3*70mm2 Medium High Voltage Power Cable 8.5KV 15Kv Armored For Underground Distribution
Basic Properties
Trading Properties
Product Summary
Product Details
8.5KV High Voltage Power Cable
,15Kv High Voltage Power Cable
,Underground Distribution Armored Power Cable
Product Description
3*70mm2 Medium High Voltage Power Cable 8.5KV 15Kv Armored For Underground Distribution
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
XLPE insulation |
|
V |
PVC inner sheath |
|
22 |
Steel tape armour + PVC outer sheath |
|
8.7/15 kV |
Rated voltage U₀/U = 8.7 kV / 15 kV |
|
3×70 mm² |
Three cores of 70 mm² copper conductor |
Construction: Three 70 mm² compacted copper conductors, XLPE insulation on each core, copper tape screen over each core, PVC inner sheath over laid-up cores, steel tape armour, PVC outer sheath.
Applicable Standards
- GB/T 12706.3-2020 / IEC 60502-2 — Power cables with extruded insulation for rated voltages from 6 kV up to 30 kV
- GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables (Class 2 compacted circular)
- GB/T 18380.3 / IEC 60332-3-24 — Flame retardant (Category C)
- GB/T 2951-2008 / IEC 60811 — Common test methods for insulating and sheathing materials
- GB/T 3048-2007 — Test methods for electric cables
- GB/T 19216 — Fire resistance (optional)

ZC-YJV22 8.7/15 kV 3×70 mm² — Medium-Voltage XLPE Steel-Tape Armoured Power Cable — Specification
1. Overview & Ratings. ZC-YJV22 8.7/15 kV 3×70 is a medium-voltage armoured power cable: three 70 mm² compacted copper cores with a three-layer co-extruded conductor screen + XLPE insulation + insulation screen, cabled triangularly over PVC bedding, double steel-tape armour and a black PVC sheath. Rated 8.7/15 kV, 90 °C XLPE. OD ≈ 58 mm, ≈ 8500 kg/km (est.), ≈ 210 A per core at 30 °C (est.). Class C flame-retardant — an ordinary MV distribution cable, not a 950 °C fire-rated circuit. Scope: 10 kV feeders, ring main units, substation-to-plant supply.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor (×3) | 3×70 compacted Cu, class 2 | R ≤0.268 Ω/km @20°C |
| Conductor screen | Extruded semiconducting, ≈0.8 mm | Smooths field at conductor |
| XLPE insulation | ≈4.5 mm, 90 °C | MV dielectric |
| Insulation screen | Bonded semiconducting | Outer field control |
| Bedding / inner sheath | PVC ≈1.5 mm | Bed for armour |
| Double steel-tape armour | Two tapes, ≈54 mm | Crush/impact protection |
| PVC outer sheath | ≈2.5 mm, black UV | Environmental jacket |
3. Electrical Characteristics. R ≤0.268 Ω/km @20 °C. Power-frequency withstand 21 kV AC / 5 min; partial discharge ≤10 pC at rated voltage; ≈210 A per core (est.); short-circuit ≈16 kA/1s (est.); lightning impulse type-tested; 50/60 Hz.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (Cross-linked Polyethylene) |
|
Inner sheath material |
PVC (Type ST2) |
|
Outer sheath material |
PVC (Type ST2) |
|
Armour material |
Steel tape (double layer) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
30.5 kV (phase-to-phase) |
|
Partial discharge test |
≤ 10 pC at 13 kV |
|
Dielectric strength |
≥ 25 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁵ Ω·cm |
|
Shield |
Copper tape screen per core + steel tape armour (earthable) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
8.7 / 15 kV |
GB/T 12706.3 / IEC 60502-2 |
|
Max. system voltage Um |
17.5 kV |
— |
|
Test voltage AC (5 min) |
30.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 0.268 Ω/km per core |
GB/T 3956 Class 2 Cu max (70 mm²) |
|
AC resistance @90 °C (est.) |
≈ 0.34 Ω/km per core |
— |
|
Current rating in air (30 °C) |
Three-phase AC: 230 A (per phase core) |
3×70, touching, in free air |
|
Current rating in tray (30 °C) |
Three-phase AC: 250 A (per phase core) |
3×70, spaced |
|
Current rating buried (20 °C, 0.8 m depth) |
Three-phase AC: 210 A (per phase core) |
direct buried, thermal resistivity 1.0 K·m/W |
|
Single-phase current capacity |
Single-phase AC: 230 A (L-N, if applicable) |
— |
|
DC current capacity |
230 A per core |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 7,700 A per core |
— |
|
Capacitance (core-to-screen, approx.) |
≈ 0.25 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.10 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: ZC-YJV22 8.7/15 kV 3×70 at 230 A three-phase, 10 kV → max load ≈ 3.99 MVA (cos φ = 1.0). At 15 kV line-to-line → max load ≈ 5.98 MVA (cos φ = 1.0). Suitable for medium-voltage power distribution in industrial plants, substations, and underground buried circuits.
