4x10mm2+1x6mm2 XLPE Copper Cable 0.6kV 1kV Flame Retardant
Product Summary
Product Details
ISO 5 core electrical cable
,Black 5 core electrical cable
,xlpe insulated pvc sheathed cable
Product Description
ZR-YJV 4x10mm²+1x6mm² XLPE Copper Cable 0.6/1kV Flame Retardant
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
4×10 mm² + 1×6 mm² |
Four cores of 10 mm² (3 phase + 1 neutral) + one earth core of 6 mm² copper conductor |
Construction: Three 10 mm² copper conductors (phase L1/L2/L3) + one 10 mm² copper conductor (neutral N) + one 6 mm² copper conductor (earth PE), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).
ZC-YJV 4×10+1×6 mm² — LV Flame-Retardant 4+1 Small Distribution Cable — Specification
1. Overview & Ratings. ZC-YJV 4×10+1×6 is a 4+1 LV small distribution cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C PVC sheath: four 10 mm² compacted copper cores (L1/L2/L3 plus PE/spare) and one reduced 6 mm² neutral, dry-cured XLPE, unarmored. OD ≈ 13 mm, ≈ 550 kg/km (est.), ≈ 40 A per large core free air at 30 °C (est.). Scope: compact three-phase branches, control outlets, small feeders and light motor/socket circuits — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Cores L1/L2/L3/PE | 4×10 compacted Cu, Class 2, ≈7 strands | Phases + earth/spare; R ≤1.91 |
| Neutral N | 1×6 compacted Cu, reduced, ≈4 strands | Balanced return; R ≤3.08 |
| Strand compaction | Concentric layers rolled compact per core | Compact round bundle, clean lugs |
| XLPE large-core insulation | Dry-cured PE, ≈1.0 mm | Uniform 90°C dielectric |
| XLPE neutral insulation | Dry-cured PE, ≈0.8 mm | Matched to reduced core |
| 4+1 core laying | Four large cores around reduced neutral | Compact round bundle |
| PVC ZC sheath | Class C, ≈1.4 mm overall | Self-extinguishes, prints clear |
3. Electrical Characteristics. Large-core R ≤ 1.91 Ω/km, neutral R ≤ 3.08 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 40 A per large core (est., air 30 °C); neutral ≈ 30 A (est.); short-circuit ≈ 1.4 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C (phase/neutral) |
≤ 1.83 Ω/km per core |
GB/T 3956 Class 2 Cu max (10 mm²) |
|
DC resistance @20 °C (earth) |
≤ 3.08 Ω/km per core |
GB/T 3956 Class 2 Cu max (6 mm²) |
|
AC resistance @90 °C (est., phase/neutral) |
≈ 2.35 Ω/km per core |
— |
|
AC resistance @90 °C (est., earth) |
≈ 3.95 Ω/km per core |
— |
|
Current rating in air (30 °C) |
3-phase: 55 A |
4×10+1×6, touching, in free air |
|
Current rating in tray (30 °C) |
3-phase: 62 A |
4×10+1×6, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
3-phase: 58 A |
direct buried |
|
Current rating in conduit (30 °C) |
3-phase: 48 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C, phase/neutral) |
≈ 1.1 kA (1,100 A) per core |
— |
|
Short-circuit current (1 s, Cu, 250 °C, earth) |
≈ 0.66 kA (660 A) per core |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.15 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 4×10+1×6 at 55 A three-phase, 400 V → max load ≈ 33 kW (cos φ = 0.8). Suitable for small three-phase distribution with reduced earth, control panels, and light machinery.
