Polyolefin Single Core Earth Cable ZR-YJV 1 X 35mm2 Single Conductor 0.6/1kV Indoor Power

Polyolefin Single Core Earth Cable ZR-YJV 1 X 35mm2 Single Conductor 0.6/1kV Indoor Power

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 1*35mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

ZR-YJV 1*35mm² Fire Retardant Single Conductor Wire, 0.6/1kV Solid Copper, XLPE Insulation PVC Jacket, Indoor Power Use Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed ZR-YJV 1×35 is a flame-retardant, copper-conductor, XLPE-insulated, PVC-sheathed power cable for 0.6/1 kV ...

Product Details

Highlight:

Polyolefin single core earth cable

,

single core earth cable ZR-YJV

,

0.6/1kV 35mm single core cable

Conductor:
Bare Annealed Copper, Class 2 Stranded Circular, 7×∅2.52 Mm​ (typical), Conductor Ø ≈ 7.5 Mm
Conductor nominal area:
35 Mm²
Conductor construction:
Class 2, 7×∅2.52 Mm,min. 7 Wires Per GB/T 3956 (≤35 Mm²)
Conductor diameter (approx.):
7.5 Mm
Insulation:
XLPE Compound, Extruded
Insulation thickness (nominal):
0.9 Mm​ (GB/T 12706.1, 25–35 Mm² Class)
Diameter over insulation (approx.):
9.3 Mm(7.5 + 2×0.9)
Sheath nominal thickness:
1.4 Mm,single-core (some Makers 1.5)
Outer sheath:
Polyolefin (PO) Compound, Flame-retardant Grade (ZR)​
Filler / binder:
Flame-retardant (FR) Non-hygroscopic Tape / PP Mesh​
Long-term service temperature:
90 °C
Short-circuit temperature (≤5 s):
250 °C
Emergency overload:
105–130 °C (limited Duration)
Routine test:
3.5 KV AC / 5 Min; Type Test 4.0 KV
Volume resistivity @90 °C:
≥ 10¹² Ω·cm
Insulation resistance constant:
≈ 3.67 MΩ·km @90 °C

Product Description

ZR-YJV 1*35mm² Fire Retardant Single Conductor Wire, 0.6/1kV Solid Copper, XLPE Insulation PVC Jacket, Indoor Power Use

 

Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed

 

ZR-YJV 1×35 is a flame-retardant, copper-conductor, XLPE-insulated, PVC-sheathed power cable for 0.6/1 kV distribution, designed and tested to GB/T 12706.1 and IEC 60502-1.

1. Product Structure (from conductor to outer sheath)

No. Layer Material / Construction Key data
1 Conductor (Cu) Plain annealed copper, Class 1/2 (typical Class 2 stranded), nominal 35 mm² Typical stranding 7 × 2.52 mm (7/2.52); Ø ≈ 7.0 mm (7.0–7.6 mm); max. DC resistance ≤ 0.524 Ω/km @ 20 °C (GB/T 3956)
2 Insulation (XLPE) Cross-linked polyethylene (thermoset) Nominal thickness 0.9 mm; Ø over insulation ≈ 8.8 mm; 90 °C continuous rating
3 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black Nominal thickness 1.4 mm; overall Ø ≈ 11.8–12.0 mm; flame retardance ZC (ZR)

Overall diameter ≈ 12.0 mm (11.8–12.0 mm) and weight ≈ 357 kg/km (350–357 kg/km).

2. Product Performance

  • Electrical: Conductor DC resistance ≤ 0.524 Ω/km @ 20 °C; routine AC withstand test 3.5 kV / 5 min without breakdown; finished-cable insulation resistance ≥ 36.7 MΩ·km @ 20 °C (typical reference); XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km.
  • Thermal: Max. continuous conductor temperature 90 °C; short-circuit (≤ 5 s) 250 °C; ambient service −20 to +45 °C; laying temperature not below 0 °C.
  • Flame retardance: "ZR" = flame-retardant, default class ZC per GB/T 19666; passes single-cable vertical flame test (GB/T 18380.12) and class-C bunched test (GB/T 18380.35: ≥ 1.5 L/m non-metallic volume, 20 min flame, char extent ≤ 2.5 m).
  • Ampacity (reference): ≈ 190 A in air (single core, 30 °C); direct burial ≈ 160–195 A depending on soil thermal resistivity — always apply correction factors per GB/T 16895 / IEC 60364.
  • Mechanical/installation: min. bending radius 20 × OD (single-core); site DC withstand test after installation 4U0 = 2.4 kV / 15 min (per Q/GDW 13244.1-2018 practice).

