Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE

Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZR-YJV 4x35mm²+1x16mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath — ...

Product Details

Highlight:

xlpe 5 core cable

,

xlpe copper conductor cable

,

flame retardant 5 core cable

Phase/Neutral conductor (×4):
Bare Annealed Copper, Class 2 Stranded, 7×∅2.52 Mm, Conductor Ø ≈ 7.56–8.05 Mm Depending On Compaction
PE conductor (×1):
Bare Annealed Copper, Class 2 Stranded, 7×∅1.70 Mm, Conductor Ø ≈ 5.10–5.45 Mm Depending On Compaction
Phase/Neutral conductor nominal area:
35 Mm²
PE conductor nominal area:
16 Mm²
Number of cores:
5 (4+1)
Phase/Neutral conductor construction:
Class 2, 7×∅2.52 Mm,IEC 60228 / GB/T 3956
PE conductor construction:
Class 2, 7×∅1.70 Mm,IEC 60228 / GB/T 3956
Phase/Neutral conductor diameter (approx.):
7.56–8.05 Mm
PE conductor diameter (approx.):
5.10–5.45 Mm
Insulation (×5):
XLPE
Phase/Neutral insulation thickness:
1.1 Mm (35 Mm² Class)
PE insulation thickness:
0.7 Mm (16 Mm² Class)
Diameter over phase/neutral insulated core:
9.76–10.25 Mm
Diameter over PE insulated core:
6.50–6.85 Mm
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.6 Mm (GB/T 12706 Multi-core 25–50 Mm² Range)
Overall cable diameter:
21.0 – 25.5 Mm
Design outer diameter:
≈ 22.5 Mm
Approx. weight:
820 – 1000 Kg/km
Design weight:
≈ 900 Kg/km
Cable shape:
Round

Product Description

Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


Cable Designation & Meaning


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×35+1×16 mm²

Four equal phase/neutral cores of 35 mm² copper + one reduced protective earth (PE) core of 16 mm² copper


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


ZR-YJV 4×35+1×16 mm² — Cable Specification & Engineering Data

1. Product Overview & Rating Summary. ZR-YJV 4×35+1×16 sits between the 4×25+1×16 and the heavier 4×50 range in the flame-retardant 4+1-core low-voltage family: four 35 mm² annealed copper phase conductors are cabled around a central 16 mm² copper neutral/PE core, each insulated in XLPE and enclosed in a single ST2 PVC oversheath rated for 0.6/1 kV at 50 Hz. Manufacture and type testing are performed to GB/T 12706.1 / IEC 60502-1, stranding complies with GB/T 3956, and the ZR marking denotes class ZC flame retardance under GB/T 19666. The finished outer diameter is roughly 28.5 mm and the nominal mass is about 1750 kg per kilometre in copper (850 kg/km for the aluminium YJLV equivalent), delivered in 100 m coils or wooden drums with ≥ Ø 1000 mm flanges — approximately 175 kg per 100 m.


2. Layer-by-Layer Construction (Conductor to Jacket).

Layer Construction Wall Diameter
Phase conductor (×4) Annealed Cu, Class 2 compact, 7 × 2.52 mm (1+6) each — ≈ 7.5 mm
Neutral conductor (×1) Annealed Cu, Class 2 compact, 7 × 1.70 mm (1+6) — ≈ 5.4 mm
Phase insulation (×4) XLPE 1.4 mm ≈ 10.3 mm
Neutral insulation (×1) XLPE 1.0 mm ≈ 7.4 mm
Core assembly Central neutral + 4 phase cores cabled around + PP filler + polyester binder — ≈ 25.3 mm (derived)
Outer jacket Flame-retarded PVC, ST2 compound, black 1.6 mm ≈ 28.5 mm (finished)


