XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV

XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
YJLV22-3*50mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV Cable Designation & Meaning Code Meaning YJ XLPE (cross-linked polyethylene) insulation L Aluminium conductor​ (Al) V PVC inner bedding / outer sheath 22 Steel tape armour (double steel tape, overlapping) + PVC sheath 8.7/10 kV ...

Product Details

Highlight:

xlpe heavy aluminum cable

,

xlpe medium voltage power cable

,

aluminum medium voltage power cable

Conductor (×3):
Aluminium, Class 2 Stranded Circular, Typical 19×∅1.82 Mm (50 Mm²), Conductor Ø ≈ 9.1–10.2 Mm
Conductor screen:
Extruded Semi-conductive Compound (XLPE-based)
Insulation:
XLPE (cross-linked Polyethylene), Nominal Thickness 4.5 Mm​ (8.7/10 KV & 8.7/15 KV)
Insulation screen:
Extruded Semi-conductive Compound (strippable Or Bonded)
Metallic screen (per core):
Copper Tape, Copper Wire, Or Combined Copper Tape + Wire, Min. Cross-section 16 Mm² (typically 1×0.1 Mm Copper Tape Overlapping)
Filler & bedding:
PVC Filler + PVC Inner Bedding (tape Wrap Or Extruded), Thickness ≈ 1.5 Mm
Armour:
Double Steel Tape, 0.5 Mm × 2
Outer sheath:
PVC (polyvinyl Chloride), Nominal Thickness 2.5 Mm (typical), Color: Black
Conductor nominal area:
50 Mm² (Al)
Number of cores:
3
Conductor material:
Aluminium (Al)
Conductor class:
Class 2 Stranded
Conductor construction:
19×∅1.82 Mm (typical)
Conductor diameter (approx.):
9.1–10.2 Mm
Conductor screen thickness:
0.5 Mm
Insulation thickness:
4.5 Mm
Insulation screen thickness:
0.5 Mm
Diameter over insulated core (approx.):
16.1–18.2 Mm
Metallic screen:
Copper Tape 0.1 Mm Overlapping
Inner bedding thickness:
1.5 Mm
Outer sheath thickness:
2.5 Mm
Overall cable diameter:
47 – 55 Mm
Design outer diameter:
≈ 50.5 Mm
Approx. weight:
4.0 – 5.2 Kg/m (4000–5200 Kg/km)
Design weight:
≈ 4600 Kg/km

Product Description

XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV

Cable Designation & Meaning

Code

Meaning

YJ

XLPE (cross-linked polyethylene) insulation

L

Aluminium conductor​ (Al)

V

PVC inner bedding / outer sheath

22

Steel tape armour (double steel tape, overlapping) + PVC sheath

8.7/10 kV

Rated voltage U₀/U = 8.7/10 kV; Uₘ = 12 kV

8.7/15 kV

Rated voltage U₀/U = 8.7/15 kV; Uₘ = 17.5 kV

3×50 mm²

Three power cores, each 50 mm² aluminium (3-core, no neutral, no PE)


Construction: XLPE insulated, aluminium conductor, steel-tape armoured, PVC sheathed, three-core medium-voltage power cable.

Applicable Standards

  • GB/T 12706.2-2020 / IEC 60502-2 — Power cables with extruded insulation and their accessories for rated voltages from 6 kV up to 30 kV
  • GB/T 3956 / IEC 60228 — Conductors (Class 2 stranded circular, aluminium)
  • GB/T 2951 / IEC 60811 — Insulating and sheathing materials — Common test methods
  • GB/T 3048 — Test methods for electric cables
  • GB/T 18380 / IEC 60332 — Flame retardant tests (Category C or B available)


XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV


XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV


YJLV22-3×50 mm² 8.7/10 kV (and 8.7/15 kV) — Cable Specification & Engineering Data 

1. Product Overview & Rating Summary. YJLV22-3×50 is a mid-to-large size medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 50 mm² compacted-stranded ALUMINIUM conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The "L" in YJLV22 distinguishes the aluminium conductor from the copper YJV22 — same insulation and armour system, but at roughly one-third the weight and one-third the conductor cost. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV distribution feeders serving 1600–2500 kVA distribution transformers and MV motors in the 630–1000 kW range. Finished diameter is about 65 mm (10 kV) and nominal mass about 4800 kg/km (≈ 480 kg per 100 m). With all three cores loaded, the cable carries about 150 A in free air at 25 °C (engineering estimate).