4. Thermal & Flame. 90 °C normal, 250 °C short-time; Class C self-extinguishing. It is ordinary MV cable — not fire-survival; choose fire-rated cable for life-safety circuits.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (PVC) / −20 °C (with pre-heating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV22 — Flame Retardant Class C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.3 / IEC 60332-3-24 (Category C, flame propagation limited) |
|
Flame retardant class |
Class C (ZC) |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned |
|
EMI shielding |
Steel tape armour provides partial shielding |
5. Installation Practice & Handling. Bend ≥ 15×OD ≈ 870 mm; use qualified MV terminations and joints to keep the system PD-free; earth the steel-tape armour at both ends; direct bury, duct or tray; test insulation after pulling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 870 mm at Ø58.0 mm |
armoured cable |
|
Max. pulling tension |
1,050 N per core (70 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (steel tape armour protects against mechanical damage) |
— |
|
Surface mounting |
Cable tray, conduit, trench |
— |
|
Trench width |
≥ 300 mm |
— |
|
Fixing |
heavy-duty cable clamps, brackets |
— |
|
Impact resistance |
High (steel tape armour) |
— |
|
Water resistance |
Limited (PVC sheath) |
— |
|
UV resistance |
Poor (PVC degrades outdoors, use UV-resistant or conduit) |
— |
|
Flex life |
Limited (Class 2 compacted, not flexible) |
fixed installation only |
|
Termination note |
Heat-shrink terminations, cold-shrink terminations, or pre-moulded joints (MV rated) |
— |
6. Typical Service Applications. 10 kV distribution feeders, ring main units, substation-to-plant MV supply, mines and industrial MV networks.

7. Testing & QA Regime (16 items). Routine: DC resistance, partial discharge, 21 kV withstand, insulation resistance, conductor construction, insulation/sheath thickness, dimensional check, armour check, print legibility, mass, appearance, packing. Type: flame class, impulse withstand, bending.
