Mega Industrial Main Cable YJV22 3x120mm² 8.7/15kV Armored MV XLPE
Product Summary
Product Details
yjv22 heavy aluminum cable
,yjv22 medium voltage power cable
,15kv heavy aluminum cable
Product Description
Mega Industrial Main Cable YJV22 3x120mm² 8.7/15kV Armored MV XLPE
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC inner bedding / outer sheath |
|
22 |
Steel tape armour (double steel tape, overlapping) + PVC sheath |
|
8.7/10 kV |
Rated voltage U₀/U = 8.7/10 kV; Uₘ = 12 kV |
|
8.7/15 kV |
Rated voltage U₀/U = 8.7/15 kV; Uₘ = 17.5 kV |
|
3×120 mm² |
Three power cores, each 120 mm² (3-core, no neutral, no PE) |
Construction: XLPE insulated, steel-tape armoured, PVC sheathed, three-core medium-voltage power cable.
Applicable Standards
- GB/T 12706.2-2020 / IEC 60502-2 — Power cables with extruded insulation and their accessories for rated voltages from 6 kV up to 30 kV
- GB/T 3956 / IEC 60228 — Conductors (Class 2 stranded circular)
- GB/T 2951 / IEC 60811 — Insulating and sheathing materials — Common test methods
- GB/T 3048 — Test methods for electric cables
- GB/T 18380 / IEC 60332 — Flame retardant tests (Category C or B available)


YJV22-3×120 mm² 8.7/10 kV (and 8.7/15 kV) — Cable Specification & Engineering Data
1. Product Overview & Rating Summary. YJV22-3×120 is a medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 120 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV primary distribution feeders serving 4000–6300 kVA distribution transformers and medium-voltage motors in the 1000–1600 kW range. Finished diameter is about 82 mm (10 kV) and nominal mass about 11200 kg/km (≈ 1120 kg per 100 m). With all three cores loaded, the cable carries about 340 A in free air at 25 °C (engineering estimate).
2. Layer-by-Layer Construction (Conductor to Outer Jacket).
| Layer | Construction | Wall | Diameter |
|---|---|---|---|
| Conductor (Cu) ×3 | Compacted stranded annealed Cu, Class 2 — 30×2.25 mm equivalent | — | ≈ 14.0 mm |
| Conductor screen | Extruded semi-conducting XLPE, co-extruded | ≈ 0.8 mm | ≈ 15.6 mm |
| XLPE insulation | Cross-linked polyethylene, triple-extruded | 4.5 mm (10 kV) / 5.5 mm (15 kV) | ≈ 24.6 / ≈ 26.6 mm |
| Insulation screen | Strippable semi-conducting XLPE | ≈ 0.8 mm | ≈ 26.2 / ≈ 28.2 mm |
| Copper-tape screen | 0.1 × 25 mm annealed Cu tape, lapped | ≈ 0.1 mm tape | ≈ 26.4 / ≈ 28.4 mm |
| Filler & bedding | PP/PE rope + non-woven binder | — | ≈ 70 / ≈ 74 mm bundle |
| Inner sheath | PVC/PE extruded bedding | ≈ 1.5 mm | ≈ 73 / ≈ 77 mm |
| Steel armour (type 22) | Double galvanised steel tape, helical lapped | 2 × 0.5 mm | ≈ 74 / ≈ 78 mm |
| PVC outer jacket | ST2 PVC, flame-retardant, black | 2.5 mm | ≈ 82 / ≈ 85 mm (finished) |
3. Electrical Characteristics. Each 120 mm² conductor is held to a maximum DC resistance of 0.153 Ω/km at 20 °C, rising to about 0.20 Ω/km at the 90 °C operating point. Every length survives the routine 21.5 kV AC power-frequency proof held for five minutes (30.5 kV for the 15 kV grade). Partial discharge at 1.5 U0 must not exceed 20 pC. Dissipation factor tan δ ≤ 0.001 at U0. Insulation resistance ≥ 1000 MΩ·km, typical capacitance ≈ 0.48 μF/km. Impulse withstand (BIL) is 75 kV for the 10 kV grade and 95 kV for the 15 kV grade. With all three cores energised, reference loading is about 340 A in free air at 25 °C, about 335 A direct-buried.
