation (XLPE) | Cross-linked polyethylene | 1.4 | ≈ 16.6 (Ø over insulation) | Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min |
| 3 | Outer sheath (PVC) | Flame-retardant PVC, ST2 type, black | 2 | ≈ 20.6 (Ø overall) | Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666 |
| Key Dimensions & Properties | |||||
| Overall diameter | 20.6 | mm | 20.6–21 mm (up to 23 mm incl. tolerance); cabhr 20.6; Hongqi 21 | ||
| Approx. cable weight | ≈ 1590 | kg/km | cabhr / Hongqi / Lvbao agree; Cu core alone ≈ 1333 kg/km | ||
| Rated voltage | 0.6/1 | kV | AC 50 Hz; max system voltage Um = 1.2 kV | ||
| Max conductor temperature | 90 / 250 | °C | Continuous / short-circuit (≤ 5 s) | ||
| Min. bending radius (single-core) | 20 × OD | — | OD = actual cable diameter | ||
| Flame-retardant class | ZC (ZR) | — | GB/T 19666 | ||
8. Handling & Safety Notes. Unroll from the drum without twisting the single core; avoid kinking at terminations; protect the sheath from UV and sharp edges during and after laying; run the site DC test and verify insulation integrity before energising; never exceed the 3.5 kV/5 min level for site checks unless the project allows otherwise.
9. Applications. Heavy low-voltage feeders, large motor and pump circuits, transformer secondary connections, main switchboard tails and industrial distribution risers — in trays, conduits, trenches, tunnels and ducts, indoors or in sheltered outdoor positions.

10. Packing & Ordering. Normally delivered 100 m per drum/coil, with standard marking (model, voltage, maker, year, length marks). Order: ZR-YJV 0.6/1 kV 1×150, with length and drum type. Reconcile all data against the factory certificate and GB/T 12706.1 / IEC 60502-1 test report before installation.