YJV22 Medium Voltage Power Cable 3x150mm2 Copper Mv Armoured Cable 15kV

YJV22 Medium Voltage Power Cable 3x150mm2 Copper Mv Armoured Cable 15kV

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
YJV22 3x150mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

YJV22 3x150mm² Copper XLPE Armored MV Cable 8.7/15kV Reliable Underground Power Cable Designation & Meaning Code Meaning YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath 22 Steel tape armoured (double steel tape) 3×150 mm² Three cores, each 150 mm² copper Construction: Copper ...

Product Details

Highlight:

yjv22 medium voltage power cable

,

medium voltage power cable 3x150mm2

,

mv armoured cable 15kv

Conductor (×3):
Copper, Class 2 Stranded Sector-shaped, Nominal 37×∅2.27 Mm (150 Mm²), Conductor Ø ≈ 16–18 Mm (sector Width)
Conductor screen:
Semi-conductive Compound Layer, Thickness ≈ 0.5 Mm
Insulation:
XLPE (cross-linked Polyethylene), Nominal Thickness 4.5 Mm​ (for 8.7/15 KV Class)
Insulation screen:
Semi-conductive Compound Layer, Thickness ≈ 0.5 Mm
Metallic screen:
Copper Tape Screen Over Each Core (optional) Or Collective Copper Wire Screen
Filler & bedding:
PVC Filler, Round Profile, Inner PVC Bedding Thickness ≈ 1.2 Mm
Armour:
Double Steel Tape, Thickness 0.5 Mm × 2 Layers (overlapped)
Outer sheath:
PVC​ (polyvinyl Chloride), Nominal Thickness 2.5 Mm (typical), Colour: Black
Conductor nominal area:
150 Mm² (Cu)
Number of cores:
3
Conductor material:
Copper (Cu)
Conductor class:
Class 2 Stranded Sector
Conductor construction:
37×∅2.27 Mm (typical)
Conductor diameter (approx.):
16–18 Mm (sector Width)
Insulation thickness:
4.5 Mm
Diameter over insulation (approx.):
25–28 Mm
Bedding thickness:
1.2 Mm
Armour (steel tape):
0.5 Mm × 2 Layers
Outer sheath thickness:
2.5 Mm
Overall cable diameter:
60 – 72 Mm
Design outer diameter:
≈ 66 Mm
Approx. weight:
6.0 – 7.5 Kg/m (6000–7500 Kg/km)
Design weight:
≈ 6700 Kg/km
Cable shape:
Round

Product Description

YJV22 3x150mm² Copper XLPE Armored MV Cable 8.7/15kV Reliable Underground Power

Cable Designation & Meaning

Code

Meaning

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath

22

Steel tape armoured (double steel tape)

3×150 mm²

Three cores, each 150 mm² copper

 

Construction: Copper conductor, XLPE insulation, semi-con screens, steel tape armour, PVC sheath, three-core medium voltage power cable.

 

YJV22 Medium Voltage Power Cable 3x150mm2 Copper Mv Armoured Cable 15kV

 

YJV22 Medium Voltage Power Cable 3x150mm2 Copper Mv Armoured Cable 15kV

 

 

YJV22-3×150 mm² (8.7/15 kV) — Compact Medium-Voltage XLPE Insulated Steel-Tape Armored Copper Power Cable — Specification & Engineering Data

1. Overview & Ratings. YJV22-3×150 — compact medium-voltage XLPE-insulated, double steel-tape armored, PVC-sheathed copper-conductor power cable, three 150 mm² compacted copper conductors (L1/L2/L3), rated 8.7/15 kV (Um = 17.5 kV), 50 Hz; built and tested per GB/T 12701 / IEC 60840. Copper conductors deliver higher current density in a smaller footprint than the aluminum 400 mm² version. Ø ≈ 62 mm, ≈ 5800 kg/km, steel drums.