2. Layer-by-Layer Construction (Conductor to Outer Jacket).

Layer Construction Wall Diameter
Conductor (Al) ×3 Compacted stranded annealed Al, Class 2 — 19×1.78 mm equivalent — ≈ 10.0 mm
Conductor screen Extruded semi-conducting XLPE, co-extruded ≈ 0.8 mm ≈ 11.6 mm
XLPE insulation Cross-linked polyethylene, triple-extruded 4.5 mm (10 kV) / 5.5 mm (15 kV) ≈ 21.2 / ≈ 23.2 mm
Insulation screen Strippable semi-conducting XLPE ≈ 0.8 mm ≈ 22.8 / ≈ 24.8 mm
Copper-tape screen 0.1 × 16 mm annealed Cu tape, lapped ≈ 0.1 mm tape ≈ 23.0 / ≈ 25.0 mm
Filler & bedding PP/PE rope + non-woven binder — ≈ 56 / ≈ 59 mm bundle
Inner sheath PVC/PE extruded bedding ≈ 1.2 mm ≈ 58 / ≈ 61 mm
Steel armour (type 22) Double galvanised steel tape, helical lapped 2 × 0.3 mm ≈ 59 / ≈ 62 mm
PVC outer jacket ST2 PVC, flame-retardant, black 2.2 mm ≈ 65 / ≈ 68 mm (finished)


3. Electrical Characteristics. Each 50 mm² aluminium conductor is held to a maximum DC resistance of 0.641 Ω/km at 20 °C — about 26% lower resistance than the 35 mm² aluminium version, which translates directly into higher ampacity and lower voltage drop on long MV runs. Every length survives the routine 21.5 kV AC power-frequency proof held for five minutes (30.5 kV for the 15 kV grade). Partial discharge at 1.5 U0 must not exceed 20 pC. Dissipation factor tan δ ≤ 0.001 at U0. Insulation resistance ≥ 1000 MΩ·km, typical capacitance ≈ 0.62 μF/km. Impulse withstand (BIL) is 75 kV for the 10 kV grade and 95 kV for the 15 kV grade. With all three cores energised, reference loading is about 150 A in free air at 25 °C, about 145 A direct-buried.

Dimensional Data

Item

Typical value

Remarks

Conductor nominal area

50 mm² (Al)

3 cores

Number of cores

3

—

Conductor material

Aluminium (Al)

—

Conductor class

Class 2 stranded

IEC 60228 / GB/T 3956

Conductor construction

19×∅1.82 mm (typical)

circular stranded

Conductor diameter (approx.)

9.1–10.2 mm

—

Conductor screen thickness

0.5 mm

semi-conductive

Insulation thickness

4.5 mm

XLPE, 8.7/10 kV & 8.7/15 kV

Insulation screen thickness

0.5 mm

semi-conductive

Diameter over insulated core (approx.)

16.1–18.2 mm

—

Metallic screen

Copper tape 0.1 mm overlapping

per core

Inner bedding thickness

1.5 mm

PVC

Armour

Double steel tape, 0.5 mm × 2

overlapping

Outer sheath thickness

2.5 mm

PVC, black

Overall cable diameter

47 – 55 mm

round profile

Design outer diameter

≈ 50.5 mm

common Chinese maker value

Approx. weight

4.0 – 5.2 kg/m (4000–5200 kg/km)

typical ≈ 4600 kg/km

Design weight

≈ 4600 kg/km

Al conductor is ~55% lighter than Cu equivalent

Cable shape

Round

—

Insulation Data

Property

Value

Material

XLPE (cross-linked polyethylene)

Nominal thickness

4.5 mm

Long-term service temp.

90 °C

Short-circuit temp. (≤5 s)

250 °C​ (Al conductor limit per IEC 60228)

Emergency overload temp.

130 °C

Routine test voltage (AC, 5 min)

22 kV (8.7/10 kV); 30.5 kV (8.7/15 kV)

Type-test voltage (AC)

30 kV (8.7/10 kV); 45 kV (8.7/15 kV)

Partial discharge test

≤ 10 pC at 1.73 U₀ (15 kV)

Tan δ (dissipation factor)

≤ 0.004 at 20 °C

Electrical Parameters

Parameter

Value (8.7/10 kV)

Value (8.7/15 kV)

Note

Rated voltage U₀/U

8.7 / 10 kV

8.7 / 15 kV

—

Max. system voltage Uₘ

12 kV

17.5 kV

—

Test voltage AC (5 min)

22 kV

30.5 kV

Routine

Type-test voltage

30 kV

45 kV

—

DC resistance @20 °C

≤ 0.641 Ω/km

≤ 0.641 Ω/km

GB/T 3956 Class 2 Al max, 50 mm²

AC resistance @90 °C (est.)

