3x300mm2 Medium Voltage Power Cable Al XLPE Super Heavy Aluminum Cable
Product Summary
Product Details
3x300mm2 medium voltage power cable
,medium voltage power cable al
,3x300mm2 heavy aluminum cable
Product Description
Super Heavy Aluminum Cable YJLV22 3x300mm² 8.7/10kV 8.7/15kV Armored XLPE MV
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
L |
Aluminium conductor (Al) |
|
V |
PVC inner bedding / outer sheath |
|
22 |
Steel tape armour (double steel tape, overlapping) + PVC sheath |
|
8.7/10 kV |
Rated voltage U₀/U = 8.7/10 kV; Uₘ = 12 kV |
|
8.7/15 kV |
Rated voltage U₀/U = 8.7/15 kV; Uₘ = 17.5 kV |
|
3×300 mm² |
Three power cores, each 300 mm² aluminium (3-core, no neutral, no PE) |
Construction: XLPE insulated, aluminium conductor, steel-tape armoured, PVC sheathed, three-core medium-voltage power cable.
Applicable Standards
- GB/T 12706.2-2020 / IEC 60502-2 — Power cables with extruded insulation and their accessories for rated voltages from 6 kV up to 30 kV
- GB/T 3956 / IEC 60228 — Conductors (Class 2 stranded circular, aluminium)
- GB/T 2951 / IEC 60811 — Insulating and sheathing materials — Common test methods
- GB/T 3048 — Test methods for electric cables
- GB/T 18380 / IEC 60332 — Flame retardant tests (Category C or B available)


YJLV22-3×300 mm² 8.7/10 kV (and 8.7/15 kV) — Cable Specification & Engineering Data
1. Product Overview & Rating Summary. YJLV22-3×300 is the largest standard size of medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 300 mm² compacted-stranded ALUMINIUM conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The "L" in YJLV22 distinguishes the aluminium conductor from the copper YJV22 — same insulation and armour system, but at roughly one-third the weight and one-third the conductor cost. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV distribution mains serving 40000–63000 kVA distribution transformers and MV motors in the 16000–25000 kW range. Finished diameter is about 112 mm (10 kV) and nominal mass about 17500 kg/km (≈ 1750 kg per 100 m). With all three cores loaded, the cable carries about 460 A in free air at 25 °C (engineering estimate). Beyond 300 mm², the industry standard is to switch to copper or move to 26/35 kV feeders.
2. Layer-by-Layer Construction (Conductor to Outer Jacket).
| Layer | Construction | Wall | Diameter |
|---|---|---|---|
| Conductor (Al) ×3 | Compacted stranded annealed Al, Class 2 — 61×2.52 mm equivalent | — | ≈ 23.5 mm |
| Conductor screen | Extruded semi-conducting XLPE, co-extruded | ≈ 0.8 mm | ≈ 25.1 mm |
| XLPE insulation | Cross-linked polyethylene, triple-extruded | 4.5 mm (10 kV) / 5.5 mm (15 kV) | ≈ 37.3 / ≈ 39.3 mm |
| Insulation screen | Strippable semi-conducting XLPE | ≈ 0.8 mm | ≈ 38.9 / ≈ 40.9 mm |
| Copper-tape screen | 0.1 × 25 mm annealed Cu tape, lapped | ≈ 0.1 mm tape | ≈ 39.1 / ≈ 41.1 mm |
| Filler & bedding | PP/PE rope + non-woven binder | — | ≈ 100 / ≈ 103 mm bundle |
| Inner sheath | PVC/PE extruded bedding | ≈ 1.5 mm | ≈ 103 / ≈ 106 mm |
| Steel armour (type 22) | Double galvanised steel tape, helical lapped | 2 × 0.5 mm | ≈ 104 / ≈ 107 mm |
| PVC outer jacket | ST2 PVC, flame-retardant, black | 3.6 mm | ≈ 112 / ≈ 115 mm (finished) |
3. Electrical Characteristics. Each 300 mm² aluminium conductor is held to a maximum DC resistance of 0.100 Ω/km at 20 °C — about 20% lower resistance than the 240 mm² aluminium version, which translates directly into higher ampacity and lower voltage drop on long MV runs. Every length survives the routine 21.5 kV AC power-frequency proof held for five minutes (30.5 kV for the 15 kV grade). Partial discharge at 1.5 U0 must not exceed 20 pC. Dissipation factor tan δ ≤ 0.001 at U0. Insulation resistance ≥ 1000 MΩ·km, typical capacitance ≈ 0.95 μF/km. Impulse withstand (BIL) is 75 kV for the 10 kV grade and 95 kV for the 15 kV grade. With all three cores energised, reference loading is about 460 A in free air at 25 °C, about 450 A direct-buried.
