Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
YJV22-3*35mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

Underground Distribution Cable 3 Core 35mm² YJV22 8.7/15kV Armored XLPE Cable Designation & Meaning Code Meaning YJ XLPE (cross-linked polyethylene) insulation V PVC inner bedding / outer sheath 22 Steel tape armour (double steel tape, overlapping) + PVC sheath 8.7/10 kV Rated voltage U₀/U = 8.7/10 ...

Product Details

Highlight:

High Voltage Power Cable 3 Core

,

High Voltage Power Cable 35mm2

,

35mm2 Underground Distribution Cable

Conductor (×3):
Bare Annealed Copper, Class 2 Stranded Circular, Typical 7×∅2.52 Mm (35 Mm²), Conductor Ø ≈ 7.3–8.4 Mm
Conductor nominal area:
35 Mm²
Number of cores:
3
Conductor class:
Class 2 Stranded
Conductor construction:
7×∅2.52 Mm (typical)
Conductor diameter (approx.):
7.3–8.4 Mm
Conductor screen thickness:
0.5 Mm
Conductor screen:
Extruded Semi-conductive Compound (XLPE-based)
Insulation:
XLPE (cross-linked Polyethylene), Nominal Thickness 4.5 Mm​ (8.7/10 KV & 8.7/15 KV)
Insulation thickness:
4.5 Mm
Insulation screen thickness:
0.5 Mm
Diameter over insulated core (approx.):
14.3–16.4 Mm
Insulation screen:
Extruded Semi-conductive Compound (strippable Or Bonded)
Metallic screen (per core):
Copper Tape, Copper Wire, Or Combined Copper Tape + Wire, Min. Cross-section 16 Mm² (typically 1×0.1 Mm Copper Tape Overlapping)
Metallic screen:
Copper Tape 0.1 Mm Overlapping
Filler & bedding:
PVC Filler + PVC Inner Bedding (tape Wrap Or Extruded), Thickness ≈ 1.5–2.0 Mm
Inner bedding thickness:
1.5–2.0 Mm
Armour:
Double Steel Tape, Overlapping (galvanized Or Mill Finish), Thickness 0.5 Mm (typical)
Outer sheath:
PVC (polyvinyl Chloride), Nominal Thickness 2.5 Mm (typical), Color: Black
Outer sheath thickness:
2.5 Mm
Overall cable diameter:
44 – 52 Mm
Design outer diameter:
≈ 47.5 Mm
Approx. weight:
3.2 – 4.0 Kg/m (3200–4000 Kg/km)
Design weight:
≈ 3600 Kg/km
Cable shape:
Round

Product Description

Underground Distribution Cable 3 Core 35mm² YJV22 8.7/15kV Armored XLPE

 

Cable Designation & Meaning

 

Code

Meaning

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC inner bedding / outer sheath

22

Steel tape armour (double steel tape, overlapping) + PVC sheath

8.7/10 kV

Rated voltage U₀/U = 8.7/10 kV; Uₘ = 12 kV

8.7/15 kV

Rated voltage U₀/U = 8.7/15 kV; Uₘ = 17.5 kV

3×35 mm²

Three power cores, each 35 mm² (3-core, no neutral, no PE)

 

Construction: XLPE insulated, steel-tape armoured, PVC sheathed, three-core medium-voltage power cable.

 

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

 

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

YJV22-3×35 mm² 8.7/10 kV (and 8.7/15 kV) — Cable Specification & Engineering Data 

1. Product Overview & Rating Summary. YJV22-3×35 is a medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 35 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV distribution feeders serving 630–1000 kVA distribution transformers and larger industrial MV loads. Finished diameter is about 58 mm (10 kV) and nominal mass about 4700 kg/km (≈ 470 kg per 100 m). With all three cores loaded, the cable carries about 150 A in free air at 25 °C (engineering estimate).