3. Electrical Characteristics. Each 35 mm² phase conductor is limited to 0.524 Ω/km at 20 °C, climbing to around 0.66 Ω/km at the 90 °C operating point; the 16 mm² neutral/PE is capped at 1.15 Ω/km. Every production length survives the routine 3.5 kV AC power-frequency proof held for five minutes. Finished-cable insulation resistance remains above 36.7 MΩ·km, XLPE volume resistivity exceeds 1×10¹² Ω·cm, and typical values include capacitance ≤ 0.40 μF/km, inductance ≈ 0.28 mH/km and 50 Hz AC impedance ≈ 0.53 Ω/km. On a one-second short circuit each 35 mm² phase withstands about 4.03 kA (the 16 mm² neutral on a 1.84 kA basis), using I = k·A/√t with k = 115 for copper/XLPE. With all four phase cores energised, reference loading is 140 A in free air at 25 °C and 115 A directly buried at 25 °C — engineering estimates to be confirmed against the factory test certificate.


Electrical Parameters


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (phase/neutral, per core)

≤ 0.524 Ω/km

GB/T 3956 max, 35 mm²

DC resistance @20 °C (PE, per core)

≤ 1.15 Ω/km

GB/T 3956 max, 16 mm²

AC resistance @90 °C (est., phase/neutral)

≈ 0.681 Ω/km

per core

AC resistance @90 °C (est., PE)

≈ 1.50 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core+1)

≈ 115–130 A

based on 35 mm² phase

Current rating in air (design)

≈ 120 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 135–152 A

common catalogue 140–146 A

Design buried rating

≈ 143 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, phase/neutral)

≈ 3.5 kA

35 mm² reference

Short-circuit current (1 s, Cu, 250 °C, PE)

≈ 1.6 kA

16 mm² reference

Frequency

50/60 Hz AC

—


Cable Parametes


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


Cable Test Parameters


Test Parameters — ZR-YJV 4×35+1×16 mm²
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3048.4, 20 °C Phase ≤ 0.524 Ω/km; Neutral ≤ 1.15 Ω/km Routine
2 Power-frequency withstand 3.5 kV AC, 5 min No breakdown Routine
3 Insulation resistance GB/T 3048.5, 90 °C ≥ 36.7 MΩ·km Routine
4 Conductor continuity Visual + electrical All 5 cores continuous Routine
5 Dimensional check Micrometer Phase ins. ≥ 1.4 mm; neutral ≥ 1.0 mm; sheath ≥ 1.6 mm; OD ≈ 28.5 mm Routine
6 XLPE hot-set test 200 ± 3 °C, 15 min, 0.2 MPa Load elongation ≤ 175 %; permanent set ≤ 15 % Type
7 XLPE tensile & elongation GB/T 2951.11 Tensile ≥ 12.5 MPa; elongation ≥ 200 % Type
8 PVC sheath tensile & elongation GB/T 2951.11 Tensile ≥ 10 MPa; elongation ≥ 125 % Type
9 PVC thermal stability 200 °C, HCl evolution ≥ 200 min Type
10 Single-cable vertical flame GB/T 18380.12 Self-extinguishing; char ≤ 50 mm above burner Type
11 Bunched cable flame (cat. C) GB/T 18380.35 Char height ≤ 2.5 m Type
12 Bending test ≥ 15 × OD mandrel No crack in insulation or sheath Type
13 Heat deformation (PVC) 80 °C, 4 h, load Deformation ≤ 50 % Type
14 XLPE shrinkage test 130 °C, 1 h Shrinkage ≤ 4 % Type
15 Site DC withstand 4U0 = 2.4 kV DC, 15 min No breakdown (Q/GDW 13244.1-2018) Site
16 Core identification Visual + continuity Correct L1/L2/L3/N/PE identification Site