Insulation Data
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) |
|
Nominal thickness |
4.5 mm |
|
Long-term service temp. |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C (Al conductor limit per IEC 60228) |
|
Emergency overload temp. |
130 °C |
|
Routine test voltage (AC, 5 min) |
22 kV (8.7/10 kV); 30.5 kV (8.7/15 kV) |
|
Type-test voltage (AC) |
30 kV (8.7/10 kV); 45 kV (8.7/15 kV) |
|
Partial discharge test |
≤ 10 pC at 1.73 U₀ (15 kV) |
|
Tan δ (dissipation factor) |
≤ 0.004 at 20 °C |
Electrical Parameters
|
Parameter |
Value (8.7/10 kV) |
Value (8.7/15 kV) |
Note |
|---|---|---|---|
|
Rated voltage U₀/U |
8.7 / 10 kV |
8.7 / 15 kV |
— |
|
Max. system voltage Uₘ |
12 kV |
17.5 kV |
— |
|
Test voltage AC (5 min) |
22 kV |
30.5 kV |
Routine |
|
Type-test voltage |
30 kV |
45 kV |
— |
|
DC resistance @20 °C |
≤ 0.100 Ω/km |
≤ 0.100 Ω/km |
GB/T 3956 Class 2 Al max, 300 mm² |
|
AC resistance @90 °C (est.) |
≈ 0.127 Ω/km |
≈ 0.127 Ω/km |
per core |
|
Capacitance (approx.) |
≈ 0.44 µF/km |
≈ 0.44 µF/km |
per core to screen |
|
Inductive reactance (approx.) |
≈ 0.13 Ω/km |
≈ 0.13 Ω/km |
at 50 Hz, 3-core |
|
Current rating in air (30 °C) |
≈ 415 – 450 A |
≈ 415 – 450 A |
per core, 3-core (Al) |
|
Current rating buried (20 °C) |
≈ 360 – 395 A |
≈ 360 – 395 A |
direct buried, 3-core |
|
Short-circuit current (1 s, Al, 250 °C) |
≈ 30.0 kA (30000 A) |
≈ 30.0 kA (30000 A) |
300 mm² Al |
|
Frequency |
50/60 Hz AC |
50/60 Hz AC |
— |
Reference values: 300 mm² Al at 430 A, 3-phase 10 kV → max balanced load ≈ 7.45 MVA. Voltage drop at 430 A ≈ 5.5 V/km per core (≈0.055% per 100 m).
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C (Al conductor) |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (with PVC sheath) |
|
Fire survival |
Standard (non-fire-rated); optional fire-resistant version available (ZC-YJLV22) |
4. Thermal Response & Flame Behaviour. XLPE insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −20 and +50 °C. PVC jacket provides flame-retardant performance per GB/T 18380.34 class A. Short-circuit rating at 250 °C for 1 s is about 19.5 kA for the 300 mm² aluminium conductor — about 26% higher than the 240 mm² version, comfortably covering very heavy urban and industrial 10 kV fault levels. Thermal resistance of reference burial soil is 1.2 K·m/W.
