Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable

Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
YJV22-3x400mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable Cable Designation & Meaning Code Meaning YJ XLPE (cross-linked polyethylene) insulation V PVC inner bedding / outer sheath 22 Steel tape armour (double steel tape, overlapping) + PVC sheath 8.7/10 kV Rated voltage U₀/U = 8.7/10 kV; Uₘ = ...

Product Details

Highlight:

yjv22 heavy aluminum cable

,

yjv22 medium voltage power cable

,

15kv heavy aluminum cable

Conductor (×3):
Bare Annealed Copper, Class 2 Stranded Circular, Typical 37×∅3.70 Mm (400 Mm²), Conductor Ø ≈ 25.5–28.0 Mm
Conductor screen:
Extruded Semi-conductive Compound (XLPE-based)
Insulation:
XLPE (cross-linked Polyethylene), Nominal Thickness 4.5 Mm​ (8.7/10 KV & 8.7/15 KV)
Insulation screen:
Extruded Semi-conductive Compound (strippable Or Bonded)
Metallic screen (per core):
Copper Tape, Copper Wire, Or Combined Copper Tape + Wire, Min. Cross-section 16 Mm² (typically 1×0.1 Mm Copper Tape Overlapping)
Filler & bedding:
PVC Filler + PVC Inner Bedding (tape Wrap Or Extruded), Thickness ≈ 2.0–2.5 Mm
Armour:
Double Steel Tape, 0.5 Mm × 2
Outer sheath:
PVC (polyvinyl Chloride), Nominal Thickness 2.5 Mm (typical), Color: Black
Conductor nominal area:
400 Mm²
Number of cores:
3
Conductor class:
Class 2 Stranded
Conductor construction:
37×∅3.70 Mm (typical)
Conductor diameter (approx.):
25.5–28.0 Mm
Conductor screen thickness:
0.5 Mm
Insulation thickness:
4.5 Mm
Insulation screen thickness:
0.5 Mm
Diameter over insulated core (approx.):
32.5–37.0 Mm
Metallic screen:
Copper Tape 0.1 Mm Overlapping
Inner bedding thickness:
2.0–2.5 Mm
Outer sheath thickness:
2.5 Mm
Overall cable diameter:
85 – 96 Mm
Design outer diameter:
≈ 89.0 Mm
Approx. weight:
17.0 – 20.5 Kg/m (17000–20500 Kg/km)
Design weight:
≈ 18800 Kg/km
Cable shape:
Round

Product Description

Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable

Cable Designation & Meaning

Code

Meaning

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC inner bedding / outer sheath

22

Steel tape armour (double steel tape, overlapping) + PVC sheath

8.7/10 kV

Rated voltage U₀/U = 8.7/10 kV; Uₘ = 12 kV

8.7/15 kV

Rated voltage U₀/U = 8.7/15 kV; Uₘ = 17.5 kV

3×400 mm²

Three power cores, each 400 mm² (3-core, no neutral, no PE)


Construction: XLPE insulated, steel-tape armoured, PVC sheathed, three-core medium-voltage power cable.

Applicable Standards

  • GB/T 12706.2-2020 / IEC 60502-2 — Power cables with extruded insulation and their accessories for rated voltages from 6 kV up to 30 kV
  • GB/T 3956 / IEC 60228 — Conductors (Class 2 stranded circular)
  • GB/T 2951 / IEC 60811 — Insulating and sheathing materials — Common test methods
  • GB/T 3048 — Test methods for electric cables
  • GB/T 18380 / IEC 60332 — Flame retardant tests (Category C or B available)

Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable


Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable

YJV22-3×400 mm² 8.7/10 kV (and 8.7/15 kV) — Cable Specification & Engineering Data 

1. Product Overview & Rating Summary. YJV22-3×400 is a maximum-size medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 400 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV primary distribution feeders serving 40000–63000 kVA distribution transformers and medium-voltage motors in the 10000–16000 kW range. Finished diameter is about 125 mm (10 kV) and nominal mass about 34500 kg/km (≈ 3450 kg per 100 m). With all three cores loaded, the cable carries about 745 A in free air at 25 °C (engineering estimate).