 

2. Construction Stack (Conductor → Outer).

Layer Build Wall Diameter
Conductors (×3) Compacted stranded Cu, Class 2, 3×150 mm² — ≈ 14.5 mm
Conductor screen Extruded semi-conducting — —
XLPE insulation Cross-linked polyethylene ≈ 4.5 mm ≈ 24 mm
Insulation screen Semi-conducting + Cu tape ≈ 0.1 mm Cu —
Inner PVC bedding PVC over cored assembly ≈ 1.5 mm ≈ 55 mm
Steel tape armor (22) Double galvanized steel tape ≈ 2×0.5 mm ≈ 58 mm
Outer PVC sheath PVC ST2, black, UV-resistant ≈ 2.2 mm ≈ 62 mm (finished)

 

3. Electrical Characteristics. R ≤ 0.124 Ω/km at 20 °C (Cu 150 mm²); routine test 25 kV AC / 5 min; partial discharge ≤ 10 pC at 12 kV; insulation resistance ≥ 1500 MΩ·km; capacitance ≈ 0.20 μF/km; tan δ ≤ 0.0004 at 90 °C. Reference ampacity ≈ 265 A (free air, 25 °C).

Insulation Data

 

Property

Value

Material

XLPE (cross-linked polyethylene)

Nominal thickness

4.5 mm (8.7/15 kV class)

Long-term service temp.

90 °C

Short-circuit temp. (≤5 s)

250 °C​ (Cu conductor limit per IEC 60228)

Emergency overload temp.

130 °C

Routine test voltage (AC, 5 min)

30.5 kV (for 8.7/15 kV)

Type-test voltage (AC)

45 kV (for 8.7/15 kV)

Partial discharge test

≤ 10 pC at 1.5 U₀ (13.05 kV)

Tan δ (dissipation factor)

≤ 0.004 at 20 °C

Electrical Parameters

 

Parameter

Value

Note

Rated voltage U₀/U

8.7 / 15 kV (typical) or 6.35 / 11 kV

GB/T 12706.2 / IEC 60502-2

Max. system voltage Uₘ

17.5 kV (for 15 kV class)

—

Test voltage AC (5 min)

30.5 kV

Routine test (8.7/15 kV)

DC resistance @20 °C

≤ 0.124 Ω/km

GB/T 3956 Class 2 Cu max, 150 mm²

AC resistance @90 °C (est.)

≈ 0.158 Ω/km

per core

Capacitance (approx.)

≈ 0.24 µF/km

core to screen

Inductive reactance (approx.)

≈ 0.10 Ω/km

at 50 Hz, 3-core armoured

Current rating in air (30 °C)

310 A​

3-core, 8.7/15 kV

Current rating buried (20 °C)

275 A​

direct buried, 3-core

Current rating in conduit (30 °C)

260 A​

3-core

Short-circuit current (1 s, Cu, 250 °C)

≈ 15.0 kA (15000 A)

150 mm² Cu

Frequency

50/60 Hz AC

—

Reference values: 150 mm² Cu at 310 A, 3-phase 10 kV → max balanced load ≈ 5.4 MVA. Voltage drop at 310 A ≈ 49.0 V/km per core (≈0.49% per km at 10 kV).

 

4. Thermal & Mechanical. 90 °C continuous conductor temperature; 250 °C short-circuit (≤ 5 s); 105 °C overload short duration; operating ambient −40~+50 °C; lay ≥ 0 °C. Double steel tape armor provides crush and mechanical protection for direct burial and tray installation.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C (Cu conductor)

Emergency overload temp.

130 °C

Min. installation ambient temp.

0 °C (PVC sheath); below 0 °C pre-heating required

Service ambient range

−20 °C to +90 °C (with PVC sheath)

Fire survival

Standard (flame retardant single cable)

Fire Performance (YJV22 — Standard)

Property

Value / Requirement

Flame retardant

IEC 60332-1 (single cable, passes)

Halogen content

Contains halogen (PVC sheath & XLPE)

Smoke density

Standard (non-low-smoke)

Corrosivity

Corrosive (PVC)

Fire survival (circuit integrity)

Not applicable (standard version); use NH-YJV22 for circuit integrity

 