Cable Cross Section Structure


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


ZR-YJV 4×35+1×16 mm² — Cross-Section Construction Diagram (Schematic)
Layered 4+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 28.5 mm per cross-referenced industry sample
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Phase conductor (Cu) × 4 Annealed copper, Class 2 compact strand — 7 wires of 2.52 mm per core (7/2.52, 1+6 layout), nominal area 35 mm² each — ≈ 7.5 (Ø each phase core) Line-current carrying phase conductors; DC resistance capped at 0.524 Ω/km at 20 °C
2 Neutral conductor (Cu) × 1 Annealed copper, Class 2 compact strand — 7 wires of 1.70 mm (7/1.70, 1+6 layout), nominal area 16 mm² — ≈ 5.4 (Ø neutral core) Return / PE path; DC resistance capped at 1.15 Ω/km at 20 °C
3 Phase insulation (XLPE) × 4 Cross-linked polyethylene dielectric 1.4 ≈ 10.3 (Ø each phase core, incl. insulation) Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min
4 Neutral insulation (XLPE) × 1 Cross-linked polyethylene dielectric 1 ≈ 7.4 (Ø neutral core, incl. insulation) Electrical isolation for the neutral/PE conductor
5 Core assembly Neutral core at centre + four phase cores cabled around + PP filler + polyester binder tape — ≈ 25.3 (Ø over assembled cores) 4+1 configuration; derived from finished Ø 28.5 − 2×1.6 sheath
6 Outer jacket (PVC) Flame-retardant PVC, ST2 compound, black 1.6 ≈ 28.5 (Ø finished cable) Mechanical and moisture protection; ZC flame retardance per GB/T 19666
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 28.5 mm Cross-referenced industry 4+1 sample

Approximate cable mass ≈ 1750 kg/km Cu build-up (cross-referenced industry data)

Approximate mass, aluminium build ≈ 850 kg/km YJLV equivalent (est.)

Nominal voltage rating 0.6/1 kV AC 50 Hz; maximum system voltage Um = 1.2 kV

Conductor temperature limits 90 / 250 °C Continuous service / short-circuit (≤ 5 s)

Minimum bend radius (multi-core) ≥ 15 × OD ≈ 428 mm OD = actual finished cable diameter

Flame-retardant classification ZC (ZR) — Per GB/T 19666

Short-circuit current, phase (1 s) ≈ 4.03 kA I = k·A/√t, k=115 for Cu/XLPE

Short-circuit current, neutral (1 s) ≈ 1.84 kA 16 mm² neutral, same k factor

AC impedance @ 50 Hz ≈ 0.53 Ω/km √(R² + X²); R-dominant (est.)

Capacitance (typical) ≤ 0.40 μF/km Per phase core (est.)

Inductance (typical) ≈ 0.28 mH/km Multi-core cable (est.)

Air ampacity @ 25 °C ≈ 140 A 4 phase cores loaded, Cu (est.)

Buried ampacity @ 25 °C ≈ 115 A 4 phase cores loaded, Cu (est.)

Maximum pulling tension ≤ 5600 N 40 N/mm² of main phase core area (est.)







Schematic — not to exact scale. Finished Ø ≈ 28.5 mm and weight ≈ 1750 kg/km from cross-referenced industry samples; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1; ampacity 140/115 A is an engineering estimate for 4+1 cables. Values marked (est.) require confirmation against the factory test certificate.


Cable Construction Description


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


4. Thermal Response & Flame Performance. XLPE sustains a 90 °C continuous conductor temperature and tolerates a 250 °C short-circuit peak for up to five seconds. The cable is rated for service ambients between −20 and +45 °C, must not be uncoiled below 0 °C without pre-conditioning, and uses 25 °C as the reference soil temperature for buried ratings. Flame behaviour meets class ZC of GB/T 19666, proven by both the single-cable vertical test (GB/T 18380.12) and the category-C bunched test (GB/T 18380.35) with char height limited to 2.5 m. The PVC jacket is halogenated and will emit smoke and acid gas in a fire; low-smoke zero-halogen projects must specify WDZ-YJY instead.


5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 428 mm for this size. Before first energisation, apply the DC site withstand at 4U0 = 2.4 kV for 15 minutes in line with Q/GDW 13244.1-2018. Drums held below 0 °C in storage must be warmed indoors before uncoiling; pulling tension should stay within 5600 N. The 140 A (air) and 115 A (buried) references require derating whenever ambient temperature, cable grouping or soil thermal resistivity deviates from reference conditions. Crimp lugs, glands and heat-shrink termination kits must be matched to the 7.5 mm phase core, 5.4 mm neutral core and ≈ 28.5 mm jacket, and both phase and neutral short-circuit withstand should be coordinated with upstream protective device settings.


