0.6/1kV XLPE Copper Cable ZR-YJV 4x25mm²+1x16mm² Flame Retardant for Power Supply
Product Summary
Product Details
xlpe 5 core cable
,xlpe copper conductor cable
,flame retardant 5 core cable
Product Description
0.6/1kV XLPE Copper Cable ZR-YJV 4x25mm²+1x16mm² Flame Retardant for Power Supply
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
4×25 mm² + 1×16 mm² |
Four cores of 25 mm² (3 phase + 1 neutral) + one earth core of 16 mm² copper conductor |
Construction: Three 25 mm² copper conductors (phase L1/L2/L3) + one 25 mm² copper conductor (neutral N) + one 16 mm² copper conductor (earth PE), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).
Applicable Standards
- GB/T 12706.1-2020 / IEC 60502-1 — Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) — Part 1: Cables for rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV)
- GB/T 19666-2019 — Flame retardant and fire resistant wires and cables
- GB/T 18380.12 / IEC 60332-1-2 — Flame propagation test for a single vertical insulated wire
- GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables
- GB/T 2951-2008 / IEC 60811 — Common test methods for insulating and sheathing materials

ZR-YJV 4×25+1×16 mm² — Cable Specification & Engineering Data
1. Product Overview & Rating Summary. Sitting one size above the 4×16+1×10 in the flame-retardant 4+1-core low-voltage ladder, ZR-YJV 4×25+1×16 is built around four 25 mm² annealed copper phase conductors wrapped around a central 16 mm² copper neutral/PE core, each layer insulated in XLPE and enclosed in a single ST2 PVC oversheath rated 0.6/1 kV at 50 Hz. Manufacture and type testing are performed to GB/T 12706.1 / IEC 60502-1, stranding complies with GB/T 3956, and the ZR marking denotes class ZC flame retardance under GB/T 19666. The finished outer diameter is roughly 25.7 mm and the nominal mass is about 1347 kg per kilometre in copper (650 kg/km for the aluminium YJLV equivalent), delivered in 100 m coils or wooden drums with ≥ Ø 1000 mm flanges — approximately 135 kg per 100 m.
2. Layer-by-Layer Construction (Conductor to Jacket).
| Layer | Construction | Wall | Diameter |
|---|---|---|---|
| Phase conductor (×4) | Annealed Cu, Class 2 compact, 7 × 2.14 mm (1+6) each | — | ≈ 6.7 mm |
| Neutral conductor (×1) | Annealed Cu, Class 2 compact, 7 × 1.70 mm (1+6) | — | ≈ 5.4 mm |
| Phase insulation (×4) | XLPE | 1.2 mm | ≈ 9.1 mm |
| Neutral insulation (×1) | XLPE | 1.0 mm | ≈ 7.4 mm |
| Core assembly | Central neutral + 4 phase cores cabled around + PP filler + polyester binder | — | ≈ 22.5 mm (derived) |
| Outer jacket | Flame-retarded PVC, ST2 compound, black | 1.6 mm | ≈ 25.7 mm (finished) |
3. Electrical Characteristics. Each 25 mm² phase conductor is limited to 0.741 Ω/km at 20 °C, climbing to around 0.94 Ω/km at the 90 °C operating point; the 16 mm² neutral/PE is capped at 1.15 Ω/km. Every production length survives the routine 3.5 kV AC power-frequency proof held for five minutes. Finished-cable insulation resistance remains above 36.7 MΩ·km, XLPE volume resistivity exceeds 1×10¹² Ω·cm, and typical values include capacitance ≤ 0.45 μF/km, inductance ≈ 0.30 mH/km and 50 Hz AC impedance ≈ 0.75 Ω/km. On a one-second short circuit each 25 mm² phase withstands about 2.88 kA (the 16 mm² neutral on a 1.84 kA basis), using I = k·A/√t with k = 115 for copper/XLPE. With all four phase cores energised, reference loading is 115 A in free air at 25 °C and 95 A directly buried at 25 °C — engineering estimates to be confirmed against the factory test certificate.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine |
|
Type-test voltage |
4.0 kV |
IEC 60502-1 |
|
DC resistance @20 °C (phase/neutral, per core) |
≤ 0.727 Ω/km |
GB/T 3956 max, 25 mm² |
|
DC resistance @20 °C (PE, per core) |
≤ 1.15 Ω/km |
GB/T 3956 max, 16 mm² |
|
AC resistance @90 °C (est., phase/neutral) |
≈ 0.945 Ω/km |
per core |
|
AC resistance @90 °C (est., PE) |
≈ 1.50 Ω/km |
per core |
|
Current rating in air (30 °C, single circuit, 4-core+1) |