5. Installation Practice & Handling. Bend ≥ 15 × OD ≈ 930 mm fixed. Use MV cold-shrink / heat-shrink terminations rated 8.7/15 kV. Qualified personnel only — MV jointing requires specialized training. At 5800 kg/km, heavy steel drums require mechanical handling. The compact Ø62 mm makes it suitable for restricted spaces.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 990 mm at Ø66 mm

static installation

Max. pulling tension

15000 N

Cu conductor, use proper pulling grips

Direct burial

Excellent​ (steel tape armour protects from mechanical damage)

use warning tape

Conduit ID

≥ 1.5 × OD → ≥ 99 mm; use 100 mm, 125 mm or 150 mm

—

Fixing

cable clamps, tray, direct buried

—

Impact resistance

High​ (steel tape armour)

—

Water resistance

Good (PVC sheath + armour)

not watertight; use lead-sheathed for submerged

UV resistance

Good (black PVC, outdoor rated)

—

Termination note

Cu conductors — standard compression lugs or mechanical lugs

strip length 25–30 mm per core

 

6. Typical Service Applications. Compact MV power distribution, building MV risers, industrial substations, wind/solar farm collector circuits, urban grid secondary feeders — where space is constrained but 8.7/15 kV rating is required.

 

YJV22 Medium Voltage Power Cable 3x150mm2 Copper Mv Armoured Cable 15kV

 

7. Testing & QA Regime. Routine: conductor DC resistance, 25 kV AC / 5 min withstand, partial discharge ≤ 10 pC at 12 kV, insulation resistance. Type: impulse voltage 95 kV, tan δ at 90 °C, bending test, heating cycle, dimensional check.

 

Cable Parameters

 

YJV22-3×150 mm² (8.7/15 kV) — Medium-Voltage XLPE Insulated Steel-Tape Armored Copper Power Cable — Full Parameter Sheet
Compact MV cable · Cu conductor / XLPE insulation / Cu tape screen / inner PVC / double steel tape armor (22) / outer PVC · 3×150 mm² · 8.7/15 kV · 90 °C · GB/T 12701 / IEC 60840 · finished Ø ≈ 62 mm
Section Parameter Value Unit Remarks / Standard
01 · Identification
  Cable type YJV22 — XLPE insulated, steel tape armored, PVC sheathed, Cu conductor — MV power distribution
  Rated voltage (U0/U) 8.7/15 (Um=17.5) kV Medium-voltage power
  Number of cores 3 × 150 — 3-phase (L1/L2/L3)
  Conductor material Annealed copper — Class 2 compacted per GB/T 3956
  Insulation material XLPE (cross-linked polyethylene) — 90 °C rated, semi-conducting screen
  Armor type Double steel tape (22) — Mechanical / crush protection
  Outer sheath material PVC (ST2), black — UV / weather protection
  Standard GB/T 12701 / IEC 60840 — MV XLPE cable
  Shielding Cu tape screen over insulation — Corona / partial discharge control
02 · Conductor (Copper)
  Conductor type Compacted stranded copper — Class 2 per GB/T 3956
  Conductor area 3 × 150 mm² 3-phase power
  Stranding construction 30 × 2.52 mm (approx.) — Compacted round
  DC resistance @ 20 °C ≤ 0.124 Ω/km Cu 150 mm² max per GB/T 3956
  Conductor screen Extruded semi-conducting — Stress control at conductor
  Conductor weight per km ≈ 4050 kg/km 3×150 Cu
03 · Insulation & Screening
  Insulation type XLPE (cross-linked polyethylene) — 90 °C rated
  Insulation thickness ≈ 4.5 mm 8.7/15 kV level
  Insulation screen Extruded semi-conducting + Cu tape — Cu tape ≈ 0.1 mm
  Inner sheath (bedding) PVC ≈ 1.5 Over cored assembly
  Steel tape armor Double galvanized steel tape ≈ 2×0.5 22 armor
  Outer PVC sheath PVC ST2, black ≈ 2.2 UV / weather resistant
  Finished outer diameter ≈ 62 mm Overall
04 · Electrical
  Rated voltage (U0/U) 8.7/15 kV Medium voltage
  Max system voltage (Um) 17.5 kV Temporary overvoltage
  DC resistance @ 20 °C ≤ 0.124 Ω/km Cu 150 mm²
  Insulation resistance ≥ 1500 MΩ·km XLPE — very high
  Routine test voltage (AC) 25 kV / 5 min — Power-frequency withstand
  Partial discharge test ≤ 10 pC at 12 kV — MV cable requirement
  Capacitance ≈ 0.20 μF/km XLPE MV
  Dielectric loss (tan δ) ≤ 0.0004 at 90 °C — MV quality
05 · Thermal
  Max continuous conductor temp. 90 °C XLPE rated
  Short-circuit temp. 250 °C Max 5 s duration
  Overload temp. 105 °C Short duration
  Ambient operating range -40 ~ +50 °C Outdoor / buried
  Laying temperature ≥ 0 °C Pre-heat below 0 °C
06 · Mechanical
  Min bending radius (fixed) ≥ 15 × OD ≈ 930 mm Armed MV cable
  Min bending radius (flexed) ≥ 20 × OD ≈ 1240 mm Repeated flexing
  Crush resistance Good — Steel tape armor
  Tensile strength Per GB/T 12701 — Installation pull
07 · Ampacity
  Air ampacity (3×150 Cu) ≈ 265 A 25 °C ambient (est.)
  Buried ampacity ≈ 245 A Direct burial, 25 °C soil
  Free air current ≈ 290 A Open tray
08 · Installation
  Laying methods Tray, direct burial, duct, trench — MV distribution
  Terminations MV cold-shrink / heat-shrink terminations — 8.7/15 kV rated
  Joints MV straight joints / branch joints — 8.7/15 kV rated
  Special tools MV jointing kits, torque wrenches — Qualified personnel only
09 · Packing
  Standard supply length 500 m / drum m MV cable on steel drums
  Reel / packing type Steel drum, sealed ends — Ends must be sealed
  Surface marking YJV22, 3×150, 8.7/15kV, GB/T 12701, metre marks — Continuous printing
  Storage conditions Dry, indoor, sealed ends — Protect from moisture
10 · Applications
  Typical use MV power distribution, compact transformer feeders, industrial substations, urban grid, building MV risers — Medium-voltage power
  Max system voltage 17.5 kV (Um) 8.7/15 kV rated
  Application level Medium voltage — Distribution grid

