3x400mm2 Medium Voltage Power Cable Aluminum XLPE Armored Mv Cable 8.7kV
Product Summary
Product Details
3x400mm2 medium voltage power cable
,medium voltage power cable aluminum
,armored mv cable 8.7kv
Product Description
YJLV22 3x400mm² Aluminum XLPE Armored MV Cable 8.7/15kV Cost Effective Underground
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
L |
Aluminium conductor (Lü = aluminium) |
|
V |
PVC outer sheath |
|
22 |
Steel tape armoured (double steel tape) |
|
3×400 mm² |
Three cores, each 400 mm² aluminium |
Construction: Aluminium conductor, XLPE insulation, steel tape armour, PVC sheath, three-core medium voltage power cable.


YJLV22-3×400 mm² (8.7/10 kV) — Medium-Voltage XLPE Insulated Steel-Tape Armored Aluminum Power Cable — Specification & Engineering Data
1. Overview & Ratings. YJLV22-3×400 — medium-voltage XLPE-insulated, double steel-tape armored, PVC-sheathed aluminum-conductor power cable, three 400 mm² compacted aluminum conductors (L1/L2/L3), rated 8.7/10 kV (Um = 12 kV), 50 Hz; built and tested per GB/T 12701 / IEC 60840, stranding per GB/T 3956. This is a standard MV distribution cable — NOT a fire-resistant cable. Ø ≈ 85 mm, ≈ 6200 kg/km, steel drums.
2. Construction Stack (Conductor → Outer).
| Layer | Build | Wall | Diameter |
|---|---|---|---|
| Conductors (×3) | Compacted stranded Al, Class 2, 3×400 mm² | — | ≈ 24 mm |
| Conductor screen | Extruded semi-conducting | — | — |
| XLPE insulation | Cross-linked polyethylene | ≈ 5.5 mm | ≈ 35 mm |
| Insulation screen | Semi-conducting + Cu tape | ≈ 0.1 mm Cu | — |
| Inner PVC bedding | PVC over cored assembly | ≈ 1.8 mm | ≈ 72 mm |
| Steel tape armor (22) | Double galvanized steel tape | ≈ 2×0.5 mm | ≈ 78 mm |
| Outer PVC sheath | PVC ST2, black, UV-resistant | ≈ 2.5 mm | ≈ 85 mm (finished) |
3. Electrical Characteristics. R ≤ 0.124 Ω/km at 20 °C (Al 400 mm²); routine test 21 kV AC / 5 min; partial discharge ≤ 10 pC at 12 kV; insulation resistance ≥ 1000 MΩ·km; capacitance ≈ 0.22 μF/km; tan δ ≤ 0.0004 at 90 °C. Reference ampacity ≈ 410 A (free air, 25 °C).
Insulation Data
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) |
|
Nominal thickness |
4.5 mm (8.7/15 kV class) |
|
Long-term service temp. |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C (Al conductor limit) |
|
Emergency overload temp. |
130 °C |
|
Routine test voltage (AC, 5 min) |
30.5 kV (for 8.7/15 kV) |
|
Type-test voltage (AC) |
45 kV (for 8.7/15 kV) |
|
Partial discharge test |
≤ 10 pC at 1.5 U₀ (13.05 kV) |
|
Tan δ (dissipation factor) |
≤ 0.004 at 20 °C |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
8.7 / 15 kV (typical) or 6.35 / 11 kV |
GB/T 12706.2 / IEC 60502-2 |
|
Max. system voltage Uₘ |
17.5 kV (for 15 kV class) |
— |
|
Test voltage AC (5 min) |
30.5 kV |
Routine test (8.7/15 kV) |
|
DC resistance @20 °C |
≤ 0.0778 Ω/km |
GB/T 3956 Class 2 Al max, 400 mm² |
|
AC resistance @90 °C (est.) |
≈ 0.099 Ω/km |
per core |
|
Capacitance (approx.) |
≈ 0.28 µF/km |
core to screen |
|
Inductive reactance (approx.) |
≈ 0.12 Ω/km |
at 50 Hz, 3-core armoured |
|
Current rating in air (30 °C) |
450 A |
3-core, 8.7/15 kV (Al conductor derated) |
|
Current rating buried (20 °C) |
400 A |
direct buried, 3-core |
|
Current rating in conduit (30 °C) |
380 A |
3-core |
|
Short-circuit current (1 s, Al, 250 °C) |
≈ 12.0 kA (12000 A) |
400 mm² Al |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 400 mm² Al at 450 A, 3-phase 10 kV → max balanced load ≈ 7.8 MVA. Voltage drop at 450 A ≈ 44.6 V/km per core (≈0.45% per km at 10 kV).