≈ 0.817 Ω/km

≈ 0.817 Ω/km

per core

Capacitance (approx.)

≈ 0.27 µF/km

≈ 0.27 µF/km

per core to screen

Inductive reactance (approx.)

≈ 0.11 Ω/km

≈ 0.11 Ω/km

at 50 Hz, 3-core

Current rating in air (30 °C)

≈ 125 – 145 A

≈ 125 – 145 A

per core, 3-core (Al)

Current rating buried (20 °C)

≈ 110 – 130 A

≈ 110 – 130 A

direct buried, 3-core

Short-circuit current (1 s, Al, 250 °C)

≈ 5.0 kA (5000 A)

≈ 5.0 kA (5000 A)

50 mm² Al

Frequency

50/60 Hz AC

50/60 Hz AC

—

Reference values: 50 mm² Al at 135 A, 3-phase 10 kV → max balanced load ≈ 2.34 MVA. Voltage drop at 135 A ≈ 11.0 V/km per core (≈0.110% per 100 m).

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C (Al conductor)

Emergency overload temp.

130 °C

Min. installation ambient temp.

0 °C (PVC sheath); below 0 °C pre-heating required

Service ambient range

−20 °C to +90 °C (with PVC sheath)

Fire survival

Standard (non-fire-rated); optional fire-resistant version available (ZC-YJLV22)


4. Thermal Response & Flame Behaviour. XLPE insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −20 and +50 °C. PVC jacket provides flame-retardant performance per GB/T 18380.34 class A. Short-circuit rating at 250 °C for 1 s is about 3.4 kA for the 50 mm² aluminium conductor — about 40% higher than the 35 mm² version, though still well below copper of equivalent cross-section. Thermal resistance of reference burial soil is 1.2 K·m/W.

Fire Performance (YJLV22 — Standard)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 Category C (ZC), Category B (ZB) available

Halogen content

Contains halogen (PVC sheath)

Smoke density

Standard (non-low-smoke)

Corrosivity

Corrosive (PVC sheath)

Fire survival (circuit integrity)

Not applicable (standard version); use ZA-YJLV22 for flame-retardant A


5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 975 mm for this size. The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice. Critically, the aluminium conductors must be terminated with bimetallic Al-Cu lugs — direct contact between aluminium and copper in the presence of moisture causes galvanic corrosion and joint failure. MV heat-shrink or cold-shrink termination kits are mandatory. Laying temperature must not fall below 0 °C. At about 480 kg per 100 m, this lightweight cable is still manageable on site, but the larger conductor requires properly rated pulling gear and drum jacks.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 758 mm at Ø50.5 mm

static installation

Max. pulling tension

3000 N

Al conductor has ~60% of Cu tensile strength; use proper pulling grips

Direct burial

Suitable

steel tape armour provides mechanical protection

Conduit ID

≥ 1.5 × OD → ≥ 76 mm; use 80 mm or 100 mm

—

Fixing

cable clamps, steel straps

—

Impact resistance

High

steel tape armour absorbs mechanical shock

Water resistance

Moisture-resistant (PVC sheath + inner bedding)

not fully watertight; use YJLV32 for wet locations

Armour type

Double steel tape, overlapping

galvanized or mill finish

Armour short-circuit rating

≈ 5 kA (1 s, steel tape)

—

Termination note

Al conductors require Al-compatible lugs​ (bimetallic or Al-Cu transition)

critical for installation


6. Typical Service Applications. This YJLV22-3×50 aluminium MV cable is the mid-to-large cost-effective choice for 10 kV / 15 kV distribution feeders where mechanical strength and burial protection are needed and loads are significant: 1600–2500 kVA distribution transformer primary feeds in industrial parks, suburban commercial districts and larger rural networks, 10 kV branch feeds to medium industrial plants and workshops, MV motor branch feeds for motors in the 630–1000 kW range (large pumps, fans, compressors, machine-tool drives, woodworking and textile mill drives), township and county 10 kV overhead-to-underground transition feeders, residential-commercial estate and hospital 10 kV incoming mains, municipal water-supply and wastewater 10 kV supply lines, medium-to-large PV / solar-farm 10 kV collection laterals, mining auxiliary 10 kV power supplies, and any circuit where the lightweight aluminium conductor reduces installation and support-structure costs relative to copper. Approved installation methods include direct burial, cable tray, concrete duct, and indoor MV cable trench.


XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV


7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance ≤ 0.641 Ω/km at 20 °C, the 21.5 kV AC / 5 min withstand (30.5 kV for 15 kV grade), partial discharge ≤ 20 pC at 1.5 U0, tan δ ≤ 0.001, insulation resistance ≥ 1000 MΩ·km, conductor continuity across all three cores, steel-armour and copper-screen continuity, and dimensional inspection. Sample and type tests comprise impulse withstand at ±75 kV (or ±95 kV for 15 kV), heating-cycle load-loss test, bending at 15 × OD, short-circuit to 250 °C, flame spread GB/T 18380.34 class A, and voltage re-test after thermal ageing. A factory test certificate accompanies each drum.


Cable Parameters


YJLV22-3×50 mm² 8.7/10 kV (and 8.7/15 kV variant) — Full Parameter Sheet 
Medium-voltage power cable · ALUMINIUM conductor / XLPE insulation / copper-tape screen / double-steel-tape armour (type 22) / PVC outer sheath · per GB/T 12706.2 · 3 cores · finished Ø ≈ 65 mm (10 kV) / ≈ 68 mm (15 kV)
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type YJLV22 — Al conductor / XLPE insulation / double-steel-tape armour / PVC outer sheath

Rated voltage (U0/U) 8.7/10 kV AC 50 Hz; Um = 12 kV (10 kV grade)

Alternative voltage grade 8.7/15 kV AC 50 Hz; Um = 17.5 kV (15 kV grade) — thicker XLPE

Number of cores 3 × 50 — 3 phase cores (50 mm²) — no separate neutral in MV cable

Conductor material Compacted stranded ALUMINIUM — Class 2 stranded per GB/T 3956; lighter, lower cost than Cu

Conductor screen Extruded semi-conducting XLPE — Conductor screen layer (radial field control)

Insulation material Cross-linked polyethylene (XLPE) — 90 °C continuous, 250 °C short-circuit

Insulation screen Extruded semi-conducting, strippable — Outer screen layer

Metallic screen Copper tape, lapped — 0.1 × 16 mm Cu tape; equipotential earth

Armour Double galvanised steel tape — Type 22 armour — mechanical protection

Outer sheath PVC (ST2), flame-retardant — UV- and abrasion-resistant

Standard reference GB/T 12706.2 / IEC 60502-2; GB/T 3956 — Medium-voltage power cables 1.8/3 kV to 26/35 kV
02 · Conductor (Aluminium)

Stranding — 50 mm² Compacted stranded aluminium — Class 2, circular compacted

Strand count (typical) 19 × 1.78 mm (or equivalent) — Compacted after stranding

Conductor diameter ≈ 10.0 mm After compacting (est.)

DC resistance @ 20 °C ≤ 0.641 Ω/km Maximum per GB/T 3956 Class 2 (Al)

AC resistance @ 50 Hz (≈ 90 °C) ≈ 0.92 Ω/km Skin/proximity effect included

Conductor screen thickness ≈ 0.8 mm Extruded semi-conducting layer

Conductor weight per km ≈ 136 kg/km Aluminium density 2.70 g/cm³
03 · Insulation

Insulation type Cross-linked polyethylene (XLPE) — Extruded, triple-layer co-extrusion

Insulation thickness — 8.7/10 kV 4.5 mm Nominal, per GB/T 12706.2

Insulation thickness — 8.7/15 kV 5.5 mm Thicker for 15 kV grade

Core Ø over insulation — 10 kV ≈ 21.2 mm 10.0 + 2×(0.8+4.5+0.8)

Core Ø over insulation screen — 15 kV ≈ 23.2 mm 10.0 + 2×(0.8+5.5+0.8)

Insulation screen thickness ≈ 0.8 mm Strippable semi-conducting

Impulse withstand (BIL) — 10 kV 75 kV Lightning impulse test

Impulse withstand (BIL) — 15 kV 95 kV Lightning impulse test
04 · Metallic Screen & Filler

Screen material Annealed copper tape — Lapped with overlap

Screen tape dimensions 0.1 × 16 mm Two layers lapped (typical)

Screen function Equipotential earth / fault-current path — Earthed at terminations

Filler material PP / jute rope, flame-retardant — Fills interstices for round cable

Bedding / binder tape Semi-conducting or non-woven tape — Holds bundle; anti-corrosion layer

Assembled bundle Ø — 10 kV ≈ 56 mm Before inner sheath (est.)