3. Key Parameters 

  • Rated voltage 0.6/1 kV (Um = 1.2 kV); 50 Hz; single core; 35 mm²
  • Conductor: Cu Class 2, 7 × 2.52 mm, Ø ≈ 7.0 mm; DC R ≤ 0.524 Ω/km
  • Insulation: XLPE, 0.9 mm; Sheath: flame-retardant PVC ST2, 1.4 mm
  • Weight ≈ 357 kg/km; OD ≈ 12.0 mm; length 100 m per coil/drum

Polyolefin Single Core Earth Cable ZR-YJV 1 X 35mm2 Single Conductor 0.6/1kV Indoor Power

 

ZR-YJV 1×35 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV)
Construction: CU / XLPE / PVC  •  Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance)  •  Nominal values for reference — confirm against factory test certificate
No. Category Parameter Value Unit Notes / Standard Reference
A. Product Identification
1 Identification Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable — Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing)
2 Identification Model designation ZR-YJV 1×35 — Cu / XLPE / PVC
3 Identification Design standards GB/T 12706.1; IEC 60502-1 — Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence
4 Identification Rated voltage U0/U 0.6/1 kV Max system voltage Um = 1.2 kV
5 Identification Rated frequency 50 Hz AC power distribution
6 Identification Number of cores 1 — Single-core cable
7 Identification Nominal cross-sectional area 35 mm² Nominal conductor cross-section per GB/T 3956
B. Cable Construction (from conductor to outer sheath)
8 Conductor Material Plain annealed copper (Cu) — High-conductivity electrolytic / oxygen-free copper
9 Conductor Conductor class Class 1 or Class 2 (typical: Class 2, stranded) — GB/T 3956 / IEC 60228
10 Conductor Typical stranding construction 7 wires × 2.52 mm (7/2.52) — Class 2 round stranded; nominal section ≈ 35 mm²
11 Conductor Conductor diameter ≈ 7.0 mm 7.0–7.6 mm per manufacturer tables (Qifan 7.0 mm; 7/2.52 → ≈ 7.6 mm)
12 Conductor Max. DC resistance of conductor at 20 °C 0.524 Ω/km GB/T 3956, Class 2 copper; acceptance criterion for 35 mm²
13 Insulation Material Cross-linked polyethylene (XLPE) — Thermally cross-linked; natural/transparent colour
14 Insulation Nominal insulation thickness 0.9 mm GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 35 mm²)
15 Insulation Diameter over insulation ≈ 8.8 mm ≈ 7.0 + 2 × 0.9 (calculated)
16 Sheath Material Flame-retardant polyvinyl chloride (PVC, ST2 type) — Colour: black (or as ordered)
17 Sheath Nominal sheath thickness 1.4 mm GB/T 12706.1 / IEC 60502-1
18 Dimensions Approx. overall diameter 11.8–12.0 mm Qifan 12.0 mm; Weiguang 11.8 mm
19 Dimensions Approx. cable weight ≈ 357 kg/km Range 350–357 kg/km across manufacturers (Qifan 357; Weiguang 350)
C. Electrical Performance
20 Electrical Max. DC conductor resistance at 20 °C 0.524 Ω/km GB/T 3956; routine measurement
21 Electrical Power-frequency withstand voltage (routine test) 3.5 kV / 5 min, no breakdown — AC 50 Hz; per GB/T 12706.1 / IEC 60502-1
22 Electrical Insulation resistance (finished cable, 20 °C) ≥ 36.7 MΩ·km Typical finished-cable requirement for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method
23 Electrical XLPE volume resistivity at 20 °C ≥ 1 × 10¹² Ω·cm Material-level requirement (manufacturer reference)
24 Electrical Capacitance (single-core, approx.) ≤ 0.45 μF/km Manufacturer reference value
25 Electrical Reference ampacity — in air, 30 °C, single core ≈ 190 A Reference value (Guangheng); depends on laying, grouping, ambient — apply correction factors per GB/T 16895 / IEC 60364
26 Electrical Reference ampacity — direct burial, 25 °C ≈ 160–195 A Reference value; depends on soil thermal resistivity and depth (reference range)
D. Thermal Performance
27 Thermal Max. continuous conductor temperature 90 °C XLPE insulation temperature class
28 Thermal Max. conductor temperature under short-circuit (≤ 5 s) 250 °C Per GB/T 12706.1 / IEC 60502-1
29 Thermal Ambient service temperature range -20 to +45 °C Per Qifan datasheet; check project specification
30 Thermal Min. installation (laying) temperature 0 °C Pre-heat the cable if ambient is below 0 °C
E. Flame Retardance (ZR)
31 Flame retardance Flame-retardant class ZC (class C) by default for "ZR" — GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH)
32 Flame retardance Single-cable vertical flame-spread test Pass — GB/T 18380.12
33 Flame retardance Bunched flame-spread test (class C) Char extent ≤ 2.5 m above burner bottom edge — GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min
34 Flame retardance Halogen content Halogen-containing (PVC) — For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type
F. Installation
35 Installation Min. bending radius — single-core cable 20 × OD — Qifan & Huaneng datasheets; some manufacturers specify 15 × OD; OD = actual cable diameter
36 Installation Laying methods Conduit, tray, cable trench, tunnel, duct, supported/suspended aerial — Also direct burial with mechanical protection where permitted
37 Installation Site withstand test after installation DC 4U0 = 2.4 kV, 15 min (recommended) — Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project
G. Packing & Delivery
38 Packing Standard delivery length 100 m per coil/drum (or as ordered) — Typical industry practice; custom lengths available
39 Packing Cable marking Model, rated voltage, manufacturer, year of manufacture, sequential length marks — Per GB/T 6995 / project specification
40 Packing Packing form Wooden drum / coil / export packing — As per customer requirement