2. Layer-by-Layer Construction (Conductor to Outer Jacket).

Layer Construction Wall Diameter
Conductor (Cu) ×3 Compacted stranded annealed Cu, Class 2 — 61×2.96 mm equivalent — ≈ 25.5 mm
Conductor screen Extruded semi-conducting XLPE, co-extruded ≈ 0.8 mm ≈ 27.1 mm
XLPE insulation Cross-linked polyethylene, triple-extruded 4.5 mm (10 kV) / 5.5 mm (15 kV) ≈ 36.1 / ≈ 38.1 mm
Insulation screen Strippable semi-conducting XLPE ≈ 0.8 mm ≈ 37.7 / ≈ 39.7 mm
Copper-tape screen 0.1 × 25 mm annealed Cu tape, lapped ≈ 0.1 mm tape ≈ 37.9 / ≈ 39.9 mm
Filler & bedding PP/PE rope + non-woven binder — ≈ 108 / ≈ 112 mm bundle
Inner sheath PVC/PE extruded bedding ≈ 1.5 mm ≈ 111 / ≈ 115 mm
Steel armour (type 22) Double galvanised steel tape, helical lapped 2 × 0.5 mm ≈ 112 / ≈ 116 mm
PVC outer jacket ST2 PVC, flame-retardant, black 2.5 mm ≈ 125 / ≈ 128 mm (finished)

3. Electrical Characteristics. Each 400 mm² conductor is held to a maximum DC resistance of 0.0470 Ω/km at 20 °C, rising to about 0.065 Ω/km at the 90 °C operating point. Every length survives the routine 21.5 kV AC power-frequency proof held for five minutes (30.5 kV for the 15 kV grade). Partial discharge at 1.5 U0 must not exceed 20 pC. Dissipation factor tan δ ≤ 0.001 at U0. Insulation resistance ≥ 1000 MΩ·km, typical capacitance ≈ 0.72 μF/km. Impulse withstand (BIL) is 75 kV for the 10 kV grade and 95 kV for the 15 kV grade. With all three cores energised, reference loading is about 745 A in free air at 25 °C, about 740 A direct-buried.

Insulation Data

Property

Value

Material

XLPE (cross-linked polyethylene)

Nominal thickness

4.5 mm

Long-term service temp.

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C

Routine test voltage (AC, 5 min)

22 kV (8.7/10 kV); 30.5 kV (8.7/15 kV)

Type-test voltage (AC)

30 kV (8.7/10 kV); 45 kV (8.7/15 kV)

Partial discharge test

≤ 10 pC at 1.73 U₀ (15 kV)

Tan δ (dissipation factor)

≤ 0.004 at 20 °C

Electrical Parameters

Parameter

Value (8.7/10 kV)

Value (8.7/15 kV)

Note

Rated voltage U₀/U

8.7 / 10 kV

8.7 / 15 kV

—

Max. system voltage Uₘ

12 kV

17.5 kV

—

Test voltage AC (5 min)

22 kV

30.5 kV

Routine

Type-test voltage

30 kV

45 kV

—

DC resistance @20 °C

≤ 0.0470 Ω/km

≤ 0.0470 Ω/km

GB/T 3956 Class 2 max, 400 mm²

AC resistance @90 °C (est.)

≈ 0.060 Ω/km

≈ 0.060 Ω/km

per core

Capacitance (approx.)

≈ 0.50 µF/km

≈ 0.50 µF/km

per core to screen

Inductive reactance (approx.)

≈ 0.13 Ω/km

≈ 0.13 Ω/km

at 50 Hz, 3-core

Current rating in air (30 °C)

≈ 530 – 600 A

≈ 530 – 600 A

per core, 3-core

Current rating buried (20 °C)

≈ 470 – 535 A

≈ 470 – 535 A

direct buried, 3-core

Short-circuit current (1 s, Cu, 250 °C)

≈ 40.0 kA (40000 A)

≈ 40.0 kA (40000 A)

400 mm²

Frequency

50/60 Hz AC

50/60 Hz AC

—

Reference values: 400 mm² at 565 A, 3-phase 10 kV → max balanced load ≈ 9.80 MVA. Voltage drop at 565 A ≈ 3.4 V/km per core (≈0.034% per 100 m).