≈ 88–100 A |
based on 25 mm² phase |
|
Current rating in air (design) |
≈ 93 A |
apply grouping + ambient correction |
|
Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) |
≈ 105–118 A |
common catalogue 108–113 A |
|
Design buried rating |
≈ 110 A |
soil thermal resistivity correction required |
|
Short-circuit current (1 s, Cu, 250 °C, phase/neutral) |
≈ 2.5 kA |
25 mm² reference |
|
Short-circuit current (1 s, Cu, 250 °C, PE) |
≈ 1.6 kA |
16 mm² reference |
|
Frequency |
50/60 Hz AC |
— |
4. Thermal Response & Flame Performance. XLPE sustains a 90 °C continuous conductor temperature and tolerates a 250 °C short-circuit peak for up to five seconds. The cable is rated for service ambients between −20 and +45 °C, must not be uncoiled below 0 °C without pre-conditioning, and uses 25 °C as the reference soil temperature for buried ratings. Flame behaviour meets class ZC of GB/T 19666, proven by both the single-cable vertical test (GB/T 18380.12) and the category-C bunched test (GB/T 18380.35) with char height limited to 2.5 m. The PVC jacket is halogenated and will emit smoke and acid gas in a fire; low-smoke zero-halogen projects must specify WDZ-YJY instead.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 386 mm for this size. Before first energisation, apply the DC site withstand at 4U0 = 2.4 kV for 15 minutes in line with Q/GDW 13244.1-2018. Drums held below 0 °C in storage must be warmed indoors before uncoiling; pulling tension should stay within 4000 N. The 115 A (air) and 95 A (buried) references require derating whenever ambient temperature, cable grouping or soil thermal resistivity deviates from reference conditions. Crimp lugs, glands and heat-shrink termination kits must be matched to the 6.7 mm phase core, 5.4 mm neutral core and ≈ 25.7 mm jacket, and both phase and neutral short-circuit withstand should be coordinated with upstream protective device settings.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 315 mm at Ø21.0 mm |
five-core unarmoured |
|
Max. pulling tension (phase/neutral) |
375 N per core (25 mm² × 15 N/mm²) |
Cu conductor limit |
|
Max. pulling tension (earth) |
240 N per core (16 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Cable tray, ladder, cleats |
— |
|
Conduit ID |
≥ 40 mm |
— |
|
Fixing |
cable ties, small cleats |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. This cross-section serves sub-main and equipment circuits where the 4×16+1×10 rating is too small: sub-main distribution risers in commercial buildings, larger motor feeds in the 11–37 kW range, machine-tool and process-equipment power leads, workshop distribution panels, elevator and escalator power circuits, and auxiliary supplies in light-industrial installations. Approved installation methods include steel or PVC conduit, cable trunking, tray and indoor ducting, both indoors and in covered outdoor locations. For direct burial or mechanically exposed routing, the steel-tape armoured ZR-YJV22 variant is recommended.

7. Testing & Quality Assurance Regime. Routine tests on every length include phase and neutral DC resistance verification (≤ 0.741 / 1.15 Ω/km at 20 °C), the 3.5 kV AC / 5 min withstand, conductor continuity across all five cores and dimensional inspection covering phase insulation ≥ 1.2 mm, neutral insulation ≥ 1.0 mm, sheath ≥ 1.6 mm and overall diameter ≈ 25.7 mm. Sample and type tests comprise the XLPE hot-set trial at 200 ± 3 °C for 15 minutes under 0.2 MPa (load elongation ≤ 175 %, permanent set ≤ 15 %), XLPE tensile ≥ 12.5 MPa with elongation ≥ 200 %, PVC sheath tensile ≥ 10 MPa with elongation ≥ 125 %, PVC thermal stability ≥ 200 minutes at 200 °C, single-cable and category-C bunched flame trials, and bending assessment. Commissioning on site requires insulation-resistance measurement, the DC 2.4 kV / 15 min withstand and positive L1/L2/L3/N/PE identification before switching. A factory test certificate accompanies each drum.
