1x185mm² Single Core Cable Stranded Copper Conductor Pvc Sheath Fire Resistant C Level
Product Summary
Product Details
1x185mm2 Single Core Cable
,Single Core Cable Fire Resistant
,pvc sheath cable 1944kg/km
Product Description
0.6/1kV ZC-YJV 1x185mm² Stranded Copper Conductor XLPE Insulation PVC Outer Sheath Fire Resistant C Level
Technical Datasheet — ZC-YJV 0.6/1 kV 1×185 mm²
1. Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant, Class C (bundled combustion test) |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC (polyvinyl chloride) outer sheath |
|
0.6/1 kV |
Rated voltage U₀/U = 600/1000 V; max. system voltage Uₘ = 1.2 kV |
|
1×185 mm² |
Single core, nominal copper conductor area 185 mm² |
|
Construction |
Unarmoured, non-screened, round cable |
2. Applicable Standards
- GB/T 12706.1-2020 (equivalent to IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
- GB/T 3956 / IEC 60228 — Conductors
- GB/T 19666-2019 — Flame retardant & fire resistant cables
- GB/T 18380.3 — Bundled flame propagation test (Class C)

3. Product Components / Construction (inside → outside)
- Conductor — Bare annealed copper, Class 2 stranded compacted circular (37 wires typical; GB/T 3956 requires min. 30 wires for compacted round 185 mm²)
- Conductor screen — Not required for 0.6/1 kV Class 2; normally omitted
- Insulation — XLPE compound, extruded (black / red / blue etc. on request)
- Insulation thickness (nominal) — 1.6 mm (GB/T 12706 for 185–240 mm² at 0.6/1 kV)
- Filler / binder — Generally none for single-core; thin non-hygroscopic binder tape optional per factory process
- Outer sheath — Flame-retardant PVC compound (ZC grade)
- Sheath thickness (nominal) — 1.7 mm
- Sheath colour — Black (standard); red / yellow-green / blue / brown available
- Armour — None
- Metallic screen — None

4. Dimensional Data
|
Item |
Typical value |
Remarks |
|---|---|---|
|
Conductor nominal area |
185 mm² |
— |
|
Conductor construction |
Class 2 compacted stranded Cu, 37×∅2.50 mm (typical) |
|
|
Conductor diameter (approx.) |
16.5 mm |
|
|
Insulation nominal thickness |
1.6 mm |
|
|
Diameter over insulation (approx.) |
19.7 mm |
16.5 + 2×1.6 |
|
Sheath nominal thickness |
1.7 mm |
|
|
Overall cable diameter |
22.0 – 24.0 mm |
Typical ~23.9 mm; Nexans 22.0 mm, Libo 22.66 mm, Alfanar 23.2 mm, Class 5 24.0 mm |
|
Approx. weight |
1750 – 1944 kg/km |
1750 (Nexans), 1885 (structure table), 1944 (ZC-YJV62 sample) |
|
Cable shape |
Round |
— |

