Armored XLPE High Voltage Power Cable 3 Core 25mm2 YJV22 Underground Power Cable
Product Summary
Product Details
High Voltage Power Cable 25mm2
,XLPE High Voltage Power Cable
,semi conductive Armored XLPE Cable
Product Description
Armored XLPE Cable 3 Core 25mm² YJV22 8.7/10kV Underground Power Cable
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC inner bedding / outer sheath |
|
22 |
Steel tape armour (double steel tape, overlapping) + PVC sheath |
|
8.7/10 kV |
Rated voltage U₀/U = 8.7/10 kV; Uₘ = 12 kV |
|
8.7/15 kV |
Rated voltage U₀/U = 8.7/15 kV; Uₘ = 17.5 kV |
|
3×25 mm² |
Three power cores, each 25 mm² (3-core, no neutral, no PE) |
Construction: XLPE insulated, steel-tape armoured, PVC sheathed, three-core medium-voltage power cable

YJV22-3×25 mm² 8.7/10 kV (and 8.7/15 kV) — Cable Specification & Engineering Data
1. Product Overview & Rating Summary. YJV22-3×25 is a medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 25 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for primary distribution networks, industrial substations and transformer-feeder circuits. Finished diameter is about 55 mm (10 kV) and nominal mass about 4200 kg/km (≈ 420 kg per 100 m). With all three cores loaded, the cable carries about 120 A in free air at 25 °C (engineering estimate).