Cable Parameters
| YJV22-3×70 mm² 8.7/10 kV (and 8.7/15 kV variant) — Full Parameter Sheet | ||||
| Medium-voltage power cable · Cu conductor / XLPE insulation / copper-tape screen / double-steel-tape armour (type 22) / PVC outer sheath · per GB/T 12706.2 · 3 cores · finished Ø ≈ 68 mm (10 kV) / ≈ 71 mm (15 kV) | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | YJV22 | — | Cu conductor / XLPE insulation / double-steel-tape armour / PVC outer sheath | |
| Rated voltage (U0/U) | 8.7/10 | kV | AC 50 Hz; Um = 12 kV (10 kV grade) | |
| Alternative voltage grade | 8.7/15 | kV | AC 50 Hz; Um = 17.5 kV (15 kV grade) — thicker XLPE | |
| Number of cores | 3 × 70 | — | 3 phase cores (70 mm²) — no separate neutral in MV cable | |
| Conductor material | Annealed copper, compacted stranded | — | Class 2 stranded per GB/T 3956 | |
| Conductor screen | Extruded semi-conducting XLPE | — | Conductor screen layer (radial field control) | |
| Insulation material | Cross-linked polyethylene (XLPE) | — | 90 °C continuous, 250 °C short-circuit | |
| Insulation screen | Extruded semi-conducting, strippable | — | Outer screen layer | |
| Metallic screen | Copper tape, lapped | — | 0.1 × 25 mm Cu tape; equipotential earth | |
| Armour | Double galvanised steel tape | — | Type 22 armour — mechanical protection | |
| Outer sheath | PVC (ST2), flame-retardant | — | UV- and abrasion-resistant | |
| Standard reference | GB/T 12706.2 / IEC 60502-2; GB/T 3956 | — | Medium-voltage power cables 1.8/3 kV to 26/35 kV | |
| 02 · Conductor | ||||
| Stranding — 70 mm² | Compacted stranded copper | — | Class 2, circular compacted | |
| Strand count (typical) | 19 × 2.14 mm (or equivalent) | — | Compacted after stranding | |
| Conductor diameter | ≈ 10.5 | mm | After compacting (est.) | |
| DC resistance @ 20 °C | ≤ 0.268 | Ω/km | Maximum per GB/T 3956 Class 2 | |
| AC resistance @ 50 Hz (≈ 90 °C) | ≈ 0.35 | Ω/km | Skin/proximity effect included | |
| Conductor screen thickness | ≈ 0.8 | mm | Extruded semi-conducting layer | |
| 03 · Insulation | ||||
| Insulation type | Cross-linked polyethylene (XLPE) | — | Extruded, triple-layer co-extrusion | |
| Insulation thickness — 8.7/10 kV | 4.5 | mm | Nominal, per GB/T 12706.2 | |
| Insulation thickness — 8.7/15 kV | 5.5 | mm | Thicker for 15 kV grade | |
| Core Ø over insulation — 10 kV | ≈ 21.1 | mm | 10.5 + 2×(0.8+4.5+0.8) | |
| Core Ø over insulation screen — 15 kV | ≈ 23.1 | mm | 10.5 + 2×(0.8+5.5+0.8) | |
| Insulation screen thickness | ≈ 0.8 | mm | Strippable semi-conducting | |
| Impulse withstand (BIL) — 10 kV | 75 | kV | Lightning impulse test | |
| Impulse withstand (BIL) — 15 kV | 95 | kV | Lightning impulse test | |
| 04 · Metallic Screen & Filler | ||||
| Screen material | Annealed copper tape | — | Lapped with overlap | |
| Screen tape dimensions | 0.1 × 25 | mm | Two layers lapped (typical) | |
| Screen function | Equipotential earth / fault-current path | — | Earthed at terminations | |
| Filler material | PP / jute rope, flame-retardant | — | Fills interstices for round cable | |
| Bedding / binder tape | Semi-conducting or non-woven tape | — | Holds bundle; anti-corrosion layer | |
| Assembled bundle Ø — 10 kV | ≈ 58 | mm | Before inner sheath (est.) | |
| Assembled bundle Ø — 15 kV | ≈ 62 | mm | Before inner sheath (est.) | |
| 05 · Inner Sheath & Armour | ||||