4. Thermal Response & Flame Performance. XLPE supports a continuous conductor temperature of 90 °C and a short-circuit peak of 250 °C for durations up to five seconds. The cable is rated for service ambients between −20 and +45 °C, should not be laid below 0 °C without pre-warming, and uses 25 °C as the reference soil temperature for buried ratings. Flame behaviour meets class ZC of GB/T 19666, proven by both the single-cable vertical test (GB/T 18380.12) and the category-C bunched test (GB/T 18380.35) with char height limited to 2.5 m. The PVC jacket is halogenated and will produce smoke and acid gas in a fire; projects requiring low-smoke zero-halogen performance must specify WDZ-YJY.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — approximately 270 mm for this size. Prior to first energisation, apply the DC site withstand at 4U0 = 2.4 kV for 15 minutes in line with Q/GDW 13244.1-2018. Drums held in cold storage below 0 °C must be brought up to temperature before uncoiling; pulling tension should be kept within 1600 N. The 65 A (air) and 55 A (buried) references require derating whenever ambient temperature, cable grouping or soil thermal resistivity deviates from reference conditions. Crimp lugs, glands and heat-shrink termination kits must be selected for the 3.8 mm phase core, 3.0 mm neutral core and ≈ 18 mm jacket, and both phase and neutral short-circuit withstand should be coordinated with upstream protective device settings.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 233 mm at Ø15.5 mm |
five-core unarmoured |
|
Max. pulling tension (phase/neutral) |
150 N per core (10 mm² × 15 N/mm²) |
Cu conductor limit |
|
Max. pulling tension (earth) |
90 N per core (6 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Cable tray, ladder, cleats |
— |
|
Conduit ID |
≥ 25 mm |
— |
|
Fixing |
cable ties, small cleats |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. This cross-section is the workhorse of building and light-industrial distribution: branch circuits feeding sub-panels, equipment power leads, motor connections in the 5–15 kW range, lighting and socket distribution in commercial and residential buildings, control panel feeds, workshop and laboratory circuits, and auxiliary power connections. Approved installation methods include conduit (steel or PVC), cable trunking, tray and indoor ducting, both indoors and in covered outdoor locations. For direct burial or mechanically exposed routing, the steel-tape armoured ZR-YJV22 variant is recommended.

7. Testing & Quality Assurance Regime. Routine tests on every length include phase and neutral DC resistance verification (≤ 1.83 / 3.08 Ω/km at 20 °C), the 3.5 kV AC / 5 min withstand, conductor continuity across all five cores and dimensional inspection covering phase insulation ≥ 1.0 mm, neutral insulation ≥ 0.7 mm, sheath ≥ 1.4 mm and overall diameter ≈ 18 mm. Sample and type tests comprise the XLPE hot-set trial at 200 ± 3 °C for 15 minutes under 0.2 MPa (load elongation ≤ 175 %, permanent set ≤ 15 %), XLPE tensile ≥ 12.5 MPa with elongation ≥ 200 %, PVC sheath tensile ≥ 10 MPa with elongation ≥ 125 %, PVC thermal stability ≥ 200 minutes at 200 °C, single-cable and category-C bunched flame trials, and bending assessment. Commissioning on site requires insulation-resistance measurement, the DC 2.4 kV / 15 min withstand and positive L1/L2/L3/N/PE identification before switching. A factory test certificate accompanies each drum.
