Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects

Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZR-YJV 3×185mm²+1×95mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation ...

Product Details

Highlight:

xlpe 4 cores cable

,

xlpe 25 sq mm 4 core cable

,

zr-yjv 4 cores cable

Phase conductor (×3):
Bare Annealed Copper, Class 2 Stranded, 37×∅2.52 Mm, Conductor Ø ≈ 17.6–18.6 Mm Depending On Compaction
Neutral conductor (×1):
Bare Annealed Copper, Class 2 Stranded, 19×∅2.52 Mm, Conductor Ø ≈ 12.6–13.2 Mm Depending On Compaction
Phase conductor nominal area:
185 Mm²
Neutral conductor nominal area:
95 Mm²
Number of cores:
4 (3+1)
Phase conductor construction:
Class 2, 37×∅2.52 Mm,IEC 60228 / GB/T 3956
Neutral conductor construction:
Class 2, 19×∅2.52 Mm,IEC 60228 / GB/T 3956
Phase conductor diameter (approx.):
17.6–18.6 Mm
Neutral conductor diameter (approx.):
12.6–13.2 Mm
Insulation (×4):
XLPE
Phase insulation thickness:
1.6 Mm (185 Mm² Class)
Neutral insulation thickness:
1.1 Mm (95 Mm² Class)
Diameter over phase insulated core:
20.8–21.8 Mm
Diameter over neutral insulated core:
14.8–15.4 Mm
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
2.0 Mm
Overall cable diameter:
38.5 – 45.5 Mm
Design outer diameter:
≈ 41.5 Mm
Approx. weight:
2300 – 2850 Kg/km
Design weight:
≈ 2530 Kg/km
Cable shape:
Round

Product Description

Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects


Cable Designation & Meaning


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

3×185+1×95 mm²

Three phase cores of 185 mm² copper + one reduced neutral core of 95 mm² copper

Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects

ZR-YJV 3×185+1×95 mm² — Cable Specification & Engineering Data

1. Overview & Ratings. ZR-YJV 3×185+1×95 is a high-capacity flame-retarding 3+1-core cable: three 185 mm² copper phase conductors and one 95 mm² copper neutral conductor, XLPE insulation and one ST2 PVC jacket, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; manufactured and proof-tested to GB/T 12706.1 / IEC 60502-1, stranding to GB/T 3956, ZC fire class to GB/T 19666. Finished diameter ≈ 47.4 mm, mass ≈ 6628 kg/km (Zhongce 3+1 table), supplied in 100 m coils or wooden drums.


2. Construction Stack. Conductor → outer jacket:

Layer Build Wall Diameter
Phase conductor (×3) Annealed Cu, Class 2 compact, 37 × 2.53 mm (1+6+12+18) each — ≈ 17.7 mm
Neutral conductor (×1) Annealed Cu, Class 2 compact, 19 × 2.52 mm (1+6+12) — ≈ 12.6 mm
Phase insulation (×3) XLPE 1.6 mm ≈ 20.9 mm
Neutral insulation (×1) XLPE 1.1 mm ≈ 14.8 mm
Core assembly Central neutral + 3 phase cores around + PP filler + polyester binder — ≈ 41.4 mm (derived)
Outer jacket Flame-retarded PVC, ST2 compound, black 3.0 mm ≈ 47.4 mm (Zhongce)


3. Electrical Ratings. Phase R ≤ 0.0991 Ω/km (≈ 0.126 Ω/km @ 90 °C), neutral R ≤ 0.193 Ω/km @ 20 °C; factory proof 3.5 kV AC / 5 min; finished-cable insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.34 μF/km; inductance ≈ 0.24 mH/km; AC impedance ≈ 0.12 Ω/km; short-circuit current ≈ 21.3 kA for 1 s. Reference current (3 phase cores loaded) ≈ 505 A in air @ 30 °C / 435 A buried @ 25 °C — Zhongce 3+1 table basis.