Cable Parameters
| ZR-YJV 4×25+1×16 mm² — Full Parameter Sheet | ||||
| Flame-retardant 4+1-core CU/XLPE/PVC power cable · 0.6/1 kV · GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 25.7 mm · ≈ 1347 kg/km (Cu) — cross-referenced industry sample data | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | ZR-YJV | — | Flame-retardant, Cu conductor, XLPE insulation, PVC sheath | |
| Rated voltage (U0/U) | 0.6/1 | kV | AC 50 Hz; maximum system voltage Um = 1.2 kV | |
| Rated cross-sectional areas | 4 × 25 (phase) + 1 × 16 (neutral) | mm² | 4+1 five-core configuration, reduced neutral/PE | |
| Conductor material | Annealed copper (Cu) | — | Class 2 compact stranded per GB/T 3956 / IEC 60228 | |
| Insulation material | Cross-linked polyethylene (XLPE) | — | 90 °C continuous rating | |
| Sheath material | Flame-retardant PVC, ST2 compound | — | Black; halogen-bearing | |
| Flame-retardant class | ZC (ZR) | — | Per GB/T 19666; ZA/ZB available on request | |
| Standard reference | GB/T 12706.1 / IEC 60502-1 | — | 0.6/1 kV extruded-insulation power cables | |
| 02 · Conductor | ||||
| Phase stranding (×4) | 7 × 2.14 mm (7/2.14) | — | 1+6 compact lay-up; 25 mm² each | |
| Neutral stranding (×1) | 7 × 1.70 mm (7/1.70) | — | 1+6 compact lay-up; 16 mm² | |
| Phase conductor diameter | ≈ 6.7 | mm | Compact strand-lay diameter (est.) | |
| Neutral conductor diameter | ≈ 5.4 | mm | Compact strand-lay diameter (est.) | |
| Phase DC resistance @ 20 °C | 0.741 | Ω/km | Maximum per GB/T 3956 Class 2 | |
| Neutral DC resistance @ 20 °C | 1.15 | Ω/km | Maximum per GB/T 3956 Class 2 | |
| Phase DC resistance @ 90 °C | ≈ 0.94 | Ω/km | Temperature-corrected (est.) | |
| Copper mass — phase (per core) | ≈ 222 | kg/km | 25 mm² × 8.89 g/cm³ | |
| Copper mass — neutral | ≈ 142 | kg/km | 16 mm² × 8.89 g/cm³ | |
| Total copper mass | ≈ 1030 | kg/km | 4 × 222 + 142 | |
| 03 · Insulation | ||||
| Phase insulation thickness | 1.2 | mm | GB/T 12706.1 specified for 25 mm² | |
| Neutral insulation thickness | 1 | mm | GB/T 12706.1 specified for 16 mm² | |
| Phase core Ø over insulation | ≈ 9.1 | mm | 6.7 + 2 × 1.2 | |
| Neutral core Ø over insulation | ≈ 7.4 | mm | 5.4 + 2 × 1.0 | |
| Insulation material | XLPE | — | Cross-linked polyethylene | |
| XLPE volume resistivity | ≥ 1×10¹² | Ω·cm | At 20 °C | |
| XLPE tensile strength | ≥ 12.5 | MPa | Type test | |
| XLPE elongation at break | ≥ 200 | % | Type test | |
| XLPE hot-set (200 °C, 15 min, 0.2 MPa) | ≤ 175 / ≤ 15 | % / % | Load elongation / permanent set | |
| Total XLPE mass | ≈ 80 | kg/km | 4 phase + 1 neutral (est.) | |
| 04 · Assembly | ||||
| Core arrangement | Neutral at centre + 4 phase cores around | — | 4+1 five-core lay-up | |
| Filler material | Polypropylene (PP) rope | — | Fills interstices between cores | |
| Binder tape | Polyester non-woven tape | — | Holds assembled cores | |
| Assembled core Ø | ≈ 22.5 | mm | Derived: 25.7 − 2 × 1.6 sheath | |
| Lay-up direction | Right-hand (S) | — | Standard multi-core convention | |
| 05 · Sheath | ||||
| Sheath material | Flame-retardant PVC, ST2 | — | Black, halogen-bearing | |
| Sheath thickness | 1.6 | mm | Per GB/T 12706.1 for ≈ 22.5 mm assembled Ø | |
| Overall finished diameter | ≈ 25.7 | mm | Cross-referenced industry 4+1 sample | |
| Approximate cable mass (Cu) | ≈ 1347 | kg/km | Cross-referenced industry data | |
| Approximate cable mass (Al) | ≈ 650 | kg/km | YJLV equivalent (cross-referenced) | |