Insulation Data
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) |
|
Nominal thickness |
4.5 mm |
|
Long-term service temp. |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C |
|
Routine test voltage (AC, 5 min) |
22 kV (8.7/10 kV); 30.5 kV (8.7/15 kV) |
|
Type-test voltage (AC) |
30 kV (8.7/10 kV); 45 kV (8.7/15 kV) |
|
Partial discharge test |
≤ 10 pC at 1.73 U₀ (15 kV) |
|
Tan δ (dissipation factor) |
≤ 0.004 at 20 °C |
Electrical Parameters
|
Parameter |
Value (8.7/10 kV) |
Value (8.7/15 kV) |
Note |
|---|---|---|---|
|
Rated voltage U₀/U |
8.7 / 10 kV |
8.7 / 15 kV |
— |
|
Max. system voltage Uₘ |
12 kV |
17.5 kV |
— |
|
Test voltage AC (5 min) |
22 kV |
30.5 kV |
Routine |
|
Type-test voltage |
30 kV |
45 kV |
— |
|
DC resistance @20 °C |
≤ 0.153 Ω/km |
≤ 0.153 Ω/km |
GB/T 3956 Class 2 max, 120 mm² |
|
AC resistance @90 °C (est.) |
≈ 0.195 Ω/km |
≈ 0.195 Ω/km |
per core |
|
Capacitance (approx.) |
≈ 0.35 µF/km |
≈ 0.35 µF/km |
per core to screen |
|
Inductive reactance (approx.) |
≈ 0.11 Ω/km |
≈ 0.11 Ω/km |
at 50 Hz, 3-core |
|
Current rating in air (30 °C) |
≈ 265 – 305 A |
≈ 265 – 305 A |
per core, 3-core |
|
Current rating buried (20 °C) |
≈ 235 – 270 A |
≈ 235 – 270 A |
direct buried, 3-core |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 12.0 kA (12000 A) |
≈ 12.0 kA (12000 A) |
120 mm² |
|
Frequency |
50/60 Hz AC |
50/60 Hz AC |
— |
Reference values: 120 mm² at 285 A, 3-phase 10 kV → max balanced load ≈ 4.94 MVA. Voltage drop at 285 A ≈ 5.6 V/km per core (≈0.056% per 100 m).
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (with PVC sheath) |
|
Fire survival |
Standard (non-fire-rated); optional fire-resistant version available (ZC-YJV22) |
4. Thermal Response & Flame Behaviour. XLPE insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −20 and +50 °C. PVC jacket provides flame-retardant performance per GB/T 18380.34 class A. Short-circuit rating at 250 °C for 1 s is about 17.4 kA for the 120 mm² copper conductor. Thermal resistance of reference burial soil is 1.2 K·m/W.
