3x400mm2 Medium Voltage Cable XLPE Armored XLPE Wire 26KV 35kV
Product Summary
Product Details
3x400mm2 medium voltage cable
,xlpe wire 26kv
,3x400mm2 xlpe wire
Product Description
YJLV22 3x400mm² Aluminum XLPE Armored HV Cable 26/35kV for Urban Power Distribution
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
26/35 kV |
Rated voltage: U₀ = 26 kV (phase-to-earth), U = 35 kV (phase-to-phase) |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
L |
Aluminium conductor (Lü = aluminium) |
|
V |
PVC outer sheath |
|
22 |
Steel tape armoured (double steel tape) |
|
3×400 mm² |
Three cores, each 400 mm² aluminium |
Construction: Aluminium conductor, XLPE insulation, semi-con screens, steel tape armour, PVC sheath, three-core medium voltage power cable.


YJLV22-3×400 mm² (26/35 kV) — High-Voltage XLPE Insulated Steel-Tape Armored Aluminum Power Cable — Specification & Engineering Data
1. Overview & Ratings. YJLV22-3×400 — medium-voltage XLPE-insulated, double steel-tape armored, PVC-sheathed aluminum-conductor power cable, three 400 mm² compacted aluminum conductors (L1/L2/L3), rated 8.7/10 kV (Um = 12 kV), 50 Hz; built and tested per GB/T 12701 / IEC 60840, stranding per GB/T 3956. This is a standard MV distribution cable — NOT a fire-resistant cable. Ø ≈ 85 mm, ≈ 6200 kg/km, steel drums.
2. Construction Stack (Conductor → Outer).
| Layer | Build | Wall | Diameter |
|---|---|---|---|
| Conductors (×3) | Compacted stranded Al, Class 2, 3×400 mm² | — | ≈ 24 mm |
| Conductor screen | Extruded semi-conducting | — | — |
| XLPE insulation | Cross-linked polyethylene | ≈ 5.5 mm | ≈ 35 mm |
| Insulation screen | Semi-conducting + Cu tape | ≈ 0.1 mm Cu | — |
| Inner PVC bedding | PVC over cored assembly | ≈ 1.8 mm | ≈ 72 mm |
| Steel tape armor (22) | Double galvanized steel tape | ≈ 2×0.5 mm | ≈ 78 mm |
| Outer PVC sheath | PVC ST2, black, UV-resistant | ≈ 2.5 mm | ≈ 85 mm (finished) |
3. Electrical Characteristics. R ≤ 0.124 Ω/km at 20 °C (Al 400 mm²); routine test 21 kV AC / 5 min; partial discharge ≤ 10 pC at 12 kV; insulation resistance ≥ 1000 MΩ·km; capacitance ≈ 0.22 μF/km; tan δ ≤ 0.0004 at 90 °C. Reference ampacity ≈ 410 A (free air, 25 °C).
Insulation Data
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) |
|
Nominal thickness |
10.5 mm (26/35 kV class) |
|
Long-term service temp. |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C (Al conductor limit per IEC 60228) |
|
Emergency overload temp. |
130 °C |
|
Routine test voltage (AC, 5 min) |
65 kV (for 26/35 kV) |
|
Type-test voltage (AC) |
91 kV (for 26/35 kV) |
|
Partial discharge test |
≤ 10 pC at 1.5 U₀ (39 kV) |
|
Tan δ (dissipation factor) |
≤ 0.004 at 20 °C |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
26 / 35 kV |
GB/T 12706.2 / IEC 60502-2 |
|
Max. system voltage Uₘ |
40.5 kV |
— |
|
Test voltage AC (5 min) |
65 kV |
Routine test (26/35 kV) |
|
DC resistance @20 °C |
≤ 0.0778 Ω/km |
GB/T 3956 Class 2 Al max, 400 mm² |
|
AC resistance @90 °C (est.) |
≈ 0.099 Ω/km |
per core |
|
Capacitance (approx.) |
≈ 0.22 µF/km |
core to screen |
|
Inductive reactance (approx.) |
≈ 0.13 Ω/km |
at 50 Hz, 3-core armoured |
|
Current rating in air (30 °C) |
415 A |
3-core, 26/35 kV (Al conductor derated) |
|
Current rating buried (20 °C) |
370 A |
direct buried, 3-core |
|
Current rating in conduit (30 °C) |
350 A |
3-core |
|
Short-circuit current (1 s, Al, 250 °C) |
≈ 12.0 kA (12000 A) |
400 mm² Al |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 400 mm² Al at 415 A, 3-phase 35 kV → max balanced load ≈ 25.2 MVA. Voltage drop at 415 A ≈ 41.1 V/km per core (≈0.12% per km at 35 kV).