Electrical Parameters


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (phase, per core)

≤ 0.0991 Ω/km

GB/T 3956 max, 185 mm²

DC resistance @20 °C (neutral, per core)

≤ 0.193 Ω/km

GB/T 3956 max, 95 mm²

AC resistance @90 °C (est., phase)

≈ 0.129 Ω/km

per core

AC resistance @90 °C (est., neutral)

≈ 0.251 Ω/km

per core

Current rating in air (30 °C, single circuit, 3-core+1)

≈ 345–385 A

based on 185 mm² phase

Current rating in air (design)

≈ 360 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 385–420 A

common catalogue 395–408 A

Design buried rating

≈ 400 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, phase)

≈ 18.5 kA

185 mm² reference

Short-circuit current (1 s, Cu, 250 °C, neutral)

≈ 9.5 kA

95 mm² reference

Frequency

50/60 Hz AC

—


Cable Parameters & Test Parameters


Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects


ZR-YJV 3×185+1×95 mm² — Test & Verification Schedule (GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Phase conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.0991 Ω/km @ 20 °C (185 mm²) Every production length
Routine Neutral conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.193 Ω/km @ 20 °C (95 mm²) Every production length
Routine Power-frequency withstand GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor to earth/water bath
Routine Dimensional inspection GB/T 2951 Phase ins. ≥ 1.6 mm; neutral ins. ≥ 1.1 mm; sheath ≥ 3.0 mm; OD within tolerance Wall & diameter check
Routine Conductor continuity Visual / electrical All cores continuous, no break Every length
Sample XLPE hot-set test GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking verification
Sample XLPE tensile & elongation GB/T 2951 Tensile ≥ 12.5 MPa; elongation ≥ 200 % Aged and unaged
Sample PVC sheath tensile & elongation GB/T 2951 Tensile ≥ 10.0 MPa; elongation ≥ 125 % Aged and unaged
Sample PVC thermal stability GB/T 2951 (Congo-red) ≥ 200 min @ 200 °C HCI evolution test
Sample Conductor geometry GB/T 3956 Phase: 37 × 2.53 mm Ø ≈ 17.7; neutral: 19 × 2.52 mm Ø ≈ 12.6 Per batch
Type Single-cable flame test GB/T 18380.12 No flame to upper reference mark ZR property
Type Bunched flame test — C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m Class C compliance
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core bending rule
Type Insulation resistance Factory method ≥ 36.7 MΩ·km @ 20 °C Not routine under GB/T 12706.1
Post-install DC withstand commissioning Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown Required for new installations
Post-install Phase identification Visual / continuity L1/L2/L3/N correctly labelled at both ends Before energisation


Cable Cross Section Strcuture 


Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects


ZR-YJV 3×185+1×95 mm² — Cross-Section Construction Diagram (Schematic)
Layered 3+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · primary data from Zhongce 3+1 table
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Phase conductor (Cu) × 3 Annealed copper, Class 2 compact strand — 37 wires of 2.53 mm per core (37/2.53, 1+6+12+18 layout), nominal area 185 mm² each — ≈ 17.7 (Ø each phase core) Line-current carrying phase conductors; DC resistance capped at 0.0991 Ω/km at 20 °C
2 Neutral conductor (Cu) × 1 Annealed copper, Class 2 compact strand — 19 wires of 2.52 mm (19/2.52, 1+6+12 layout), nominal area 95 mm² — ≈ 12.6 (Ø neutral core) Return / neutral path; DC resistance capped at 0.193 Ω/km at 20 °C
3 Phase insulation (XLPE) × 3 Cross-linked polyethylene dielectric 1.6 ≈ 20.9 (Ø each phase core, incl. insulation) Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min
4 Neutral insulation (XLPE) × 1 Cross-linked polyethylene dielectric 1.1 ≈ 14.8 (Ø neutral core, incl. insulation) Electrical isolation for the neutral conductor
5 Core assembly Neutral core at centre + three phase cores cabled around + PP filler + polyester binder tape — ≈ 41.4 (Ø over assembled cores) 3+1 configuration; derived from Zhongce OD − 2×sheath
6 Outer jacket (PVC) Flame-retardant PVC, ST2 compound, black 3 ≈ 47.4 (Ø finished cable, Zhongce) Mechanical and moisture protection; ZC flame retardance per GB/T 19666
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 47.4 mm Zhongce 3+1 unarmored table

