1x25mm2 Single Core Cable Pure Copper XLPE Insulation For Indoor Power Wiring

1x25mm2 Single Core Cable Pure Copper XLPE Insulation For Indoor Power Wiring

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 1*25mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

ZR-YJV 1*25mm² Flame Retardant Single Core Cable, 0.6/1kV Pure Copper XLPE Insulation PVC Sheath for Indoor Power Wiring Code Mean:ZR-Flame Retardant, YJ-XLPE Insulation, V-PVC Outrt Sheathed. ZR-YJV 1×25 mm² — Detailed Product Introduction ZR-YJV 1×25 is a flame-retardant, copper-conductor, XLPE...

Product Details

Highlight:

1x25mm2Single Core Cable

,

Single Core Cable 316kg/km

,

Power Wiring Pure Copper Cable

Conductor​:
Bare Annealed Copper, Class 2 Stranded Circular, 7×∅2.07 Mm​ (typical), Conductor Ø ≈ 6.2 Mm
Conductor nominal area:
25 Mm²
Conductor construction:
Class 2, 7×∅2.07 Mm​ Min. 7 Wires Per GB/T 3956 (≤35 Mm²)
Conductor diameter (approx.):
6.2 Mm
Insulation:
XLPE Compound, Extruded
Insulation thickness (nominal):
0.9 Mm​ (GB/T 12706.1, 25 Mm² Class)
Diameter over insulation (approx.):
8.0 Mm(6.2 + 2×0.9)
Sheath nominal thickness:
1.4 Mm,single-core (some Makers 1.5)
Filler / binder​:
Flame-retardant (FR) Non-hygroscopic Tape / PP Mesh
Outer sheath​:
Polyolefin (PO) Compound, Flame-retardant Grade (ZR)
Overall cable diameter:
10.7 – 11.8 Mm
Approx. weight:
280 – 316 Kg/km
Long-term service temperature:
90 °C
Short-circuit temperature (≤5 s):
250 °C
Emergency overload:
105–130 °C (limited Duration)
Routine test:
3.5 KV AC / 5 Min; Type Test 4.0 KV
Volume resistivity @90 °C:
≥ 10¹² Ω·cm
Insulation resistance constant:
≈ 3.67 MΩ·km @90 °C

Product Description

ZR-YJV 1*25mm² Flame Retardant Single Core Cable, 0.6/1kV Pure Copper XLPE Insulation PVC Sheath for Indoor Power Wiring

 

Code Mean:ZR-Flame Retardant, YJ-XLPE Insulation, V-PVC Outrt Sheathed.

 

ZR-YJV 1×25 mm² — Detailed Product Introduction

ZR-YJV 1×25 is a flame-retardant, copper-conductor, XLPE-insulated, PVC-sheathed power cable for 0.6/1 kV distribution, designed and tested to GB/T 12706.1 and IEC 60502-1.

1. Product Structure (from conductor to outer sheath)

No. Layer Material / Construction Key data
1 Conductor (Cu) Plain annealed copper, Class 1/2 (typical Class 2 stranded), nominal 25 mm² Typical stranding 7 × 2.14 mm (7/2.14); Ø ≈ 6.4 mm (6.1–6.4 mm); max. DC resistance ≤ 0.727 Ω/km @ 20 °C (GB/T 3956)
2 Insulation (XLPE) Cross-linked polyethylene (thermoset, cross-linked for heat resistance) Nominal thickness 0.9 mm; Ø over insulation ≈ 8.2 mm; 90 °C continuous rating
3 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black Nominal thickness 1.4 mm; overall Ø ≈ 10.5–10.8 mm; flame retardance ZC (ZR)

Overall diameter ≈ 10.8 mm (10.5–10.8 mm across manufacturers) and weight ≈ 298 kg/km (290–298 kg/km).

 

2. Product Performance

  • Electrical: Conductor DC resistance ≤ 0.727 Ω/km @ 20 °C; routine AC withstand test 3.5 kV / 5 min without breakdown; finished-cable insulation resistance ≥ 36.7 MΩ·km @ 20 °C (typical reference); XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km.
  • Thermal: Max. continuous conductor temperature 90 °C; short-circuit (≤ 5 s) 250 °C; ambient service −20 to +45 °C; laying temperature not below 0 °C.
  • Flame retardance: "ZR" = flame-retardant, default class ZC per GB/T 19666; passes single-cable vertical flame test (GB/T 18380.12) and class-C bunched test (GB/T 18380.35: ≥ 1.5 L/m non-metallic volume, 20 min flame, char extent ≤ 2.5 m).
  • Ampacity (reference): ≈ 155 A in air (single core, 30 °C); direct burial ≈ 130–160 A depending on soil thermal resistivity — always apply correction factors per GB/T 16895 / IEC 60364.
  • Mechanical/installation: min. bending radius 20 × OD (single-core); site DC withstand test after installation 4U0 = 2.4 kV / 15 min (per Q/GDW 13244.1-2018 practice).