| Inner sheath / bedding | PVC or PE extruded | — | Corrosion barrier under armour | |
| Inner sheath thickness | ≈ 1.5 | mm | Over bundle | |
| Armour type | Double steel tape (type 22) | — | Double-tape helical armour | |
| Armour tape thickness | 2 × 0.5 | mm | Galvanised steel, lapped | |
| Armour function | Mechanical protection against crush / impact | — | Permits direct burial / tray | |
| Armour diameter — 10 kV | ≈ 62 | mm | Over inner sheath (est.) | |
| 06 · Outer Sheath | ||||
| Jacket material | PVC, ST2, flame-retardant | — | GB/T 12706.1 | |
| Jacket thickness | 2.5 | mm | Minimum over armour | |
| Overall finished diameter — 10 kV | ≈ 68 | mm | Cross-referenced industry sample | |
| Overall finished diameter — 15 kV | ≈ 71 | mm | Thicker insulation version | |
| Approx. cable mass — 10 kV | ≈ 7200 | kg/km | Cu + XLPE + steel + PVC | |
| Approx. cable mass — 15 kV | ≈ 7400 | kg/km | Heavier due to thicker insulation | |
| Jacket colour | Black (standard) | — | UV-resistant carbon-black PVC | |
| Mass per 100 m — 10 kV | ≈ 720 | kg/100 m | For drum loading | |
| 07 · Electrical | ||||
| Rated voltage U0/U | 8.7/10 | kV | AC 50 Hz; Um = 12 kV | |
| Maximum system voltage Um (10 kV) | 12 | kV | — | |
| DC resistance @ 20 °C | ≤ 0.268 | Ω/km | 70 mm² Cu Class 2 | |
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE at 20 °C | |
| Capacitance (typical) | ≈ 0.42 | μF/km | Per core (est.) | |
| Dissipation factor tan δ (at U0) | ≤ 0.001 | — | XLPE, 20 °C | |
| Routine test voltage (AC) — 10 kV | 21.5 kV / 5 min | — | Power-frequency withstand | |
| Routine test voltage (AC) — 15 kV | 30.5 kV / 5 min | — | Power-frequency withstand | |
| Air ampacity @ 25 °C | ≈ 230 | A | 3 cores loaded, Cu, in free air (est.) | |
| Buried ampacity @ 25 °C soil | ≈ 225 | A | 3 cores loaded, Cu, direct burial (est.) | |
| 08 · Thermal & Fire | ||||
| Max continuous conductor temp. | 90 | °C | Normal service | |
| Short-circuit temp. (≤ 5 s) | 250 | °C | XLPE limit | |
| Fire behaviour | Flame-retardant (PVC jacket) | — | GB/T 18380.34 class A | |
| Service ambient range | −20 to +50 | °C | Fixed installation | |
| Thermal resistance (soil) | 1.2 | K·m/W | Reference burial conditions | |
| Short-circuit rating (1 s) | ≈ 10.2 | kA | 70 mm² Cu at 250 °C | |
| 09 · Installation | ||||
| Min bending radius | ≥ 15 × OD ≈ 1020 | mm | Fixed installation (armoured) | |
| Laying temperature | ≥ 0 | °C | Pre-heat below 0 °C | |
| Laying methods | Tray, direct burial, conduit, duct | — | Armour permits direct burial | |
| Armour earthing | Both ends earthed | — | Steel armour must be earthed | |
| Copper screen earthing | At both ends (or single point for cross-bonding) | — | MV cable screen bonding | |
| Termination / joints | Heat-shrink or cold-shrink MV kits | — | Separable connectors / outdoor terminations | |
| Special tools | Cable cutter, crimping tool, torque wrench | — | MV lugs required | |
| 10 · Packing | ||||
| Standard supply length | 500 or 1000 | m/drum | Custom cut lengths available | |
| Reel / packing type | Wooden-steel drum | — | Sealed ends against moisture | |
| Surface marking | YJV22, 8.7/10 kV, 3×70, supplier, year, metre marks | — | Per GB/T 6995 | |
| Storage conditions | Dry, covered, −20 to +40 °C | — | Sealed ends; protect from UV | |
| Transport | Drums secured against rolling | — | Heavy cable, do not drag | |