Approximate cable mass ≈ 6628 kg/km Zhongce copper-conductor figure

Nominal voltage rating 0.6/1 kV AC 50 Hz; maximum system voltage Um = 1.2 kV

Conductor temperature limits 90 / 250 °C Continuous service / short-circuit (≤ 5 s)

Minimum bend radius (multi-core) ≥ 15 × OD ≈ 711 mm OD = actual finished cable diameter

Flame-retardant classification ZC (ZR) — Per GB/T 19666

Short-circuit current (1 s) ≈ 21.3 kA I = k·A/√t, k=115 for Cu/XLPE (est.)

AC impedance @ 50 Hz ≈ 0.12 Ω/km √(R² + X²); R-dominant (est.)

Capacitance (typical) ≤ 0.34 μF/km Per phase core (est.)

Inductance (typical) ≈ 0.24 mH/km Three-core cable (est.)

Air ampacity @ 30 °C ≈ 505 A Zhongce basis; Cu, 3 phase loaded

Buried ampacity @ 25 °C ≈ 435 A Zhongce basis; Cu, 3 phase loaded

Schematic — not to exact scale. Primary data (OD, weight, ampacity) from Zhongce 3+1 table; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1. Values marked (est.) are engineering estimates.


Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects


4. Thermal & Fire. 90 °C continuous conductor, 250 °C short-circuit (≤ 5 s); service ambient −20 to +45 °C, minimum laying temp 0 °C; max burial soil temp 25 °C; ZC per GB/T 19666 — GB/T 18380.12 single-cable + GB/T 18380.35 category-C bunched (char ≤ 2.5 m); PVC jacket is halogenated and emits smoke under fire — specify WDZ-YJY for LSZH.