| PVC tensile strength | ≥ 10 | MPa | Type test | |
| PVC elongation at break | ≥ 125 | % | Type test | |
| PVC thermal stability | ≥ 200 | min | @ 200 °C (HCl evolution) | |
| Mass per 100 m (Cu) | ≈ 135 | kg/100 m | For drum loading estimation | |
| 06 · Electrical | ||||
| Rated voltage U0/U | 0.6/1 | kV | AC 50 Hz | |
| Maximum system voltage Um | 1.2 | kV | — | |
| Phase DC resistance @ 20 °C | ≤ 0.741 | Ω/km | GB/T 3956 Class 2 | |
| Neutral DC resistance @ 20 °C | ≤ 1.15 | Ω/km | GB/T 3956 Class 2 | |
| AC impedance @ 50 Hz | ≈ 0.75 | Ω/km | √(R² + X²); R-dominant (est.) | |
| Capacitance (typical) | ≤ 0.45 | μF/km | Per phase core (est.) | |
| Inductance (typical) | ≈ 0.30 | mH/km | Multi-core cable (est.) | |
| Insulation resistance @ 90 °C | ≥ 36.7 | MΩ·km | Finished cable, minimum | |
| Routine test voltage | 3.5 kV AC / 5 min | — | Power-frequency withstand, no breakdown | |
| Site commissioning test | DC 2.4 kV / 15 min | — | 4U0 per Q/GDW 13244.1-2018 | |
| Air ampacity @ 25 °C | ≈ 115 | A | 4 phase cores loaded, Cu (est.) | |
| Buried ampacity @ 25 °C | ≈ 95 | A | 4 phase cores loaded, Cu (est.) | |
| Short-circuit current (1 s) | ≈ 2.88 | kA | Phase: I = k·A/√t, k=115 for Cu/XLPE | |
| 07 · Thermal | ||||
| Max continuous conductor temp. | 90 | °C | XLPE rated | |
| Max short-circuit temp. (≤ 5 s) | 250 | °C | XLPE limit | |
| Min ambient temp. (service) | −20 | °C | — | |
| Max ambient temp. (service) | +45 | °C | — | |
| Min laying temperature | 0 | °C | Warm drums below 0 °C | |
| Max burial soil temp. | 25 | °C | Reference for ampacity | |
| Thermal coefficient of resistance (Cu) | 0.00393 | 1/°C | At 20 °C reference | |
| 08 · Fire (ZR) | ||||
| Flame-retardant class | ZC | — | GB/T 19666 default for ZR marking | |
| Single-cable flame test | GB/T 18380.12 | — | Equivalent IEC 60332-1-2 | |
| Bunched flame test | GB/T 18380.35 category C | — | Char height ≤ 2.5 m | |
| Halogen content | Halogen-bearing (PVC) | — | Specify WDZ-YJY for LSZH | |
| Smoke emission | Emits smoke under fire | — | PVC jacket; LSZH alternative available | |
| 09 · Installation | ||||
| Min bending radius (multi-core) | ≥ 15 × OD ≈ 386 | mm | OD = actual finished diameter | |
| Max pulling tension | ≤ 4000 | N | 40 N/mm² of main phase core area (est.) | |
| Recommended drum flange Ø | ≥ 1000 | mm | For this section | |
| Laying methods | Conduit, tray, trunking, indoor ducting | — | Indoor or sheltered outdoor | |
| Direct burial note | Use armoured ZR-YJV22 for burial | — | Unarmoured YJV needs conduit/protection | |
| Termination | Crimp lugs + heat-shrink or screw terminals | — | Size for 6.7 mm phase / 5.4 mm neutral core | |
| 10 · Packing | ||||
| Standard supply length | 100 | m/coil or drum | Custom lengths available | |
| Drum type | Wooden drum (≥ Ø 1000 mm flange) | — | Sealed until installation | |
| Surface marking | Type, voltage, supplier, year, metre marks | — | Per GB/T 6995 | |
| Storage conditions | Dry, covered, −20 to +45 °C | — | Away from sunlight, moisture, oils, sharp objects | |
| Transport | Coils/drums secured against rolling | — | Do not drag cable over rough ground | |
Cable Test Parameters
| Test Parameters — ZR-YJV 4×25+1×16 mm² | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3048.4, 20 °C | Phase ≤ 0.741 Ω/km; Neutral ≤ 1.15 Ω/km | Routine |