Fire Performance (YJV22 — Standard)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.3 Category C (ZC), Category B (ZB) available |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC sheath) |
|
Fire survival (circuit integrity) |
Not applicable (standard version); use ZA-YJV22 for flame-retardant A |
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 1230 mm for this size. The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends, or cross-bonded for longer routes). MV heat-shrink or cold-shrink termination kits are mandatory — do not treat this as an LV cable. Laying temperature must not fall below 0 °C; reels must be pre-heated in cold weather. At about 1120 kg per 100 m, the cable requires heavy-duty drum jacks, winches and rated pulling gear.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 953 mm at Ø63.5 mm |
static installation |
|
Max. pulling tension |
7200 N |
use proper pulling grips |
|
Direct burial |
Suitable |
steel tape armour provides mechanical protection |
|
Conduit ID |
≥ 1.5 × OD → ≥ 96 mm; use 100 mm or 110 mm |
— |
|
Fixing |
cable clamps, steel straps |
— |
|
Impact resistance |
High |
steel tape armour absorbs mechanical shock |
|
Water resistance |
Moisture-resistant (PVC sheath + inner bedding) |
not fully watertight; use YJV32 for wet locations |
|
Armour type |
Double steel tape, overlapping |
galvanized or mill finish |
|
Armour short-circuit rating |
≈ 5 kA (1 s, steel tape) |
— |
6. Typical Service Applications. This YJV22-3×120 MV cable is used in 10 kV / 15 kV primary distribution networks serving very heavy industrial and utility loads: 4000–6300 kVA distribution transformer primary feeds, substation 10 kV outgoing main feeders to heavy industrial plants, 10 kV motor branch feeds for MV motors in the 1000–1600 kW range (large pump stations, compressor stations, mill drives, crushers, rolling-mill main drives), steel-mill / cement-plant / paper-mill / chemical-plant 10 kV power distribution mains, high-rise commercial and hospital 10 kV main risers, large data-centre and district-cooling 10 kV switchboard feeders, mining and quarry 10 kV heavy-duty power supply lines, direct-buried urban 10 kV primary network feeders, PV / wind-farm 10 kV collection mains, and any circuit where mechanical protection against crush or impact is required. Approved installation methods include direct burial, cable tray, concrete duct, and indoor MV cable trench.

7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance ≤ 0.153 Ω/km at 20 °C, the 21.5 kV AC / 5 min withstand (30.5 kV for 15 kV grade), partial discharge ≤ 20 pC at 1.5 U0, tan δ ≤ 0.001, insulation resistance ≥ 1000 MΩ·km, conductor continuity across all three cores, steel-armour and copper-screen continuity, and dimensional inspection. Sample and type tests comprise impulse withstand at ±75 kV (or ±95 kV for 15 kV), heating-cycle load-loss test, bending at 15 × OD, short-circuit to 250 °C, flame spread GB/T 18380.34 class A, and voltage re-test after thermal ageing. A factory test certificate accompanies each drum.
Cable Parameters
| YJV22-3×120 mm² 8.7/10 kV (and 8.7/15 kV variant) — Full Parameter Sheet | ||||
| Medium-voltage power cable · Cu conductor / XLPE insulation / copper-tape screen / double-steel-tape armour (type 22) / PVC outer sheath · per GB/T 12706.2 · 3 cores · finished Ø ≈ 82 mm (10 kV) / ≈ 85 mm (15 kV) | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | YJV22 | — | Cu conductor / XLPE insulation / double-steel-tape armour / PVC outer sheath | |
| Rated voltage (U0/U) | 8.7/10 | kV | AC 50 Hz; Um = 12 kV (10 kV grade) | |