Assembled bundle Ø — 15 kV ≈ 59 mm Before inner sheath (est.)
05 · Inner Sheath & Armour

Inner sheath / bedding PVC or PE extruded — Corrosion barrier under armour

Inner sheath thickness ≈ 1.2 mm Over bundle

Armour type Double steel tape (type 22) — Double-tape helical armour

Armour tape thickness 2 × 0.3 mm Galvanised steel, lapped

Armour function Mechanical protection against crush / impact — Permits direct burial / tray

Armour diameter — 10 kV ≈ 59 mm Over inner sheath (est.)
06 · Outer Sheath

Jacket material PVC, ST2, flame-retardant — GB/T 12706.1

Jacket thickness 2.2 mm Minimum over armour

Overall finished diameter — 10 kV ≈ 65 mm Cross-referenced industry sample

Overall finished diameter — 15 kV ≈ 68 mm Thicker insulation version

Approx. cable mass — 10 kV ≈ 4800 kg/km Al + XLPE + steel + PVC (lightweight)

Approx. cable mass — 15 kV ≈ 4950 kg/km Heavier due to thicker insulation

Jacket colour Black (standard) — UV-resistant carbon-black PVC

Mass per 100 m — 10 kV ≈ 480 kg/100 m For drum loading
07 · Electrical

Rated voltage U0/U 8.7/10 kV AC 50 Hz; Um = 12 kV

Maximum system voltage Um (10 kV) 12 kV —

DC resistance @ 20 °C ≤ 0.641 Ω/km 50 mm² Al Class 2

Insulation resistance ≥ 1000 MΩ·km XLPE at 20 °C

Capacitance (typical) ≈ 0.62 μF/km Per core (est.)

Dissipation factor tan δ (at U0) ≤ 0.001 — XLPE, 20 °C

Routine test voltage (AC) — 10 kV 21.5 kV / 5 min — Power-frequency withstand

Routine test voltage (AC) — 15 kV 30.5 kV / 5 min — Power-frequency withstand

Air ampacity @ 25 °C ≈ 150 A 3 cores loaded, Al, in free air (est.)

Buried ampacity @ 25 °C soil ≈ 145 A 3 cores loaded, Al, direct burial (est.)
08 · Thermal & Fire

Max continuous conductor temp. 90 °C Normal service

Short-circuit temp. (≤ 5 s) 250 °C XLPE limit

Fire behaviour Flame-retardant (PVC jacket) — GB/T 18380.34 class A

Service ambient range −20 to +50 °C Fixed installation

Thermal resistance (soil) 1.2 K·m/W Reference burial conditions

Short-circuit rating (1 s) ≈ 3.4 kA 50 mm² Al at 250 °C
09 · Installation

Min bending radius ≥ 15 × OD ≈ 975 mm Fixed installation (armoured)

Laying temperature ≥ 0 °C Pre-heat below 0 °C

Laying methods Tray, direct burial, conduit, duct — Armour permits direct burial

Armour earthing Both ends earthed — Steel armour must be earthed

Copper screen earthing At both ends (or single point for cross-bonding) — MV cable screen bonding

Termination / joints Al-Cu transition lugs required — Al conductor — use bimetallic lugs to avoid galvanic corrosion

Special tools Cable cutter, crimping tool, torque wrench — MV lugs required
10 · Packing

Standard supply length 500 or 1000 m/drum Custom cut lengths available

Reel / packing type Wooden-steel drum — Sealed ends against moisture

Surface marking YJLV22, 8.7/10 kV, 3×50, supplier, year, metre marks — Per GB/T 6995