| 2 | Power-frequency withstand | 3.5 kV AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | GB/T 3048.5, 90 °C | ≥ 36.7 MΩ·km | Routine |
| 4 | Conductor continuity | Visual + electrical | All 5 cores continuous | Routine |
| 5 | Dimensional check | Micrometer | Phase ins. ≥ 1.2 mm; neutral ≥ 1.0 mm; sheath ≥ 1.6 mm; OD ≈ 25.7 mm | Routine |
| 6 | XLPE hot-set test | 200 ± 3 °C, 15 min, 0.2 MPa | Load elongation ≤ 175 %; permanent set ≤ 15 % | Type |
| 7 | XLPE tensile & elongation | GB/T 2951.11 | Tensile ≥ 12.5 MPa; elongation ≥ 200 % | Type |
| 8 | PVC sheath tensile & elongation | GB/T 2951.11 | Tensile ≥ 10 MPa; elongation ≥ 125 % | Type |
| 9 | PVC thermal stability | 200 °C, HCl evolution | ≥ 200 min | Type |
| 10 | Single-cable vertical flame | GB/T 18380.12 | Self-extinguishing; char ≤ 50 mm above burner | Type |
| 11 | Bunched cable flame (cat. C) | GB/T 18380.35 | Char height ≤ 2.5 m | Type |
| 12 | Bending test | ≥ 15 × OD mandrel | No crack in insulation or sheath | Type |
| 13 | Heat deformation (PVC) | 80 °C, 4 h, load | Deformation ≤ 50 % | Type |
| 14 | XLPE shrinkage test | 130 °C, 1 h | Shrinkage ≤ 4 % | Type |
| 15 | Site DC withstand | 4U0 = 2.4 kV DC, 15 min | No breakdown (Q/GDW 13244.1-2018) | Site |
| 16 | Core identification | Visual + continuity | Correct L1/L2/L3/N/PE identification | Site |
Cable Cross Section Structure

| ZR-YJV 4×25+1×16 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Layered 4+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 25.7 mm per cross-referenced industry sample | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Phase conductor (Cu) × 4 | Annealed copper, Class 2 compact strand — 7 wires of 2.14 mm per core (7/2.14, 1+6 layout), nominal area 25 mm² each | — | ≈ 6.7 (Ø each phase core) | Line-current carrying phase conductors; DC resistance capped at 0.741 Ω/km at 20 °C |
| 2 | Neutral conductor (Cu) × 1 | Annealed copper, Class 2 compact strand — 7 wires of 1.70 mm (7/1.70, 1+6 layout), nominal area 16 mm² | — | ≈ 5.4 (Ø neutral core) | Return / PE path; DC resistance capped at 1.15 Ω/km at 20 °C |
| 3 | Phase insulation (XLPE) × 4 | Cross-linked polyethylene dielectric | 1.2 | ≈ 9.1 (Ø each phase core, incl. insulation) | Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min |
| 4 | Neutral insulation (XLPE) × 1 | Cross-linked polyethylene dielectric | 1 | ≈ 7.4 (Ø neutral core, incl. insulation) | Electrical isolation for the neutral/PE conductor |
| 5 | Core assembly | Neutral core at centre + four phase cores cabled around + PP filler + polyester binder tape | — | ≈ 22.5 (Ø over assembled cores) | 4+1 configuration; derived from finished Ø 25.7 − 2×1.6 sheath |
| 6 | Outer jacket (PVC) | Flame-retardant PVC, ST2 compound, black | 1.6 | ≈ 25.7 (Ø finished cable) | Mechanical and moisture protection; ZC flame retardance per GB/T 19666 |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 25.7 | mm | Cross-referenced industry 4+1 sample | ||
| Approximate cable mass | ≈ 1347 | kg/km | Cu build-up (cross-referenced industry data) | ||
| Approximate mass, aluminium build | ≈ 650 | kg/km | YJLV equivalent (cross-referenced) | ||
| Nominal voltage rating | 0.6/1 | kV | AC 50 Hz; maximum system voltage Um = 1.2 kV | ||
| Conductor temperature limits | 90 / 250 | °C | Continuous service / short-circuit (≤ 5 s) | ||
| Minimum bend radius (multi-core) | ≥ 15 × OD ≈ 386 | mm | OD = actual finished cable diameter | ||
| Flame-retardant classification | ZC (ZR) | — | Per GB/T 19666 | ||