3. Key Parameters

  • Rated voltage 0.6/1 kV (Um = 1.2 kV); 50 Hz; single core; 25 mm²
  • Conductor: Cu Class 2, 7 × 2.14 mm, Ø ≈ 6.4 mm; DC R ≤ 0.727 Ω/km
  • Insulation: XLPE, 0.9 mm; Sheath: flame-retardant PVC ST2, 1.4 mm
  • Weight ≈ 298 kg/km; OD ≈ 10.8 mm; length 100 m per coil/drum
ZR-YJV 1×25 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV)
Construction: CU / XLPE / PVC  •  Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance)  •  Nominal values for reference — confirm against factory test certificate
No. Category Parameter Value Unit Notes / Standard Reference
A. Product Identification
1 Identification Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable — Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing)
2 Identification Model designation ZR-YJV 1×25 — Cu / XLPE / PVC
3 Identification Design standards GB/T 12706.1; IEC 60502-1 — Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence
4 Identification Rated voltage U0/U 0.6/1 kV Max system voltage Um = 1.2 kV
5 Identification Rated frequency 50 Hz AC power distribution
6 Identification Number of cores 1 — Single-core cable
7 Identification Nominal cross-sectional area 25 mm² Nominal conductor cross-section per GB/T 3956
B. Cable Construction (from conductor to outer sheath)
8 Conductor Material Plain annealed copper (Cu) — High-conductivity electrolytic / oxygen-free copper
9 Conductor Conductor class Class 1 or Class 2 (typical: Class 2, stranded) — GB/T 3956 / IEC 60228
10 Conductor Typical stranding construction 7 wires × 2.14 mm (7/2.14) — Class 2 round stranded; nominal section ≈ 25 mm²
11 Conductor Conductor diameter ≈ 6.4 mm 6.1–6.4 mm per manufacturer tables (Qifan 6.1 mm; 7/2.14 → ≈ 6.4 mm)
12 Conductor Max. DC resistance of conductor at 20 °C 0.727 Ω/km GB/T 3956, Class 2 copper; acceptance criterion for 25 mm²
13 Insulation Material Cross-linked polyethylene (XLPE) — Thermally cross-linked; natural/transparent colour
14 Insulation Nominal insulation thickness 0.9 mm GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 25 mm²)
15 Insulation Diameter over insulation ≈ 8.2 mm ≈ 6.4 + 2 × 0.9 (calculated)
16 Sheath Material Flame-retardant polyvinyl chloride (PVC, ST2 type) — Colour: black (or as ordered)
17 Sheath Nominal sheath thickness 1.4 mm GB/T 12706.1 / IEC 60502-1
18 Dimensions Approx. overall diameter 10.5–10.8 mm Qifan 10.8 mm; Weiguang 10.5 mm
19 Dimensions Approx. cable weight ≈ 298 kg/km Range 290–298 kg/km across manufacturers (Qifan 298; Weiguang 290)
C. Electrical Performance
20 Electrical Max. DC conductor resistance at 20 °C 0.727 Ω/km GB/T 3956; routine measurement
21 Electrical Power-frequency withstand voltage (routine test) 3.5 kV / 5 min, no breakdown — AC 50 Hz; per GB/T 12706.1 / IEC 60502-1
22 Electrical Insulation resistance (finished cable, 20 °C) ≥ 36.7 MΩ·km Typical finished-cable requirement for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method
23 Electrical XLPE volume resistivity at 20 °C ≥ 1 × 10¹² Ω·cm Material-level requirement (manufacturer reference)
24 Electrical Capacitance (single-core, approx.) ≤ 0.45 μF/km Manufacturer reference value
25 Electrical Reference ampacity — in air, 30 °C, single core ≈ 155 A Reference value (Guangheng); depends on laying, grouping, ambient — apply correction factors per GB/T 16895 / IEC 60364
26 Electrical Reference ampacity — direct burial, 25 °C ≈ 155 A Reference value; depends on soil thermal resistivity and depth (reference range 130–160 A)
D. Thermal Performance
27 Thermal Max. continuous conductor temperature 90 °C XLPE insulation temperature class
28 Thermal Max. conductor temperature under short-circuit (≤ 5 s) 250 °C Per GB/T 12706.1 / IEC 60502-1
29 Thermal Ambient service temperature range -20 to +45 °C Per Qifan datasheet; check project specification
30 Thermal Min. installation (laying) temperature 0 °C Pre-heat the cable if ambient is below 0 °C
E. Flame Retardance (ZR)
31 Flame retardance Flame-retardant class ZC (class C) by default for "ZR" — GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH)
32 Flame retardance Single-cable vertical flame-spread test Pass — GB/T 18380.12
33 Flame retardance Bunched flame-spread test (class C) Char extent ≤ 2.5 m above burner bottom edge — GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min
34 Flame retardance Halogen content Halogen-containing (PVC) — For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type
F. Installation
35 Installation Min. bending radius — single-core cable 20 × OD — Qifan & Huaneng datasheets; some manufacturers specify 15 × OD; OD = actual cable diameter
36 Installation Laying methods Conduit, tray, cable trench, tunnel, duct, supported/suspended aerial — Also direct burial with mechanical protection where permitted
37 Installation Site withstand test after installation DC 4U0 = 2.4 kV, 15 min (recommended) — Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project
G. Packing & Delivery
38 Packing Standard delivery length 100 m per coil/drum (or as ordered) — Typical industry practice; custom lengths available
39 Packing Cable marking Model, rated voltage, manufacturer, year of manufacture, sequential length marks — Per GB/T 6995 / project specification
40 Packing Packing form Wooden drum / coil / export packing — As per customer requirement