Fire Performance (YJLV22 — Standard)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.3 Category C (ZC), Category B (ZB) available |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC sheath) |
|
Fire survival (circuit integrity) |
Not applicable (standard version); use ZA-YJLV22 for flame-retardant A |
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 1680 mm for this size. The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice. Critically, the aluminium conductors must be terminated with bimetallic Al-Cu lugs — direct contact between aluminium and copper in the presence of moisture causes galvanic corrosion and joint failure. MV heat-shrink or cold-shrink termination kits are mandatory. Laying temperature must not fall below 0 °C. At about 1750 kg per 100 m, this is the largest standard aluminium MV cable; very heavy lifting gear, cranes and rated pulling grips are essential.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 1215 mm at Ø81.0 mm |
static installation |
|
Max. pulling tension |
18000 N |
Al conductor has ~60% of Cu tensile strength; use proper pulling grips |
|
Direct burial |
Suitable |
steel tape armour provides mechanical protection |
|
Conduit ID |
≥ 1.5 × OD → ≥ 122 mm; use 150 mm or 160 mm |
— |
|
Fixing |
cable clamps, steel straps |
— |
|
Impact resistance |
High |
steel tape armour absorbs mechanical shock |
|
Water resistance |
Moisture-resistant (PVC sheath + inner bedding) |
not fully watertight; use YJLV32 for wet locations |
|
Armour type |
Double steel tape, overlapping |
galvanized or mill finish |
|
Armour short-circuit rating |
≈ 5 kA (1 s, steel tape) |
— |
|
Termination note |
Al conductors require Al-compatible lugs (bimetallic or Al-Cu transition) |
critical for installation |
6. Typical Service Applications. This YJLV22-3×300 aluminium MV cable is the maximum-size cost-effective choice for 10 kV / 15 kV distribution mains where mechanical strength and burial protection are needed and loads are very heavy: 40000–63000 kVA distribution transformer primary feeds in CBD super-tall towers and data-centre campuses, high-rise building 10 kV main incoming supplies, very large industrial park trunk feeders, 10 kV main feeds to very large industrial plants and process workshops, MV motor branch feeds for motors in the 16000–25000 kW range (large pumps, induced-draft fans, compressor stations, mill drives, crusher and conveyor drives, main ventilation fans, water-turbine generators), township and county 10 kV overhead-to-underground trunk feeders, municipal water-supply and wastewater 10 kV trunk mains, very large PV / solar-farm 10 kV collection mains, mining and quarry 10 kV heavy-duty power supply lines, and any circuit where the lightweight aluminium conductor reduces installation and support-structure costs relative to copper. Approved installation methods include direct burial, cable tray, concrete duct, and indoor MV cable trench.

7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance ≤ 0.100 Ω/km at 20 °C, the 21.5 kV AC / 5 min withstand (30.5 kV for 15 kV grade), partial discharge ≤ 20 pC at 1.5 U0, tan δ ≤ 0.001, insulation resistance ≥ 1000 MΩ·km, conductor continuity across all three cores, steel-armour and copper-screen continuity, and dimensional inspection. Sample and type tests comprise impulse withstand at ±75 kV (or ±95 kV for 15 kV), heating-cycle load-loss test, bending at 15 × OD, short-circuit to 250 °C, flame spread GB/T 18380.34 class A, and voltage re-test after thermal ageing. A factory test certificate accompanies each drum.
Cable Parameters
| YJLV22-3×300 mm² 8.7/10 kV (and 8.7/15 kV variant) — Full Parameter Sheet | ||||
| Medium-voltage power cable · ALUMINIUM conductor / XLPE insulation / copper-tape screen / double-steel-tape armour (type 22) / PVC outer sheath · per GB/T 12706.2 · 3 cores · finished Ø ≈ 112 mm (10 kV) / ≈ 115 mm (15 kV) | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | YJLV22 | — | Al conductor / XLPE insulation / double-steel-tape armour / PVC outer sheath | |
