1x25mm2 Single Core Cable Pure Copper XLPE Insulation For Indoor Power Wiring
Product Summary
Product Details
1x25mm2Single Core Cable
,Single Core Cable 316kg/km
,Power Wiring Pure Copper Cable
Product Description
ZR-YJV 1*25mm² Flame Retardant Single Core Cable, 0.6/1kV Pure Copper XLPE Insulation PVC Sheath for Indoor Power Wiring
Code Mean:ZR-Flame Retardant, YJ-XLPE Insulation, V-PVC Outrt Sheathed.
ZR-YJV 1×25 mm² — Detailed Product Introduction
ZR-YJV 1×25 is a flame-retardant, copper-conductor, XLPE-insulated, PVC-sheathed power cable for 0.6/1 kV distribution, designed and tested to GB/T 12706.1 and IEC 60502-1.
1. Product Structure (from conductor to outer sheath)
| No. | Layer | Material / Construction | Key data |
|---|---|---|---|
| 1 | Conductor (Cu) | Plain annealed copper, Class 1/2 (typical Class 2 stranded), nominal 25 mm² | Typical stranding 7 × 2.14 mm (7/2.14); Ø ≈ 6.4 mm (6.1–6.4 mm); max. DC resistance ≤ 0.727 Ω/km @ 20 °C (GB/T 3956) |
| 2 | Insulation (XLPE) | Cross-linked polyethylene (thermoset, cross-linked for heat resistance) | Nominal thickness 0.9 mm; Ø over insulation ≈ 8.2 mm; 90 °C continuous rating |
| 3 | Outer sheath (PVC) | Flame-retardant PVC, ST2 type, black | Nominal thickness 1.4 mm; overall Ø ≈ 10.5–10.8 mm; flame retardance ZC (ZR) |
Overall diameter ≈ 10.8 mm (10.5–10.8 mm across manufacturers) and weight ≈ 298 kg/km (290–298 kg/km).
2. Product Performance
- Electrical: Conductor DC resistance ≤ 0.727 Ω/km @ 20 °C; routine AC withstand test 3.5 kV / 5 min without breakdown; finished-cable insulation resistance ≥ 36.7 MΩ·km @ 20 °C (typical reference); XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km.
- Thermal: Max. continuous conductor temperature 90 °C; short-circuit (≤ 5 s) 250 °C; ambient service −20 to +45 °C; laying temperature not below 0 °C.
- Flame retardance: "ZR" = flame-retardant, default class ZC per GB/T 19666; passes single-cable vertical flame test (GB/T 18380.12) and class-C bunched test (GB/T 18380.35: ≥ 1.5 L/m non-metallic volume, 20 min flame, char extent ≤ 2.5 m).
- Ampacity (reference): ≈ 155 A in air (single core, 30 °C); direct burial ≈ 130–160 A depending on soil thermal resistivity — always apply correction factors per GB/T 16895 / IEC 60364.
- Mechanical/installation: min. bending radius 20 × OD (single-core); site DC withstand test after installation 4U0 = 2.4 kV / 15 min (per Q/GDW 13244.1-2018 practice).
3. Key Parameters
- Rated voltage 0.6/1 kV (Um = 1.2 kV); 50 Hz; single core; 25 mm²
- Conductor: Cu Class 2, 7 × 2.14 mm, Ø ≈ 6.4 mm; DC R ≤ 0.727 Ω/km
- Insulation: XLPE, 0.9 mm; Sheath: flame-retardant PVC ST2, 1.4 mm
- Weight ≈ 298 kg/km; OD ≈ 10.8 mm; length 100 m per coil/drum
| ZR-YJV 1×25 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV) | |||||
| Construction: CU / XLPE / PVC • Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance) • Nominal values for reference — confirm against factory test certificate | |||||
| No. | Category | Parameter | Value | Unit | Notes / Standard Reference |
| A. Product Identification | |||||
| 1 | Identification | Product name | Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable | — | Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing) |
| 2 | Identification | Model designation | ZR-YJV 1×25 | — | Cu / XLPE / PVC |
| 3 | Identification | Design standards | GB/T 12706.1; IEC 60502-1 | — | Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence |
| 4 | Identification | Rated voltage U0/U | 0.6/1 | kV | Max system voltage Um = 1.2 kV |
| 5 | Identification | Rated frequency | 50 | Hz | AC power distribution |
| 6 | Identification | Number of cores | 1 | — | Single-core cable |
| 7 | Identification | Nominal cross-sectional area | 25 | mm² | Nominal conductor cross-section per GB/T 3956 |
| B. Cable Construction (from conductor to outer sheath) | |||||
| 8 | Conductor | Material | Plain annealed copper (Cu) | — | High-conductivity electrolytic / oxygen-free copper |
| 9 | Conductor | Conductor class | Class 1 or Class 2 (typical: Class 2, stranded) | — | GB/T 3956 / IEC 60228 |