| Short-circuit current, phase (1 s) | ≈ 2.88 | kA | I = k·A/√t, k=115 for Cu/XLPE | ||
| Short-circuit current, neutral (1 s) | ≈ 1.84 | kA | 16 mm² neutral, same k factor | ||
| AC impedance @ 50 Hz | ≈ 0.75 | Ω/km | √(R² + X²); R-dominant (est.) | ||
| Capacitance (typical) | ≤ 0.45 | μF/km | Per phase core (est.) | ||
| Inductance (typical) | ≈ 0.30 | mH/km | Multi-core cable (est.) | ||
| Air ampacity @ 25 °C | ≈ 115 | A | 4 phase cores loaded, Cu (est.) | ||
| Buried ampacity @ 25 °C | ≈ 95 | A | 4 phase cores loaded, Cu (est.) | ||
| Maximum pulling tension | ≤ 4000 | N | 40 N/mm² of main phase core area (est.) | ||
| Schematic — not to exact scale. Finished Ø ≈ 25.7 mm and weight ≈ 1347 kg/km from cross-referenced industry samples; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1; ampacity 115/95 A is an engineering estimate for 4+1 cables. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — ZR-YJV 4×25+1×16 mm² | |||
| Layer-by-layer build-up narrative, conductor through outer jacket · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV class · finished Ø ≈ 25.7 mm (cross-referenced industry sample) | |||
| 1. Product Identity & Ratings | |||
| ZR-YJV 4×25+1×16 occupies the next rung above 4×16+1×10 in the 4+1-core flame-retardant range: four 25 mm² copper phase conductors encircle a 16 mm² copper neutral/PE core, all XLPE-insulated and wrapped in a single ST2 PVC jacket for 0.6/1 kV service. It is produced and type-tested to GB/T 12706.1 / IEC 60502-1, stranded to GB/T 3956, and marked ZR for class ZC flame retardance under GB/T 19666. The finished cable is about 25.7 mm across (cross-referenced industry sample) and weighs roughly 1347 kg per kilometre in copper (650 kg/km for the aluminium YJLV equivalent); standard supply is 100 m coils or wooden drums with ≥ Ø 1000 mm flanges (≈ 135 kg per 100 m). | |||
| With all four phase cores energised, the cable supports about 115 A in free air at 25 °C and 95 A directly buried at 25 °C (engineering estimate) — suited to sub-main distribution, larger motor feeds and industrial equipment circuits where the 4×16+1×10 rating would be marginal. The 4+1 arrangement places the reduced 16 mm² core at the centre and lays the four 25 mm² phase cores around it. | |||
| 2. Copper Stranded Conductors | |||
| Each 25 mm² phase core is stranded from seven 2.14 mm annealed wires in the 1+6 compact arrangement (7/2.14) — the Class 2 standard at this cross-section — giving a strand-lay diameter of about 6.7 mm and a DC resistance ceiling of 0.741 Ω/km at 20 °C (about 0.94 Ω/km at the 90 °C operating point). The 16 mm² neutral/PE core uses seven 1.70 mm wires (7/1.70, 1+6) to about 5.4 mm strand-lay Ø, with resistance capped at 1.15 Ω/km. Copper mass alone is about 222 kg/km per phase core and 142 kg/km for the neutral; the seven-wire compact lay-up keeps the core flexible enough for conduit pulling while remaining robust enough for repeated bending in tray installations. | |||
| 3. XLPE Dielectric Insulation | |||
| XLPE is extruded at 1.2 mm onto each 25 mm² phase core and 1.0 mm onto the 16 mm² neutral core — producing approximately 9.1 mm per phase core and 7.4 mm for the neutral core over the insulation. The dielectric is rated for 90 °C continuous duty and 250 °C for five seconds, maintains volume resistivity above 1×10¹² Ω·cm, passes the routine 3.5 kV AC five-minute voltage proof, and offers tensile strength ≥ 12.5 MPa with elongation ≥ 200 %. Total XLPE mass is about 80 kg/km. | |||