| Rated voltage (U0/U) | 8.7/10 | kV | AC 50 Hz; Um = 12 kV (10 kV grade) | |
| Alternative voltage grade | 8.7/15 | kV | AC 50 Hz; Um = 17.5 kV (15 kV grade) — thicker XLPE | |
| Number of cores | 3 × 300 | — | 3 phase cores (300 mm²) — no separate neutral in MV cable | |
| Conductor material | Compacted stranded ALUMINIUM | — | Class 2 stranded per GB/T 3956; largest standard Al MV size | |
| Conductor screen | Extruded semi-conducting XLPE | — | Conductor screen layer (radial field control) | |
| Insulation material | Cross-linked polyethylene (XLPE) | — | 90 °C continuous, 250 °C short-circuit | |
| Insulation screen | Extruded semi-conducting, strippable | — | Outer screen layer | |
| Metallic screen | Copper tape, lapped | — | 0.1 × 25 mm Cu tape; equipotential earth | |
| Armour | Double galvanised steel tape | — | Type 22 armour — mechanical protection | |
| Outer sheath | PVC (ST2), flame-retardant | — | UV- and abrasion-resistant | |
| Standard reference | GB/T 12706.2 / IEC 60502-2; GB/T 3956 | — | Medium-voltage power cables 1.8/3 kV to 26/35 kV | |
| 02 · Conductor (Aluminium) | ||||
| Stranding — 300 mm² | Compacted stranded aluminium | — | Class 2, circular compacted | |
| Strand count (typical) | 61 × 2.52 mm (or 37 × 3.20 mm equivalent) | — | Compacted after stranding | |
| Conductor diameter | ≈ 23.5 | mm | After compacting (est.) | |
| DC resistance @ 20 °C | ≤ 0.100 | Ω/km | Maximum per GB/T 3956 Class 2 (Al) | |
| AC resistance @ 50 Hz (≈ 90 °C) | ≈ 0.15 | Ω/km | Skin/proximity effect included | |
| Conductor screen thickness | ≈ 0.8 | mm | Extruded semi-conducting layer | |
| Conductor weight per km | ≈ 810 | kg/km | Aluminium density 2.70 g/cm³ | |
| 03 · Insulation | ||||
| Insulation type | Cross-linked polyethylene (XLPE) | — | Extruded, triple-layer co-extrusion | |
| Insulation thickness — 8.7/10 kV | 4.5 | mm | Nominal, per GB/T 12706.2 | |
| Insulation thickness — 8.7/15 kV | 5.5 | mm | Thicker for 15 kV grade | |
| Core Ø over insulation — 10 kV | ≈ 37.3 | mm | 23.5 + 2×(0.8+4.5+0.8) | |
| Core Ø over insulation screen — 15 kV | ≈ 39.3 | mm | 23.5 + 2×(0.8+5.5+0.8) | |
| Insulation screen thickness | ≈ 0.8 | mm | Strippable semi-conducting | |
| Impulse withstand (BIL) — 10 kV | 75 | kV | Lightning impulse test | |
| Impulse withstand (BIL) — 15 kV | 95 | kV | Lightning impulse test | |
| 04 · Metallic Screen & Filler | ||||
| Screen material | Annealed copper tape | — | Lapped with overlap | |
| Screen tape dimensions | 0.1 × 25 | mm | Two layers lapped (typical) | |
| Screen function | Equipotential earth / fault-current path | — | Earthed at terminations | |
| Filler material | PP / jute rope, flame-retardant | — | Fills interstices for round cable | |
| Bedding / binder tape | Semi-conducting or non-woven tape | — | Holds bundle; anti-corrosion layer | |
| Assembled bundle Ø — 10 kV | ≈ 100 | mm | Before inner sheath (est.) | |
| Assembled bundle Ø — 15 kV | ≈ 103 | mm | Before inner sheath (est.) | |
| 05 · Inner Sheath & Armour | ||||
| Inner sheath / bedding | PVC or PE extruded | — | Corrosion barrier under armour | |
| Inner sheath thickness | ≈ 1.5 | mm | Over bundle | |
| Armour type | Double steel tape (type 22) | — | Double-tape helical armour | |
| Armour tape thickness | 2 × 0.5 | mm | Galvanised steel, lapped | |
| Armour function | Mechanical protection against crush / impact | — | Permits direct burial / tray | |
| Armour diameter — 10 kV | ≈ 104 | mm | Over inner sheath (est.) | |
| 06 · Outer Sheath | ||||
| Jacket material | PVC, ST2, flame-retardant | — | GB/T 12706.1 | |
| Jacket thickness | 3.6 | mm | Minimum over armour | |
| Overall finished diameter — 10 kV | ≈ 112 | mm | Cross-referenced industry sample | |