| 10 | Conductor | Typical stranding construction | 7 wires × 2.14 mm (7/2.14) | — | Class 2 round stranded; nominal section ≈ 25 mm² |
| 11 | Conductor | Conductor diameter | ≈ 6.4 | mm | 6.1–6.4 mm per manufacturer tables (Qifan 6.1 mm; 7/2.14 → ≈ 6.4 mm) |
| 12 | Conductor | Max. DC resistance of conductor at 20 °C | 0.727 | Ω/km | GB/T 3956, Class 2 copper; acceptance criterion for 25 mm² |
| 13 | Insulation | Material | Cross-linked polyethylene (XLPE) | — | Thermally cross-linked; natural/transparent colour |
| 14 | Insulation | Nominal insulation thickness | 0.9 | mm | GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 25 mm²) |
| 15 | Insulation | Diameter over insulation | ≈ 8.2 | mm | ≈ 6.4 + 2 × 0.9 (calculated) |
| 16 | Sheath | Material | Flame-retardant polyvinyl chloride (PVC, ST2 type) | — | Colour: black (or as ordered) |
| 17 | Sheath | Nominal sheath thickness | 1.4 | mm | GB/T 12706.1 / IEC 60502-1 |
| 18 | Dimensions | Approx. overall diameter | 10.5–10.8 | mm | Qifan 10.8 mm; Weiguang 10.5 mm |
| 19 | Dimensions | Approx. cable weight | ≈ 298 | kg/km | Range 290–298 kg/km across manufacturers (Qifan 298; Weiguang 290) |
| C. Electrical Performance | |||||
| 20 | Electrical | Max. DC conductor resistance at 20 °C | 0.727 | Ω/km | GB/T 3956; routine measurement |
| 21 | Electrical | Power-frequency withstand voltage (routine test) | 3.5 kV / 5 min, no breakdown | — | AC 50 Hz; per GB/T 12706.1 / IEC 60502-1 |
| 22 | Electrical | Insulation resistance (finished cable, 20 °C) | ≥ 36.7 | MΩ·km | Typical finished-cable requirement for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method |
| 23 | Electrical | XLPE volume resistivity at 20 °C | ≥ 1 × 10¹² | Ω·cm | Material-level requirement (manufacturer reference) |
| 24 | Electrical | Capacitance (single-core, approx.) | ≤ 0.45 | μF/km | Manufacturer reference value |
| 25 | Electrical | Reference ampacity — in air, 30 °C, single core | ≈ 155 | A | Reference value (Guangheng); depends on laying, grouping, ambient — apply correction factors per GB/T 16895 / IEC 60364 |
| 26 | Electrical | Reference ampacity — direct burial, 25 °C | ≈ 155 | A | Reference value; depends on soil thermal resistivity and depth (reference range 130–160 A) |
| D. Thermal Performance | |||||
| 27 | Thermal | Max. continuous conductor temperature | 90 | °C | XLPE insulation temperature class |
| 28 | Thermal | Max. conductor temperature under short-circuit (≤ 5 s) | 250 | °C | Per GB/T 12706.1 / IEC 60502-1 |
| 29 | Thermal | Ambient service temperature range | -20 to +45 | °C | Per Qifan datasheet; check project specification |
| 30 | Thermal | Min. installation (laying) temperature | 0 | °C | Pre-heat the cable if ambient is below 0 °C |
| E. Flame Retardance (ZR) | |||||
| 31 | Flame retardance | Flame-retardant class | ZC (class C) by default for "ZR" | — | GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH) |
| 32 | Flame retardance | Single-cable vertical flame-spread test | Pass | — | GB/T 18380.12 |
| 33 | Flame retardance | Bunched flame-spread test (class C) | Char extent ≤ 2.5 m above burner bottom edge | — | GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min |
| 34 | Flame retardance | Halogen content | Halogen-containing (PVC) | — | For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type |
| F. Installation | |||||
| 35 | Installation | Min. bending radius — single-core cable | 20 × OD | — | Qifan & Huaneng datasheets; some manufacturers specify 15 × OD; OD = actual cable diameter |
| 36 | Installation | Laying methods | Conduit, tray, cable trench, tunnel, duct, supported/suspended aerial | — | Also direct burial with mechanical protection where permitted |
| 37 | Installation | Site withstand test after installation | DC 4U0 = 2.4 kV, 15 min (recommended) | — | Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project |
| G. Packing & Delivery | |||||
| 38 | Packing | Standard delivery length | 100 m per coil/drum (or as ordered) | — | Typical industry practice; custom lengths available |