4. Thermal & Mechanical. 90 °C continuous conductor temperature; 250 °C short-circuit (≤ 5 s); 105 °C overload short duration; operating ambient −40~+50 °C; lay ≥ 0 °C. Double steel tape armor provides crush and mechanical protection for direct burial and tray installation.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C (Al conductor) |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (with PVC sheath) |
|
Fire survival |
Standard (flame retardant single cable) |
Fire Performance (YJLV22 — Standard)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
IEC 60332-1 (single cable) |
|
Halogen content |
Contains halogen (PVC sheath & XLPE) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC) |
|
Fire survival (circuit integrity) |
Not applicable (standard version) |
5. Installation Practice & Handling. Bend ≥ 15 × OD ≈ 1275 mm fixed. Use MV cold-shrink / heat-shrink terminations rated 8.7/10 kV. Qualified personnel only — MV jointing requires specialized training. DC site test 21 kV before energising. At 6200 kg/km, heavy steel drums require mechanical handling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 1380 mm at Ø92 mm |
static installation |
|
Max. pulling tension |
12000 N |
Al conductor (lower than Cu) |
|
Direct burial |
Excellent (steel tape armour protects from mechanical damage) |
use warning tape |
|
Conduit ID |
≥ 1.5 × OD → ≥ 138 mm; use 150 mm or larger |
— |
|
Fixing |
cable clamps, tray, direct buried |
— |
|
Impact resistance |
High (steel tape armour) |
— |
|
Water resistance |
Good (PVC sheath + armour) |
not watertight; use lead-sheathed for submerged |
|
Termination note |
Al conductors require Al-compatible lugs (bimetallic Cu/Al or Al compression lugs) |
anti-oxidation compound required |
6. Typical Service Applications. Medium-voltage power distribution, transformer feeders (10 kV side), industrial substations, urban grid, wind/solar farm collector circuits, mining plant power — buried, duct, tray, or trench.

7. Testing & QA Regime. Routine: conductor DC resistance, 21 kV AC / 5 min withstand, partial discharge ≤ 10 pC at 12 kV, insulation resistance. Type: impulse voltage 75 kV, tan δ at 90 °C, bending test, heating cycle, dimensional check.
Cable Parameters
| YJLV22-3×400 mm² (8.7/10 kV) — Medium-Voltage XLPE Insulated Steel-Tape Armored Aluminum Power Cable — Full Parameter Sheet | ||||
| Medium-voltage power cable · Al conductor / XLPE insulation / Cu tape screen / inner PVC / double steel tape armor (22) / outer PVC · 3×400 mm² · 8.7/10 kV · 90 °C · GB/T 12701 / IEC 60840 · finished Ø ≈ 85 mm | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | YJLV22 — XLPE insulated, steel tape armored, PVC sheathed, Al conductor | — | MV power distribution | |
| Rated voltage (U0/U) | 8.7/10 (Um=12) | kV | Medium-voltage power | |
| Number of cores | 3 × 400 | — | 3-phase (L1/L2/L3) | |
| Conductor material | Aluminum (alloy 1370) | — | Class 2 compacted per GB/T 3956 | |
| Insulation material | XLPE (cross-linked polyethylene) | — | 90 °C rated, semi-conducting screen | |
| Armor type | Double steel tape (22) | — | Mechanical / crush protection | |
| Outer sheath material | PVC (ST2), black | — | UV / weather protection | |
| Standard | GB/T 12701 / IEC 60840 | — | MV XLPE cable | |
| Shielding | Cu tape screen over insulation | — | Corona / partial discharge control | |
| 02 · Conductor (Aluminum) | ||||
| Conductor type | Compacted stranded aluminum | — | Class 2 per GB/T 3956 | |
| Conductor area | 3 × 400 | mm² | 3-phase power | |
| Stranding construction | 61 × 2.85 mm (approx.) | — | Compacted round | |
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Al 400 mm² max per GB/T 3956 | |
| Conductor screen | Extruded semi-conducting | — | Stress control at conductor | |
| Conductor weight per km | ≈ 3240 | kg/km | 3×400 Al | |
| 03 · Insulation & Screening | ||||
| Insulation type | XLPE (cross-linked polyethylene) | — | 90 °C rated | |