| 4. Cabling & PVC Outer Jacket | |||
| After insulation, the 16 mm² neutral core is placed at the centre and the four 25 mm² phase cores are cabled around it in a square arrangement with polypropylene filler and a polyester binder tape, forming a bundle of about 22.5 mm diameter (derived from the finished size). A 1.6 mm layer of flame-retarded ST2 PVC is then extruded over the assembly to the ≈ 25.7 mm finish. The jacket provides ZC behaviour through GB/T 18380.12 and GB/T 18380.35, offers tensile strength ≥ 10 MPa and elongation ≥ 125 %; because PVC is halogenated, low-smoke zero-halogen projects should specify WDZ-YJY, and direct-burial projects without added protection should specify steel-tape armoured ZR-YJV22. | |||
| 5. Site Handling & Operational Notes | |||
| • Observe the 15 × OD minimum bending radius (≈ 386 mm). • Perform the DC 4U0 = 2.4 kV / 15 min commissioning test before first energisation. • Service ambient spans −20 to +45 °C; warm drums below 0 °C before pulling. • Derate the 115 A (air) / 95 A (buried) references for ambient temperature, grouping and soil conditions. • Maximum pulling tension ≤ 4000 N; use appropriate pulling grips. • Select lugs and terminals matched to the 6.7 mm phase core, 5.4 mm neutral core and ≈ 25.7 mm jacket. • Short-circuit rating ≈ 2.88 kA for 1 s on the phase (≈ 1.84 kA basis on the neutral) — verify against protective device settings. • Use drums with ≥ Ø 1000 mm flanges (≈ 135 kg per 100 m). |
8. Factory Advantages.
- Balanced 4+1 sizing — 4×25 duty cores plus a 16 neutral saves copper on balanced small branches.
- Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
- Dosed ZC compound — self-extinguishing jacket protects branch circuits and local boards.
- Length-on-demand — cut to exact branch meter with sealed ends.
- Dual-section resistance log — 25 cores and 16 neutral R recorded to lot.
- Continuous print line — type, size, ZC, voltage and length readable along conduit runs.
- Color-coded cores — phase, neutral and PE distinguished at terminals.
- Lightweight compact pack — small section on a compact drum, easy pulling.
- Certified QA pack — routine + type test record shipped per batch.

9. Packaging, Storage & Logistics. Standard delivery is 100 m per coil or wooden drum, with bespoke cut lengths available on request. Each drum carries type, voltage, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +45 °C, shielded from direct sunlight, moisture, oils and sharp objects; coils and drums remain sealed until installation and are stored upright on their flanges rather than flat. In cold conditions, condition drums indoors to ≥ 0 °C before pulling. During transit, coils and drums must be secured against rolling and impact, and the cable must never be dragged across abrasive ground or sharp edges.

10. Procurement Specification. State "ZR-YJV 0.6/1 kV 4×25+1×16" together with the required length or drum arrangement and marking preferences. Specify the flame-retardant class (ZC is standard; ZA or ZB available), jacket colour and any special drum requirements. Always request the factory test certificate to confirm the actual unarmoured diameter (≈ 25.7 mm), weight (≈ 1347 kg/km) and ampacity for the production batch. Where low-smoke zero-halogen or armoured construction is needed, order WDZ-YJY or ZR-YJV22 respectively.