5. Insulation Data
- Material: XLPE (cross-linked polyethylene)
- Nominal thickness: 1.6 mm (GB/T 12706, 185–240 mm² class)
- Long-term service temperature rating: 90 °C
- Short-circuit temperature rating (≤5 s): 250 °C
- Emergency overload temperature: 105 °C (limited duration)
- Dielectric strength: Pass 3.5 kV AC / 5 min routine test; 4.0 kV type test
- Volume resistivity @90 °C: ≥ 10¹² Ω·cm (typical XLPE)
- Insulation resistance constant (R₀·L @90 °C): ≈ 3.67 MΩ·km
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene), Type TR-XLPE |
|
Outer sheath material |
PVC (polyvinyl chloride), Type ST₂ |
|
Long-term service temp. |
90 °C (continuous, XLPE insulation) |
|
Short-circuit temp. (≤5 s) |
250 °C (Cu conductor limit for XLPE) |
|
Emergency overload temp. |
130 °C (short term, ≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV (routine test, 0.6/1 kV class) |
|
Dielectric strength |
≥ 20 kV/mm (room temp.) |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
6. Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test (conductor-to-sheath) |
|
DC resistance @20 °C |
≤ 0.0991 Ω/km |
GB/T 3956 Class 2 Cu max, 185 mm² |
|
AC resistance @90 °C (est.) |
≈ 0.127 Ω/km |
per core |
|
Current rating in air (30 °C) |
430 A |
single-core, touching, in free air |
|
Current rating in tray (30 °C) |
410 A |
single-core, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
380 A |
single-core, direct buried |
|
Current rating in conduit (30 °C) |
360 A |
single-core in conduit |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 20.4 kA (20,400 A) |
185 mm² Cu |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.22 µF/km |
XLPE insulation |
|
Inductive reactance (approx.) |
≈ 0.10 Ω/km |
at 50 Hz, single-core |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 1×185 mm² at 430 A, single-phase 230 V → max load ≈ 99 kW; three-phase 400 V → max load ≈ 298 kW. Suitable for main power distribution, feeder circuits, and large motor supply.
7. Temperature Characteristics
- Max. conductor operating temperature (continuous): 90 °C
- Max. conductor temp. during short circuit (≤5 s): 250 °C
- Emergency overload temperature: 105 °C (limited duration, general XLPE practice)
- Min. ambient temperature during installation: 0 °C (below 0 °C requires pre-heating)
- Service ambient temperature range: −20 °C to +90 °C (sheath/environment)
- Flame retardant class: Category C, bundled flame test, self-extinguishing, limited flame spread per GB/T 19666
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C (Cu conductor, XLPE limit) |
|
Emergency overload temp. |
130 °C (≤1 h, not recommended for continuous) |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (XLPE insulation, PVC sheath) |
|
Flexing temp. range |
0 °C to +90 °C |
|
Fire survival |
Standard (flame retardant C, single cable) |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
IEC 60332-3-24 Category C (bundled, 3.5 L/m cable volume, self-extinguishing) |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC sheath) |
|
Fire survival (circuit integrity) |
Not applicable (standard version) |
8. Mechanical & Installation Parameters
- Minimum bending radius (single-core unarmoured): ≥ 20 × overall diameter → ≈ 440–480 mm at Ø22–24 mm
- Maximum pulling tension (copper conductor only): 50 N/mm² × 185 mm² = 9250 N
- PVC sheath pulling limit: significantly lower — avoid direct sheath grip; use conductor pulling eye
- Direct burial: Allowed in non-aggressive soil without heavy impact; use sand bed + warning tape, deeper layout or conduit under roads
- Magnetic conduit warning (AC single-core): Must NOT be laid in magnetic steel pipe/conduit in AC circuits; use non-magnetic conduit or trefoil/flat arrangement to avoid eddy-current heating
- Elevation difference: No limitation for XLPE insulated cable.
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 327 mm at Ø21.8 mm |
unarmoured single-core |
|
Max. pulling tension |
2,775 N (185 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding and warning tape) |
unarmoured — protect from mechanical damage |
|
Surface mounting |
Good (cable tray, ladder, cleats) |
— |
|
Conduit ID |
≥ 40 mm |
— |
|
Fixing |
cable cleats, clamps, tray |
— |
|
Impact resistance |
Low (PVC sheath only) |
protect with conduit or mechanical cover in exposed areas |
|
Water resistance |
Moisture-resistant (XLPE + PVC) |
not waterproof |
|
UV resistance |
Poor (PVC degrades in sunlight) |
indoor or buried use; for outdoor aerial use UV-stabilised sheath or conduit |
|
Flex life |
Low (Class 2 stranded, not for repeated flexing) |
fixed installation only |
|
Termination note |
Crimp lug or compression terminal; no ferrules needed (Class 2 stranded) |
— |

9. Scope of Application / Usage Range
The ZC-YJV 0.6/1 kV 1×185 mm² cable is intended for fixed installation in low-voltage power distribution & transmission systems up to 1.2 kV system voltage, where basic flame-retardant (Class C) performance is required but fire-survival (fire-resistant) function is not mandated.
Typical applicable locations:
- Indoor power distribution rooms, switchboards, busbar risers in high-rise buildings
- Cable trays, cable ducts, cable trenches & shafts in commercial / residential buildings
- Fixed wiring in industrial plants, warehouses, light/medium machinery feeders
- Direct buried routes in non-aggressive soil with low mechanical impact
- Street lighting, PV inverter AC output / combiner circuits, EV fast-charger feeders (DC side requires polarity check)
- Metro/rail auxiliary power, stations, general civil engineering projects requiring ZC flame-retardant grade
Not suitable for:
- Heavy tensile / armour-protected routes → use YJV22 / ZC-YJV22
- Fire-survival emergency circuits → use NH-ZC-YJV
- Highly corrosive / hydrocarbon-rich environments without extra barrier
- Magnetic conduit AC single-core runs (eddy-current risk)
- Oil-filled / submerged without dedicated design.

Key engineering notes for this size
- Insulation thickness jumps at 185 mm² — it is 1.6 mm (the 120 mm² value of 1.2 mm does not apply here). This is a common design error to avoid.
- Current rating is formation-dependent — single-core 185 mm² in air ranges 510–661 A depending on flat/trefoil/spaced; always state laying method. For budget design, 530 A (air) / 480 A (buried) is conservative.
- Weight is ~1.9 t/km — plan drum handling and tray loading accordingly.
- DC resistance 0.0991 Ω/km is the hard compliance limit (GB/T 3956 Class 2); real cables typically 5–15 % below.
FAQ
1. Product Identification & Naming