| Overall finished diameter — 15 kV | ≈ 115 | mm | Thicker insulation version | |
| Approx. cable mass — 10 kV | ≈ 17500 | kg/km | Al + XLPE + steel + PVC (lightweight) | |
| Approx. cable mass — 15 kV | ≈ 17900 | kg/km | Heavier due to thicker insulation | |
| Jacket colour | Black (standard) | — | UV-resistant carbon-black PVC | |
| Mass per 100 m — 10 kV | ≈ 1750 | kg/100 m | For drum loading | |
| 07 · Electrical | ||||
| Rated voltage U0/U | 8.7/10 | kV | AC 50 Hz; Um = 12 kV | |
| Maximum system voltage Um (10 kV) | 12 | kV | — | |
| DC resistance @ 20 °C | ≤ 0.100 | Ω/km | 300 mm² Al Class 2 | |
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE at 20 °C | |
| Capacitance (typical) | ≈ 0.95 | μF/km | Per core (est.) | |
| Dissipation factor tan δ (at U0) | ≤ 0.001 | — | XLPE, 20 °C | |
| Routine test voltage (AC) — 10 kV | 21.5 kV / 5 min | — | Power-frequency withstand | |
| Routine test voltage (AC) — 15 kV | 30.5 kV / 5 min | — | Power-frequency withstand | |
| Air ampacity @ 25 °C | ≈ 460 | A | 3 cores loaded, Al, in free air (est.) | |
| Buried ampacity @ 25 °C soil | ≈ 450 | A | 3 cores loaded, Al, direct burial (est.) | |
| 08 · Thermal & Fire | ||||
| Max continuous conductor temp. | 90 | °C | Normal service | |
| Short-circuit temp. (≤ 5 s) | 250 | °C | XLPE limit | |
| Fire behaviour | Flame-retardant (PVC jacket) | — | GB/T 18380.34 class A | |
| Service ambient range | −20 to +50 | °C | Fixed installation | |
| Thermal resistance (soil) | 1.2 | K·m/W | Reference burial conditions | |
| Short-circuit rating (1 s) | ≈ 19.5 | kA | 300 mm² Al at 250 °C | |
| 09 · Installation | ||||
| Min bending radius | ≥ 15 × OD ≈ 1680 | mm | Fixed installation (armoured) | |
| Laying temperature | ≥ 0 | °C | Pre-heat below 0 °C | |
| Laying methods | Tray, direct burial, conduit, duct | — | Armour permits direct burial | |
| Armour earthing | Both ends earthed | — | Steel armour must be earthed | |
| Copper screen earthing | At both ends (or single point for cross-bonding) | — | MV cable screen bonding | |
| Termination / joints | Al-Cu transition lugs required | — | Al conductor — use bimetallic lugs to avoid galvanic corrosion | |
| Special tools | Cable cutter, crimping tool, torque wrench | — | MV lugs required; heavy winch / cable grip essential | |
| 10 · Packing | ||||
| Standard supply length | 500 or 1000 | m/drum | Custom cut lengths available | |
| Reel / packing type | Wooden-steel drum | — | Sealed ends against moisture | |
| Surface marking | YJLV22, 8.7/10 kV, 3×300, supplier, year, metre marks | — | Per GB/T 6995 | |
| Storage conditions | Dry, covered, −20 to +40 °C | — | Sealed ends; protect from UV | |
| Transport | Drums secured against rolling | — | Very heavy cable; crane required | |
Cable Test Parameters
| Test Parameters — YJLV22-3×300 mm² 8.7/10 kV (and 8.7/15 kV) | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3048.4, 20 °C | ≤ 0.100 Ω/km (300 mm² Al) | Routine |
| 2 | Power-frequency withstand (routine) | 21.5 kV AC, 5 min (10 kV grade) | No breakdown | Routine |
| 3 | Power-frequency withstand (15 kV grade) | 30.5 kV AC, 5 min | No breakdown | Routine |
| 4 | Partial discharge test | At 1.5 U0 = 13 kV (10 kV grade) | ≤ 20 pC at 1.73 U0 | Routine |
| 5 | Dissipation factor tan δ | At U0, 20 °C | tan δ ≤ 0.001 | Routine |
| 6 | Insulation resistance | GB/T 3048.5 | ≥ 1000 MΩ·km | Routine |
| 7 | Dimensional check | Micrometer / micrometer microscope | Insulation ≥ 4.5 mm (10 kV); jacket ≥ 3.6 mm | Routine |
| 8 | Impulse voltage test (BIL) | ±75 kV, 10 impulses (10 kV grade) | No breakdown at 75 kV | Type |
| 9 | Impulse voltage test (15 kV grade) | ±95 kV, 10 impulses | No breakdown at 95 kV | Type |
| 10 | Heating cycle / load loss | 3 cycles U0 + rated current | No damage; tan δ stable | Type |
| 11 | Bending test | 15 × OD mandrel, 3 cycles | No damage to insulation or sheath | Type |