1x25mm2 Single Core Cable Pure Copper XLPE Insulation For Indoor Power Wiring

 

4. Test Parameters

ZR-YJV 1×25 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Test Stage Test Item Method / Standard Requirement / Acceptance Criterion Notes
Routine test Conductor DC resistance measurement GB/T 3956 (IEC 60228) ≤ 0.727 Ω/km at 20 °C Measured on every production length
Routine test Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC, 5 min, no breakdown Applied between conductor and water/earth; 50 Hz
Routine test Construction check — insulation & sheath thickness, outer diameter GB/T 2951 Within GB/T 12706.1 tolerances Insulation ≥ 0.9 mm nominal; sheath ≥ 1.4 mm nominal
Sample test Hot set (thermal elongation) test — XLPE insulation GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % Verifies degree of cross-linking
Sample test Conductor construction & diameter check GB/T 3956 Class 2; 7 × 2.14 mm; Ø ≈ 6.4 mm Sampled per batch
Type test Single-cable vertical flame-spread test (flame retardance) GB/T 18380.12 No flame spread; charring does not reach top reference point ZR / ZC flame-retardant property
Type test Bunched flame-spread test, class C GB/T 18380.35 Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m Class ZC per GB/T 19666
Type test Bending test (mechanical) GB/T 12706.1 Bend around specified mandrel without insulation/sheath damage Mandrel diameter related to cable OD
Post-installation DC withstand test after installation Q/GDW 13244.1-2018 (recommended practice) 4U0 = 2.4 kV DC, 15 min, no breakdown For new installations; verify project specification
Optional Insulation resistance measurement at 20 °C Manufacturer test method ≥ 36.7 MΩ·km (typical finished-cable value) Not a routine item in GB/T 12706.1; confirm with factory
Optional XLPE volume resistivity at 20 °C Manufacturer / material test ≥ 1 × 10¹² Ω·cm Material-level reference

 

5.Cable Cross Section

1x25mm2 Single Core Cable Pure Copper XLPE Insulation For Indoor Power Wiring

No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) Annealed copper, Class 2 stranded — 7 × 2.14 mm (7/2.14), nominal 25 mm² — ≈ 6.4 (Ø) Current-carrying element; max DC resistance ≤ 0.727 Ω/km @ 20 °C
2 Insulation (XLPE) Cross-linked polyethylene 0.9 ≈ 8.2 (Ø over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.4 ≈ 10.8 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
           
           
Key Dimensions & Properties
Overall diameter 10.5–10.8 mm Qifan 10.8 mm; Weiguang 10.5 mm    
Approx. cable weight ≈ 298 kg/km Range 290–298 kg/km across manufacturers    
Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV    
Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)    
Min. bending radius (single-core) 20 × OD — OD = actual cable diameter    
Flame-retardant class ZC (ZR) — GB/T 19666    

 

6. Usage Precautions

  1. Install only when ambient ≥ 0 °C; pre-heat the cable if colder.
  2. Min. bending radius 20 × OD — avoid sharp bends and kinking.
  3. ZR-YJV contains halogen (PVC); for LSZH requirements choose WDZ-YJY.
  4. Ampacity must be derated for grouping, ambient temperature and burial conditions.
  5. Perform the site DC test only after verifying insulation integrity; avoid prolonged overvoltage.
  6. Store on drums/coils, away from direct sunlight and mechanical damage.

7. Application Range

Indoor/outdoor distribution and branch circuits at 0.6/1 kV in industrial plants, commercial buildings, residential complexes, substations and similar installations — in conduits, trays, trenches, tunnels and ducts; suitable where flame-retardant performance is required (not for direct sunlight exposure unless UV-protected).

 