4. Thermal & Mechanical. 90 °C continuous conductor temperature; 250 °C short-circuit (≤ 5 s); 105 °C overload short duration; operating ambient −40~+50 °C; lay ≥ 0 °C. Double steel tape armor provides crush and mechanical protection for direct burial and tray installation.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C (Al conductor) |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (with PVC sheath) |
|
Fire survival |
Standard (flame retardant single cable) |
Fire Performance (YJLV22 — Standard)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
IEC 60332-1 (single cable) |
|
Halogen content |
Contains halogen (PVC sheath & XLPE) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC) |
|
Fire survival (circuit integrity) |
Not applicable (standard version) |
5. Installation Practice & Handling. Bend ≥ 15 × OD ≈ 1275 mm fixed. Use MV cold-shrink / heat-shrink terminations rated 8.7/10 kV. Qualified personnel only — MV jointing requires specialized training. DC site test 21 kV before energising. At 6200 kg/km, heavy steel drums require mechanical handling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 1725 mm at Ø115 mm |
static installation |
|
Max. pulling tension |
12000 N |
Al conductor (lower than Cu) |
|
Direct burial |
Excellent (steel tape armour protects from mechanical damage) |
use warning tape |
|
Conduit ID |
≥ 1.5 × OD → ≥ 172 mm; use 200 mm or larger |
— |
|
Fixing |
cable clamps, tray, direct buried |
heavy-duty supports required |
|
Impact resistance |
High (steel tape armour) |
— |
|
Water resistance |
Good (PVC sheath + armour) |
not watertight |
|
UV resistance |
Good (black PVC, outdoor rated) |
— |
|
Termination note |
Al conductors require Al-compatible lugs (bimetallic Cu/Al or Al compression lugs) + anti-oxidation compound; requires 35 kV class terminations |
strip length 40–45 mm per core |
6. Typical Service Applications. Medium-voltage power distribution, transformer feeders (10 kV side), industrial substations, urban grid, wind/solar farm collector circuits, mining plant power — buried, duct, tray, or trench.

7. Testing & QA Regime. Routine: conductor DC resistance, 21 kV AC / 5 min withstand, partial discharge ≤ 10 pC at 12 kV, insulation resistance. Type: impulse voltage 75 kV, tan δ at 90 °C, bending test, heating cycle, dimensional check.
Cable Parameters
| YJLV22-3×400 mm² (26/35 kV) — Medium-Voltage XLPE Insulated Steel-Tape Armored Aluminum Power Cable — Full Parameter Sheet | ||||
| Medium-voltage power cable · Al conductor / XLPE insulation / Cu tape screen / inner PVC / double steel tape armor (22) / outer PVC · 3×400 mm² · 8.7/10 kV · 90 °C · GB/T 12701 / IEC 60840 · finished Ø ≈ 85 mm | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | YJLV22 — XLPE insulated, steel tape armored, PVC sheathed, Al conductor | — | MV power distribution | |
| Rated voltage (U0/U) | 8.7/10 (Um=12) | kV | Medium-voltage power | |
| Number of cores | 3 × 400 | — | 3-phase (L1/L2/L3) | |
| Conductor material | Aluminum (alloy 1370) | — | Class 2 compacted per GB/T 3956 | |
| Insulation material | XLPE (cross-linked polyethylene) | — | 90 °C rated, semi-conducting screen | |
| Armor type | Double steel tape (22) | — | Mechanical / crush protection | |
| Outer sheath material | PVC (ST2), black | — | UV / weather protection | |
| Standard | GB/T 12701 / IEC 60840 | — | MV XLPE cable | |
| Shielding | Cu tape screen over insulation | — | Corona / partial discharge control | |
| 02 · Conductor (Aluminum) | ||||
| Conductor type | Compacted stranded aluminum | — | Class 2 per GB/T 3956 | |
| Conductor area | 3 × 400 | mm² | 3-phase power | |
| Stranding construction | 61 × 2.85 mm (approx.) | — | Compacted round | |
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Al 400 mm² max per GB/T 3956 | |
| Conductor screen | Extruded semi-conducting | — | Stress control at conductor | |
| Conductor weight per km | ≈ 3240 | kg/km | 3×400 Al | |
| 03 · Insulation & Screening | ||||