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C

Min. installation ambient temp.

0 °C (PVC sheath); below 0 °C pre-heating required

Service ambient range

−20 °C to +90 °C (with PVC sheath)

Fire survival

Standard (non-fire-rated); optional fire-resistant version available (ZC-YJV22)



4. Thermal Response & Flame Behaviour. XLPE insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −20 and +50 °C. PVC jacket provides flame-retardant performance per GB/T 18380.34 class A. Short-circuit rating at 250 °C for 1 s is about 57.6 kA for the 400 mm² copper conductor. Thermal resistance of reference burial soil is 1.2 K·m/W.

Fire Performance (YJV22 — Standard)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 Category C (ZC), Category B (ZB) available

Halogen content

Contains halogen (PVC sheath)

Smoke density

Standard (non-low-smoke)

Corrosivity

Corrosive (PVC sheath)

Fire survival (circuit integrity)

Not applicable (standard version); use ZA-YJV22 for flame-retardant A


5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 1875 mm for this size. The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends, or cross-bonded for longer routes). MV heat-shrink or cold-shrink termination kits are mandatory — do not treat this as an LV cable. Laying temperature must not fall below 0 °C; reels must be pre-heated in cold weather. At about 3450 kg per 100 m, the cable requires extra-heavy-duty drum jacks, winches and rated pulling gear.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 1335 mm at Ø89.0 mm

static installation

Max. pulling tension

24000 N

use proper pulling grips

Direct burial

Suitable

steel tape armour provides mechanical protection

Conduit ID

≥ 1.5 × OD → ≥ 134 mm; use 150 mm or 160 mm

—

Fixing

heavy-duty cable clamps, steel straps

—

Impact resistance

High

steel tape armour absorbs mechanical shock

Water resistance

Moisture-resistant (PVC sheath + inner bedding)

not fully watertight; use YJV32 for wet locations

Armour type

Double steel tape, overlapping

galvanized or mill finish

Armour short-circuit rating

≈ 5 kA (1 s, steel tape)

—


6. Typical Service Applications. This YJV22-3×400 MV cable is used in 10 kV / 15 kV primary distribution networks serving very heavy industrial and utility loads: 40000–63000 kVA distribution transformer primary feeds, substation 10 kV outgoing main feeders to very heavy industrial plants, 10 kV motor branch feeds for MV motors in the 10000–16000 kW range (very large pump stations, compressor stations, mill drives, crushers, rolling-mill main drives), steel-mill / cement-plant / paper-mill / chemical-plant 10 kV power distribution mains, high-rise commercial and hospital 10 kV main risers, very large data-centre and district-cooling 10 kV switchboard feeders, mining and quarry 10 kV heavy-duty power supply lines, direct-buried urban 10 kV primary network feeders, PV / wind-farm 10 kV collection mains, and any circuit where mechanical protection against crush or impact is required. Approved installation methods include direct burial, cable tray, concrete duct, and indoor MV cable trench.


Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable


7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance ≤ 0.0470 Ω/km at 20 °C, the 21.5 kV AC / 5 min withstand (30.5 kV for 15 kV grade), partial discharge ≤ 20 pC at 1.5 U0, tan δ ≤ 0.001, insulation resistance ≥ 1000 MΩ·km, conductor continuity across all three cores, steel-armour and copper-screen continuity, and dimensional inspection. Sample and type tests comprise impulse withstand at ±75 kV (or ±95 kV for 15 kV), heating-cycle load-loss test, bending at 15 × OD, short-circuit to 250 °C, flame spread GB/T 18380.34 class A, and voltage re-test after thermal ageing. A factory test certificate accompanies each drum.