Cable Parameters
| ZR-YJV 4×10+1×6 mm² — Full Parameter Sheet | ||||
| Flame-retardant 4+1-core CU/XLPE/PVC power cable · 0.6/1 kV · GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 18 mm · ≈ 625 kg/km (Cu) — Tongdu / Tongdu | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | ZR-YJV | — | Flame-retardant, Cu conductor, XLPE insulation, PVC sheath | |
| Rated voltage (U0/U) | 0.6/1 | kV | AC 50 Hz; maximum system voltage Um = 1.2 kV | |
| Rated cross-sectional areas | 4 × 10 (phase) + 1 × 6 (neutral) | mm² | 4+1 five-core configuration, reduced neutral/PE | |
| Conductor material | Annealed copper (Cu) | — | Class 2 compact stranded per GB/T 3956 / IEC 60228 | |
| Insulation material | Cross-linked polyethylene (XLPE) | — | 90 °C continuous rating | |
| Sheath material | Flame-retardant PVC, ST2 compound | — | Black; halogen-bearing | |
| Flame-retardant class | ZC (ZR) | — | Per GB/T 19666; ZA/ZB available on request | |
| Standard reference | GB/T 12706.1 / IEC 60502-1 | — | 0.6/1 kV extruded-insulation power cables | |
| 02 · Conductor | ||||
| Phase stranding (×4) | 7 × 1.35 mm (7/1.35) | — | 1+6 compact lay-up; 10 mm² each | |
| Neutral stranding (×1) | 7 × 1.08 mm (7/1.08) | — | 1+6 compact lay-up; 6 mm² | |
| Phase conductor diameter | ≈ 3.8 | mm | Compact strand-lay diameter (est.) | |
| Neutral conductor diameter | ≈ 3.0 | mm | Compact strand-lay diameter (est.) | |
| Phase DC resistance @ 20 °C | 1.83 | Ω/km | Maximum per GB/T 3956 Class 2 | |
| Neutral DC resistance @ 20 °C | 3.08 | Ω/km | Maximum per GB/T 3956 Class 2 | |
| Phase DC resistance @ 90 °C | ≈ 2.33 | Ω/km | Temperature-corrected (est.) | |
| Copper mass — phase (per core) | ≈ 89 | kg/km | 10 mm² × 8.89 g/cm³ | |
| Copper mass — neutral | ≈ 53 | kg/km | 6 mm² × 8.89 g/cm³ | |
| Total copper mass | ≈ 409 | kg/km | 4 × 89 + 53 | |
| 03 · Insulation | ||||
| Phase insulation thickness | 1 | mm | GB/T 12706.1 specified for 10 mm² | |
| Neutral insulation thickness | 0.7 | mm | GB/T 12706.1 specified for 6 mm² | |
| Phase core Ø over insulation | ≈ 5.8 | mm | 3.8 + 2 × 1.0 | |
| Neutral core Ø over insulation | ≈ 4.4 | mm | 3.0 + 2 × 0.7 | |
| Insulation material | XLPE | — | Cross-linked polyethylene | |
| XLPE volume resistivity | ≥ 1×10¹² | Ω·cm | At 20 °C | |
| XLPE tensile strength | ≥ 12.5 | MPa | Type test | |
| XLPE elongation at break | ≥ 200 | % | Type test | |
| XLPE hot-set (200 °C, 15 min, 0.2 MPa) | ≤ 175 / ≤ 15 | % / % | Load elongation / permanent set | |
| Total XLPE mass | ≈ 35 | kg/km | 4 phase + 1 neutral (est.) | |
| 04 · Assembly | ||||
| Core arrangement | Neutral at centre + 4 phase cores around | — | 4+1 five-core lay-up | |
| Filler material | Polypropylene (PP) rope | — | Fills interstices between cores | |
| Binder tape | Polyester non-woven tape | — | Holds assembled cores | |
| Assembled core Ø | ≈ 15.2 | mm | Derived: 18 − 2 × 1.4 sheath | |
| Lay-up direction | Right-hand (S) | — | Standard multi-core convention | |
| 05 · Sheath | ||||
| Sheath material | Flame-retardant PVC, ST2 | — | Black, halogen-bearing | |
| Sheath thickness | 1.4 | mm | Per GB/T 12706.1 for ≈ 15 mm assembled Ø | |
| Overall finished diameter | ≈ 18.0 | mm | Tongdu / Chengtian Tai 4+1 sample | |
| Approximate cable mass (Cu) | ≈ 625 | kg/km | Tongdu 619 / Chengtian 636 cross-ref. | |
| Approximate cable mass (Al) | ≈ 340 | kg/km | YJLV equivalent (est.) | |