2. Layer-by-Layer Construction (Conductor to Outer Jacket).
| Layer | Construction | Wall | Diameter |
|---|---|---|---|
| Conductor (Cu) ×3 | Compacted stranded annealed Cu, Class 2 — 7×2.14 mm equivalent | — | ≈ 6.0 mm |
| Conductor screen | Extruded semi-conducting XLPE, co-extruded | ≈ 0.8 mm | ≈ 7.6 mm |
| XLPE insulation | Cross-linked polyethylene, triple-extruded | 4.5 mm (10 kV) / 5.5 mm (15 kV) | ≈ 15.6 / ≈ 17.6 mm |
| Insulation screen | Strippable semi-conducting XLPE | ≈ 0.8 mm | ≈ 17.2 / ≈ 19.2 mm |
| Copper-tape screen | 0.1 × 25 mm annealed Cu tape, lapped | ≈ 0.1 mm tape | ≈ 17.4 / ≈ 19.4 mm |
| Filler & bedding | PP/PE rope + non-woven binder | — | ≈ 46 / ≈ 50 mm bundle |
| Inner sheath | PVC/PE extruded bedding | ≈ 1.5 mm | ≈ 49 / ≈ 53 mm |
| Steel armour (type 22) | Double galvanised steel tape, helical lapped | 2 × 0.5 mm | ≈ 50 / ≈ 54 mm |
| PVC outer jacket | ST2 PVC, flame-retardant, black | 2.5 mm | ≈ 55 / ≈ 58 mm (finished) |
3. Electrical Characteristics. Each 25 mm² conductor is held to a maximum DC resistance of 0.727 Ω/km at 20 °C, rising to about 0.94 Ω/km at the 90 °C operating point. Every length survives the routine 21.5 kV AC power-frequency proof held for five minutes (30.5 kV for the 15 kV grade). Partial discharge at 1.5 U0 must not exceed 20 pC. Dissipation factor tan δ ≤ 0.001 at U0. Insulation resistance ≥ 1000 MΩ·km, typical capacitance ≈ 0.33 μF/km. Impulse withstand (BIL) is 75 kV for the 10 kV grade and 95 kV for the 15 kV grade. With all three cores energised, reference loading is about 120 A in free air at 25 °C, about 115 A direct-buried.
Insulation Data
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) |
|
Nominal thickness |
4.5 mm |
|
Long-term service temp. |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C |
|
Routine test voltage (AC, 5 min) |
22 kV (8.7/10 kV); 30.5 kV (8.7/15 kV) |
|
Type-test voltage (AC) |
30 kV (8.7/10 kV); 45 kV (8.7/15 kV) |
|
Partial discharge test |
≤ 10 pC at 1.73 U₀ (15 kV) |
|
Tan δ (dissipation factor) |
≤ 0.004 at 20 °C |
Electrical Parameters
|
Parameter |
Value (8.7/10 kV) |
Value (8.7/15 kV) |
Note |
|---|---|---|---|
|
Rated voltage U₀/U |
8.7 / 10 kV |
8.7 / 15 kV |
— |
|
Max. system voltage Uₘ |
12 kV |
17.5 kV |
— |
|
Test voltage AC (5 min) |
22 kV |
30.5 kV |
Routine |
|
Type-test voltage |
30 kV |
45 kV |
— |
|
DC resistance @20 °C |
≤ 0.727 Ω/km |
≤ 0.727 Ω/km |
GB/T 3956 Class 2 max, 25 mm² |
|
AC resistance @90 °C (est.) |
≈ 0.929 Ω/km |
≈ 0.929 Ω/km |
per core |
|
Capacitance (approx.) |
≈ 0.22 µF/km |
≈ 0.22 µF/km |
per core to screen |
|
Inductive reactance (approx.) |
≈ 0.10 Ω/km |
≈ 0.10 Ω/km |
at 50 Hz, 3-core |
|
Current rating in air (30 °C) |
≈ 110 – 130 A |
≈ 110 – 130 A |
per core, 3-core |
|
Current rating buried (20 °C) |
≈ 100 – 120 A |
≈ 100 – 120 A |
direct buried, 3-core |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 2.5 kA (2500 A) |
≈ 2.5 kA (2500 A) |
25 mm² |
|
Frequency |
50/60 Hz AC |
50/60 Hz AC |
— |
Reference values: 25 mm² at 120 A, 3-phase 10 kV → max balanced load ≈ 2.08 MVA. Voltage drop at 120 A ≈ 11.1 V/km per core (≈0.11% per 100 m).
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (with PVC sheath) |
|
Fire survival |
Standard (non-fire-rated); optional fire-resistant version available (ZC-YJV22) |
4. Thermal Response & Flame Behaviour. XLPE insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −20 and +50 °C. PVC jacket provides flame-retardant performance per GB/T 18380.34 class A. Short-circuit rating at 250 °C for 1 s is about 3.6 kA for the 25 mm² copper conductor. Thermal resistance of reference burial soil is 1.2 K·m/W.
Fire Performance (YJV22 — Standard)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.3 Category C (ZC), Category B (ZB) available |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC sheath) |
|
Fire survival (circuit integrity) |
Not applicable (standard version); use ZA-YJV22 for flame-retardant A |
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 825 mm for this size. The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends, or cross-bonded for longer routes). MV heat-shrink or cold-shrink termination kits are mandatory — do not treat this as an LV cable. Laying temperature must not fall below 0 °C; reels must be pre-heated in cold weather. At about 420 kg per 100 m, the cable requires drum jacks and rated pulling gear.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 675 mm at Ø45 mm |
static installation |
|
Max. pulling tension |
1500 N |
use proper pulling grips |
|
Direct burial |
Suitable |
steel tape armour provides mechanical protection |
|
Conduit ID |
≥ 1.5 × OD → ≥ 68 mm; use 75 mm or 90 mm |
— |
|
Fixing |
cable clamps, steel straps |
— |
|
Impact resistance |
High |
steel tape armour absorbs mechanical shock |
|
Water resistance |
Moisture-resistant (PVC sheath + inner bedding) |
not fully watertight; use YJV32 for wet locations |
|
Armour type |
Double steel tape, overlapping |
galvanized or mill finish |
|
Armour short-circuit rating |
≈ 5 kA (1 s, steel tape) |
— |
6. Typical Service Applications. This YJV22-3×25 MV cable is used in 10 kV / 15 kV distribution networks: primary distribution feeders from 10 kV switchgear to distribution transformers, industrial plant 10 kV power distribution circuits, substation to factory main switchboard links, mining and quarry power supply lines (armour permits mechanical abuse), direct-buried urban distribution network feeders, factory 10 kV motor branch feeds (large motors), commercial building 10 kV incoming cables, photovoltaic / wind farm 10 kV collection circuits, tunnel and tunnel-feeder MV power cables, oil and gas plant MV distribution, and any circuit where mechanical protection against crush or impact is required. Approved installation methods include direct burial, cable tray, concrete duct, and indoor MV cable trench.