Cable Test Parameters
| Test Parameters — YJV22-3×70 mm² 8.7/10 kV (and 8.7/15 kV) | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3048.4, 20 °C | ≤ 0.268 Ω/km (70 mm² Cu) | Routine |
| 2 | Power-frequency withstand (routine) | 21.5 kV AC, 5 min (10 kV grade) | No breakdown | Routine |
| 3 | Power-frequency withstand (15 kV grade) | 30.5 kV AC, 5 min | No breakdown | Routine |
| 4 | Partial discharge test | At 1.5 U0 = 13 kV (10 kV grade) | ≤ 20 pC at 1.73 U0 | Routine |
| 5 | Dissipation factor tan δ | At U0, 20 °C | tan δ ≤ 0.001 | Routine |
| 6 | Insulation resistance | GB/T 3048.5 | ≥ 1000 MΩ·km | Routine |
| 7 | Dimensional check | Micrometer / micrometer microscope | Insulation ≥ 4.5 mm (10 kV); jacket ≥ 2.5 mm | Routine |
| 8 | Impulse voltage test (BIL) | ±75 kV, 10 impulses (10 kV grade) | No breakdown at 75 kV | Type |
| 9 | Impulse voltage test (15 kV grade) | ±95 kV, 10 impulses | No breakdown at 95 kV | Type |
| 10 | Heating cycle / load loss | 3 cycles U0 + rated current | No damage; tan δ stable | Type |
| 11 | Bending test | 15 × OD mandrel, 3 cycles | No damage to insulation or sheath | Type |
| 12 | Short-circuit temperature test | 250 °C, 5 s equivalent | No insulation collapse | Type |
| 13 | Flame propagation | GB/T 18380.34 class A | No vertical flame spread | Type |
| 14 | Sheath / armour continuity | Continuity meter | Steel armour and Cu tape continuous | Routine |
| 15 | Voltage test after ageing | After thermal ageing cycle | Withstands 2.5 U0 AC | Type |
| 16 | Marking legibility | Visual + rubbing | YJV22 / 8.7/10 kV / 3×70 / metre marks legible | Routine |
Cable Cross Section Structure

| YJV22-3×70 mm² 8.7/10 kV — Cross-Section Construction Diagram (Schematic) | |||||
| MV layered build-up: Cu conductor → conductor screen → XLPE insulation → insulation screen → Cu-tape screen → filler → bedding → double-steel-tape armour → PVC jacket · 8.7/10 kV (8.7/15 kV variant noted) · finished Ø ≈ 68 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Cu) ×3 | Annealed compacted stranded copper, Class 2 — 19×2.14 mm equivalent per core | — | ≈ 10.5 | Power conductor; R ≤ 0.268 Ω/km at 20 °C |
| 2 | Conductor screen | Extruded semi-conducting XLPE, co-extruded with insulation | ≈ 0.8 | ≈ 12.1 | Eliminates air gaps; smooth radial field |
| 3 | XLPE insulation | Cross-linked polyethylene, triple-layer co-extrusion | 4.5 (10 kV) / 5.5 (15 kV) | ≈ 21.1 / ≈ 23.1 | Main dielectric; 90 °C continuous |
| 4 | Insulation screen | Strippable semi-conducting XLPE | ≈ 0.8 | ≈ 22.7 / ≈ 24.7 | Outer screen; equipotential |
| 5 | Copper-tape screen | Annealed Cu tape, lapped, 0.1 × 25 mm | ≈ 0.1 tape | ≈ 22.9 / ≈ 24.9 | Earth path / fault-current return |
| 6 | Filler & bedding | PP/PE rope filler + non-woven binder tape | — | ≈ 58 / ≈ 62 bundle | Round shape; anti-corrosion bedding |
| 7 | Inner sheath | PVC/PE extruded bedding over bundle | ≈ 1.5 | ≈ 61 / ≈ 65 | Corrosion barrier under armour |
| 8 | Steel armour (type 22) | Double galvanised steel tape, helically lapped | 2 × 0.5 | ≈ 62 / ≈ 66 | Mechanical crush / impact protection |
| 9 | PVC outer jacket | ST2 PVC, flame-retardant, black | 2.5 | ≈ 68 / ≈ 71 (finished) | UV, abrasion and chemical protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter (10 kV) | ≈ 68 | mm | Cross-referenced industry sample | ||