| Insulation type | XLPE (cross-linked polyethylene) | — | 90 °C rated | |
| Insulation thickness | ≈ 5.5 | mm | 8.7/10 kV level | |
| Insulation screen | Extruded semi-conducting + Cu tape | — | Cu tape ≈ 0.1 mm | |
| Inner sheath (bedding) | PVC | ≈ 1.8 | Over cored assembly | |
| Steel tape armor | Double galvanized steel tape | ≈ 2×0.5 | 22 armor | |
| Outer PVC sheath | PVC ST2, black | ≈ 2.5 | UV / weather resistant | |
| Finished outer diameter | ≈ 85 | mm | Overall | |
| 04 · Electrical | ||||
| Rated voltage (U0/U) | 8.7/10 | kV | Medium voltage | |
| Max system voltage (Um) | 12 | kV | Temporary overvoltage | |
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Al 400 mm² | |
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE — very high | |
| Routine test voltage (AC) | 21 kV / 5 min | — | Power-frequency withstand | |
| Partial discharge test | ≤ 10 pC at 12 kV | — | MV cable requirement | |
| Capacitance | ≈ 0.22 | μF/km | XLPE MV | |
| Dielectric loss (tan δ) | ≤ 0.0004 at 90 °C | — | MV quality | |
| 05 · Thermal | ||||
| Max continuous conductor temp. | 90 | °C | XLPE rated | |
| Short-circuit temp. | 250 | °C | Max 5 s duration | |
| Overload temp. | 105 | °C | Short duration | |
| Ambient operating range | -40 ~ +50 | °C | Outdoor / buried | |
| Laying temperature | ≥ 0 | °C | Pre-heat below 0 °C | |
| 06 · Mechanical | ||||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 1275 | mm | Armed MV cable | |
| Min bending radius (flexed) | ≥ 20 × OD ≈ 1700 | mm | Repeated flexing | |
| Crush resistance | Good | — | Steel tape armor | |
| Tensile strength | Per GB/T 12701 | — | Installation pull | |
| 07 · Ampacity | ||||
| Air ampacity (3×400 Al) | ≈ 410 | A | 25 °C ambient (est.) | |
| Buried ampacity | ≈ 380 | A | Direct burial, 25 °C soil | |
| Free air current | ≈ 450 | A | Open tray | |
| 08 · Installation | ||||
| Laying methods | Tray, direct burial, duct, trench | — | MV distribution | |
| Terminations | MV cold-shrink / heat-shrink terminations | — | 26/35 kV rated | |
| Joints | MV straight joints / branch joints | — | 26/35 kV rated | |
| Special tools | MV jointing kits, torque wrenches | — | Qualified personnel only | |
| 09 · Packing | ||||
| Standard supply length | 500 m / drum | m | HV cable on steel drums | |
| Reel / packing type | Steel drum, sealed ends | — | Ends must be sealed | |
| Surface marking | YJLV22, 3×400, 8.7/10kV, GB/T 12701, metre marks | — | Continuous printing | |
| Storage conditions | Dry, indoor, sealed ends | — | Protect from moisture | |
| 10 · Applications | ||||
| Typical use | MV power distribution, transformer feeders, industrial substations, urban grid, wind/solar farm collector circuits | High-voltage power | ||
| Max system voltage | 12 | kV (Um) | 26/35 kV rated | |
| Application level | Medium voltage | — | Distribution grid | |
Cable Test Parameters
| Test Parameters — YJLV22-3×400 mm² (26/35 kV) | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 0.124 Ω/km (Al 400 mm²) | Routine |
| 2 | Power-frequency withstand | 21 kV AC, 5 min | No breakdown | Routine |
| 3 | Partial discharge test | 12 kV, 5 min | ≤ 10 pV | Routine |
| 4 | Insulation resistance | 5000 V DC | ≥ 1000 MΩ·km | Routine |
| 5 | Dielectric loss (tan δ) | 90 °C, U0 voltage | ≤ 0.0004 | Type |
| 6 | Impulse voltage test | 75 kV lightning impulse, 10 shots | No breakdown | Type |
| 7 | Bending test | 15× OD, 3 cycles | No damage | Type |
| 8 | Dimensional check | Micrometer / caliper | OD ≈ 85 mm, XLPE ≈ 5.5 mm | Routine |
| 9 | Heating cycle test | 90 °C ↔ ambient, 10 cycles | No damage | Type |
| 10 | Torsion / armor check | Visual + dimensional | Steel tape intact | Routine |
| 11 | Conductor continuity | Per GB/T 3956 | All 3 cores continuous | Routine |
| 12 | Sheath thickness | Micrometer | PVC ≥ 2.5 mm | Routine |
Cable Cross Section Structure

| YJLV22-3×400 mm² (26/35 kV) — Cross-Section Construction Diagram (Schematic) | |||||