 

2. Layer-by-Layer Construction (Conductor to Outer Jacket).

Layer Construction Wall Diameter
Conductor (Cu) ×3 Compacted stranded annealed Cu, Class 2 — 7×2.52 mm equivalent — ≈ 7.0 mm
Conductor screen Extruded semi-conducting XLPE, co-extruded ≈ 0.8 mm ≈ 8.6 mm
XLPE insulation Cross-linked polyethylene, triple-extruded 4.5 mm (10 kV) / 5.5 mm (15 kV) ≈ 16.8 / ≈ 18.8 mm
Insulation screen Strippable semi-conducting XLPE ≈ 0.8 mm ≈ 18.4 / ≈ 20.4 mm
Copper-tape screen 0.1 × 25 mm annealed Cu tape, lapped ≈ 0.1 mm tape ≈ 18.6 / ≈ 20.6 mm
Filler & bedding PP/PE rope + non-woven binder — ≈ 48 / ≈ 52 mm bundle
Inner sheath PVC/PE extruded bedding ≈ 1.5 mm ≈ 51 / ≈ 55 mm
Steel armour (type 22) Double galvanised steel tape, helical lapped 2 × 0.5 mm ≈ 52 / ≈ 56 mm
PVC outer jacket ST2 PVC, flame-retardant, black 2.5 mm ≈ 58 / ≈ 61 mm (finished)

 

3. Electrical Characteristics. Each 35 mm² conductor is held to a maximum DC resistance of 0.524 Ω/km at 20 °C, rising to about 0.68 Ω/km at the 90 °C operating point. Every length survives the routine 21.5 kV AC power-frequency proof held for five minutes (30.5 kV for the 15 kV grade). Partial discharge at 1.5 U0 must not exceed 20 pC. Dissipation factor tan δ ≤ 0.001 at U0. Insulation resistance ≥ 1000 MΩ·km, typical capacitance ≈ 0.36 μF/km. Impulse withstand (BIL) is 75 kV for the 10 kV grade and 95 kV for the 15 kV grade. With all three cores energised, reference loading is about 150 A in free air at 25 °C, about 145 A direct-buried.

Insulation Data

Property

Value

Material

XLPE (cross-linked polyethylene)

Nominal thickness

4.5 mm

Long-term service temp.

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C

Routine test voltage (AC, 5 min)

22 kV (8.7/10 kV); 30.5 kV (8.7/15 kV)

Type-test voltage (AC)

30 kV (8.7/10 kV); 45 kV (8.7/15 kV)

Partial discharge test

≤ 10 pC at 1.73 U₀ (15 kV)

Tan δ (dissipation factor)

≤ 0.004 at 20 °C

Electrical Parameters

 

Parameter

Value (8.7/10 kV)

Value (8.7/15 kV)

Note

Rated voltage U₀/U

8.7 / 10 kV

8.7 / 15 kV

—

Max. system voltage Uₘ

12 kV

17.5 kV

—

Test voltage AC (5 min)

22 kV

30.5 kV

Routine

Type-test voltage

30 kV

45 kV

—

DC resistance @20 °C

≤ 0.524 Ω/km

≤ 0.524 Ω/km

GB/T 3956 Class 2 max, 35 mm²

AC resistance @90 °C (est.)

≈ 0.669 Ω/km

≈ 0.669 Ω/km

per core

Capacitance (approx.)

≈ 0.24 µF/km

≈ 0.24 µF/km

per core to screen

Inductive reactance (approx.)

≈ 0.10 Ω/km

≈ 0.10 Ω/km

at 50 Hz, 3-core

Current rating in air (30 °C)

≈ 130 – 155 A

≈ 130 – 155 A

per core, 3-core

Current rating buried (20 °C)

≈ 120 – 140 A

≈ 120 – 140 A

direct buried, 3-core

Short-circuit current (1 s, Cu, 250 °C)

≈ 3.5 kA (3500 A)

≈ 3.5 kA (3500 A)

35 mm²

Frequency

50/60 Hz AC

50/60 Hz AC

—

Reference values: 35 mm² at 145 A, 3-phase 10 kV → max balanced load ≈ 2.51 MVA. Voltage drop at 145 A ≈ 9.7 V/km per core (≈0.097% per 100 m).