| PVC tensile strength | ≥ 10 | MPa | Type test | |
| PVC elongation at break | ≥ 125 | % | Type test | |
| PVC thermal stability | ≥ 200 | min | @ 200 °C (HCl evolution) | |
| Mass per 100 m (Cu) | ≈ 62.5 | kg/100 m | For drum loading estimation | |
| 06 · Electrical | ||||
| Rated voltage U0/U | 0.6/1 | kV | AC 50 Hz | |
| Maximum system voltage Um | 1.2 | kV | — | |
| Phase DC resistance @ 20 °C | ≤ 1.83 | Ω/km | GB/T 3956 Class 2 | |
| Neutral DC resistance @ 20 °C | ≤ 3.08 | Ω/km | GB/T 3956 Class 2 | |
| AC impedance @ 50 Hz | ≈ 1.85 | Ω/km | √(R² + X²); R-dominant (est.) | |
| Capacitance (typical) | ≤ 0.55 | μF/km | Per phase core (est.) | |
| Inductance (typical) | ≈ 0.35 | mH/km | Multi-core cable (est.) | |
| Insulation resistance @ 90 °C | ≥ 36.7 | MΩ·km | Finished cable, minimum | |
| Routine test voltage | 3.5 kV AC / 5 min | — | Power-frequency withstand, no breakdown | |
| Site commissioning test | DC 2.4 kV / 15 min | — | 4U0 per Q/GDW 13244.1-2018 | |
| Air ampacity @ 25 °C | ≈ 65 | A | 4 phase cores loaded, Cu (est.) | |
| Buried ampacity @ 25 °C | ≈ 55 | A | 4 phase cores loaded, Cu (est.) | |
| Short-circuit current (1 s) | ≈ 1.15 | kA | Phase: I = k·A/√t, k=115 for Cu/XLPE | |
| 07 · Thermal | ||||
| Max continuous conductor temp. | 90 | °C | XLPE rated | |
| Max short-circuit temp. (≤ 5 s) | 250 | °C | XLPE limit | |
| Min ambient temp. (service) | −20 | °C | — | |
| Max ambient temp. (service) | +45 | °C | — | |
| Min laying temperature | 0 | °C | Warm drums below 0 °C | |
| Max burial soil temp. | 25 | °C | Reference for ampacity | |
| Thermal coefficient of resistance (Cu) | 0.00393 | 1/°C | At 20 °C reference | |
| 08 · Fire (ZR) | ||||
| Flame-retardant class | ZC | — | GB/T 19666 default for ZR marking | |
| Single-cable flame test | GB/T 18380.12 | — | Equivalent IEC 60332-1-2 | |
| Bunched flame test | GB/T 18380.35 category C | — | Char height ≤ 2.5 m | |
| Halogen content | Halogen-bearing (PVC) | — | Specify WDZ-YJY for LSZH | |
| Smoke emission | Emits smoke under fire | — | PVC jacket; LSZH alternative available | |
| 09 · Installation | ||||
| Min bending radius (multi-core) | ≥ 15 × OD ≈ 270 | mm | OD = actual finished diameter | |
| Max pulling tension | ≤ 1600 | N | 40 N/mm² of main phase core area (est.) | |
| Recommended drum flange Ø | ≥ 800 | mm | For this section | |
| Laying methods | Conduit, tray, trunking, indoor ducting | — | Indoor or sheltered outdoor | |
| Direct burial note | Use armoured ZR-YJV22 for burial | — | Unarmoured YJV needs conduit/protection | |
| Termination | Crimp lugs + heat-shrink or screw terminals | — | Size for 3.8 mm phase / 3.0 mm neutral core | |
| 10 · Packing | ||||
| Standard supply length | 100 | m/coil or drum | Custom lengths available | |
| Drum type | Wooden drum (≥ Ø 800 mm flange) | — | Sealed until installation | |
| Surface marking | Type, voltage, manufacturer, year, metre marks | — | Per GB/T 6995 | |
| Storage conditions | Dry, covered, −20 to +45 °C | — | Away from sunlight, moisture, oils, sharp objects | |
| Transport | Coils/drums secured against rolling | — | Do not drag cable over rough ground | |
Cable Test Parameters
| Test Parameters — ZR-YJV 4×10+1×6 mm² | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3048.4, 20 °C | Phase ≤ 1.83 Ω/km; Neutral ≤ 3.08 Ω/km | Routine |