Storage conditions Dry, covered, −20 to +40 °C — Sealed ends; protect from UV

Transport Drums secured against rolling — Light cable, easy to handle


Cable Test Parameters


Test Parameters — YJLV22-3×50 mm² 8.7/10 kV (and 8.7/15 kV)
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3048.4, 20 °C ≤ 0.641 Ω/km (50 mm² Al) Routine
2 Power-frequency withstand (routine) 21.5 kV AC, 5 min (10 kV grade) No breakdown Routine
3 Power-frequency withstand (15 kV grade) 30.5 kV AC, 5 min No breakdown Routine
4 Partial discharge test At 1.5 U0 = 13 kV (10 kV grade) ≤ 20 pC at 1.73 U0 Routine
5 Dissipation factor tan δ At U0, 20 °C tan δ ≤ 0.001 Routine
6 Insulation resistance GB/T 3048.5 ≥ 1000 MΩ·km Routine
7 Dimensional check Micrometer / micrometer microscope Insulation ≥ 4.5 mm (10 kV); jacket ≥ 2.2 mm Routine
8 Impulse voltage test (BIL) ±75 kV, 10 impulses (10 kV grade) No breakdown at 75 kV Type
9 Impulse voltage test (15 kV grade) ±95 kV, 10 impulses No breakdown at 95 kV Type
10 Heating cycle / load loss 3 cycles U0 + rated current No damage; tan δ stable Type
11 Bending test 15 × OD mandrel, 3 cycles No damage to insulation or sheath Type
12 Short-circuit temperature test 250 °C, 5 s equivalent No insulation collapse Type
13 Flame propagation GB/T 18380.34 class A No vertical flame spread Type
14 Sheath / armour continuity Continuity meter Steel armour and Cu tape continuous Routine
15 Voltage test after ageing After thermal ageing cycle Withstands 2.5 U0 AC Type
16 Marking legibility Visual + rubbing YJLV22 / 8.7/10 kV / 3×50 / metre marks legible Routine


Cable Cross Section Structure


XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV


YJLV22-3×50 mm² 8.7/10 kV — Cross-Section Construction Diagram (Schematic)
MV layered build-up: ALUMINIUM conductor → conductor screen → XLPE insulation → insulation screen → Cu-tape screen → filler → bedding → double-steel-tape armour → PVC jacket · 8.7/10 kV (8.7/15 kV variant noted) · finished Ø ≈ 65 mm
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Al) ×3 Compacted stranded ALUMINIUM, Class 2 — 19×1.78 mm equivalent per core — ≈ 10.0 Power conductor; R ≤ 0.641 Ω/km at 20 °C
2 Conductor screen Extruded semi-conducting XLPE, co-extruded with insulation ≈ 0.8 ≈ 11.6 Eliminates air gaps; smooth radial field
3 XLPE insulation Cross-linked polyethylene, triple-layer co-extrusion 4.5 (10 kV) / 5.5 (15 kV) ≈ 21.2 / ≈ 23.2 Main dielectric; 90 °C continuous
4 Insulation screen Strippable semi-conducting XLPE ≈ 0.8 ≈ 22.8 / ≈ 24.8 Outer screen; equipotential
5 Copper-tape screen Annealed Cu tape, lapped, 0.1 × 16 mm ≈ 0.1 tape ≈ 23.0 / ≈ 25.0 Earth path / fault-current return
6 Filler & bedding PP/PE rope filler + non-woven binder tape — ≈ 56 / ≈ 59 bundle Round shape; anti-corrosion bedding
7 Inner sheath PVC/PE extruded bedding over bundle ≈ 1.2 ≈ 58 / ≈ 61 Corrosion barrier under armour
8 Steel armour (type 22) Double galvanised steel tape, helically lapped 2 × 0.3 ≈ 59 / ≈ 62 Mechanical crush / impact protection
9 PVC outer jacket ST2 PVC, flame-retardant, black 2.2 ≈ 65 / ≈ 68 (finished) UV, abrasion and chemical protection
Key Dimensions & Properties (expanded)
Finished cable diameter (10 kV) ≈ 65 mm Cross-referenced industry sample

Finished cable diameter (15 kV) ≈ 68 mm Thicker XLPE variant

Approx. cable mass (10 kV) ≈ 4800 kg/km Al + XLPE + steel + PVC (lightweight)

Approx. cable mass (15 kV) ≈ 4950 kg/km Heavier due to thicker insulation

Nominal voltage rating 8.7/10 kV AC 50 Hz; Um = 12 kV

Alternative voltage grade 8.7/15 kV Um = 17.5 kV; 5.5 mm XLPE

Max continuous conductor temp. 90 °C Normal service

Short-circuit temp. (≤5 s) 250 °C XLPE limit

Impulse withstand (BIL) 75 (10 kV) / 95 (15 kV) kV Lightning impulse

Min bending radius ≥ 15 × OD ≈ 975 mm Fixed installation

DC resistance @ 20 °C ≤ 0.641 Ω/km 50 mm² Al

Insulation resistance ≥ 1000 MΩ·km XLPE

Routine test voltage 21.5 kV AC / 5 min — 10 kV grade; 30.5 kV for 15 kV

Air ampacity @ 25 °C ≈ 150 A 3 cores loaded, Al (est.)