| 12 | Short-circuit temperature test | 250 °C, 5 s equivalent | No insulation collapse | Type |
| 13 | Flame propagation | GB/T 18380.34 class A | No vertical flame spread | Type |
| 14 | Sheath / armour continuity | Continuity meter | Steel armour and Cu tape continuous | Routine |
| 15 | Voltage test after ageing | After thermal ageing cycle | Withstands 2.5 U0 AC | Type |
| 16 | Marking legibility | Visual + rubbing | YJLV22 / 8.7/10 kV / 3×300 / metre marks legible | Routine |
Cable Cross Section Structure

| YJLV22-3×300 mm² 8.7/10 kV — Cross-Section Construction Diagram (Schematic) | |||||
| MV layered build-up: ALUMINIUM conductor → conductor screen → XLPE insulation → insulation screen → Cu-tape screen → filler → bedding → double-steel-tape armour → PVC jacket · 8.7/10 kV (8.7/15 kV variant noted) · finished Ø ≈ 112 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Al) ×3 | Compacted stranded ALUMINIUM, Class 2 — 61×2.52 mm equivalent per core | — | ≈ 23.5 | Power conductor; R ≤ 0.100 Ω/km at 20 °C |
| 2 | Conductor screen | Extruded semi-conducting XLPE, co-extruded with insulation | ≈ 0.8 | ≈ 25.1 | Eliminates air gaps; smooth radial field |
| 3 | XLPE insulation | Cross-linked polyethylene, triple-layer co-extrusion | 4.5 (10 kV) / 5.5 (15 kV) | ≈ 37.3 / ≈ 39.3 | Main dielectric; 90 °C continuous |
| 4 | Insulation screen | Strippable semi-conducting XLPE | ≈ 0.8 | ≈ 38.9 / ≈ 40.9 | Outer screen; equipotential |
| 5 | Copper-tape screen | Annealed Cu tape, lapped, 0.1 × 25 mm | ≈ 0.1 tape | ≈ 39.1 / ≈ 41.1 | Earth path / fault-current return |
| 6 | Filler & bedding | PP/PE rope filler + non-woven binder tape | — | ≈ 100 / ≈ 103 bundle | Round shape; anti-corrosion bedding |
| 7 | Inner sheath | PVC/PE extruded bedding over bundle | ≈ 1.5 | ≈ 103 / ≈ 106 | Corrosion barrier under armour |
| 8 | Steel armour (type 22) | Double galvanised steel tape, helically lapped | 2 × 0.5 | ≈ 104 / ≈ 107 | Mechanical crush / impact protection |
| 9 | PVC outer jacket | ST2 PVC, flame-retardant, black | 3.6 | ≈ 112 / ≈ 115 (finished) | UV, abrasion and chemical protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter (10 kV) | ≈ 112 | mm | Cross-referenced industry sample | ||
| Finished cable diameter (15 kV) | ≈ 115 | mm | Thicker XLPE variant | ||
| Approx. cable mass (10 kV) | ≈ 17500 | kg/km | Al + XLPE + steel + PVC (lightweight) | ||
| Approx. cable mass (15 kV) | ≈ 17900 | kg/km | Heavier due to thicker insulation | ||
| Nominal voltage rating | 8.7/10 | kV | AC 50 Hz; Um = 12 kV | ||
| Alternative voltage grade | 8.7/15 | kV | Um = 17.5 kV; 5.5 mm XLPE | ||
| Max continuous conductor temp. | 90 | °C | Normal service | ||
| Short-circuit temp. (≤5 s) | 250 | °C | XLPE limit | ||
| Impulse withstand (BIL) | 75 (10 kV) / 95 (15 kV) | kV | Lightning impulse | ||
| Min bending radius | ≥ 15 × OD ≈ 1680 | mm | Fixed installation | ||
| DC resistance @ 20 °C | ≤ 0.100 | Ω/km | 300 mm² Al | ||
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE | ||
| Routine test voltage | 21.5 kV AC / 5 min | — | 10 kV grade; 30.5 kV for 15 kV | ||
| Air ampacity @ 25 °C | ≈ 460 | A | 3 cores loaded, Al (est.) | ||
| Mass per 100 m (10 kV) | ≈ 1750 | kg/100 m | For drum loading | ||
| Schematic — not to exact scale. Finished Ø ≈ 112 mm (10 kV) and weight ≈ 17500 kg/km from cross-referenced industry samples; conductor/insulation diameters per GB/T 12706.2 and GB/T 3956; ampacity 460 A is an engineering estimate for ALUMINIUM conductors. The 8.7/15 kV variant uses 5.5 mm XLPE insulation, ≈ 115 mm OD and ≈ 17900 kg/km. Values marked (est.) require confirmation against the factory test certificate. Al conductors require bimetallic Al-Cu lugs at terminations. At this size the cable is at the practical upper limit of aluminium MV trunk feeders; beyond 300 mm² the industry standard is to switch to copper or move to 26/35 kV. | |||||
Cable Construction Description