6. Typical Service Applications. This cross-section serves main and sub-main distribution circuits where the 4×25+1×16 rating is inadequate: main distribution risers in mid-rise commercial buildings, transformer secondary feeders up to about 160 kVA, motor connections in the 15–37 kW range, machine-tool and process-line power leads, workshop and warehouse distribution panels, elevator and escalator supply circuits, and auxiliary power in light-industrial installations. Approved installation methods include steel or PVC conduit, cable trunking, tray and indoor ducting, both indoors and in covered outdoor locations. For direct burial or mechanically exposed routing, the steel-tape armoured ZR-YJV22 variant is recommended.


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


7. Testing & Quality Assurance Regime. Routine tests on every length include phase and neutral DC resistance verification (≤ 0.524 / 1.15 Ω/km at 20 °C), the 3.5 kV AC / 5 min withstand, conductor continuity across all five cores and dimensional inspection covering phase insulation ≥ 1.4 mm, neutral insulation ≥ 1.0 mm, sheath ≥ 1.6 mm and overall diameter ≈ 28.5 mm. Sample and type tests comprise the XLPE hot-set trial at 200 ± 3 °C for 15 minutes under 0.2 MPa (load elongation ≤ 175 %, permanent set ≤ 15 %), XLPE tensile ≥ 12.5 MPa with elongation ≥ 200 %, PVC sheath tensile ≥ 10 MPa with elongation ≥ 125 %, PVC thermal stability ≥ 200 minutes at 200 °C, single-cable and category-C bunched flame trials, and bending assessment. Commissioning on site requires insulation-resistance measurement, the DC 2.4 kV / 15 min withstand and positive L1/L2/L3/N/PE identification before switching. A factory test certificate accompanies each drum.


Cable Flame Retarment Parameters


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


Cable Insulation Parameters


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


8. Standards & Conformity. Design and production are governed by GB/T 12706.1 and IEC 60502-1 for 0.6/1 kV extruded-insulation power cables. Conductors satisfy GB/T 3956 / IEC 60228 Class 2 — the 35 mm² phase as seven wires of 2.52 mm with R ≤ 0.524 Ω/km, and the 16 mm² neutral as seven wires of 1.70 mm with R ≤ 1.15 Ω/km. Flame retardance is classified under GB/T 19666 (ZC as the default for the ZR marking) and proven by GB/T 18380.12 and GB/T 18380.35 category C. Installation acceptance follows Q/GDW 13244.1-2018 and GB 50168, while surface marking complies with GB/T 6995. Cables can also be supplied to IEC, BS, DIN, ICEA or JIS requirements on request. Because the ST2 PVC jacket contains halogen, tunnels, metro systems, hospitals and other confined public areas call for WDZ-YJY.


9. Packaging, Storage & Logistics. Standard delivery is 100 m per coil or wooden drum, with bespoke cut lengths available on request. Each drum carries type, voltage, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +45 °C, shielded from direct sunlight, moisture, oils and sharp objects; coils and drums remain sealed until installation and are stored upright on their flanges rather than flat. In cold conditions, condition drums indoors to ≥ 0 °C before pulling. During transit, coils and drums must be secured against rolling and impact, and the cable must never be dragged across abrasive ground or sharp edges.


Construction Site Power Cable ZR-YJV 4x35mm²+1x16mm² Flame Retardant Copper XLPE


10. Procurement Specification. State "ZR-YJV 0.6/1 kV 4×35+1×16" together with the required length or drum arrangement and marking preferences. Specify the flame-retardant class (ZC is standard; ZA or ZB available), jacket colour and any special drum requirements. Always request the factory test certificate to confirm the actual unarmoured diameter (≈ 28.5 mm), weight (≈ 1750 kg/km) and ampacity for the production batch. Where low-smoke zero-halogen or armoured construction is needed, order WDZ-YJY or ZR-YJV22 respectively.