| Finished cable diameter (15 kV) | ≈ 71 | mm | Thicker XLPE variant | ||
| Approx. cable mass (10 kV) | ≈ 7200 | kg/km | Cu + XLPE + steel + PVC | ||
| Approx. cable mass (15 kV) | ≈ 7400 | kg/km | Heavier due to thicker insulation | ||
| Nominal voltage rating | 8.7/10 | kV | AC 50 Hz; Um = 12 kV | ||
| Alternative voltage grade | 8.7/15 | kV | Um = 17.5 kV; 5.5 mm XLPE | ||
| Max continuous conductor temp. | 90 | °C | Normal service | ||
| Short-circuit temp. (≤5 s) | 250 | °C | XLPE limit | ||
| Impulse withstand (BIL) | 75 (10 kV) / 95 (15 kV) | kV | Lightning impulse | ||
| Min bending radius | ≥ 15 × OD ≈ 1020 | mm | Fixed installation | ||
| DC resistance @ 20 °C | ≤ 0.268 | Ω/km | 70 mm² Cu | ||
| Insulation resistance | ≥ 1000 | MΩ·km | XLPE | ||
| Routine test voltage | 21.5 kV AC / 5 min | — | 10 kV grade; 30.5 kV for 15 kV | ||
| Air ampacity @ 25 °C | ≈ 230 | A | 3 cores loaded, Cu (est.) | ||
| Mass per 100 m (10 kV) | ≈ 720 | kg/100 m | For drum loading | ||
| Schematic — not to exact scale. Finished Ø ≈ 68 mm (10 kV) and weight ≈ 7200 kg/km from cross-referenced industry samples; conductor/insulation diameters per GB/T 12706.2 and GB/T 3956; ampacity 230 A is an engineering estimate. The 8.7/15 kV variant uses 5.5 mm XLPE insulation, ≈ 71 mm OD and ≈ 7400 kg/km. Values marked (est.) require confirmation against the factory test certificate. | |||||
Cable Construction Description
| Construction Description — YJV22-3×70 mm² 8.7/10 kV | |||
| Layer-by-layer MV build-up narrative · 8.7/10 kV (and 8.7/15 kV variant) · Cu / triple-extruded XLPE / Cu-tape screen / double-steel-tape armour / PVC jacket · finished Ø ≈ 68 mm | |||
| 1. Product Identity & Ratings | |||
| YJV22-3×70 is a medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 70 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV primary distribution feeders serving 1600–2500 kVA distribution transformers and medium-voltage motors in the 400–630 kW range. Finished diameter is about 68 mm (10 kV) and nominal mass about 7200 kg/km (≈ 720 kg per 100 m). With all three cores loaded, the cable carries about 230 A in free air at 25 °C (engineering estimate). | |||
| 2. Copper Conductor & Screens | |||
| Each 70 mm² conductor is compacted-stranded annealed copper (Class 2), with a strand-lay diameter of about 10.5 mm and DC resistance ≤ 0.268 Ω/km at 20 °C. A semi-conducting conductor screen (≈ 0.8 mm) is co-extruded directly over the copper to eliminate air gaps and smooth the electric field — this is essential at MV voltages because even tiny voids cause partial discharge and eventual insulation failure. The conductor screen bonds electrically to the copper conductor. | |||
| 3. XLPE Insulation | |||
| Cross-linked polyethylene (XLPE) is extruded in a triple-layer co-extrusion process: conductor screen → XLPE insulation → insulation screen, all in one pass to avoid contamination. For the 8.7/10 kV grade the insulation thickness is 4.5 mm; for the 8.7/15 kV grade it is 5.5 mm. XLPE sustains 90 °C continuous conductor temperature and 250 °C short-circuit for ≤ 5 s. The outer insulation screen is strippable for termination work. Over the insulation screen a 0.1 × 25 mm copper tape is lapped to provide an equipotential earth and fault-current return path. | |||
| 4. Bedding, Steel Armour & PVC Jacket | |||