| MV power cable: Al conductors → XLPE insulation → Cu tape screen → inner PVC → double steel tape armor (22) → outer PVC · 8.7/10 kV · 90 °C · finished Ø ≈ 85 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductors (×3) | Compacted stranded aluminum, Class 2, 3 × 400 mm² | — | ≈ 24 | R ≤ 0.124 Ω/km |
| 2 | Insulation screen | Extruded semi-conducting + Cu tape | ≈ 0.1 (Cu tape) | — | Partial discharge control |
| 3 | XLPE insulation | Cross-linked polyethylene | ≈ 5.5 | ≈ 35 | 90 °C rated, 8.7/10 kV |
| 4 | Inner sheath (bedding) | PVC over cored assembly | ≈ 1.8 | ≈ 72 | Bed over cores |
| 5 | Steel tape armor (22) | Double galvanized steel tape | ≈ 2×0.5 | ≈ 78 | Mechanical / crush protection |
| 6 | Outer PVC sheath | PVC ST2, black, UV-resistant | ≈ 2.5 | ≈ 85 (finished) | Weather / UV protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 85 | mm | Overall | ||
| Approx. cable mass | ≈ 6200 | kg/km | Al conductors + XLPE + armor + PVC | ||
| Nominal voltage rating | 8.7/10 | kV | Medium-voltage power | ||
| Max system voltage (Um) | 12 | kV | Temporary overvoltage | ||
| Max continuous conductor temp. | 90 | °C | XLPE rated | ||
| Short-circuit temp. | 250 | °C | Max 5 s | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 1275 | mm | Armed MV cable | ||
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Al 400 mm² | ||
| Routine test voltage (AC) | 21 kV / 5 min | — | Power-frequency withstand | ||
| Partial discharge | ≤ 10 pC at 12 kV | — | MV requirement | ||
| Air ampacity @ 25 °C | ≈ 410 | A | 3 cores loaded (est.) | ||
| Buried ampacity | ≈ 380 | A | Direct burial | ||
| Armor type | Double steel tape (22) | — | Mechanical protection | ||
| Conductor material | Aluminum | — | Cost-effective MV | ||
| Schematic — not to exact scale. Finished Ø ≈ 85 mm and weight ≈ 6200 kg/km from cross-referenced industry samples. YJLV22-3×400 is a medium-voltage (8.7/10 kV) XLPE-insulated, steel-tape-armored, aluminum-conductor power cable. Unlike NG-A(BTLY) 4×35+1×16 (low-voltage 0.6/1 kV fire-resistant cable, mica tape insulation, aluminum tube sheath, 750 °C fire-rated, 90 °C, 2450 kg/km), YJLV22 is a medium-voltage power distribution cable: 8.7/10 kV rated, XLPE insulation (5.5 mm thick), copper tape screen for partial discharge control, double steel tape armor for mechanical protection, and aluminum conductors for cost-effective long-distance power transmission. This is not a fire-resistant cable — it is a standard MV distribution cable. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — YJLV22-3×400 mm² (8.7/10 kV MV armored cable) | |||
| Layer-by-layer MV power cable: Al conductors / XLPE insulation / Cu tape screen / inner PVC / double steel tape armor / outer PVC · 8.7/10 kV · 90 °C · finished Ø ≈ 85 mm | |||
| 1. Product Identity & Ratings | |||
| YJLV22-3×400 is a medium-voltage (8.7/10 kV) XLPE-insulated, steel-tape-armored, aluminum-conductor power cable built and tested per GB/T 12701 / IEC 60840. It has 3 aluminum conductors (400 mm² each, L1/L2/L3), XLPE insulation with copper tape screening, inner PVC bedding, double steel tape armor, and outer PVC sheath. Rated 90 °C continuous conductor temperature. Unlike NG-A(BTLY) (low-voltage fire-resistant cable, 0.6/1 kV, mica tape, aluminum tube, 750 °C fire-rated), YJLV22 is a standard MV power distribution cable. Finished Ø ≈ 85 mm, mass ≈ 6200 kg/km, steel drums. | |||
| 2. Aluminum Conductors (3×400) | |||
| The 3 conductors use 400 mm² compacted stranded aluminum (R ≤ 0.124 Ω/km). Aluminum is lighter and cheaper than copper, making it the standard for long-distance MV distribution. Each conductor has an extruded semi-conducting screen to control electrical stress at the conductor surface — essential for MV cables to prevent corona and partial discharge. | |||
| 3. XLPE Insulation & Copper Tape Screen | |||
| XLPE (cross-linked polyethylene) insulation ≈ 5.5 mm thick, rated 90 °C continuous. Over the insulation is a semi-conducting layer plus copper tape screen (≈ 0.1 mm) to control the electrical field and prevent partial discharge. This is fundamentally different from NG-A(BTLY)'s mica tape — XLPE is a thermoplastic insulation for MV power, not a fire barrier. | |||