| Insulation thickness | ≈ 5.5 | mm | 8.7/10 kV level | |
| Insulation screen | Extruded semi-conducting + Cu tape | — | Cu tape ≈ 0.1 mm | |
| Inner sheath (bedding) | PVC | ≈ 1.8 | Over cored assembly | |
| Steel tape armor | Double galvanized steel tape | ≈ 2×0.5 | 22 armor | |
| Outer PVC sheath | PVC ST2, black | ≈ 2.5 | UV / weather resistant | |
| Finished outer diameter | ≈ 85 | mm | Overall | |
| 04 · Electrical | ||||
| Rated voltage (U0/U) | 8.7/10 | kV | Medium voltage | |
| Max system voltage (Um) | 12 | kV | Temporary overvoltage | |
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Al 400 mm² | |
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE — very high | |
| Routine test voltage (AC) | 21 kV / 5 min | — | Power-frequency withstand | |
| Partial discharge test | ≤ 10 pC at 12 kV | — | MV cable requirement | |
| Capacitance | ≈ 0.22 | μF/km | XLPE MV | |
| Dielectric loss (tan δ) | ≤ 0.0004 at 90 °C | — | MV quality | |
| 05 · Thermal | ||||
| Max continuous conductor temp. | 90 | °C | XLPE rated | |
| Short-circuit temp. | 250 | °C | Max 5 s duration | |
| Overload temp. | 105 | °C | Short duration | |
| Ambient operating range | -40 ~ +50 | °C | Outdoor / buried | |
| Laying temperature | ≥ 0 | °C | Pre-heat below 0 °C | |
| 06 · Mechanical | ||||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 1275 | mm | Armed MV cable | |
| Min bending radius (flexed) | ≥ 20 × OD ≈ 1700 | mm | Repeated flexing | |
| Crush resistance | Good | — | Steel tape armor | |
| Tensile strength | Per GB/T 12701 | — | Installation pull | |
| 07 · Ampacity | ||||
| Air ampacity (3×400 Al) | ≈ 410 | A | 25 °C ambient (est.) | |
| Buried ampacity | ≈ 380 | A | Direct burial, 25 °C soil | |
| Free air current | ≈ 450 | A | Open tray | |
| 08 · Installation | ||||
| Laying methods | Tray, direct burial, duct, trench | — | MV distribution | |
| Terminations | MV cold-shrink / heat-shrink terminations | — | 8.7/10 kV rated | |
| Joints | MV straight joints / branch joints | — | 8.7/10 kV rated | |
| Special tools | MV jointing kits, torque wrenches | — | Qualified personnel only | |
| 09 · Packing | ||||
| Standard supply length | 500 m / drum | m | MV cable on steel drums | |
| Reel / packing type | Steel drum, sealed ends | — | Ends must be sealed | |
| Surface marking | YJLV22, 3×400, 8.7/10kV, GB/T 12701, metre marks | — | Continuous printing | |
| Storage conditions | Dry, indoor, sealed ends | — | Protect from moisture | |
| 10 · Applications | ||||
| Typical use | MV power distribution, transformer feeders, industrial substations, urban grid, wind/solar farm collector circuits | — | Medium-voltage power | |
| Max system voltage | 12 | kV (Um) | 8.7/10 kV rated | |
| Application level | Medium voltage | — | Distribution grid | |
Cable Test Parameters
| Test Parameters — YJLV22-3×400 mm² (8.7/10 kV) | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 0.124 Ω/km (Al 400 mm²) | Routine |
| 2 | Power-frequency withstand | 21 kV AC, 5 min | No breakdown | Routine |
| 3 | Partial discharge test | 12 kV, 5 min | ≤ 10 pV | Routine |
| 4 | Insulation resistance | 5000 V DC | ≥ 1000 MΩ·km | Routine |
| 5 | Dielectric loss (tan δ) | 90 °C, U0 voltage | ≤ 0.0004 | Type |
| 6 | Impulse voltage test | 75 kV lightning impulse, 10 shots | No breakdown | Type |
| 7 | Bending test | 15× OD, 3 cycles | No damage | Type |
| 8 | Dimensional check | Micrometer / caliper | OD ≈ 85 mm, XLPE ≈ 5.5 mm | Routine |
| 9 | Heating cycle test | 90 °C ↔ ambient, 10 cycles | No damage | Type |
| 10 | Torsion / armor check | Visual + dimensional | Steel tape intact | Routine |
| 11 | Conductor continuity | Per GB/T 3956 | All 3 cores continuous | Routine |
| 12 | Sheath thickness | Micrometer | PVC ≥ 2.5 mm | Routine |
Cable Cross Section Structure

| YJLV22-3×400 mm² (8.7/10 kV) — Cross-Section Construction Diagram (Schematic) | |||||