 

Test Parameters

 

Test Parameters — YJV22-3×150 mm² (8.7/15 kV)
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 0.124 Ω/km (Cu 150 mm²) Routine
2 Power-frequency withstand 25 kV AC, 5 min No breakdown Routine
3 Partial discharge test 12 kV, 5 min ≤ 10 pC Routine
4 Insulation resistance 5000 V DC ≥ 1500 MΩ·km Routine
5 Dielectric loss (tan δ) 90 °C, U0 voltage ≤ 0.0004 Type
6 Impulse voltage test 95 kV lightning impulse, 10 shots No breakdown Type
7 Bending test 15× OD, 3 cycles No damage Type
8 Dimensional check Micrometer / caliper OD ≈ 62 mm, XLPE ≈ 4.5 mm Routine
9 Heating cycle test 90 °C ↔ ambient, 10 cycles No damage Type
10 Torsion / armor check Visual + dimensional Steel tape intact Routine
11 Conductor continuity Per GB/T 3956 All 3 cores continuous Routine
12 Sheath thickness Micrometer PVC ≥ 2.2 mm Routine

 

Cable Cross Section Structure

 

YJV22 Medium Voltage Power Cable 3x150mm2 Copper Mv Armoured Cable 15kV

 

YJV22-3×150 mm² (8.7/15 kV) — Cross-Section Construction Diagram (Schematic)
Compact MV power cable: Cu conductors → XLPE insulation → Cu tape screen → inner PVC → double steel tape armor (22) → outer PVC · 8.7/15 kV · 90 °C · finished Ø ≈ 62 mm
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductors (×3) Compacted stranded copper, Class 2, 3 × 150 mm² — ≈ 14.5 R ≤ 0.124 Ω/km
2 Insulation screen Extruded semi-conducting + Cu tape ≈ 0.1 (Cu tape) — Partial discharge control
3 XLPE insulation Cross-linked polyethylene ≈ 4.5 ≈ 24 90 °C rated, 8.7/15 kV
4 Inner sheath (bedding) PVC over cored assembly ≈ 1.5 ≈ 55 Bed over cores
5 Steel tape armor (22) Double galvanized steel tape ≈ 2×0.5 ≈ 58 Mechanical / crush protection
6 Outer PVC sheath PVC ST2, black, UV-resistant ≈ 2.2 ≈ 62 (finished) Weather / UV protection
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 62 mm Overall    
Approx. cable mass ≈ 5800 kg/km Cu conductors + XLPE + armor + PVC    
Nominal voltage rating 8.7/15 kV Medium-voltage power    
Max system voltage (Um) 17.5 kV Temporary overvoltage    
Max continuous conductor temp. 90 °C XLPE rated    
Short-circuit temp. 250 °C Max 5 s    
Min bending radius (fixed) ≥ 15 × OD ≈ 930 mm Armed MV cable    
DC resistance @ 20 °C ≤ 0.124 Ω/km Cu 150 mm²    
Routine test voltage (AC) 25 kV / 5 min — Power-frequency withstand    
Partial discharge ≤ 10 pC at 12 kV — MV requirement    
Air ampacity @ 25 °C ≈ 265 A 3 cores loaded (est.)    
Buried ampacity ≈ 245 A Direct burial    
Armor type Double steel tape (22) — Mechanical protection    
Conductor material Copper — High current density    