Cable Parameters


YJV22-3×400 mm² 8.7/10 kV (and 8.7/15 kV variant) — Full Parameter Sheet 
Medium-voltage power cable · Cu conductor / XLPE insulation / copper-tape screen / double-steel-tape armour (type 22) / PVC outer sheath · per GB/T 12706.2 · 3 cores · finished Ø ≈ 125 mm (10 kV) / ≈ 128 mm (15 kV)
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type YJV22 — Cu conductor / XLPE insulation / double-steel-tape armour / PVC outer sheath

Rated voltage (U0/U) 8.7/10 kV AC 50 Hz; Um = 12 kV (10 kV grade)

Alternative voltage grade 8.7/15 kV AC 50 Hz; Um = 17.5 kV (15 kV grade) — thicker XLPE

Number of cores 3 × 400 — 3 phase cores (400 mm²) — no separate neutral in MV cable

Conductor material Annealed copper, compacted stranded — Class 2 stranded per GB/T 3956

Conductor screen Extruded semi-conducting XLPE — Conductor screen layer (radial field control)

Insulation material Cross-linked polyethylene (XLPE) — 90 °C continuous, 250 °C short-circuit

Insulation screen Extruded semi-conducting, strippable — Outer screen layer

Metallic screen Copper tape, lapped — 0.1 × 25 mm Cu tape; equipotential earth

Armour Double galvanised steel tape — Type 22 armour — mechanical protection

Outer sheath PVC (ST2), flame-retardant — UV- and abrasion-resistant

Standard reference GB/T 12706.2 / IEC 60502-2; GB/T 3956 — Medium-voltage power cables 1.8/3 kV to 26/35 kV
02 · Conductor

Stranding — 400 mm² Compacted stranded copper — Class 2, circular compacted

Strand count (typical) 61 × 2.96 mm (or equivalent) — Compacted after stranding

Conductor diameter ≈ 25.5 mm After compacting (est.)

DC resistance @ 20 °C ≤ 0.0470 Ω/km Maximum per GB/T 3956 Class 2

AC resistance @ 50 Hz (≈ 90 °C) ≈ 0.06 Ω/km Skin/proximity effect included

Conductor screen thickness ≈ 0.8 mm Extruded semi-conducting layer
03 · Insulation

Insulation type Cross-linked polyethylene (XLPE) — Extruded, triple-layer co-extrusion

Insulation thickness — 8.7/10 kV 4.5 mm Nominal, per GB/T 12706.2

Insulation thickness — 8.7/15 kV 5.5 mm Thicker for 15 kV grade

Core Ø over insulation — 10 kV ≈ 36.1 mm 25.5 + 2×(0.8+4.5+0.8)

Core Ø over insulation screen — 15 kV ≈ 38.1 mm 25.5 + 2×(0.8+5.5+0.8)

Insulation screen thickness ≈ 0.8 mm Strippable semi-conducting

Impulse withstand (BIL) — 10 kV 75 kV Lightning impulse test

Impulse withstand (BIL) — 15 kV 95 kV Lightning impulse test
04 · Metallic Screen & Filler

Screen material Annealed copper tape — Lapped with overlap

Screen tape dimensions 0.1 × 25 mm Two layers lapped (typical)

Screen function Equipotential earth / fault-current path — Earthed at terminations

Filler material PP / jute rope, flame-retardant — Fills interstices for round cable

Bedding / binder tape Semi-conducting or non-woven tape — Holds bundle; anti-corrosion layer

Assembled bundle Ø — 10 kV ≈ 108 mm Before inner sheath (est.)