| 2 | Power-frequency withstand | 3.5 kV AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | GB/T 3048.5, 90 °C | ≥ 36.7 MΩ·km | Routine |
| 4 | Conductor continuity | Visual + electrical | All 5 cores continuous | Routine |
| 5 | Dimensional check | Micrometer | Phase ins. ≥ 1.0 mm; neutral ≥ 0.7 mm; sheath ≥ 1.4 mm; OD ≈ 18 mm | Routine |
| 6 | XLPE hot-set test | 200 ± 3 °C, 15 min, 0.2 MPa | Load elongation ≤ 175 %; permanent set ≤ 15 % | Type |
| 7 | XLPE tensile & elongation | GB/T 2951.11 | Tensile ≥ 12.5 MPa; elongation ≥ 200 % | Type |
| 8 | PVC sheath tensile & elongation | GB/T 2951.11 | Tensile ≥ 10 MPa; elongation ≥ 125 % | Type |
| 9 | PVC thermal stability | 200 °C, HCl evolution | ≥ 200 min | Type |
| 10 | Single-cable vertical flame | GB/T 18380.12 | Self-extinguishing; char ≤ 50 mm above burner | Type |
| 11 | Bunched cable flame (cat. C) | GB/T 18380.35 | Char height ≤ 2.5 m | Type |
| 12 | Bending test | ≥ 15 × OD mandrel | No crack in insulation or sheath | Type |
| 13 | Heat deformation (PVC) | 80 °C, 4 h, load | Deformation ≤ 50 % | Type |
| 14 | XLPE shrinkage test | 130 °C, 1 h | Shrinkage ≤ 4 % | Type |
| 15 | Site DC withstand | 4U0 = 2.4 kV DC, 15 min | No breakdown (Q/GDW 13244.1-2018) | Site |
| 16 | Core identification | Visual + continuity | Correct L1/L2/L3/N/PE identification | Site |
Cable Cross Section Structure

| ZR-YJV 4×10+1×6 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Layered 4+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 18 mm per / / /cross-referenced sample | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Phase conductor (Cu) × 4 | Annealed copper, Class 2 compact strand — 7 wires of 1.35 mm per core (7/1.35, 1+6 layout), nominal area 10 mm² each | — | ≈ 3.8 (Ø each phase core) | Line-current carrying phase conductors; DC resistance capped at 1.83 Ω/km at 20 °C |
| 2 | Neutral conductor (Cu) × 1 | Annealed copper, Class 2 compact strand — 7 wires of 1.08 mm (7/1.08, 1+6 layout), nominal area 6 mm² | — | ≈ 3.0 (Ø neutral core) | Return / PE path; DC resistance capped at 3.08 Ω/km at 20 °C |
| 3 | Phase insulation (XLPE) × 4 | Cross-linked polyethylene dielectric | 1 | ≈ 5.8 (Ø each phase core, incl. insulation) | Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min |
| 4 | Neutral insulation (XLPE) × 1 | Cross-linked polyethylene dielectric | 0.7 | ≈ 4.4 (Ø neutral core, incl. insulation) | Electrical isolation for the neutral/PE conductor |
| 5 | Core assembly | Neutral core at centre + four phase cores cabled around + PP filler + polyester binder tape | — | ≈ 15.2 (Ø over assembled cores) | 4+1 configuration; derived from finished Ø 18 − 2×1.4 sheath |
| 6 | Outer jacket (PVC) | Flame-retardant PVC, ST2 compound, black | 1.4 | ≈ 18.0 (Ø finished cable) | Mechanical and moisture protection; ZC flame retardance per GB/T 19666 |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 18.0 | mm | / | ||
| Approximate cable mass | ≈ 625 | kg/km | Cu build-up | ||
| Approximate mass, aluminium build | ≈ 340 | kg/km | YJLV equivalent (est.) | ||
| Nominal voltage rating | 0.6/1 | kV | AC 50 Hz; maximum system voltage Um = 1.2 kV | ||
| Conductor temperature limits | 90 / 250 | °C | Continuous service / short-circuit (≤ 5 s) | ||
| Minimum bend radius (multi-core) | ≥ 15 × OD ≈ 270 | mm | OD = actual finished cable diameter | ||
| Flame-retardant classification | ZC (ZR) | — | Per GB/T 19666 | ||