Flame Retardant Characteristics


Flame-Retardant (FR) Characteristics — ZR-YJV 3×185+1×95 mm²
ZR-YJV 3×185+1×95 mm²  (3 (L1+L2+L3, 185 mm²) + 1 (N, 95 mm²); 3+1 = L1+L2+L3+N)   ·   0.6/1 kV
1.  Cable Identification
Code / Item Meaning / Value Standard / Note
Designation ZR-YJV 3×185+1×95 mm² GB/T 12706.1-2020
ZR Flame Retardant (legacy); under GB/T 19666-2019 defaults to Class C; modern = ZC GB/T 19666-2019
YJ XLPE insulation (cross-linked polyethylene) —
V PVC outer sheath — flame-retardant, contains halogen (Cl) GB/T 19666-2019
0.6/1 kV U₀/U = 600/1000 V; Uₘ = 1.2 kV IEC 60502-1
3×185+1×95 mm² Three 185 mm² phase cores + one 95 mm² neutral core (reduced neutral, 3+1 construction) —
Construction Unarmoured, non-screened, round multi-core (3+1) —
Application note 3+1 core → three-phase AC with neutral (L1+L2+L3+N); neutral reduced to 95 mm². No separate PE (use 4-core or 5-core if PE required). —
2.  Flame-Retardant & Fire Performance  (CORE)
Property Value / Requirement Standard
Flame Retardant Class Class C (bundled cables, char length ≤ 2.5 m) GB/T 19666-2019; GB/T 18380.3 / IEC 60332-3-24
Legacy designation Phase 1.6 mm; Neutral 1.1 mm (185 / 95 mm² classes) GB/T 19666-2019
Test method — flame Bunched flame test (category C), char ≤ 2.5 m after flame removal GB/T 18380.3 (IEC 60332-3-24)
Halogen content Contains halogen — Cl from PVC sheath; releases HCl on burning GB/T 17650 / IEC 60754-1/-2
Smoke density Heavy dark smoke — NOT low-smoke (no LSZH certification) GB/T 17651 / IEC 61034
Corrosivity Corrosive — HCl gas generated during fire GB/T 17650 / IEC 60754-2
pH / conductivity of gases Not certified (PVC base — acidic / conductive combustion gases) GB/T 17650 / IEC 60754-2
Limited Oxygen Index (LOI) PVC typical ≈ 45–49 % O₂ (reference, design value) ASTM D2863 / GB/T 2406, reference
Max. conductor operating temp. 90 °C (long-term service) GB/T 12706.1-2020
Max. short-circuit temp. (≤5 s) Phase 86.5 mm; Neutral 50.1 mm — phase 83.25 + 2×1.6 / neutral 47.88 + 2×1.1 conductor + 2×insulation (phase 8.3 + 2×1.6 / neutral 4.8 + 2×1.1)
Insulation (×4) XLPE (cross-linked polyethylene), phase 1.6 mm / neutral 1.1 mm nominal (185 / 95 mm² respectively) GB/T 12706.1-2020
Service ambient range (PVC sheath) −15 °C to +90 °C —
Min. installation ambient temp. Class C (bundled cables, char length ≤ 2.5 m); ZR-YJV 3×185+1×95 design value —
3.  Fire Test Summary
Test Requirement ZR-YJV 3×185+1×95 Verdict
Bunched flame test (Class C) Char length ≤ 2.5 m PASS (design, Class C)
Single flame test (IEC 60332-1) Self-extinguishing PASS (XLPE/PVC FR)
Smoke density (IEC 61034) Light transmittance ≥ 60 % for LSZH N/A (PVC = heavy smoke)
Halogen content (IEC 60754) ≤ 0.5 % HCl for LSZH N/A (contains Cl)
Acidity / corrosivity (IEC 60754-2) pH ≥ 4.3; conductivity ≤ 10 µS/mm for LSZH N/A (corrosive HCl)
Fire-survival (BS 6387 / IEC 60331) Circuit integrity during/after fire N/A — use NH-ZR-YJV
4.  Key Electrical & Thermal Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (phase, 185 mm²) ≤ 0.0991 Ω/km GB/T 3956 / IEC 60228, Class 2 max
DC resistance @ 20 °C (neutral, 95 mm²) ≤ 0.193 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (phase, est.) ≈ 0.127 Ω/km per phase core
Current rating — in air (30 °C, single circuit) ≈ 290–325 A (design ≈ 305 A) 3+1 core
Current rating — direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) ≈ 335–370 A (design ≈ 350 A) 3+1 core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 18.5 kA (per phase core) phase core; neutral ≈ 7.0 kA
phase core; neutral ≈ 9.5 kA
Layer (inside → out) Description / Specification FR Contribution
Conductor (phase ×3) Conductor (phase ×3): Bare annealed copper, Class 2 stranded, 37ר2.25, Ø ≈ 8.3 mm — XLPE insulation 1.6 mm (e_min 1.26); L1/L2/L3 = brown/black/grey None (Cu non-combustible)