| Alternative voltage grade | 8.7/15 | kV | AC 50 Hz; Um = 17.5 kV (15 kV grade) — thicker XLPE | |
| Number of cores | 3 × 120 | — | 3 phase cores (120 mm²) — no separate neutral in MV cable | |
| Conductor material | Annealed copper, compacted stranded | — | Class 2 stranded per GB/T 3956 | |
| Conductor screen | Extruded semi-conducting XLPE | — | Conductor screen layer (radial field control) | |
| Insulation material | Cross-linked polyethylene (XLPE) | — | 90 °C continuous, 250 °C short-circuit | |
| Insulation screen | Extruded semi-conducting, strippable | — | Outer screen layer | |
| Metallic screen | Copper tape, lapped | — | 0.1 × 25 mm Cu tape; equipotential earth | |
| Armour | Double galvanised steel tape | — | Type 22 armour — mechanical protection | |
| Outer sheath | PVC (ST2), flame-retardant | — | UV- and abrasion-resistant | |
| Standard reference | GB/T 12706.2 / IEC 60502-2; GB/T 3956 | — | Medium-voltage power cables 1.8/3 kV to 26/35 kV | |
| 02 · Conductor | ||||
| Stranding — 120 mm² | Compacted stranded copper | — | Class 2, circular compacted | |
| Strand count (typical) | 30 × 2.25 mm (or equivalent) | — | Compacted after stranding | |
| Conductor diameter | ≈ 14.0 | mm | After compacting (est.) | |
| DC resistance @ 20 °C | ≤ 0.153 | Ω/km | Maximum per GB/T 3956 Class 2 | |
| AC resistance @ 50 Hz (≈ 90 °C) | ≈ 0.20 | Ω/km | Skin/proximity effect included | |
| Conductor screen thickness | ≈ 0.8 | mm | Extruded semi-conducting layer | |
| 03 · Insulation | ||||
| Insulation type | Cross-linked polyethylene (XLPE) | — | Extruded, triple-layer co-extrusion | |
| Insulation thickness — 8.7/10 kV | 4.5 | mm | Nominal, per GB/T 12706.2 | |
| Insulation thickness — 8.7/15 kV | 5.5 | mm | Thicker for 15 kV grade | |
| Core Ø over insulation — 10 kV | ≈ 24.6 | mm | 14.0 + 2×(0.8+4.5+0.8) | |
| Core Ø over insulation screen — 15 kV | ≈ 26.6 | mm | 14.0 + 2×(0.8+5.5+0.8) | |
| Insulation screen thickness | ≈ 0.8 | mm | Strippable semi-conducting | |
| Impulse withstand (BIL) — 10 kV | 75 | kV | Lightning impulse test | |
| Impulse withstand (BIL) — 15 kV | 95 | kV | Lightning impulse test | |
| 04 · Metallic Screen & Filler | ||||
| Screen material | Annealed copper tape | — | Lapped with overlap | |
| Screen tape dimensions | 0.1 × 25 | mm | Two layers lapped (typical) | |
| Screen function | Equipotential earth / fault-current path | — | Earthed at terminations | |
| Filler material | PP / jute rope, flame-retardant | — | Fills interstices for round cable | |
| Bedding / binder tape | Semi-conducting or non-woven tape | — | Holds bundle; anti-corrosion layer | |
| Assembled bundle Ø — 10 kV | ≈ 70 | mm | Before inner sheath (est.) | |
| Assembled bundle Ø — 15 kV | ≈ 74 | mm | Before inner sheath (est.) | |
| 05 · Inner Sheath & Armour | ||||
| Inner sheath / bedding | PVC or PE extruded | — | Corrosion barrier under armour | |
| Inner sheath thickness | ≈ 1.5 | mm | Over bundle | |
| Armour type | Double steel tape (type 22) | — | Double-tape helical armour | |
| Armour tape thickness | 2 × 0.5 | mm | Galvanised steel, lapped | |
| Armour function | Mechanical protection against crush / impact | — | Permits direct burial / tray | |
| Armour diameter — 10 kV | ≈ 74 | mm | Over inner sheath (est.) | |
| 06 · Outer Sheath | ||||
| Jacket material | PVC, ST2, flame-retardant | — | GB/T 12706.1 | |
| Jacket thickness | 2.5 | mm | Minimum over armour | |
| Overall finished diameter — 10 kV | ≈ 82 | mm | Cross-referenced industry sample | |