| Short-circuit current, phase (1 s) | ≈ 1.15 | kA | I = k·A/√t, k=115 for Cu/XLPE | ||
| Short-circuit current, neutral (1 s) | ≈ 0.69 | kA | 6 mm² neutral, same k factor | ||
| AC impedance @ 50 Hz | ≈ 1.85 | Ω/km | √(R² + X²); R-dominant (est.) | ||
| Capacitance (typical) | ≤ 0.55 | μF/km | Per phase core (est.) | ||
| Inductance (typical) | ≈ 0.35 | mH/km | Multi-core cable (est.) | ||
| Air ampacity @ 25 °C | ≈ 65 | A | 4 phase cores loaded, Cu (est.) | ||
| Buried ampacity @ 25 °C | ≈ 55 | A | 4 phase cores loaded, Cu (est.) | ||
| Maximum pulling tension | ≤ 1600 | N | 40 N/mm² of main phase core area (est.) | ||
| Schematic — not to exact scale. Finished Ø ≈ 18 mm and weight ≈ 625 kg/km from / / /cross-reference; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1; ampacity 65/55 A is an engineering estimate for small-section 4+1 cables. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — ZR-YJV 4×10+1×6 mm² | |||
| Layer-by-layer build-up narrative, conductor through outer jacket · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV class · finished Ø ≈ 18 mm | |||
| 1. Product Identity & Ratings | |||
| ZR-YJV 4×10+1×6 is a compact flame-retardant 4+1-core low-voltage cable: four 10 mm² copper phase conductors and a single 6 mm² copper neutral/PE conductor, all XLPE-insulated and enclosed in one ST2 PVC jacket for 0.6/1 kV service. It is produced and type-tested to GB/T 12706.1 / IEC 60502-1, stranded to GB/T 3956, and carries the ZR marking corresponding to class ZC under GB/T 19666. The finished cable measures about 18 mm across (/ Tongdu) and weighs approximately 625 kg per kilometre in copper (340 kg/km for the aluminium YJLV equivalent); standard supply is 100 m coils or small wooden drums with ≥ Ø 800 mm flanges (≈ 62.5 kg per 100 m). | |||
| The 4+1 arrangement follows the four-wire-plus-PE format: the reduced 6 mm² core sits at the centre while four 10 mm² phase cores are laid up around it. With all four phase cores energised, the cable supports a reference current of about 65 A in free air at 25 °C and 55 A when directly buried at 25 °C (engineering estimate for small-section 4+1 cables) — suited to branch circuits, sub-panel feeds and equipment connections in buildings and light industry. | |||
| 2. Copper Stranded Conductors | |||
| Each 10 mm² phase core is formed from seven 1.35 mm annealed wires in the 1+6 compact arrangement (7/1.35) — the Class 2 standard for this cross-section — giving a strand-lay diameter of about 3.8 mm and a DC resistance ceiling of 1.83 Ω/km at 20 °C (about 2.33 Ω/km at the 90 °C operating point). The 6 mm² neutral/PE core uses seven 1.08 mm wires (7/1.08, 1+6) to about 3.0 mm strand-lay Ø, with resistance capped at 3.08 Ω/km. Copper mass alone is about 89 kg/km per phase core and 53 kg/km for the neutral; the simple seven-wire construction keeps the small-section core flexible enough for conduit pulling and screw-terminal or crimp termination. | |||
| 3. XLPE Dielectric Insulation | |||
| XLPE is extruded at 1.0 mm onto the phase cores (the GB/T 12706.1 specified value for 10 mm²) and at 0.7 mm onto the 6 mm² neutral core — producing approximately 5.8 mm per phase core and 4.4 mm for the neutral core over the insulation. The dielectric is rated for 90 °C continuous duty and 250 °C for five seconds, maintains volume resistivity above 1×10¹² Ω·cm, passes the routine 3.5 kV AC five-minute voltage proof, and offers tensile strength ≥ 12.5 MPa with elongation ≥ 200 %. Total XLPE mass is about 35 kg/km. | |||