Schematic — not to exact scale. Finished Ø ≈ 62 mm and weight ≈ 5800 kg/km from cross-referenced industry samples. YJV22-3×150 is a compact medium-voltage (8.7/15 kV) XLPE-insulated, steel-tape-armored, copper-conductor power cable. Compared to YJLV22-3×400 (8.7/10 kV, aluminum conductor, 400 mm², Ø85 mm, 6200 kg/km, 410 A), this cable uses copper conductors (higher current density, smaller footprint), a higher voltage rating (8.7/15 kV vs 8.7/10 kV), and a smaller overall diameter (Ø62 mm vs Ø85 mm). It is designed for compact MV distribution where space is constrained. Values marked (est.) require confirmation against the factory test certificate.

 

Construction Description

 

Construction Description — YJV22-3×150 mm² (8.7/15 kV compact MV armored cable)
Layer-by-layer MV power cable: Cu conductors / XLPE insulation / Cu tape screen / inner PVC / double steel tape armor / outer PVC · 8.7/15 kV · 90 °C · finished Ø ≈ 62 mm
1. Product Identity & Ratings
YJV22-3×150 is a compact medium-voltage (8.7/15 kV) XLPE-insulated, steel-tape-armored, copper-conductor power cable built and tested per GB/T 12701 / IEC 60840. It has 3 copper conductors (150 mm² each, L1/L2/L3), XLPE insulation with copper tape screening, inner PVC bedding, double steel tape armor, and outer PVC sheath. Rated 90 °C continuous. Compared to YJLV22-3×400 (aluminum, 400 mm², 8.7/10 kV, Ø85 mm), this cable uses copper for higher current density in a smaller footprint. Finished Ø ≈ 62 mm, mass ≈ 5800 kg/km, steel drums.
2. Copper Conductors (3×150)
The 3 conductors use 150 mm² compacted stranded copper (R ≤ 0.124 Ω/km). Copper has ~60% higher conductivity than aluminum, so 150 mm² Cu carries similar current to ~240 mm² Al. This makes the cable more compact — Ø62 mm vs Ø85 mm for the aluminum 400 mm² version. Copper is preferred where installation space is limited.
3. XLPE Insulation & Copper Tape Screen
XLPE insulation ≈ 4.5 mm thick, rated 90 °C. The 8.7/15 kV rating means U0 = 8.7 kV phase-to-ground, U = 15 kV phase-to-phase. Over the insulation is a semi-conducting layer plus copper tape screen (≈ 0.1 mm) to control the electrical field and prevent partial discharge. Routine test voltage is 25 kV / 5 min.
4. Steel Tape Armor (22)
Double galvanized steel tape (≈ 2×0.5 mm) over inner PVC bedding provides crush protection. The '22' designation means inner PVC + double steel tape + outer PVC. This is standard for MV cables buried in trenches or ducts. The armor does not carry current — it is purely mechanical protection.
5. Site Handling & Operational Notes
• Bend radius 15×OD (≈ 930 mm) fixed.  • Use MV cold-shrink / heat-shrink terminations rated 8.7/15 kV.  • 25 kV AC routine withstand test.  • Partial discharge ≤ 10 pC at 12 kV.  • At 5800 kg/km, supplied on heavy steel drums.  • Store with ends sealed.  • For compact MV distribution, building risers, industrial substations.