7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance ≤ 0.727 Ω/km at 20 °C, the 21.5 kV AC / 5 min withstand (30.5 kV for 15 kV grade), partial discharge ≤ 20 pC at 1.5 U0, tan δ ≤ 0.001, insulation resistance ≥ 1000 MΩ·km, conductor continuity across all three cores, steel-armour and copper-screen continuity, and dimensional inspection. Sample and type tests comprise impulse withstand at ±75 kV (or ±95 kV for 15 kV), heating-cycle load-loss test, bending at 15 × OD, short-circuit to 250 °C, flame spread GB/T 18380.34 class A, and voltage re-test after thermal ageing. A factory test certificate accompanies each drum.
Cable Parameters

Cable Test Parameters

Cable Cross Section Structure


Cable Construction Description
| Construction Description — YJV22-3×25 mm² 8.7/10 kV | |||
| Layer-by-layer MV build-up narrative · 8.7/10 kV (and 8.7/15 kV variant) · Cu / triple-extruded XLPE / Cu-tape screen / double-steel-tape armour / PVC jacket · finished Ø ≈ 55 mm | |||
| 1. Product Identity & Ratings | |||
| YJV22-3×25 is a medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 25 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for primary distribution networks, industrial substations and transformer-feeder circuits. Finished diameter is about 55 mm (10 kV) and nominal mass about 4200 kg/km (≈ 420 kg per 100 m). With all three cores loaded, the cable carries about 120 A in free air at 25 °C (engineering estimate). | |||
| 2. Copper Conductor & Screens | |||
| Each 25 mm² conductor is compacted-stranded annealed copper (Class 2), with a strand-lay diameter of about 6.0 mm and DC resistance ≤ 0.727 Ω/km at 20 °C. A semi-conducting conductor screen (≈ 0.8 mm) is co-extruded directly over the copper to eliminate air gaps and smooth the electric field — this is essential at MV voltages because even tiny voids cause partial discharge and eventual insulation failure. The conductor screen bonds electrically to the copper conductor. | |||
| 3. XLPE Insulation | |||
| Cross-linked polyethylene (XLPE) is extruded in a triple-layer co-extrusion process: conductor screen → XLPE insulation → insulation screen, all in one pass to avoid contamination. For the 8.7/10 kV grade the insulation thickness is 4.5 mm; for the 8.7/15 kV grade it is 5.5 mm. XLPE sustains 90 °C continuous conductor temperature and 250 °C short-circuit for ≤ 5 s. The outer insulation screen is strippable for termination work. Over the insulation screen a 0.1 × 25 mm copper tape is lapped to provide an equipotential earth and fault-current return path. | |||
| 4. Bedding, Steel Armour & PVC Jacket | |||
| Three screened cores are cabled round with PP/PE rope filler and a non-woven binder tape, giving a bundle of about 46 mm (10 kV). A PVC/PE inner bedding (≈ 1.5 mm) is extruded over the bundle, then a double layer of 0.5 mm galvanised steel tape is helically lapped — this is the type-22 armour that protects against crush and impact and permits direct burial. Finally a 2.5 mm black PVC (ST2) outer jacket is extruded over the armour to the ≈ 55 mm finish, providing UV, abrasion and chemical resistance. | |||
| 5. Site Handling & Operational Notes | |||
| • Observe the 15 × OD minimum bending radius (≈ 825 mm). • The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends or cross-bonded). • Use heat-shrink or cold-shrink MV termination kits — do not treat as LV cable. • Service ambient −20 to +50 °C; conductor up to 90 °C continuous. • Routine test 21.5 kV AC / 5 min (10 kV); impulse withstand 75 kV. • At ≈ 420 kg/100 m, plan drum jacks and rated pulling gear. |
8. Standards & Conformity. Design and production are governed by GB/T 12706.2-2020 (IEC 60502-2) for extruded-solid-insulation power cables from 1.8/3 kV to 26/35 kV. Conductors satisfy GB/T 3956 Class 2. Flame performance follows GB/T 18380.34. Surface marking complies with GB/T 6995. Cables can also be supplied to IEC 60502-2, BS 6622 or NFC 32-322 requirements on request.

9. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type, voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +40 °C, shielded from direct sunlight and moisture; drum end seals must remain intact until installation. MV cable terminations and joints should be scheduled immediately after laying to avoid prolonged exposure of cut ends.

10. Procurement Specification. State "YJV22-8.7/10 kV-3×25" (or "YJV22-8.7/15 kV-3×25" for the thicker-insulation grade) together with the required length or drum arrangement. Always order the matching MV termination kits (indoor/outdoor / separable connectors) and field-joint kits at both ends. Always request the factory test certificate, which must include the partial-discharge and impulse-withstand reports, to confirm the actual diameter, weight and conductor resistances for the production batch.
11. Cable Industry FAQ.
- Q1: What does the "22" in YJV22 mean? The first "2" = double-steel-tape armour; the second "2" = PVC outer sheath. YJV22 is therefore a Cu conductor / XLPE insulation / double-steel-tape armour / PVC jacket MV cable. Without the "22" suffix, YJV would be unarmoured.
- Q2: When do I choose 8.7/10 kV vs 8.7/15 kV? Choose 8.7/10 kV for nominal 10 kV distribution networks (Um = 12 kV). Choose 8.7/15 kV for nominal 15 kV networks (Um = 17.5 kV) or where the system may be up-rated — the thicker 5.5 mm XLPE gives a larger safety margin.
- Q3: Why is there no separate neutral core? At MV distribution voltages, three-phase currents are balanced and the system is typically solidly or resistance-earthed; the copper-tape screen provides the earth path. A separate neutral is not required in standard 3-core MV construction.
- Q4: Why is the triple-extrusion process important? Conductor screen, XLPE insulation and insulation screen are co-extruded in one pass to avoid air gaps and contamination at the interfaces. Even tiny voids cause partial discharge at MV voltages and lead to early insulation failure.
- Q5: Why is there a copper-tape screen? The copper tape (0.1 × 25 mm lapped) provides an equipotential outer surface around each core, equalises the electric field, and carries capacitive and fault currents to earth.
- Q6: Can this cable be directly buried? Yes — the double-steel-tape armour provides crush protection, and the PVC jacket is moisture-resistant. Direct burial depth and covering must follow the local MV cable installation code.
- Q7: What is partial discharge and why is it tested? Partial discharge (PD) is tiny electrical sparks inside the insulation caused by voids or contaminants. At 1.5 U0, PD must be ≤ 20 pC. High PD values predict early insulation failure and are the most sensitive factory-quality indicator.
- Q8: Why is the routine test 21.5 kV and not 10 kV? Routine tests apply a power-frequency withstand voltage higher than the rated voltage (typically 2.5 U0 = 21.75 kV, rounded to 21.5 kV) to catch manufacturing defects before site installation.
- Q9: Can the steel armour be used as the earth? The steel armour provides mechanical protection but is not sized or certified as the primary fault-current earth conductor. The copper-tape screen and dedicated earthing conductors carry fault currents; the armour must be bonded to earth for safety.
- Q10: Which tools and kits are needed on site? MV work requires a cable cutter, crimping tool for Cu lugs, torque wrench, megohmmeter, and the manufacturer-specified heat-shrink or cold-shrink termination kit. LV tools alone are not sufficient.
- Q11: What service life can be expected? When installed, terminated and operated within the stated temperature, voltage and current ratings, XLPE-insulated MV cables are designed for a service life of around 30 years in fixed installation. The dominant failure mode is moisture or PD at terminations, so professional jointing is critical.