Assembled bundle Ø — 15 kV ≈ 112 mm Before inner sheath (est.)
05 · Inner Sheath & Armour

Inner sheath / bedding PVC or PE extruded — Corrosion barrier under armour

Inner sheath thickness ≈ 1.5 mm Over bundle

Armour type Double steel tape (type 22) — Double-tape helical armour

Armour tape thickness 2 × 0.5 mm Galvanised steel, lapped

Armour function Mechanical protection against crush / impact — Permits direct burial / tray

Armour diameter — 10 kV ≈ 112 mm Over inner sheath (est.)
06 · Outer Sheath

Jacket material PVC, ST2, flame-retardant — GB/T 12706.1

Jacket thickness 2.5 mm Minimum over armour

Overall finished diameter — 10 kV ≈ 125 mm Cross-referenced industry sample

Overall finished diameter — 15 kV ≈ 128 mm Thicker insulation version

Approx. cable mass — 10 kV ≈ 34500 kg/km Cu + XLPE + steel + PVC

Approx. cable mass — 15 kV ≈ 34700 kg/km Heavier due to thicker insulation

Jacket colour Black (standard) — UV-resistant carbon-black PVC

Mass per 100 m — 10 kV ≈ 3450 kg/100 m For drum loading
07 · Electrical

Rated voltage U0/U 8.7/10 kV AC 50 Hz; Um = 12 kV

Maximum system voltage Um (10 kV) 12 kV —

DC resistance @ 20 °C ≤ 0.0470 Ω/km 400 mm² Cu Class 2

Insulation resistance ≥ 1000 MΩ·km XLPE at 20 °C

Capacitance (typical) ≈ 0.72 μF/km Per core (est.)

Dissipation factor tan δ (at U0) ≤ 0.001 — XLPE, 20 °C

Routine test voltage (AC) — 10 kV 21.5 kV / 5 min — Power-frequency withstand

Routine test voltage (AC) — 15 kV 30.5 kV / 5 min — Power-frequency withstand

Air ampacity @ 25 °C ≈ 745 A 3 cores loaded, Cu, in free air (est.)

Buried ampacity @ 25 °C soil ≈ 740 A 3 cores loaded, Cu, direct burial (est.)
08 · Thermal & Fire

Max continuous conductor temp. 90 °C Normal service

Short-circuit temp. (≤ 5 s) 250 °C XLPE limit

Fire behaviour Flame-retardant (PVC jacket) — GB/T 18380.34 class A

Service ambient range −20 to +50 °C Fixed installation

Thermal resistance (soil) 1.2 K·m/W Reference burial conditions

Short-circuit rating (1 s) ≈ 57.6 kA 400 mm² Cu at 250 °C
09 · Installation

Min bending radius ≥ 15 × OD ≈ 1875 mm Fixed installation (armoured)

Laying temperature ≥ 0 °C Pre-heat below 0 °C

Laying methods Tray, direct burial, conduit, duct — Armour permits direct burial

Armour earthing Both ends earthed — Steel armour must be earthed

Copper screen earthing At both ends (or single point for cross-bonding) — MV cable screen bonding

Termination / joints Heat-shrink or cold-shrink MV kits — Separable connectors / outdoor terminations

Special tools Cable cutter, crimping tool, torque wrench — MV lugs required
10 · Packing

Standard supply length 500 or 1000 m/drum Custom cut lengths available

Reel / packing type Wooden-steel drum — Sealed ends against moisture

Surface marking YJV22, 8.7/10 kV, 3×400, supplier, year, metre marks — Per GB/T 6995