| Overall finished diameter — 15 kV | ≈ 85 | mm | Thicker insulation version | |
| Approx. cable mass — 10 kV | ≈ 11200 | kg/km | Cu + XLPE + steel + PVC | |
| Approx. cable mass — 15 kV | ≈ 11400 | kg/km | Heavier due to thicker insulation | |
| Jacket colour | Black (standard) | — | UV-resistant carbon-black PVC | |
| Mass per 100 m — 10 kV | ≈ 1120 | kg/100 m | For drum loading | |
| 07 · Electrical | ||||
| Rated voltage U0/U | 8.7/10 | kV | AC 50 Hz; Um = 12 kV | |
| Maximum system voltage Um (10 kV) | 12 | kV | — | |
| DC resistance @ 20 °C | ≤ 0.153 | Ω/km | 120 mm² Cu Class 2 | |
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE at 20 °C | |
| Capacitance (typical) | ≈ 0.48 | μF/km | Per core (est.) | |
| Dissipation factor tan δ (at U0) | ≤ 0.001 | — | XLPE, 20 °C | |
| Routine test voltage (AC) — 10 kV | 21.5 kV / 5 min | — | Power-frequency withstand | |
| Routine test voltage (AC) — 15 kV | 30.5 kV / 5 min | — | Power-frequency withstand | |
| Air ampacity @ 25 °C | ≈ 340 | A | 3 cores loaded, Cu, in free air (est.) | |
| Buried ampacity @ 25 °C soil | ≈ 335 | A | 3 cores loaded, Cu, direct burial (est.) | |
| 08 · Thermal & Fire | ||||
| Max continuous conductor temp. | 90 | °C | Normal service | |
| Short-circuit temp. (≤ 5 s) | 250 | °C | XLPE limit | |
| Fire behaviour | Flame-retardant (PVC jacket) | — | GB/T 18380.34 class A | |
| Service ambient range | −20 to +50 | °C | Fixed installation | |
| Thermal resistance (soil) | 1.2 | K·m/W | Reference burial conditions | |
| Short-circuit rating (1 s) | ≈ 17.4 | kA | 120 mm² Cu at 250 °C | |
| 09 · Installation | ||||
| Min bending radius | ≥ 15 × OD ≈ 1230 | mm | Fixed installation (armoured) | |
| Laying temperature | ≥ 0 | °C | Pre-heat below 0 °C | |
| Laying methods | Tray, direct burial, conduit, duct | — | Armour permits direct burial | |
| Armour earthing | Both ends earthed | — | Steel armour must be earthed | |
| Copper screen earthing | At both ends (or single point for cross-bonding) | — | MV cable screen bonding | |
| Termination / joints | Heat-shrink or cold-shrink MV kits | — | Separable connectors / outdoor terminations | |
| Special tools | Cable cutter, crimping tool, torque wrench | — | MV lugs required | |
| 10 · Packing | ||||
| Standard supply length | 500 or 1000 | m/drum | Custom cut lengths available | |
| Reel / packing type | Wooden-steel drum | — | Sealed ends against moisture | |
| Surface marking | YJV22, 8.7/10 kV, 3×120, supplier, year, metre marks | — | Per GB/T 6995 | |
| Storage conditions | Dry, covered, −20 to +40 °C | — | Sealed ends; protect from UV | |
| Transport | Drums secured against rolling | — | Heavy cable, do not drag | |
Cable Test Parameters
| Test Parameters — YJV22-3×120 mm² 8.7/10 kV (and 8.7/15 kV) | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3048.4, 20 °C | ≤ 0.153 Ω/km (120 mm² Cu) | Routine |
| 2 | Power-frequency withstand (routine) | 21.5 kV AC, 5 min (10 kV grade) | No breakdown | Routine |
| 3 | Power-frequency withstand (15 kV grade) | 30.5 kV AC, 5 min | No breakdown | Routine |
| 4 | Partial discharge test | At 1.5 U0 = 13 kV (10 kV grade) | ≤ 20 pC at 1.73 U0 | Routine |
| 5 | Dissipation factor tan δ | At U0, 20 °C | tan δ ≤ 0.001 | Routine |
| 6 | Insulation resistance | GB/T 3048.5 | ≥ 1000 MΩ·km | Routine |
| 7 | Dimensional check | Micrometer / micrometer microscope | Insulation ≥ 4.5 mm (10 kV); jacket ≥ 2.5 mm | Routine |
| 8 | Impulse voltage test (BIL) | ±75 kV, 10 impulses (10 kV grade) | No breakdown at 75 kV | Type |
| 9 | Impulse voltage test (15 kV grade) | ±95 kV, 10 impulses | No breakdown at 95 kV | Type |