Mass per 100 m (10 kV) ≈ 480 kg/100 m For drum loading

Schematic — not to exact scale. Finished Ø ≈ 65 mm (10 kV) and weight ≈ 4800 kg/km from cross-referenced industry samples; conductor/insulation diameters per GB/T 12706.2 and GB/T 3956; ampacity 150 A is an engineering estimate for ALUMINIUM conductors. The 8.7/15 kV variant uses 5.5 mm XLPE insulation, ≈ 68 mm OD and ≈ 4950 kg/km. Values marked (est.) require confirmation against the factory test certificate. Al conductors require bimetallic Al-Cu lugs at terminations.


Cable Construction Description


Construction Description — YJLV22-3×50 mm² 8.7/10 kV 
Layer-by-layer MV build-up narrative · 8.7/10 kV (and 8.7/15 kV variant) · ALUMINIUM / triple-extruded XLPE / Cu-tape screen / double-steel-tape armour / PVC jacket · finished Ø ≈ 65 mm
1. Product Identity & Ratings
YJLV22-3×50 is a mid-to-large size medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 50 mm² compacted-stranded ALUMINIUM conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The 'L' in YJLV22 distinguishes the aluminium conductor from copper (YJV22). The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV distribution feeders serving 1600–2500 kVA distribution transformers and MV motors in the 630–1000 kW range. Finished diameter is about 65 mm (10 kV) and nominal mass about 4800 kg/km (≈ 480 kg per 100 m). With all three cores loaded, the cable carries about 150 A in free air at 25 °C (engineering estimate).
2. Aluminium Conductor & Screens
Each 50 mm² conductor is compacted-stranded aluminium (Class 2), with a strand-lay diameter of about 10.0 mm and DC resistance ≤ 0.641 Ω/km at 20 °C — roughly 26% lower resistance than the 35 mm² aluminium version. Aluminium is roughly one-third the weight of copper and one-third the cost, but it has roughly 60% lower conductivity — hence the larger cross-section needed for a given current. A semi-conducting conductor screen (≈ 0.8 mm) is co-extruded directly over the aluminium to eliminate air gaps and smooth the electric field. The conductor screen bonds electrically to the aluminium.
3. XLPE Insulation
Cross-linked polyethylene (XLPE) is extruded in a triple-layer co-extrusion process: conductor screen → XLPE insulation → insulation screen, all in one pass to avoid contamination. For the 8.7/10 kV grade the insulation thickness is 4.5 mm; for the 8.7/15 kV grade it is 5.5 mm. XLPE sustains 90 °C continuous conductor temperature and 250 °C short-circuit for ≤ 5 s. The outer insulation screen is strippable for termination work. Over the insulation screen a 0.1 × 16 mm copper tape is lapped to provide an equipotential earth and fault-current return path.
4. Bedding, Steel Armour & PVC Jacket
Three screened cores are cabled round with PP/PE rope filler and a non-woven binder tape, giving a bundle of about 56 mm (10 kV). A PVC/PE inner bedding (≈ 1.2 mm) is extruded over the bundle, then a double layer of 0.3 mm galvanised steel tape is helically lapped — this is the type-22 armour that protects against crush and impact and permits direct burial. Finally a 2.2 mm black PVC (ST2) outer jacket is extruded over the armour to the ≈ 65 mm finish, providing UV, abrasion and chemical resistance.
5. Site Handling & Operational Notes
• Observe the 15 × OD minimum bending radius (≈ 975 mm).  • The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice.  • Use bimetallic Al-Cu lugs at all terminations — direct Al-to-Cu contact causes galvanic corrosion.  • Service ambient −20 to +50 °C; conductor up to 90 °C continuous.  • Routine test 21.5 kV AC / 5 min (10 kV); impulse withstand 75 kV.  • At ≈ 480 kg/100 m, this light cable is still manageable on site, but the larger conductor requires properly rated pulling gear.