Storage conditions Dry, covered, −20 to +40 °C — Sealed ends; protect from UV

Transport Drums secured against rolling — Heavy cable, do not drag


Cable Test Parameters


Test Parameters — YJV22-3×400 mm² 8.7/10 kV (and 8.7/15 kV)
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3048.4, 20 °C ≤ 0.0470 Ω/km (400 mm² Cu) Routine
2 Power-frequency withstand (routine) 21.5 kV AC, 5 min (10 kV grade) No breakdown Routine
3 Power-frequency withstand (15 kV grade) 30.5 kV AC, 5 min No breakdown Routine
4 Partial discharge test At 1.5 U0 = 13 kV (10 kV grade) ≤ 20 pC at 1.73 U0 Routine
5 Dissipation factor tan δ At U0, 20 °C tan δ ≤ 0.001 Routine
6 Insulation resistance GB/T 3048.5 ≥ 1000 MΩ·km Routine
7 Dimensional check Micrometer / micrometer microscope Insulation ≥ 4.5 mm (10 kV); jacket ≥ 2.5 mm Routine
8 Impulse voltage test (BIL) ±75 kV, 10 impulses (10 kV grade) No breakdown at 75 kV Type
9 Impulse voltage test (15 kV grade) ±95 kV, 10 impulses No breakdown at 95 kV Type
10 Heating cycle / load loss 3 cycles U0 + rated current No damage; tan δ stable Type
11 Bending test 15 × OD mandrel, 3 cycles No damage to insulation or sheath Type
12 Short-circuit temperature test 250 °C, 5 s equivalent No insulation collapse Type
13 Flame propagation GB/T 18380.34 class A No vertical flame spread Type
14 Sheath / armour continuity Continuity meter Steel armour and Cu tape continuous Routine
15 Voltage test after ageing After thermal ageing cycle Withstands 2.5 U0 AC Type
16 Marking legibility Visual + rubbing YJV22 / 8.7/10 kV / 3×400 / metre marks legible Routine


Cable Cross Section Structure


Giant MV Cable YJV22 3x400mm² 8.7/15kV Armored XLPE Power Cable


YJV22-3×400 mm² 8.7/10 kV — Cross-Section Construction Diagram (Schematic)
MV layered build-up: Cu conductor → conductor screen → XLPE insulation → insulation screen → Cu-tape screen → filler → bedding → double-steel-tape armour → PVC jacket · 8.7/10 kV (8.7/15 kV variant noted) · finished Ø ≈ 125 mm
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) ×3 Annealed compacted stranded copper, Class 2 — 61×2.96 mm equivalent per core — ≈ 25.5 Power conductor; R ≤ 0.0470 Ω/km at 20 °C
2 Conductor screen Extruded semi-conducting XLPE, co-extruded with insulation ≈ 0.8 ≈ 27.1 Eliminates air gaps; smooth radial field
3 XLPE insulation Cross-linked polyethylene, triple-layer co-extrusion 4.5 (10 kV) / 5.5 (15 kV) ≈ 36.1 / ≈ 38.1 Main dielectric; 90 °C continuous
4 Insulation screen Strippable semi-conducting XLPE ≈ 0.8 ≈ 37.7 / ≈ 39.7 Outer screen; equipotential
5 Copper-tape screen Annealed Cu tape, lapped, 0.1 × 25 mm ≈ 0.1 tape ≈ 37.9 / ≈ 39.9 Earth path / fault-current return
6 Filler & bedding PP/PE rope filler + non-woven binder tape — ≈ 108 / ≈ 112 bundle Round shape; anti-corrosion bedding
7 Inner sheath PVC/PE extruded bedding over bundle ≈ 1.5 ≈ 111 / ≈ 115 Corrosion barrier under armour
8 Steel armour (type 22) Double galvanised steel tape, helically lapped 2 × 0.5 ≈ 112 / ≈ 116 Mechanical crush / impact protection
9 PVC outer jacket ST2 PVC, flame-retardant, black 2.5 ≈ 125 / ≈ 128 (finished) UV, abrasion and chemical protection
Key Dimensions & Properties (expanded)
Finished cable diameter (10 kV) ≈ 125 mm Cross-referenced industry sample

Finished cable diameter (15 kV) ≈ 128 mm Thicker XLPE variant

Approx. cable mass (10 kV) ≈ 34500 kg/km Cu + XLPE + steel + PVC

Approx. cable mass (15 kV) ≈ 34700 kg/km Heavier due to thicker insulation

Nominal voltage rating 8.7/10 kV AC 50 Hz; Um = 12 kV

Alternative voltage grade 8.7/15 kV Um = 17.5 kV; 5.5 mm XLPE

Max continuous conductor temp. 90 °C Normal service

Short-circuit temp. (≤5 s) 250 °C XLPE limit

Impulse withstand (BIL) 75 (10 kV) / 95 (15 kV) kV Lightning impulse

Min bending radius ≥ 15 × OD ≈ 1875 mm Fixed installation

DC resistance @ 20 °C ≤ 0.0470 Ω/km 400 mm² Cu

Insulation resistance ≥ 1000 MΩ·km XLPE

Routine test voltage 21.5 kV AC / 5 min — 10 kV grade; 30.5 kV for 15 kV

Air ampacity @ 25 °C ≈ 745 A 3 cores loaded, Cu (est.)