11. Cable Industry FAQ.
- Q1: How does 4×25+1×16 differ from the smaller 4×16+1×10? The phase area grows from 16 to 25 mm² (conductor from 7×1.70 to 7×2.14 mm) and the neutral from 10 to 16 mm² (7×1.35 to 7×1.70 mm), raising the rated current from about 85/72 A to 115/95 A, increasing the finished diameter from 21 to 25.7 mm, and lifting the one-second phase short-circuit withstand from about 1.84 to 2.88 kA.
- Q2: Why is the neutral/PE only 16 mm² when the phases are 25 mm²? In a balanced four-wire circuit the neutral carries mainly unbalance and harmonic current, so GB/T 12706.1 permits a reduced core in the 4+1 construction. Where the installation serves substantial single-phase or non-linear, harmonic-generating loads, an equal-section 5-core cable (4×25+1×16 — here the neutral already matches the previous phase size) or larger should be chosen.
- Q3: What do ZA, ZB, ZC and ZD mean? These are flame-retardant classes in GB/T 19666, assessed through the bunched-cable test GB/T 18380.35 at progressively higher fuel loads — ZA is the most demanding, ZD the least. The bare "ZR" marking defaults to ZC; ZA and ZB must be requested at ordering.
- Q4: When should a 4+1, equal 5-core, or plain 4-core cable be selected? Choose 4+1 for standard four-wire service with a reduced neutral/PE; equal 5-core (4×A+1×A) where neutral current is expected to approach phase current; plain 4-core when no separate PE conductor is required in the cable.
- Q5: Why do air and buried ratings differ, and how are they adjusted? Published figures assume 25 °C air or 25 °C soil at 1.0 K·m/W thermal resistivity with a single circuit. Manufacturer correction factors must be applied for ambient temperature, grouping, burial depth and soil resistivity — air factors range from about 1.29 at 20 °C down to 0.91 at 45 °C, and soil factors from 1.04 at 20 °C to 0.87 at 40 °C.
- Q6: Copper or aluminium? Copper (this cable) delivers lower resistance (0.741 versus roughly 1.20 Ω/km at 25 mm²), higher current per mm², better mechanical strength and more dependable terminations; aluminium (YJLV, ≈ 650 kg/km in this size) costs less and weighs less but requires larger cross-sections and anti-oxidation treatment at every joint.
- Q7: Why can XLPE run at 90 °C while PVC insulation is limited to 70 °C? Cross-linking transforms polyethylene into a three-dimensional thermoset network, which raises the continuous conductor rating to 90 °C and the short-circuit withstand to 250 °C — directly increasing the ampacity available from a given copper area.
- Q8: How is the conductor cross-section chosen? Selection is governed by (a) full-load current after derating, (b) permissible voltage drop (typically ≤ 5 % for branch circuits), (c) short-circuit withstand on an I²t basis (2.88 kA·s per phase here), and (d) coordination with overcurrent protective devices; the most stringent criterion controls.
- Q9: Why does finished diameter vary between manufacturers for the same nominal size? Standards set minimum insulation and sheath thicknesses plus electrical performance, but not a precise overall diameter. Stranding compaction, filler design and sheath tolerance differ between plants — published 4×25+1×16 figures cluster around 25.7 mm unarmoured — so the actual measured diameter must always be used when sizing glands, trays and conduits.
- Q10: Which tests confirm acceptability on delivery and before energisation? At delivery, verify the factory test certificate (resistance 0.741/1.15 Ω/km, 3.5 kV/5 min withstand, dimensions ≈ 25.7 mm), jacket legibility and drum integrity. After installation, complete an insulation-resistance test plus the DC 4U0 = 2.4 kV / 15 min withstand per Q/GDW 13244.1-2018, then confirm L1/L2/L3/N/PE identification before closing the breaker.
- Q11: What service life can be expected? When installed and operated within the stated temperature and voltage limits, XLPE 0.6/1 kV cables are designed for a minimum service life of 30 years; sustained overload, ultraviolet exposure, water ingress through a damaged sheath, or operation above 90 °C will materially shorten that life.