 

Polyolefin Single Core Earth Cable ZR-YJV 1 X 35mm2 Single Conductor 0.6/1kV Indoor Power

 

4.Test Parameters

ZR-YJV 1×35 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Test Stage Test Item Method / Standard Requirement / Acceptance Criterion Notes
Routine test Conductor DC resistance measurement GB/T 3956 (IEC 60228) ≤ 0.524 Ω/km at 20 °C Measured on every production length
Routine test Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC, 5 min, no breakdown Applied between conductor and water/earth; 50 Hz
Routine test Construction check — insulation & sheath thickness, outer diameter GB/T 2951 Within GB/T 12706.1 tolerances Insulation ≥ 0.9 mm nominal; sheath ≥ 1.4 mm nominal
Sample test Hot set (thermal elongation) test — XLPE insulation GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % Verifies degree of cross-linking
Sample test Conductor construction & diameter check GB/T 3956 Class 2; 7 × 2.52 mm; Ø ≈ 7.0 mm Sampled per batch
Type test Single-cable vertical flame-spread test (flame retardance) GB/T 18380.12 No flame spread; charring does not reach top reference point ZR / ZC flame-retardant property
Type test Bunched flame-spread test, class C GB/T 18380.35 Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m Class ZC per GB/T 19666
Type test Bending test (mechanical) GB/T 12706.1 Bend around specified mandrel without insulation/sheath damage Mandrel diameter related to cable OD
Post-installation DC withstand test after installation Q/GDW 13244.1-2018 (recommended practice) 4U0 = 2.4 kV DC, 15 min, no breakdown For new installations; verify project specification
Optional Insulation resistance measurement at 20 °C Manufacturer test method ≥ 36.7 MΩ·km (typical finished-cable value) Not a routine item in GB/T 12706.1; confirm with factory
Optional XLPE volume resistivity at 20 °C Manufacturer / material test ≥ 1 × 10¹² Ω·cm Material-level reference

 

5. Coress Section Diagram

Polyolefin Single Core Earth Cable ZR-YJV 1 X 35mm2 Single Conductor 0.6/1kV Indoor Power