| 4. Cabling & PVC Outer Jacket | |||
| After insulation, the 6 mm² neutral core is placed at the centre and the four 10 mm² phase cores are cabled around it in a square arrangement with polypropylene filler and a polyester binder tape, forming a bundle of about 15.2 mm diameter (derived from the finished size). A 1.4 mm layer of flame-retarded ST2 PVC is then extruded over the assembly to the ≈ 18 mm finish. The jacket provides ZC behaviour through GB/T 18380.12 and GB/T 18380.35, offers tensile strength ≥ 10 MPa and elongation ≥ 125 %; because PVC is halogenated, low-smoke zero-halogen projects should specify WDZ-YJY, and direct-burial projects without added protection should specify steel-tape armoured ZR-YJV22. | |||
| 5. Site Handling & Operational Notes | |||
| • Observe the 15 × OD minimum bending radius (≈ 270 mm). • Perform the DC 4U0 = 2.4 kV / 15 min commissioning test before first energisation. • Service ambient spans −20 to +45 °C; warm drums below 0 °C before pulling. • Derate the 65 A (air) / 55 A (buried) references for ambient temperature, grouping and soil conditions. • Maximum pulling tension ≤ 1600 N; use appropriate pulling grips. • Select lugs and terminals matched to the 3.8 mm phase core, 3.0 mm neutral core and ≈ 18 mm jacket. • Short-circuit rating ≈ 1.15 kA for 1 s on the phase (≈ 0.69 kA basis on the neutral) — verify against protective device settings. • Use drums with ≥ Ø 800 mm flanges (≈ 62.5 kg per 100 m). |
8. Factory Advantages.
- Balanced 4+1 sizing — four duty cores plus a reduced neutral save copper on balanced small loads.
- Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
- Dosed ZC compound — self-extinguishing jacket protects control wiring and panel rooms.
- Length-on-demand — cut to exact feeder meter with sealed ends.
- Dual-section resistance log — 10 cores and 6 neutral R recorded to lot.
- Continuous print line — type, size, ZC, voltage and length readable along runs.
- Color-coded cores — phase, neutral and PE distinguished at terminals.
- Lightweight pack — compact drum, easy conduit pulling.
- Certified QA pack — routine + type test record shipped per batch.

9. Packaging, Storage & Logistics. Standard delivery is 100 m per coil or small wooden drum, with bespoke cut lengths available on request. Each drum carries type, voltage, manufacturer, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +45 °C, shielded from direct sunlight, moisture, oils and sharp objects; coils and drums remain sealed until installation and are stored upright on their flanges rather than flat. In cold conditions, condition drums indoors to ≥ 0 °C before pulling. During transit, coils and drums must be secured against rolling and impact, and the cable must never be dragged across abrasive ground or sharp edges.

10. Procurement Specification. State "ZR-YJV 0.6/1 kV 4×10+1×6" together with the required length or drum arrangement and marking preferences. Specify the flame-retardant class (ZC is standard; ZA or ZB available), jacket colour and any special drum requirements. Always request the factory test certificate to confirm the actual unarmoured diameter (≈ 18 mm), weight (≈ 625 kg/km) and ampacity for the production batch. Where low-smoke zero-halogen or armoured construction is needed, order WDZ-YJY or ZR-YJV22 respectively.