| 10 | Heating cycle / load loss | 3 cycles U0 + rated current | No damage; tan δ stable | Type |
| 11 | Bending test | 15 × OD mandrel, 3 cycles | No damage to insulation or sheath | Type |
| 12 | Short-circuit temperature test | 250 °C, 5 s equivalent | No insulation collapse | Type |
| 13 | Flame propagation | GB/T 18380.34 class A | No vertical flame spread | Type |
| 14 | Sheath / armour continuity | Continuity meter | Steel armour and Cu tape continuous | Routine |
| 15 | Voltage test after ageing | After thermal ageing cycle | Withstands 2.5 U0 AC | Type |
| 16 | Marking legibility | Visual + rubbing | YJV22 / 8.7/10 kV / 3×120 / metre marks legible | Routine |
Cable Cross Section Structure

| YJV22-3×120 mm² 8.7/10 kV — Cross-Section Construction Diagram (Schematic) | |||||
| MV layered build-up: Cu conductor → conductor screen → XLPE insulation → insulation screen → Cu-tape screen → filler → bedding → double-steel-tape armour → PVC jacket · 8.7/10 kV (8.7/15 kV variant noted) · finished Ø ≈ 82 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Cu) ×3 | Annealed compacted stranded copper, Class 2 — 30×2.25 mm equivalent per core | — | ≈ 14.0 | Power conductor; R ≤ 0.153 Ω/km at 20 °C |
| 2 | Conductor screen | Extruded semi-conducting XLPE, co-extruded with insulation | ≈ 0.8 | ≈ 15.6 | Eliminates air gaps; smooth radial field |
| 3 | XLPE insulation | Cross-linked polyethylene, triple-layer co-extrusion | 4.5 (10 kV) / 5.5 (15 kV) | ≈ 24.6 / ≈ 26.6 | Main dielectric; 90 °C continuous |
| 4 | Insulation screen | Strippable semi-conducting XLPE | ≈ 0.8 | ≈ 26.2 / ≈ 28.2 | Outer screen; equipotential |
| 5 | Copper-tape screen | Annealed Cu tape, lapped, 0.1 × 25 mm | ≈ 0.1 tape | ≈ 26.4 / ≈ 28.4 | Earth path / fault-current return |
| 6 | Filler & bedding | PP/PE rope filler + non-woven binder tape | — | ≈ 70 / ≈ 74 bundle | Round shape; anti-corrosion bedding |
| 7 | Inner sheath | PVC/PE extruded bedding over bundle | ≈ 1.5 | ≈ 73 / ≈ 77 | Corrosion barrier under armour |
| 8 | Steel armour (type 22) | Double galvanised steel tape, helically lapped | 2 × 0.5 | ≈ 74 / ≈ 78 | Mechanical crush / impact protection |
| 9 | PVC outer jacket | ST2 PVC, flame-retardant, black | 2.5 | ≈ 82 / ≈ 85 (finished) | UV, abrasion and chemical protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter (10 kV) | ≈ 82 | mm | Cross-referenced industry sample | ||
| Finished cable diameter (15 kV) | ≈ 85 | mm | Thicker XLPE variant | ||
| Approx. cable mass (10 kV) | ≈ 11200 | kg/km | Cu + XLPE + steel + PVC | ||
| Approx. cable mass (15 kV) | ≈ 11400 | kg/km | Heavier due to thicker insulation | ||
| Nominal voltage rating | 8.7/10 | kV | AC 50 Hz; Um = 12 kV | ||
| Alternative voltage grade | 8.7/15 | kV | Um = 17.5 kV; 5.5 mm XLPE | ||
| Max continuous conductor temp. | 90 | °C | Normal service | ||
| Short-circuit temp. (≤5 s) | 250 | °C | XLPE limit | ||
| Impulse withstand (BIL) | 75 (10 kV) / 95 (15 kV) | kV | Lightning impulse | ||
| Min bending radius | ≥ 15 × OD ≈ 1230 | mm | Fixed installation | ||
| DC resistance @ 20 °C | ≤ 0.153 | Ω/km | 120 mm² Cu | ||
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE | ||
| Routine test voltage | 21.5 kV AC / 5 min | — | 10 kV grade; 30.5 kV for 15 kV | ||
| Air ampacity @ 25 °C | ≈ 340 | A | 3 cores loaded, Cu (est.) | ||
| Mass per 100 m (10 kV) | ≈ 1120 | kg/100 m | For drum loading | ||