8. Factory Advantages


XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV


9. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type (YJLV22), voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +40 °C, shielded from direct sunlight and moisture; drum end seals must remain intact until installation. MV cable terminations and joints should be scheduled immediately after laying to avoid prolonged exposure of the cut aluminium ends.


XLPE Aluminum Power Cable YJLV22 3x50mm² 8.7/15kV Armored 3 Core MV


10. Procurement Specification. State "YJLV22-8.7/10 kV-3×50" (or "YJLV22-8.7/15 kV-3×50" for the thicker-insulation grade) together with the required length or drum arrangement. Always order bimetallic Al-Cu lugs and MV termination kits at both ends — do not substitute pure copper lugs on aluminium conductors. Always request the factory test certificate, which must include the partial-discharge and impulse-withstand reports, to confirm the actual diameter, weight and conductor resistances for the production batch.


11. Cable Industry FAQ.

  • Q1: How does 50 mm² aluminium compare to 35 mm² aluminium? 50 mm² raises the reference ampacity from about 115 A to about 150 A (+30%), and lowers the DC resistance from 0.868 Ω/km to 0.641 Ω/km (−26%). It is the standard upgrade when the load grows beyond the 1000–1600 kVA transformer band and enters the 1600–2500 kVA range, or when voltage-drop on long 10 kV laterals becomes binding. Weight rises from 3700 to 4800 kg/km, still far lighter than an equivalent copper cable.
  • Q2: Why choose aluminium (YJLV22) over copper (YJV22)? Aluminium costs roughly one-third of copper per metre at the same cross-section and weighs roughly one-third, which reduces both material cost and installation labour for long MV runs. The trade-off is higher resistance — for the same ampacity you typically need to upsize by one or two cross-section steps. For moderately-loaded suburban, industrial-park and rural distribution feeders, YJLV22 is the standard cost-optimised choice.
  • Q3: What does the "L" in YJLV22 mean? "L" = aluminium conductor. Without the L, YJV22 uses copper. The "22" still means double-steel-tape armour over PVC jacket — identical mechanical and fire protection.
  • Q4: Why must I use bimetallic lugs? Aluminium and copper form a galvanic cell when directly connected in the presence of moisture. Over years this corrodes the aluminium at the joint, increasing resistance and eventually overheating. Bimetallic Al-Cu lugs have an aluminium barrel on the conductor side and a copper flange on the equipment side, isolating the two metals.
  • Q5: When do I choose 8.7/10 kV vs 8.7/15 kV? Choose 8.7/10 kV for nominal 10 kV distribution networks (Um = 12 kV). Choose 8.7/15 kV for nominal 15 kV networks (Um = 17.5 kV) or where the system may be up-rated — the thicker 5.5 mm XLPE gives a larger safety margin.
  • Q6: Why is there no separate neutral core? At MV distribution voltages, three-phase currents are balanced and the system is typically solidly or resistance-earthed; the copper-tape screen provides the earth path. A separate neutral is not required in standard 3-core MV construction.
  • Q7: Can this cable be directly buried? Yes — the double-steel-tape armour provides crush protection, and the PVC jacket is moisture-resistant. Direct burial depth and covering must follow the local MV cable installation code.
  • Q8: What is partial discharge and why is it tested? Partial discharge (PD) is tiny electrical sparks inside the insulation caused by voids or contaminants. At 1.5 U0, PD must be ≤ 20 pC. High PD values predict early insulation failure and are the most sensitive factory-quality indicator.
  • Q9: Why is the routine test 21.5 kV and not 10 kV? Routine tests apply a power-frequency withstand voltage higher than the rated voltage (typically 2.5 U0 = 21.75 kV, rounded to 21.5 kV) to catch manufacturing defects before site installation.
  • Q10: Is the short-circuit rating adequate? At 50 mm² aluminium, the 1 s short-circuit rating is about 3.4 kA — higher than 35 mm² but still well below copper because of aluminium's lower melt point and higher resistance. Protection devices (fuses, breakers) must be sized to clear faults below this level; for high-fault-level networks, upsizing to 70 or 95 mm² aluminium is recommended.
  • Q11: What service life can be expected? When installed, terminated and operated within the stated temperature, voltage and current ratings, XLPE-insulated MV cables — aluminium or copper — are designed for a service life of around 30 years in fixed installation. The dominant failure mode is moisture or PD at terminations, so professional jointing and proper bimetallic lugs are critical.