| Three screened cores are cabled round with PP/PE rope filler and a non-woven binder tape, giving a bundle of about 58 mm (10 kV). A PVC/PE inner bedding (≈ 1.5 mm) is extruded over the bundle, then a double layer of 0.5 mm galvanised steel tape is helically lapped — this is the type-22 armour that protects against crush and impact and permits direct burial. Finally a 2.5 mm black PVC (ST2) outer jacket is extruded over the armour to the ≈ 68 mm finish, providing UV, abrasion and chemical resistance. | |||
| 5. Site Handling & Operational Notes | |||
| • Observe the 15 × OD minimum bending radius (≈ 1020 mm). • The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends or cross-bonded). • Use heat-shrink or cold-shrink MV termination kits — do not treat as LV cable. • Service ambient −20 to +50 °C; conductor up to 90 °C continuous. • Routine test 21.5 kV AC / 5 min (10 kV); impulse withstand 75 kV. • At ≈ 720 kg/100 m, plan drum jacks and rated pulling gear. |
8. Factory Advantages.
- Three-layer co-extrusion — conductor screen, XLPE and insulation screen built in line for clean field control.
- Routine PD gate — every length partial-discharge tested to ≤10 pC.
- Steel-tape armour — crush/impact protection for direct burial and ducts.
- Class C flame retardant — meets common MV wiring fire rules.
- XLPE 90 °C — higher ampacity per copper than PVC.
- Black UV jacket — outdoor stable for tray and exposed runs.
- Withstand + impulse records — routine and type test evidence.
- Length-on-drum — cut to the exact MV feeder run.
- Certified support pack — documentation for distribution tenders.

9. Packaging, Storage & Logistics. Cut to feeder length on heavy wooden drums with sealed ends; store dry indoor, shaded, avoid UV.

10. Procurement Specification. State "ZC-YJV22 8.7/15 kV 3×70", length, laying method (bury/duct/tray) and the required MV terminations/joints; request the routine PD/withstand records and type test. Est. values and exact PD/impulse/withstand limits confirmed against the factory type certificate.
11. Cable Industry FAQ.
- Q1: How is this MV cable different from a 0.6/1 kV YJV? It has a much thicker XLPE wall (≈4.5 mm) plus conductor and insulation semiconducting screens to control the MV electric field, and steel-tape armour — the rating is 8.7/15 kV for 10 kV networks, not 0.6/1 kV.
- Q2: What are conductor and insulation screens? Semiconducting layers that smooth the electric field at the conductor and at the insulation boundary — essential to avoid partial discharge at MV.
- Q3: What is the PD test? Partial discharge ≤10 pC at rated voltage; it is the key MV quality gate confirmed on every length.
- Q4: DC resistance? ≤0.268 Ω/km at 20 °C per 70 mm² copper core.
- Q5: Is it fire-rated (950 °C)? No — it is Class C flame-retardant self-extinguishing; use a fire-rated cable (e.g. BTTRZ) for life-safety circuits.
- Q6: Current rating? ≈210 A per core (est.) at 30 °C; derate by laying method and grouping.
- Q7: Bending? ≈870 mm (15×OD) — armoured MV needs a large bend radius.
- Q8: What terminations? Qualified MV terminations and joints; ordinary LV joints break the PD-free rating.
- Q9: Can it be buried? Yes — steel-tape armour suits direct burial, ducts and trays.
- Q10: Packing? Heavy wooden drums with sealed ends.
- Q11: What proof ships? Routine PD and withstand records plus the type certificate; est. values confirmed against it.