| MV power cable: Al conductors → XLPE insulation → Cu tape screen → inner PVC → double steel tape armor (22) → outer PVC · 8.7/10 kV · 90 °C · finished Ø ≈ 85 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductors (×3) | Compacted stranded aluminum, Class 2, 3 × 400 mm² | — | ≈ 24 | R ≤ 0.124 Ω/km |
| 2 | Insulation screen | Extruded semi-conducting + Cu tape | ≈ 0.1 (Cu tape) | — | Partial discharge control |
| 3 | XLPE insulation | Cross-linked polyethylene | ≈ 5.5 | ≈ 35 | 90 °C rated, 8.7/10 kV |
| 4 | Inner sheath (bedding) | PVC over cored assembly | ≈ 1.8 | ≈ 72 | Bed over cores |
| 5 | Steel tape armor (22) | Double galvanized steel tape | ≈ 2×0.5 | ≈ 78 | Mechanical / crush protection |
| 6 | Outer PVC sheath | PVC ST2, black, UV-resistant | ≈ 2.5 | ≈ 85 (finished) | Weather / UV protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 85 | mm | Overall | ||
| Approx. cable mass | ≈ 6200 | kg/km | Al conductors + XLPE + armor + PVC | ||
| Nominal voltage rating | 8.7/10 | kV | Medium-voltage power | ||
| Max system voltage (Um) | 12 | kV | Temporary overvoltage | ||
| Max continuous conductor temp. | 90 | °C | XLPE rated | ||
| Short-circuit temp. | 250 | °C | Max 5 s | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 1275 | mm | Armed MV cable | ||
| DC resistance @ 20 °C | ≤ 0.124 | Ω/km | Al 400 mm² | ||
| Routine test voltage (AC) | 21 kV / 5 min | — | Power-frequency withstand | ||
| Partial discharge | ≤ 10 pC at 12 kV | — | MV requirement | ||
| Air ampacity @ 25 °C | ≈ 410 | A | 3 cores loaded (est.) | ||
| Buried ampacity | ≈ 380 | A | Direct burial | ||
| Armor type | Double steel tape (22) | — | Mechanical protection | ||
| Conductor material | Aluminum | — | Cost-effective MV | ||
| Schematic — not to exact scale. Finished Ø ≈ 85 mm and weight ≈ 6200 kg/km from cross-referenced industry samples. YJLV22-3×400 is a medium-voltage (8.7/10 kV) XLPE-insulated, steel-tape-armored, aluminum-conductor power cable. Unlike NG-A(BTLY) 4×35+1×16 (low-voltage 0.6/1 kV fire-resistant cable, mica tape insulation, aluminum tube sheath, 750 °C fire-rated, 90 °C, 2450 kg/km), YJLV22 is a medium-voltage power distribution cable: 8.7/10 kV rated, XLPE insulation (5.5 mm thick), copper tape screen for partial discharge control, double steel tape armor for mechanical protection, and aluminum conductors for cost-effective long-distance power transmission. This is not a fire-resistant cable — it is a standard MV distribution cable. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — YJLV22-3×400 mm² (8.7/10 kV MV armored cable) | |||
| Layer-by-layer MV power cable: Al conductors / XLPE insulation / Cu tape screen / inner PVC / double steel tape armor / outer PVC · 8.7/10 kV · 90 °C · finished Ø ≈ 85 mm | |||
| 1. Product Identity & Ratings | |||
| YJLV22-3×400 is a medium-voltage (8.7/10 kV) XLPE-insulated, steel-tape-armored, aluminum-conductor power cable built and tested per GB/T 12701 / IEC 60840. It has 3 aluminum conductors (400 mm² each, L1/L2/L3), XLPE insulation with copper tape screening, inner PVC bedding, double steel tape armor, and outer PVC sheath. Rated 90 °C continuous conductor temperature. Unlike NG-A(BTLY) (low-voltage fire-resistant cable, 0.6/1 kV, mica tape, aluminum tube, 750 °C fire-rated), YJLV22 is a standard MV power distribution cable. Finished Ø ≈ 85 mm, mass ≈ 6200 kg/km, steel drums. | |||
| 2. Aluminum Conductors (3×400) | |||
| The 3 conductors use 400 mm² compacted stranded aluminum (R ≤ 0.124 Ω/km). Aluminum is lighter and cheaper than copper, making it the standard for long-distance MV distribution. Each conductor has an extruded semi-conducting screen to control electrical stress at the conductor surface — essential for MV cables to prevent corona and partial discharge. | |||
| 3. XLPE Insulation & Copper Tape Screen | |||
| XLPE (cross-linked polyethylene) insulation ≈ 5.5 mm thick, rated 90 °C continuous. Over the insulation is a semi-conducting layer plus copper tape screen (≈ 0.1 mm) to control the electrical field and prevent partial discharge. This is fundamentally different from NG-A(BTLY)'s mica tape — XLPE is a thermoplastic insulation for MV power, not a fire barrier. | |||