No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) Annealed copper, Class 2 stranded — 7 × 2.52 mm (7/2.52), nominal 35 mm² — ≈ 7.0 (Ø) Current-carrying element; max DC resistance ≤ 0.524 Ω/km @ 20 °C
2 Insulation (XLPE) Cross-linked polyethylene 0.9 ≈ 8.8 (Ø over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.4 ≈ 12.0 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter 11.8–12.0 mm Qifan 12.0 mm; Weiguang 11.8 mm    
Approx. cable weight ≈ 357 kg/km Range 350–357 kg/km across manufacturers    
Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV    
Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)    
Min. bending radius (single-core) 20 × OD — OD = actual cable diameter    
Flame-retardant class ZC (ZR) — GB/T 19666    

 

Cable Structure:

1. Overall Construction
The ZR-YJV 1×35 cable is a single-core, flame-retardant power cable rated 0.6/1 kV (Um = 1.2 kV) for 50 Hz power distribution. It consists of three concentric layers built around a stranded copper conductor: an XLPE insulation layer and a flame-retardant PVC outer sheath. Design, dimensions and test requirements follow GB/T 12706.1 and IEC 60502-1; the conductor complies with GB/T 3956 / IEC 60228.
Approximate overall diameter: 11.8–12.0 mm; approximate cable weight: 350–357 kg/km (representative 357 kg/km). The cable is intended for fixed installation in conduits, trays, trenches, tunnels and ducts.
 
2. Conductor (Layer 1 — Innermost)
Material: plain annealed copper (Cu). Construction: normally Class 2 round-stranded with 7 wires of 2.52 mm diameter (7/2.52), giving a nominal cross-section of 35 mm². The stranded design keeps the cable flexible during installation while providing low electrical resistance: maximum DC resistance ≤ 0.524 Ω/km at 20 °C. Approximate conductor diameter: 7.0 mm (7.0–7.6 mm per manufacturer tables).
3. Insulation (Layer 2)
Material: cross-linked polyethylene (XLPE), applied as a 0.9 mm layer over the conductor (diameter over insulation ≈ 8.8 mm). Cross-linking transforms the thermoplastic compound into a thermoset material, which raises the maximum continuous conductor temperature to 90 °C and the short-circuit temperature to 250 °C (≤ 5 s). XLPE provides high dielectric strength, excellent insulation resistance (≥ 10¹² Ω·cm volume resistivity at 20 °C) and low dielectric losses; the finished cable withstands a routine AC test of 3.5 kV for 5 minutes.
 
4. Outer Sheath (Layer 3 — Outermost)
Material: flame-retardant polyvinyl chloride (PVC), ST2 type, black, applied as a 1.4 mm sheath (overall diameter ≈ 12.0 mm). The sheath provides mechanical protection and moisture resistance and gives the cable its “ZR” flame-retardant property — flame-retardant class ZC per GB/T 19666, passing the single-cable vertical flame test (GB/T 18380.12) and the class-C bunched flame test (GB/T 18380.35, char extent ≤ 2.5 m). Note: PVC is halogen-containing; for low-smoke, zero-halogen requirements select WDZ-YJY.
 
5. Construction Features & Installation Notes
• Single core, 35 mm² nominal section; weight ≈ 357 kg/km; standard delivery 100 m per coil/drum.  • Minimum bending radius for single-core laying: 20 × OD.  • Installation ambient temperature not below 0 °C (pre-heat the cable if colder).  • Working ambient range −20 to +45 °C.  • Confirm final values against the factory quality certificate and GB/T 12706.1 / IEC 60502-1 test reports.

6. Usage Precautions

  1. Install only when ambient ≥ 0 °C; pre-heat the cable if colder.
  2. Min. bending radius 20 × OD — avoid sharp bends and kinking.
  3. ZR-YJV contains halogen (PVC); for LSZH requirements choose WDZ-YJY.
  4. Ampacity must be derated for grouping, ambient temperature and burial conditions.
  5. Perform the site DC test only after verifying insulation integrity; avoid prolonged overvoltage.
  6. Store on drums/coils, away from direct sunlight and mechanical damage.

7. Application Range

Indoor/outdoor distribution and branch circuits at 0.6/1 kV in industrial plants, commercial buildings, residential complexes, substations and similar installations — in conduits, trays, trenches, tunnels and ducts; suitable where flame-retardant performance is required (not for direct sunlight exposure unless UV-protected).

 