Mass per 100 m (10 kV) ≈ 3450 kg/100 m For drum loading

Schematic — not to exact scale. Finished Ø ≈ 125 mm (10 kV) and weight ≈ 34500 kg/km from cross-referenced industry samples; conductor/insulation diameters per GB/T 12706.2 and GB/T 3956; ampacity 745 A is an engineering estimate. The 8.7/15 kV variant uses 5.5 mm XLPE insulation, ≈ 128 mm OD and ≈ 34700 kg/km. Values marked (est.) require confirmation against the factory test certificate.


Cable Construction Description


Construction Description — YJV22-3×400 mm² 8.7/10 kV 
Layer-by-layer MV build-up narrative · 8.7/10 kV (and 8.7/15 kV variant) · Cu / triple-extruded XLPE / Cu-tape screen / double-steel-tape armour / PVC jacket · finished Ø ≈ 125 mm
1. Product Identity & Ratings
YJV22-3×400 is a maximum-size medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 400 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV primary distribution feeders serving 40000–63000 kVA distribution transformers and medium-voltage motors in the 10000–16000 kW range. Finished diameter is about 125 mm (10 kV) and nominal mass about 34500 kg/km (≈ 3450 kg per 100 m). With all three cores loaded, the cable carries about 745 A in free air at 25 °C (engineering estimate).
2. Copper Conductor & Screens
Each 400 mm² conductor is compacted-stranded annealed copper (Class 2), with a strand-lay diameter of about 25.5 mm and DC resistance ≤ 0.0470 Ω/km at 20 °C. A semi-conducting conductor screen (≈ 0.8 mm) is co-extruded directly over the copper to eliminate air gaps and smooth the electric field — this is essential at MV voltages because even tiny voids cause partial discharge and eventual insulation failure. The conductor screen bonds electrically to the copper conductor.
3. XLPE Insulation
Cross-linked polyethylene (XLPE) is extruded in a triple-layer co-extrusion process: conductor screen → XLPE insulation → insulation screen, all in one pass to avoid contamination. For the 8.7/10 kV grade the insulation thickness is 4.5 mm; for the 8.7/15 kV grade it is 5.5 mm. XLPE sustains 90 °C continuous conductor temperature and 250 °C short-circuit for ≤ 5 s. The outer insulation screen is strippable for termination work. Over the insulation screen a 0.1 × 25 mm copper tape is lapped to provide an equipotential earth and fault-current return path.
4. Bedding, Steel Armour & PVC Jacket
Three screened cores are cabled round with PP/PE rope filler and a non-woven binder tape, giving a bundle of about 108 mm (10 kV). A PVC/PE inner bedding (≈ 1.5 mm) is extruded over the bundle, then a double layer of 0.5 mm galvanised steel tape is helically lapped — this is the type-22 armour that protects against crush and impact and permits direct burial. Finally a 2.5 mm black PVC (ST2) outer jacket is extruded over the armour to the ≈ 125 mm finish, providing UV, abrasion and chemical resistance.
5. Site Handling & Operational Notes
• Observe the 15 × OD minimum bending radius (≈ 1875 mm).  • The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends or cross-bonded).  • Use heat-shrink or cold-shrink MV termination kits — do not treat as LV cable.  • Service ambient −20 to +50 °C; conductor up to 90 °C continuous.  • Routine test 21.5 kV AC / 5 min (10 kV); impulse withstand 75 kV.  • At ≈ 3450 kg/100 m, plan extra-heavy-duty drum jacks, winches and rated pulling gear.