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C

Min. installation ambient temp.

0 °C (PVC sheath); below 0 °C pre-heating required

Service ambient range

−20 °C to +90 °C (with PVC sheath)

Fire survival

Standard (non-fire-rated); optional fire-resistant version available (ZC-YJV22)

 

 

4. Thermal Response & Flame Behaviour. XLPE insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −20 and +50 °C. PVC jacket provides flame-retardant performance per GB/T 18380.34 class A. Short-circuit rating at 250 °C for 1 s is about 5.1 kA for the 35 mm² copper conductor. Thermal resistance of reference burial soil is 1.2 K·m/W.

Fire Performance (YJV22 — Standard)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 Category C (ZC), Category B (ZB) available

Halogen content

Contains halogen (PVC sheath)

Smoke density

Standard (non-low-smoke)

Corrosivity

Corrosive (PVC sheath)

Fire survival (circuit integrity)

Not applicable (standard version); use ZA-YJV22 for flame-retardant A

 

5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 870 mm for this size. The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends, or cross-bonded for longer routes). MV heat-shrink or cold-shrink termination kits are mandatory — do not treat this as an LV cable. Laying temperature must not fall below 0 °C; reels must be pre-heated in cold weather. At about 470 kg per 100 m, the cable requires drum jacks and rated pulling gear.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 713 mm at Ø47.5 mm

static installation

Max. pulling tension

2100 N

use proper pulling grips

Direct burial

Suitable

steel tape armour provides mechanical protection

Conduit ID

≥ 1.5 × OD → ≥ 72 mm; use 80 mm or 90 mm

—

Fixing

cable clamps, steel straps

—

Impact resistance

High

steel tape armour absorbs mechanical shock

Water resistance

Moisture-resistant (PVC sheath + inner bedding)

not fully watertight; use YJV32 for wet locations

Armour type

Double steel tape, overlapping

galvanized or mill finish

Armour short-circuit rating

≈ 5 kA (1 s, steel tape)

—

 

6. Typical Service Applications. This YJV22-3×35 MV cable is used in 10 kV / 15 kV distribution networks serving medium-load feeders: 630–1000 kVA distribution transformer primary feeds, industrial plant 10 kV power distribution to medium-load MCCs, substation to factory main 10 kV switchboard links, 10 kV motor branch feeds for medium-voltage motors up to about 200 kW, commercial building 10 kV incoming and floor main feeders, hospital 10 kV emergency / normal switchboard inter-ties, data-centre 10 kV UPS / switchgear feeders, mining and quarry 10 kV power supply lines (armour permits mechanical abuse), direct-buried urban 10 kV secondary network feeders, and any circuit where mechanical protection against crush or impact is required. Approved installation methods include direct burial, cable tray, concrete duct, and indoor MV cable trench.

 

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

 

7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance ≤ 0.524 Ω/km at 20 °C, the 21.5 kV AC / 5 min withstand (30.5 kV for 15 kV grade), partial discharge ≤ 20 pC at 1.5 U0, tan δ ≤ 0.001, insulation resistance ≥ 1000 MΩ·km, conductor continuity across all three cores, steel-armour and copper-screen continuity, and dimensional inspection. Sample and type tests comprise impulse withstand at ±75 kV (or ±95 kV for 15 kV), heating-cycle load-loss test, bending at 15 × OD, short-circuit to 250 °C, flame spread GB/T 18380.34 class A, and voltage re-test after thermal ageing. A factory test certificate accompanies each drum.