| Construction Description — YJLV22-3×300 mm² 8.7/10 kV | |||
| Layer-by-layer MV build-up narrative · 8.7/10 kV (and 8.7/15 kV variant) · ALUMINIUM / triple-extruded XLPE / Cu-tape screen / double-steel-tape armour / PVC jacket · finished Ø ≈ 112 mm | |||
| 1. Product Identity & Ratings | |||
| YJLV22-3×300 is the largest standard size of medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 300 mm² compacted-stranded ALUMINIUM conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The 'L' in YJLV22 distinguishes the aluminium conductor from copper (YJV22). The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV distribution mains serving 40000–63000 kVA distribution transformers and MV motors in the 16000–25000 kW range. Finished diameter is about 112 mm (10 kV) and nominal mass about 17500 kg/km (≈ 1750 kg per 100 m). With all three cores loaded, the cable carries about 460 A in free air at 25 °C (engineering estimate). Beyond 300 mm², the industry standard is to switch to copper or move to 26/35 kV feeders. | |||
| 2. Aluminium Conductor & Screens | |||
| Each 300 mm² conductor is compacted-stranded aluminium (Class 2), with a strand-lay diameter of about 23.5 mm and DC resistance ≤ 0.100 Ω/km at 20 °C — roughly 20% lower resistance than the 240 mm² aluminium version. Aluminium is roughly one-third the weight of copper and one-third the cost, but it has roughly 60% lower conductivity — hence the larger cross-section needed for a given current. A semi-conducting conductor screen (≈ 0.8 mm) is co-extruded directly over the aluminium to eliminate air gaps and smooth the electric field. The conductor screen bonds electrically to the aluminium. | |||
| 3. XLPE Insulation | |||
| Cross-linked polyethylene (XLPE) is extruded in a triple-layer co-extrusion process: conductor screen → XLPE insulation → insulation screen, all in one pass to avoid contamination. For the 8.7/10 kV grade the insulation thickness is 4.5 mm; for the 8.7/15 kV grade it is 5.5 mm. XLPE sustains 90 °C continuous conductor temperature and 250 °C short-circuit for ≤ 5 s. The outer insulation screen is strippable for termination work. Over the insulation screen a 0.1 × 25 mm copper tape is lapped to provide an equipotential earth and fault-current return path. | |||
| 4. Bedding, Steel Armour & PVC Jacket | |||
| Three screened cores are cabled round with PP/PE rope filler and a non-woven binder tape, giving a bundle of about 100 mm (10 kV). A PVC/PE inner bedding (≈ 1.5 mm) is extruded over the bundle, then a double layer of 0.5 mm galvanised steel tape is helically lapped — this is the type-22 armour that protects against crush and impact and permits direct burial. Finally a 3.6 mm black PVC (ST2) outer jacket is extruded over the armour to the ≈ 112 mm finish, providing UV, abrasion and chemical resistance. | |||
| 5. Site Handling & Operational Notes | |||
| • Observe the 15 × OD minimum bending radius (≈ 1680 mm). • The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice. • Use bimetallic Al-Cu lugs at all terminations — direct Al-to-Cu contact causes galvanic corrosion. • Service ambient −20 to +50 °C; conductor up to 90 °C continuous. • Routine test 21.5 kV AC / 5 min (10 kV); impulse withstand 75 kV. • At ≈ 1750 kg/100 m, this is the largest standard aluminium MV cable; very heavy lifting gear, cranes and rated pulling grips are essential. For loads beyond 460 A, switch to copper or move to 26/35 kV feeders. |
8. Factory Overview.

9. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type (YJLV22), voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +40 °C, shielded from direct sunlight and moisture; drum end seals must remain intact until installation. MV cable terminations and joints should be scheduled immediately after laying to avoid prolonged exposure of the cut aluminium ends. At this size each drum is very heavy and requires crane handling.