Conductor (neutral ×1) Conductor (neutral ×1): Bare annealed copper, Class 2 stranded, 19ר2.52, Ø ≈ 4.8 mm — XLPE insulation 1.1 mm (e_min 0.86); N = blue GB/T 3956 / IEC 60228
Conductor screen Omitted (not required for 0.6/1 kV) —
Insulation (×4) XLPE (cross-linked polyethylene), phase 1.6 mm (e_min 1.26) / neutral 1.1 mm (e_min 0.86); L1/L2/L3 = brown/black/grey, N = blue GB/T 12706.1-2020
Filler XLPE — low flame spread FR additive
Binder Flame-retardant PP / PE to form round assembly FR barrier
Inner binder / assembly Flame-retardant tape over laid-up cores FR barrier
Outer sheath Flame-retardant PVC (ZR grade), 1.6 mm (multi-core, 3+1 rule), Black (standard) Primary FR layer (halogenated)
Armour Flame-retardant PVC (ZR grade), 1.8 mm (multi-core, 3+1 rule), Black (standard) GB/T 19666-2019
Metallic screen None —
6.  Dimensional Data
Item Typical Value Remarks
Conductor nominal area 3×185 mm² + 1×95 mm² phase / neutral
Number of cores 4 (3+1) —
Conductor construction Phase: Class 2, 37ר2.25 mm; Neutral: Class 2, 19ר2.52 mm min. 19 wires (≥70 mm²)
Conductor diameter (approx.) min. 19 wires (≥95 mm²) —
Insulation thickness Phase: 1.6 mm; Neutral: 1.1 mm (185 / 95 mm² classes) 1.4 / 1.0 mm class
Diameter over insulated core Phase 86.5 mm; Neutral 50.1 mm conductor + 2×insulation
Sheath thickness Diameter over insulated core — phase 8.3 + 2×1.6 / neutral 4.8 + 2×1.1 3+1 multi-core rule
Overall cable diameter 1.8 mm (multi-core, 3+1 rule) design ≈ 29.0 mm
Approx. weight 28.0 – 37.0 mm (design ≈ 32.0 mm) —
Cable shape 1800 – 2500 kg/km (use ≈ 2150/km) —
7.  Mechanical & Installation Parameters
Parameter Value Note
≥ 15 × OD ≈ 480.0 mm @ Ø ≈ 32.0 mm ≥ 15 × OD ≈ 480.0 mm @ Ø ≈ 32.0 mm —
50 N/mm² × (3×185 + 1×95) = 32 500 N total 50 N/mm² × (3×185 + 1×95) = 32 500 N total use conductor sock, avoid sheath grip
Direct burial Allowed in non-aggressive soil; for mechanical protection use ZR-YJV22 3×150+1×70 —
≥ 1.5 × OD → ≥ 44 mm (use 50 mm or 63 mm conduit) ≥ 1.5 × OD → ≥ 48 mm (use 50 mm or 75 mm conduit) —
Fixing (horizontal / vertical tray) ≈ 800 mm / ≈ 1500 mm horizontal / vertical
Elevation difference limit None (XLPE) —
8.  Selection Guide — When FR Matters
Scenario Recommended Cable Reason
Flame-retardant, halogenated acceptable (standard) ZR-YJV 3×185+1×95 mm² (this cable) Class C FR, PVC sheath, cost-effective
Low-smoke halogen-free required (LSZH) WDZ-YJY 3×185+1×95 LSZH sheath — IEC 61034 / IEC 60754 compliant
Fire-survival circuit (circuit integrity) NH-ZR-YJV / WDZN-YJY 3×185+1×95 BS 6387 / IEC 60331 fire-survival grade
Heavy mechanical load / direct burial ZR-YJV22 3×185+1×95 Steel tape armour for impact / road crossing
Separate PE + N required 5-core cable (e.g. 5×95 or 4×185+1×95) 3+1 has no separate PE
Notes
1. ZR is the legacy GB/T 19666-2019 Class C designation; modern equivalent is ZC. Class C: char ≤ 2.5 m after bunched flame test (GB/T 18380.3).
2. PVC sheath is halogenated (contains Cl, releases HCl) → heavy smoke and corrosive gases; NOT suitable for LSZH-required routes (use WDZ-YJY).
3. 3×185+1×95 mm² = three 185 mm² phase cores (L1+L2+L3) + one 95 mm² neutral (N), total 4 cores (3+1); neutral is reduced in size. Current ratings (≈ 305 A air / ≈ 350 A buried) are design values; apply grouping, ambient temperature, soil thermal resistivity and IEC 60364-5-52 correction factors.
4. For LSZH → WDZ-YJY 3×185+1×95; for fire-survival → NH-ZR-YJV / WDZN-YJY 3×185+1×95; for armour → ZR-YJV22 3×185+1×95; for separate PE → use 5-core.
5. Insulation thickness: phase 185 mm² = 1.6 mm (e_min = 1.6 − 0.3400000000000001 = 1.26 mm); neutral 95 mm² = 1.1 mm (e_min = 1.1 − 0.2400000000000001 = 0.86 mm) (GB/T 12706.1-2020, Table 3). DC resistance phase ≤ 0.0991 Ω/km, neutral ≤ 0.193 Ω/km (GB/T 3956 Class 2 max). Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.