| 4. Steel Tape Armor (22) | |||
| Double galvanized steel tape (≈ 2×0.5 mm) is applied over the inner PVC bedding. The armor provides crush and mechanical protection for direct burial and tray installation. The '22' designation means: inner PVC bedding + double steel tape armor + outer PVC. This is standard for MV cables buried in trenches or ducts. | |||
| 5. Site Handling & Operational Notes | |||
| • Bend radius 15×OD (≈ 1275 mm) fixed — large because it is an armored MV cable. • Use MV cold-shrink / heat-shrink terminations rated 8.7/10 kV. • 21 kV AC routine withstand test. • Partial discharge ≤ 10 pC at 12 kV. • At 6200 kg/km, supplied on heavy steel drums. • Store with ends sealed. • For MV distribution, transformer feeders, industrial substations. |
8. Standards & Conformity. GB/T 12701 (MV plastic-insulated power cables); IEC 60840 (XLPE MV cables); GB/T 3956 (conductors). Rated 8.7/10 kV (Um = 12 kV).
9. Packaging, Storage & Logistics. 500 m per steel drum with sealed ends. Continuous marking: YJLV22, 3×400, 8.7/10 kV, GB/T 12701, metre marks. Store dry, indoor, ends sealed.

10. Procurement Specification. State "YJLV22-3×400, 8.7/10 kV" + length. Order matching MV terminations/joints. Confirm against factory test certificate (including partial discharge report).
11. Cable Industry FAQ.
- Q1: What is the difference between YJLV22 and NG-A(BTLY)? YJLV22 is a medium-voltage (8.7/10 kV) power distribution cable with XLPE insulation and steel tape armor. NG-A(BTLY) is a low-voltage (0.6/1 kV) fire-resistant cable with mica tape insulation and aluminum tube sheath. Different voltage, different purpose, different construction — YJLV22 distributes MV power; NG-A(BTLY) survives fire.
- Q2: What does "22" mean? 22 = inner PVC bedding + double steel tape armor + outer PVC sheath. This is standard for cables buried directly or installed in ducts where crush protection is needed.
- Q3: Why use aluminum conductors instead of copper? Aluminum is ~1/3 the weight and ~1/4 the cost of copper. For long-distance MV distribution where conductor cost dominates, aluminum (YJLV) is the standard. YJV (copper) is used where space or weight is constrained.
- Q4: What is the difference between YJV22 and YJLV22? YJV22 uses copper conductors; YJLV22 uses aluminum conductors. Same insulation, same armor, same voltage — only the conductor material differs.
- Q5: Why is there a copper tape screen? At 8.7/10 kV, the electric field at the conductor surface is high. A semi-conducting layer + copper tape screen equalizes the field and prevents corona and partial discharge — essential for MV cable reliability.
- Q6: What is partial discharge? Tiny electrical sparks that occur inside the insulation at defects. MV cables must have ≤ 10 pC at rated voltage to ensure long life. Excessive partial discharge leads to insulation breakdown.
- Q7: Can YJLV22 be used outdoors? Yes — the outer PVC sheath is UV-resistant. For direct burial, the steel tape armor provides crush protection. No additional protection needed.
- Q8: What bending radius is required? 15×OD ≈ 1275 mm for fixed installation. This is much larger than LV cables because the MV insulation is thick and rigid.
- Q9: What is the routine test voltage? 21 kV AC for 5 minutes — this is 2.4× the rated phase voltage (8.7 kV). This proves the cable has no manufacturing defects.
- Q10: Can YJLV22 be used for fire pump circuits? No — YJLV22 is not fire-resistant. Fire pump circuits must use mineral-insulated fire cables (BTTRZ/BTLY). YJLV22 is for standard MV power distribution.
- Q11: How is the cable terminated? MV cold-shrink or heat-shrink terminations rated 8.7/10 kV. The termination must carefully strip the XLPE insulation, insulation screen, and conductor screen in the correct order. Only trained personnel should terminate MV cables.