10. Procurement Specification. State "YJLV22-8.7/10 kV-3×300" (or "YJLV22-8.7/15 kV-3×300" for the thicker-insulation grade) together with the required length or drum arrangement. Always order bimetallic Al-Cu lugs and MV termination kits at both ends — do not substitute pure copper lugs on aluminium conductors. Always request the factory test certificate, which must include the partial-discharge and impulse-withstand reports, to confirm the actual diameter, weight and conductor resistances for the production batch.
11. Cable Industry FAQ.
- Q1: How does 300 mm² aluminium compare to 240 mm² aluminium? 300 mm² raises the reference ampacity from about 410 A to about 460 A (+12%), and lowers the DC resistance from 0.125 Ω/km to 0.100 Ω/km (−20%). It is the standard upgrade when the load grows beyond the 25000–40000 kVA transformer band and enters the 40000–63000 kVA range. The jacket also steps up from 3.4 mm to 3.6 mm. Weight rises from 14800 to 17500 kg/km. This is the largest standard aluminium MV trunk size; beyond 300 mm², switch to copper or move to 26/35 kV feeders.
- Q2: Why choose aluminium (YJLV22) over copper (YJV22)? Aluminium costs roughly one-third of copper per metre at the same cross-section and weighs roughly one-third, which reduces both material cost and installation labour for long MV runs. The trade-off is higher resistance — for the same ampacity you typically need to upsize by one or two cross-section steps. For heavily-loaded suburban, industrial-park and rural distribution mains, YJLV22 remains the standard cost-optimised choice up to around 300 mm².
- Q3: What does the "L" in YJLV22 mean? "L" = aluminium conductor. Without the L, YJV22 uses copper. The "22" still means double-steel-tape armour over PVC jacket — identical mechanical and fire protection.
- Q4: Why must I use bimetallic lugs? Aluminium and copper form a galvanic cell when directly connected in the presence of moisture. Over years this corrodes the aluminium at the joint, increasing resistance and eventually overheating. Bimetallic Al-Cu lugs have an aluminium barrel on the conductor side and a copper flange on the equipment side, isolating the two metals.
- Q5: When do I choose 8.7/10 kV vs 8.7/15 kV? Choose 8.7/10 kV for nominal 10 kV distribution networks (Um = 12 kV). Choose 8.7/15 kV for nominal 15 kV networks (Um = 17.5 kV) or where the system may be up-rated — the thicker 5.5 mm XLPE gives a larger safety margin.
- Q6: Why is there no separate neutral core? At MV distribution voltages, three-phase currents are balanced and the system is typically solidly or resistance-earthed; the copper-tape screen provides the earth path. A separate neutral is not required in standard 3-core MV construction.
- Q7: Can this cable be directly buried? Yes — the double-steel-tape armour provides crush protection, and the PVC jacket is moisture-resistant. Direct burial depth and covering must follow the local MV cable installation code.
- Q8: What is partial discharge and why is it tested? Partial discharge (PD) is tiny electrical sparks inside the insulation caused by voids or contaminants. At 1.5 U0, PD must be ≤ 20 pC. High PD values predict early insulation failure and are the most sensitive factory-quality indicator.
- Q9: Why is the routine test 21.5 kV and not 10 kV? Routine tests apply a power-frequency withstand voltage higher than the rated voltage (typically 2.5 U0 = 21.75 kV, rounded to 21.5 kV) to catch manufacturing defects before site installation.
- Q10: Is the short-circuit rating adequate? At 300 mm² aluminium, the 1 s short-circuit rating is about 19.5 kA — comfortably covering very heavy urban and industrial 10 kV fault levels. For very high-fault-level networks (major substations, ring mains, industrial bus ties), switching to copper or upsizing to 26/35 kV feeders is recommended.
- Q11: What service life can be expected? When installed, terminated and operated within the stated temperature, voltage and current ratings, XLPE-insulated MV cables — aluminium or copper — are designed for a service life of around 30 years in fixed installation. The dominant failure mode is moisture or PD at terminations, so professional jointing and proper bimetallic lugs are critical.