Insulation Parameters


Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects


5. Installation & Care. Minimum bend ≥ 15 × OD (≈ 711 mm); commissioning DC test 4U0 = 2.4 kV / 15 min before first energisation (Q/GDW 13244.1-2018); warm drums below 0 °C before pulling; max pulling tension ≤ 7400 N; derate the 505/435 A references for ambient, grouping and soil; fit lugs and glands sized for the 17.7 mm phase core, 12.6 mm neutral core and 47.4 mm jacket; verify short-circuit rating against protective device settings.


6. Application. Heavy three-phase four-wire distribution, transformer secondaries, large building mains and industrial feeders requiring a dedicated neutral conductor in a single cable (TN-C style) — conduit, tray, trench, duct, trunking, direct burial; indoor or sheltered outdoor. Typical loads include main switchgear incomers, busbar risers in high-rise buildings, pump/compressor stations, data-centre primary feeds and municipal power networks.


Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects


7. Testing & Quality Assurance. Every production length undergoes routine tests: phase/neutral DC resistance (≤ 0.0991 / 0.193 Ω/km @ 20 °C), 3.5 kV AC / 5 min power-frequency withstand with no breakdown, conductor continuity and dimensional inspection (phase insulation ≥ 1.6 mm, neutral ≥ 1.1 mm, sheath ≥ 3.0 mm). Sample/type tests cover the XLPE hot-set test (200 ± 3 °C, 15 min, 0.2 MPa — load elongation ≤ 175 %, permanent set ≤ 15 %), XLPE tensile ≥ 12.5 MPa / elongation ≥ 200 %, PVC sheath tensile ≥ 10 MPa / elongation ≥ 125 %, PVC thermal stability ≥ 200 min @ 200 °C, single-cable and category-C bunched flame tests, and bending tests. On site, a DC 2.4 kV / 15 min withstand and phase-identification check are required before energisation. A factory test certificate accompanies each drum.


8. Standards & Compliance. Design and manufacture follow GB/T 12706.1 and IEC 60502-1 (0.6/1 kV extruded-insulation power cables); conductors comply with GB/T 3956 / IEC 60228 Class 2; flame-retardant classification follows GB/T 19666 (ZC default for "ZR"), verified by GB/T 18380.12 (single vertical wire/cable) and GB/T 18380.35 (bunched, category C); installation acceptance follows Q/GDW 13244.1-2018 and GB 50168; surface marking follows GB/T 6995. Cables can also be supplied to IEC, BS, DIN, ICEA or JIS requirements on request. Note: the ST2 PVC jacket contains halogen — for tunnels, metros, hospitals and other enclosed public spaces, specify WDZ-YJY (low-smoke zero-halogen) instead.


9. Packaging, Storage & Transport. Standard supply is 100 m per coil or wooden drum (recommended flange ≥ Ø 1800 mm for this section; net weight ≈ 663 kg per 100 m drum); custom cut lengths are available. Each drum carries type, voltage, manufacturer, year and sequential metre marks per GB/T 6995. Store in dry, covered conditions at −20 to +45 °C, away from direct sunlight, moisture, oils and sharp objects; drums must remain sealed until installation and should stand on their flanges, not lie flat. In cold weather, condition drums indoors to ≥ 0 °C before uncoiling and pulling. Transport with drums secured against rolling and impact; avoid dragging the cable over rough ground or sharp edges.