11. Cable Industry FAQ.

  • Q1: How does 4×35+1×16 differ from the smaller 4×25+1×16? The phase area grows from 25 to 35 mm² (conductor from 7×2.14 to 7×2.52 mm) while the neutral stays at 16 mm², raising the rated current from about 115/95 A to 140/115 A, increasing the finished diameter from 25.7 to 28.5 mm, and lifting the one-second phase short-circuit withstand from about 2.88 to 4.03 kA.
  • Q2: Why is the neutral/PE only 16 mm² when the phases are 35 mm²? In a balanced four-wire circuit the neutral carries mainly unbalance and harmonic current, so GB/T 12706.1 permits a reduced core in the 4+1 construction. Where the installation serves substantial single-phase or non-linear, harmonic-generating loads, an equal-section 5-core cable should be chosen.
  • Q3: What do ZA, ZB, ZC and ZD mean? These are flame-retardant classes in GB/T 19666, assessed through the bunched-cable test GB/T 18380.35 at progressively higher fuel loads — ZA is the most demanding, ZD the least. The bare "ZR" marking defaults to ZC; ZA and ZB must be requested at ordering.
  • Q4: When should a 4+1, equal 5-core, or plain 4-core cable be selected? Choose 4+1 for standard four-wire service with a reduced neutral/PE; equal 5-core (4×A+1×A) where neutral current is expected to approach phase current; plain 4-core when no separate PE conductor is required in the cable.
  • Q5: Why do air and buried ratings differ, and how are they adjusted? Published figures assume 25 °C air or 25 °C soil at 1.0 K·m/W thermal resistivity with a single circuit. Manufacturer correction factors must be applied for ambient temperature, grouping, burial depth and soil resistivity — air factors range from about 1.29 at 20 °C down to 0.91 at 45 °C, and soil factors from 1.04 at 20 °C to 0.87 at 40 °C.
  • Q6: Copper or aluminium? Copper (this cable) delivers lower resistance (0.524 versus roughly 0.87 Ω/km at 35 mm²), higher current per mm², better mechanical strength and more dependable terminations; aluminium (YJLV, ≈ 850 kg/km in this size) costs less and weighs less but requires larger cross-sections and anti-oxidation treatment at every joint.
  • Q7: Why can XLPE run at 90 °C while PVC insulation is limited to 70 °C? Cross-linking transforms polyethylene into a three-dimensional thermoset network, which raises the continuous conductor rating to 90 °C and the short-circuit withstand to 250 °C — directly increasing the ampacity available from a given copper area.
  • Q8: How is the conductor cross-section chosen? Selection is governed by (a) full-load current after derating, (b) permissible voltage drop (typically ≤ 5 % for branch circuits), (c) short-circuit withstand on an I²t basis (4.03 kA·s per phase here), and (d) coordination with overcurrent protective devices; the most stringent criterion controls.
  • Q9: Why does finished diameter vary between manufacturers for the same nominal size? Standards set minimum insulation and sheath thicknesses plus electrical performance, but not a precise overall diameter. Stranding compaction, filler design and sheath tolerance differ between plants — published 4×35+1×16 figures cluster around 28.5 mm unarmoured — so the actual measured diameter must always be used when sizing glands, trays and conduits.
  • Q10: Which tests confirm acceptability on delivery and before energisation? At delivery, verify the factory test certificate (resistance 0.524/1.15 Ω/km, 3.5 kV/5 min withstand, dimensions ≈ 28.5 mm), jacket legibility and drum integrity. After installation, complete an insulation-resistance test plus the DC 4U0 = 2.4 kV / 15 min withstand per Q/GDW 13244.1-2018, then confirm L1/L2/L3/N/PE identification before closing the breaker.
  • Q11: What service life can be expected? When installed and operated within the stated temperature and voltage limits, XLPE 0.6/1 kV cables are designed for a minimum service life of 30 years; sustained overload, ultraviolet exposure, water ingress through a damaged sheath, or operation above 90 °C will materially shorten that life.