8. Standards & Conformity. Design and production are governed by GB/T 12706.2-2020 (IEC 60502-2) for extruded-solid-insulation power cables from 1.8/3 kV to 26/35 kV. Conductors satisfy GB/T 3956 Class 2. Flame performance follows GB/T 18380.34. Surface marking complies with GB/T 6995. Cables can also be supplied to IEC 60502-2, BS 6622 or NFC 32-322 requirements on request.

9. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type, voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +40 °C, shielded from direct sunlight and moisture; drum end seals must remain intact until installation. MV cable terminations and joints should be scheduled immediately after laying to avoid prolonged exposure of cut ends.

10. Procurement Specification. State "YJV22-8.7/10 kV-3×400" (or "YJV22-8.7/15 kV-3×400" for the thicker-insulation grade) together with the required length or drum arrangement. Always order the matching MV termination kits (indoor/outdoor / separable connectors) and field-joint kits at both ends. Always request the factory test certificate, which must include the partial-discharge and impulse-withstand reports, to confirm the actual diameter, weight and conductor resistances for the production batch.

11. Cable Industry FAQ.

  • Q1: How does 400 mm² differ from 300 mm² in 10 kV service? 400 mm² raises the reference ampacity from about 645 A to about 745 A, and the short-circuit rating from about 43.2 kA to about 57.6 kA. It is the maximum standard feeder size for 40000–63000 kVA transformers and MV motors in the 10000–16000 kW range, whereas 300 mm² serves 25000–40000 kVA transformers and motors up to about 10000 kW.
  • Q2: What does the "22" in YJV22 mean? The first "2" = double-steel-tape armour; the second "2" = PVC outer jacket. YJV22 is therefore a Cu conductor / XLPE insulation / double-steel-tape armour / PVC jacket MV cable. Without the "22" suffix, YJV would be unarmoured.
  • Q3: When do I choose 8.7/10 kV vs 8.7/15 kV? Choose 8.7/10 kV for nominal 10 kV distribution networks (Um = 12 kV). Choose 8.7/15 kV for nominal 15 kV networks (Um = 17.5 kV) or where the system may be up-rated — the thicker 5.5 mm XLPE gives a larger safety margin.
  • Q4: Why is there no separate neutral core? At MV distribution voltages, three-phase currents are balanced and the system is typically solidly or resistance-earthed; the copper-tape screen provides the earth path. A separate neutral is not required in standard 3-core MV construction.
  • Q5: Why is the triple-extrusion process important? Conductor screen, XLPE insulation and insulation screen are co-extruded in one pass to avoid air gaps and contamination at the interfaces. Even tiny voids cause partial discharge at MV voltages and lead to early insulation failure.
  • Q6: Why is there a copper-tape screen? The copper tape (0.1 × 25 mm lapped) provides an equipotential outer surface around each core, equalises the electric field, and carries capacitive and fault currents to earth.
  • Q7: Can this cable be directly buried? Yes — the double-steel-tape armour provides crush protection, and the PVC jacket is moisture-resistant. Direct burial depth and covering must follow the local MV cable installation code.
  • Q8: What is partial discharge and why is it tested? Partial discharge (PD) is tiny electrical sparks inside the insulation caused by voids or contaminants. At 1.5 U0, PD must be ≤ 20 pC. High PD values predict early insulation failure and are the most sensitive factory-quality indicator.
  • Q9: Why is the routine test 21.5 kV and not 10 kV? Routine tests apply a power-frequency withstand voltage higher than the rated voltage (typically 2.5 U0 = 21.75 kV, rounded to 21.5 kV) to catch manufacturing defects before site installation.
  • Q10: Can the steel armour be used as the earth? The steel armour provides mechanical protection but is not sized or certified as the primary fault-current earth conductor. The copper-tape screen and dedicated earthing conductors carry fault currents; the armour must be bonded to earth for safety.
  • Q11: What service life can be expected? When installed, terminated and operated within the stated temperature, voltage and current ratings, XLPE-insulated MV cables are designed for a service life of around 30 years in fixed installation. The dominant failure mode is moisture or PD at terminations, so professional jointing is critical.