10. Ordering. ZR-YJV 0.6/1 kV 3×185+1×95 + supply length/drum + surface marking; state flame-retardant class (ZC default; ZA/ZB on request), jacket colour and any special drum requirements; request the manufacturer's factory test certificate to confirm actual OD, weight and ampacity; for LSZH or armoured variants, order WDZ-YJY or ZR-YJV22 respectively.


Flame Retardant XLPE Insulated ZR-YJV 3×185mm²+1×95mm² Copper Cable for Power Grid Distribution Projects


11. Cable Industry FAQ.

  • Q1: What is the difference between YJV, ZR-YJV, YJV22 and WDZ-YJY? YJV is the base XLPE/PVC cable; ZR-YJV adds flame-retardant behaviour (default class ZC); YJV22 adds steel-tape armour over the assembly for direct burial and mechanical protection; WDZ-YJY replaces the PVC jacket with a halogen-free, low-smoke compound for enclosed public spaces.
  • Q2: What do ZA / ZB / ZC / ZD mean? They are flame-retardant classes under GB/T 19666, verified by the bunched-cable test GB/T 18380.35 with different fuel loads (A the most stringent, D the least). "ZR" without a letter defaults to ZC; ZA/ZB must be stated when ordering.
  • Q3: Why is the neutral core smaller (95 mm² vs 185 mm² phase)? In balanced three-phase circuits the neutral carries mainly unbalance and harmonic current, so GB/T 12706.1 permits a reduced neutral in the 3+1 build. If heavy single-phase or non-linear (harmonic-rich) loads are expected, use an equal-section 4-core cable or a larger neutral.
  • Q4: When should I choose 3+1, 4-core equal, or 3+2 cables? 3+1 for general TN-C three-phase four-wire service with a reduced neutral; 4-core equal (3×A+1×A) when neutral current approaches phase current; 3+2 (3 phase + N + PE split) for TN-S systems requiring separate neutral and protective conductors.
  • Q5: Why do air and buried ampacities differ, and how are they corrected? Ratings assume 30 °C air or 25 °C soil at 1.0 K·m/W thermal resistivity with one circuit. Apply manufacturer correction factors for ambient temperature, cable grouping, burial depth and soil resistivity; the Zhongce table lists air factors 1.29 (20 °C) down to 0.91 (45 °C) and soil factors 1.04 (20 °C) to 0.87 (40 °C).
  • Q6: Copper or aluminium conductor? Copper (this cable) offers lower resistance, higher ampacity per mm², better mechanical strength and more reliable terminations; aluminium (YJLV) is cheaper and lighter but needs larger cross-sections and anti-oxidation treatment at joints.
  • Q7: Why is XLPE rated 90 °C while PVC insulation is only 70 °C? Cross-linking turns polyethylene into a thermoset network, raising the continuous conductor temperature to 90 °C and short-circuit tolerance to 250 °C, which directly increases ampacity for the same copper area.
  • Q8: How is the conductor cross-section selected? Size against (a) full-load current with derating factors, (b) permissible voltage drop (typically ≤ 5 % for power circuits), (c) short-circuit withstand (I²t), and (d) protection-device coordination; the largest requirement governs.
  • Q9: Why do finished-cable diameters vary between manufacturers for the same nominal size? Standards fix minimum insulation/sheath thickness and electrical performance, not exact OD. Stranding compaction, filler design and sheath tolerance differ by plant, so always use the actual measured OD for gland, tray and conduit sizing.
  • Q10: What tests prove the cable is acceptable on delivery and before energisation? On delivery: check the factory test certificate (resistance, 3.5 kV/5 min withstand, dimensions), jacket marking and drum condition. After laying: insulation-resistance test plus the DC 4U0 = 2.4 kV / 15 min withstand per Q/GDW 13244.1-2018, then phase/neutral identification before switching on.
  • Q11: What is the expected service life? Correctly installed within temperature and voltage limits, XLPE 0.6/1 kV cables are designed for ≥ 30 years of service; prolonged overload, UV exposure, water immersion of damaged jacket, or operation above 90 °C shortens life significantly.