| 39 | Packing | Cable marking | Model, rated voltage, manufacturer, year of manufacture, sequential length marks | — | Per GB/T 6995 / project specification |
| 40 | Packing | Packing form | Wooden drum / coil / export packing | — | As per customer requirement |

4. Test Parameters
| ZR-YJV 1×25 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1) | ||||
| Test Stage | Test Item | Method / Standard | Requirement / Acceptance Criterion | Notes |
| Routine test | Conductor DC resistance measurement | GB/T 3956 (IEC 60228) | ≤ 0.727 Ω/km at 20 °C | Measured on every production length |
| Routine test | Power-frequency withstand voltage | GB/T 12706.1 / IEC 60502-1 | 3.5 kV AC, 5 min, no breakdown | Applied between conductor and water/earth; 50 Hz |
| Routine test | Construction check — insulation & sheath thickness, outer diameter | GB/T 2951 | Within GB/T 12706.1 tolerances | Insulation ≥ 0.9 mm nominal; sheath ≥ 1.4 mm nominal |
| Sample test | Hot set (thermal elongation) test — XLPE insulation | GB/T 12706.1 §16.3.13 / GB/T 2951.11 | 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % | Verifies degree of cross-linking |
| Sample test | Conductor construction & diameter check | GB/T 3956 | Class 2; 7 × 2.14 mm; Ø ≈ 6.4 mm | Sampled per batch |
| Type test | Single-cable vertical flame-spread test (flame retardance) | GB/T 18380.12 | No flame spread; charring does not reach top reference point | ZR / ZC flame-retardant property |
| Type test | Bunched flame-spread test, class C | GB/T 18380.35 | Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m | Class ZC per GB/T 19666 |
| Type test | Bending test (mechanical) | GB/T 12706.1 | Bend around specified mandrel without insulation/sheath damage | Mandrel diameter related to cable OD |
| Post-installation | DC withstand test after installation | Q/GDW 13244.1-2018 (recommended practice) | 4U0 = 2.4 kV DC, 15 min, no breakdown | For new installations; verify project specification |
| Optional | Insulation resistance measurement at 20 °C | Manufacturer test method | ≥ 36.7 MΩ·km (typical finished-cable value) | Not a routine item in GB/T 12706.1; confirm with factory |
| Optional | XLPE volume resistivity at 20 °C | Manufacturer / material test | ≥ 1 × 10¹² Ω·cm | Material-level reference |
5.Cable Cross Section

| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Cu) | Annealed copper, Class 2 stranded — 7 × 2.14 mm (7/2.14), nominal 25 mm² | — | ≈ 6.4 (Ø) | Current-carrying element; max DC resistance ≤ 0.727 Ω/km @ 20 °C |
| 2 | Insulation (XLPE) | Cross-linked polyethylene | 0.9 | ≈ 8.2 (Ø over insulation) | Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min |
| 3 | Outer sheath (PVC) | Flame-retardant PVC, ST2 type, black | 1.4 | ≈ 10.8 (Ø overall) | Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666 |
| Key Dimensions & Properties | |||||
| Overall diameter | 10.5–10.8 | mm | Qifan 10.8 mm; Weiguang 10.5 mm | ||
| Approx. cable weight | ≈ 298 | kg/km | Range 290–298 kg/km across manufacturers | ||
| Rated voltage | 0.6/1 | kV | AC 50 Hz; max system voltage Um = 1.2 kV | ||
| Max conductor temperature | 90 / 250 | °C | Continuous / short-circuit (≤ 5 s) | ||
| Min. bending radius (single-core) | 20 × OD | — | OD = actual cable diameter | ||
| Flame-retardant class | ZC (ZR) | — | GB/T 19666 | ||
6. Usage Precautions
- Install only when ambient ≥ 0 °C; pre-heat the cable if colder.
- Min. bending radius 20 × OD — avoid sharp bends and kinking.
- ZR-YJV contains halogen (PVC); for LSZH requirements choose WDZ-YJY.
- Ampacity must be derated for grouping, ambient temperature and burial conditions.
- Perform the site DC test only after verifying insulation integrity; avoid prolonged overvoltage.
- Store on drums/coils, away from direct sunlight and mechanical damage.
7. Application Range
Indoor/outdoor distribution and branch circuits at 0.6/1 kV in industrial plants, commercial buildings, residential complexes, substations and similar installations — in conduits, trays, trenches, tunnels and ducts; suitable where flame-retardant performance is required (not for direct sunlight exposure unless UV-protected).

8. Package

9. Factory Overview