| 4. Steel Tape Armor (22) | |||
| Double galvanized steel tape (≈ 2×0.5 mm) is applied over the inner PVC bedding. The armor provides crush and mechanical protection for direct burial and tray installation. The '22' designation means: inner PVC bedding + double steel tape armor + outer PVC. This is standard for MV cables buried in trenches or ducts. | |||
| 5. Site Handling & Operational Notes | |||
| • Bend radius 15×OD (≈ 1275 mm) fixed — large because it is an armored MV cable. • Use MV cold-shrink / heat-shrink terminations rated 8.7/10 kV. • 21 kV AC routine withstand test. • Partial discharge ≤ 10 pC at 12 kV. • At 6200 kg/km, supplied on heavy steel drums. • Store with ends sealed. • For MV distribution, transformer feeders, industrial substations. |
8. Standards & Conformity. GB/T 12701 (MV plastic-insulated power cables); IEC 60840 (XLPE MV cables); GB/T 3956 (conductors). Rated 8.7/10 kV (Um = 12 kV).
9. Packaging, Storage & Logistics. 500 m per steel drum with sealed ends. Continuous marking: YJLV22, 3×400, 8.7/10 kV, GB/T 12701, metre marks. Store dry, indoor, ends sealed.

10. Procurement Specification. State "YJLV22-3×400, 8.7/10 kV" + length. Order matching MV terminations/joints. Confirm against factory test certificate (including partial discharge report).
11. Cable Industry FAQ.
- Q1: What is the difference between YJLV22 and NG-A(BTLY)? YJLV22 is a medium-voltage (8.7/10 kV) power distribution cable with XLPE insulation and steel tape armor. NG-A(BTLY) is a low-voltage (0.6/1 kV) fire-resistant cable with mica tape insulation and aluminum tube sheath. Different voltage, different purpose, different construction — YJLV22 distributes MV power; NG-A(BTLY) survives fire.
- Q2: What does "22" mean? 22 = inner PVC bedding + double steel tape armor + outer PVC sheath. This is standard for cables buried directly or installed in ducts where crush protection is needed.
- Q3: Why use aluminum conductors instead of copper? Aluminum is ~1/3 the weight and ~1/4 the cost of copper. For long-distance MV distribution where conductor cost dominates, aluminum (YJLV) is the standard. YJV (copper) is used where space or weight is constrained.
- Q4: What is the difference between YJV22 and YJLV22? YJV22 uses copper conductors; YJLV22 uses aluminum conductors. Same insulation, same armor, same voltage — only the conductor material differs.
- Q5: Why is there a copper tape screen? At 8.7/10 kV, the electric field at the conductor surface is high. A semi-conducting layer + copper tape screen equalizes the field and prevents corona and partial discharge — essential for MV cable reliability.
- Q6: What is partial discharge? Tiny electrical sparks that occur inside the insulation at defects. MV cables must have ≤ 10 pC at rated voltage to ensure long life. Excessive partial discharge leads to insulation breakdown.
- Q7: Can YJLV22 be used outdoors? Yes — the outer PVC sheath is UV-resistant. For direct burial, the steel tape armor provides crush protection. No additional protection needed.
- Q8: What bending radius is required? 15×OD ≈ 1275 mm for fixed installation. This is much larger than LV cables because the MV insulation is thick and rigid.
- Q9: What is the routine test voltage? 21 kV AC for 5 minutes — this is 2.4× the rated phase voltage (8.7 kV). This proves the cable has no manufacturing defects.
- Q10: Can YJLV22 be used for fire pump circuits? No — YJLV22 is not fire-resistant. Fire pump circuits must use mineral-insulated fire cables (BTTRZ/BTLY). YJLV22 is for standard MV power distribution.
- Q11: How is the cable terminated? MV cold-shrink or heat-shrink terminations rated 8.7/10 kV. The termination must carefully strip the XLPE insulation, insulation screen, and conductor screen in the correct order. Only trained personnel should terminate MV cables.