| Schematic — not to exact scale. Finished Ø ≈ 82 mm (10 kV) and weight ≈ 11200 kg/km from cross-referenced industry samples; conductor/insulation diameters per GB/T 12706.2 and GB/T 3956; ampacity 340 A is an engineering estimate. The 8.7/15 kV variant uses 5.5 mm XLPE insulation, ≈ 85 mm OD and ≈ 11400 kg/km. Values marked (est.) require confirmation against the factory test certificate. | |||||
Cable Construction Description
| Construction Description — YJV22-3×120 mm² 8.7/10 kV | |||
| Layer-by-layer MV build-up narrative · 8.7/10 kV (and 8.7/15 kV variant) · Cu / triple-extruded XLPE / Cu-tape screen / double-steel-tape armour / PVC jacket · finished Ø ≈ 82 mm | |||
| 1. Product Identity & Ratings | |||
| YJV22-3×120 is a medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 120 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV primary distribution feeders serving 4000–6300 kVA distribution transformers and medium-voltage motors in the 1000–1600 kW range. Finished diameter is about 82 mm (10 kV) and nominal mass about 11200 kg/km (≈ 1120 kg per 100 m). With all three cores loaded, the cable carries about 340 A in free air at 25 °C (engineering estimate). | |||
| 2. Copper Conductor & Screens | |||
| Each 120 mm² conductor is compacted-stranded annealed copper (Class 2), with a strand-lay diameter of about 14.0 mm and DC resistance ≤ 0.153 Ω/km at 20 °C. A semi-conducting conductor screen (≈ 0.8 mm) is co-extruded directly over the copper to eliminate air gaps and smooth the electric field — this is essential at MV voltages because even tiny voids cause partial discharge and eventual insulation failure. The conductor screen bonds electrically to the copper conductor. | |||
| 3. XLPE Insulation | |||
| Cross-linked polyethylene (XLPE) is extruded in a triple-layer co-extrusion process: conductor screen → XLPE insulation → insulation screen, all in one pass to avoid contamination. For the 8.7/10 kV grade the insulation thickness is 4.5 mm; for the 8.7/15 kV grade it is 5.5 mm. XLPE sustains 90 °C continuous conductor temperature and 250 °C short-circuit for ≤ 5 s. The outer insulation screen is strippable for termination work. Over the insulation screen a 0.1 × 25 mm copper tape is lapped to provide an equipotential earth and fault-current return path. | |||
| 4. Bedding, Steel Armour & PVC Jacket | |||
| Three screened cores are cabled round with PP/PE rope filler and a non-woven binder tape, giving a bundle of about 70 mm (10 kV). A PVC/PE inner bedding (≈ 1.5 mm) is extruded over the bundle, then a double layer of 0.5 mm galvanised steel tape is helically lapped — this is the type-22 armour that protects against crush and impact and permits direct burial. Finally a 2.5 mm black PVC (ST2) outer jacket is extruded over the armour to the ≈ 82 mm finish, providing UV, abrasion and chemical resistance. | |||
| 5. Site Handling & Operational Notes | |||
| • Observe the 15 × OD minimum bending radius (≈ 1230 mm). • The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends or cross-bonded). • Use heat-shrink or cold-shrink MV termination kits — do not treat as LV cable. • Service ambient −20 to +50 °C; conductor up to 90 °C continuous. • Routine test 21.5 kV AC / 5 min (10 kV); impulse withstand 75 kV. • At ≈ 1120 kg/100 m, plan heavy-duty drum jacks, winches and rated pulling gear. |
8. Factory Advantages

9. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type, voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +40 °C, shielded from direct sunlight and moisture; drum end seals must remain intact until installation. MV cable terminations and joints should be scheduled immediately after laying to avoid prolonged exposure of cut ends.