11. Cable Industry FAQ.
- Q1: What distinguishes YJV, ZR-YJV, YJV22 and WDZ-YJY from one another? YJV denotes the base XLPE-insulated PVC-sheathed cable; ZR-YJV adds flame-retardant properties (class ZC by default); YJV22 introduces a steel-tape armour between the assembly and sheath for direct burial and mechanical robustness; WDZ-YJY substitutes a halogen-free, low-smoke sheath for the PVC, intended for enclosed public spaces.
- Q2: What is the meaning of ZA, ZB, ZC and ZD? These are flame-retardant classes defined in GB/T 19666, assessed through the bunched-cable test GB/T 18380.35 at progressively higher fuel loads — ZA is the most demanding, ZD the least. The bare "ZR" marking defaults to ZC; ZA and ZB must be explicitly requested at the order stage.
- Q3: Why is the neutral/PE conductor only 6 mm² when the phases are 10 mm²? In a balanced four-wire circuit the neutral carries primarily unbalance and harmonic current, so GB/T 12706.1 permits a reduced core in the 4+1 construction. If the installation serves substantial single-phase or non-linear, harmonic-generating loads, an equal-section 5-core cable should be considered.
- Q4: When should a 4+1, 5-core equal, or 4-core cable be selected? Choose 4+1 for standard four-wire service with a reduced neutral/PE; 5-core equal (4×A+1×A) where neutral current is expected to approach phase current; plain 4-core for applications where no separate PE conductor is needed in the cable.
- Q5: Why do air and buried current ratings differ, and how are they adjusted? Published figures assume 25 °C air or 25 °C soil at 1.0 K·m/W thermal resistivity with a single circuit. Manufacturer correction factors must be applied for ambient temperature, cable grouping, burial depth and soil resistivity — air factors range from about 1.29 at 20 °C down to 0.91 at 45 °C, and soil factors from 1.04 at 20 °C to 0.87 at 40 °C.
- Q6: Copper or aluminium conductor? Copper (this cable) delivers lower resistance (1.83 versus roughly 3.08 Ω/km at 10 mm²), higher current per mm², superior mechanical strength and more dependable terminations; aluminium (YJLV, ≈ 340 kg/km in this size) costs less and weighs less but demands larger cross-sections and anti-oxidation treatment at every joint.
- Q7: Why can XLPE operate at 90 °C while PVC insulation is limited to 70 °C? The cross-linking process transforms polyethylene into a three-dimensional thermoset network, which raises the continuous conductor rating to 90 °C and the short-circuit withstand to 250 °C — directly boosting the ampacity available from a given copper area.
- Q8: How is the conductor cross-section determined? Selection is governed by (a) full-load current after applying derating factors, (b) permissible voltage drop (typically ≤ 5 % for branch circuits), (c) short-circuit withstand on an I²t basis (1.15 kA·s per phase here), and (d) coordination with overcurrent protective devices; the most stringent criterion controls.
- Q9: Why does finished diameter vary between manufacturers for the same nominal size? Standards mandate minimum insulation and sheath thicknesses together with electrical performance, but not a precise overall diameter. Stranding compaction, filler design and sheath tolerance differ between plants — published 4×10+1×6 figures cluster around 18 mm unarmoured — so the actual measured diameter should always be used when sizing glands, trays and conduits.
- Q10: Which tests confirm acceptability on delivery and before energisation? At delivery, verify the factory test certificate (resistance 1.83/3.08 Ω/km, 3.5 kV/5 min withstand, dimensions ≈ 18 mm), jacket legibility and drum integrity. After installation, complete an insulation-resistance test plus the DC 4U0 = 2.4 kV / 15 min withstand per Q/GDW 13244.1-2018, then confirm L1/L2/L3/N/PE identification before closing the breaker.
- Q11: What service life can be expected? When installed and operated within the stated temperature and voltage limits, XLPE 0.6/1 kV cables are designed for a minimum service life of 30 years; sustained overload, ultraviolet exposure, water ingress through a damaged sheath, or operation above 90 °C will materially reduce that lifespan.