 

8. Standards & Conformity. GB/T 12701 (MV plastic-insulated power cables); IEC 60840 (XLPE MV cables); GB/T 3956 (conductors). Rated 8.7/15 kV (Um = 17.5 kV).

 

9. Packaging, Storage & Logistics. 500 m per steel drum with sealed ends. Continuous marking: YJV22, 3×150, 8.7/15 kV, GB/T 12701, metre marks. Store dry, indoor, ends sealed.

 

YJV22 Medium Voltage Power Cable 3x150mm2 Copper Mv Armoured Cable 15kV

 

10. Procurement Specification. State "YJV22-3×150, 8.7/15 kV" + length. Order matching MV terminations/joints rated 8.7/15 kV. Confirm against factory test certificate (including partial discharge report).

 

11. Cable Industry FAQ.

  • Q1: What is the difference between YJV22-3×150 (8.7/15 kV) and YJLV22-3×400 (8.7/10 kV)? YJV22 uses copper conductors (150 mm², Ø62 mm, 265 A, 25 kV test), while YJLV22 uses aluminum conductors (400 mm², Ø85 mm, 410 A, 21 kV test). Copper has higher conductivity per area, so 150 mm² Cu carries similar current to ~240 mm² Al. The 8.7/15 kV rating is also higher than 8.7/10 kV.
  • Q2: When do I choose 8.7/15 kV instead of 8.7/10 kV? 8.7/15 kV is used in systems where the phase-to-phase voltage can reach 15 kV (e.g., 10 kV nominal with high system voltage). The higher rating provides extra margin for temporary overvoltages.
  • Q3: Why use copper instead of aluminum? Copper has ~60% higher conductivity than aluminum, so a copper 150 mm² cable is physically smaller (Ø62 mm) than an aluminum 400 mm² cable (Ø85 mm) while carrying similar current. Choose copper where space is limited; choose aluminum where long-distance cost matters.
  • Q4: What does "22" mean? 22 = inner PVC bedding + double steel tape armor + outer PVC sheath. Standard for buried or duct-installed MV cables.
  • Q5: What is the routine test voltage for 8.7/15 kV? 25 kV AC for 5 minutes — higher than the 8.7/10 kV version (21 kV), because the insulation is thicker (4.5 mm vs 5.5 mm for the 10 kV class, but rated higher U0).
  • Q6: What is partial discharge? Tiny electrical sparks inside the insulation at defects. MV cables must have ≤ 10 pC at rated voltage to ensure long life. Excessive partial discharge leads to insulation breakdown.
  • Q7: Can YJV22 be used outdoors? Yes — the outer PVC sheath is UV-resistant. For direct burial, the steel tape armor provides crush protection.
  • Q8: What bending radius is required? 15×OD ≈ 930 mm for fixed installation. Smaller than the 400 mm² version (1275 mm) because the overall diameter is smaller.
  • Q9: What is the impulse voltage test level? 95 kV lightning impulse — higher than the 8.7/10 kV version (75 kV), because the 8.7/15 kV insulation must withstand higher surge voltages.
  • Q10: Can YJV22 be used for fire pump circuits? No — YJV22 is not fire-resistant. Fire pump circuits must use mineral-insulated fire cables (BTTRZ/BTLY). YJV22 is for standard MV power distribution.
  • Q11: How is the cable terminated? MV cold-shrink or heat-shrink terminations rated 8.7/15 kV. The termination must carefully strip the XLPE insulation, insulation screen, and conductor screen in the correct order. Only trained personnel should terminate MV cables.