10. Procurement Specification. State "YJV22-8.7/10 kV-3×120" (or "YJV22-8.7/15 kV-3×120" for the thicker-insulation grade) together with the required length or drum arrangement. Always order the matching MV termination kits (indoor/outdoor / separable connectors) and field-joint kits at both ends. Always request the factory test certificate, which must include the partial-discharge and impulse-withstand reports, to confirm the actual diameter, weight and conductor resistances for the production batch.
11. Cable Industry FAQ.
- Q1: How does 120 mm² differ from 95 mm² in 10 kV service? 120 mm² raises the reference ampacity from about 285 A to about 340 A, and the short-circuit rating from about 13.8 kA to about 17.4 kA. It is the standard feeder for 4000–6300 kVA transformers and MV motors in the 1000–1600 kW range, whereas 95 mm² serves 2500–4000 kVA transformers and motors up to about 1000 kW.
- Q2: What does the "22" in YJV22 mean? The first "2" = double-steel-tape armour; the second "2" = PVC outer jacket. YJV22 is therefore a Cu conductor / XLPE insulation / double-steel-tape armour / PVC jacket MV cable. Without the "22" suffix, YJV would be unarmoured.
- Q3: When do I choose 8.7/10 kV vs 8.7/15 kV? Choose 8.7/10 kV for nominal 10 kV distribution networks (Um = 12 kV). Choose 8.7/15 kV for nominal 15 kV networks (Um = 17.5 kV) or where the system may be up-rated — the thicker 5.5 mm XLPE gives a larger safety margin.
- Q4: Why is there no separate neutral core? At MV distribution voltages, three-phase currents are balanced and the system is typically solidly or resistance-earthed; the copper-tape screen provides the earth path. A separate neutral is not required in standard 3-core MV construction.
- Q5: Why is the triple-extrusion process important? Conductor screen, XLPE insulation and insulation screen are co-extruded in one pass to avoid air gaps and contamination at the interfaces. Even tiny voids cause partial discharge at MV voltages and lead to early insulation failure.
- Q6: Why is there a copper-tape screen? The copper tape (0.1 × 25 mm lapped) provides an equipotential outer surface around each core, equalises the electric field, and carries capacitive and fault currents to earth.
- Q7: Can this cable be directly buried? Yes — the double-steel-tape armour provides crush protection, and the PVC jacket is moisture-resistant. Direct burial depth and covering must follow the local MV cable installation code.
- Q8: What is partial discharge and why is it tested? Partial discharge (PD) is tiny electrical sparks inside the insulation caused by voids or contaminants. At 1.5 U0, PD must be ≤ 20 pC. High PD values predict early insulation failure and are the most sensitive factory-quality indicator.
- Q9: Why is the routine test 21.5 kV and not 10 kV? Routine tests apply a power-frequency withstand voltage higher than the rated voltage (typically 2.5 U0 = 21.75 kV, rounded to 21.5 kV) to catch manufacturing defects before site installation.
- Q10: Can the steel armour be used as the earth? The steel armour provides mechanical protection but is not sized or certified as the primary fault-current earth conductor. The copper-tape screen and dedicated earthing conductors carry fault currents; the armour must be bonded to earth for safety.
- Q11: What service life can be expected? When installed, terminated and operated within the stated temperature, voltage and current ratings, XLPE-insulated MV cables are designed for a service life of around 30 years in fixed installation. The dominant failure mode is moisture or PD at terminations, so professional jointing is critical.