 

Cable Parameters

 

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

 

Cable Test Parameters

 

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

 

Cable Cross Section Structure

 

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

 

Cable Construction Description

 

Construction Description — YJV22-3×35 mm² 8.7/10 kV 
Layer-by-layer MV build-up narrative · 8.7/10 kV (and 8.7/15 kV variant) · Cu / triple-extruded XLPE / Cu-tape screen / double-steel-tape armour / PVC jacket · finished Ø ≈ 58 mm
1. Product Identity & Ratings
YJV22-3×35 is a medium-voltage (MV) power cable rated 8.7/10 kV (Um = 12 kV) at 50 Hz, built around three 35 mm² compacted-stranded copper conductors, each with a triple-extruded semi-conducting screen / XLPE insulation / semi-conducting screen system, a lapped copper-tape screen, and an overall double-galvanised-steel-tape armour (type 22) with a black PVC outer jacket. The same construction is also manufactured in the 8.7/15 kV grade (Um = 17.5 kV) with thicker 5.5 mm XLPE insulation. The cable is designed for 10 kV distribution feeders serving 630–1000 kVA distribution transformers and larger industrial MV loads. Finished diameter is about 58 mm (10 kV) and nominal mass about 4700 kg/km (≈ 470 kg per 100 m). With all three cores loaded, the cable carries about 150 A in free air at 25 °C (engineering estimate).
2. Copper Conductor & Screens
Each 35 mm² conductor is compacted-stranded annealed copper (Class 2), with a strand-lay diameter of about 7.0 mm and DC resistance ≤ 0.524 Ω/km at 20 °C. A semi-conducting conductor screen (≈ 0.8 mm) is co-extruded directly over the copper to eliminate air gaps and smooth the electric field — this is essential at MV voltages because even tiny voids cause partial discharge and eventual insulation failure. The conductor screen bonds electrically to the copper conductor.
3. XLPE Insulation
Cross-linked polyethylene (XLPE) is extruded in a triple-layer co-extrusion process: conductor screen → XLPE insulation → insulation screen, all in one pass to avoid contamination. For the 8.7/10 kV grade the insulation thickness is 4.5 mm; for the 8.7/15 kV grade it is 5.5 mm. XLPE sustains 90 °C continuous conductor temperature and 250 °C short-circuit for ≤ 5 s. The outer insulation screen is strippable for termination work. Over the insulation screen a 0.1 × 25 mm copper tape is lapped to provide an equipotential earth and fault-current return path.
4. Bedding, Steel Armour & PVC Jacket
Three screened cores are cabled round with PP/PE rope filler and a non-woven binder tape, giving a bundle of about 48 mm (10 kV). A PVC/PE inner bedding (≈ 1.5 mm) is extruded over the bundle, then a double layer of 0.5 mm galvanised steel tape is helically lapped — this is the type-22 armour that protects against crush and impact and permits direct burial. Finally a 2.5 mm black PVC (ST2) outer jacket is extruded over the armour to the ≈ 58 mm finish, providing UV, abrasion and chemical resistance.
5. Site Handling & Operational Notes
• Observe the 15 × OD minimum bending radius (≈ 870 mm).  • The steel armour must be earthed at both ends; the copper-tape screen must be bonded per MV practice (both ends or cross-bonded).  • Use heat-shrink or cold-shrink MV termination kits — do not treat as LV cable.  • Service ambient −20 to +50 °C; conductor up to 90 °C continuous.  • Routine test 21.5 kV AC / 5 min (10 kV); impulse withstand 75 kV.  • At ≈ 470 kg/100 m, plan drum jacks and rated pulling gear.

 

 

8. Standards & Conformity. Design and production are governed by GB/T 12706.2-2020 (IEC 60502-2) for extruded-solid-insulation power cables from 1.8/3 kV to 26/35 kV. Conductors satisfy GB/T 3956 Class 2. Flame performance follows GB/T 18380.34. Surface marking complies with GB/T 6995. Cables can also be supplied to IEC 60502-2, BS 6622 or NFC 32-322 requirements on request.

 

9. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type, voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +40 °C, shielded from direct sunlight and moisture; drum end seals must remain intact until installation. MV cable terminations and joints should be scheduled immediately after laying to avoid prolonged exposure of cut ends.

 

Underground Distribution High Voltage Power Cable 3 Core 35mm2 YJV22 XLPE

 

10. Procurement Specification. State "YJV22-8.7/10 kV-3×35" (or "YJV22-8.7/15 kV-3×35" for the thicker-insulation grade) together with the required length or drum arrangement. Always order the matching MV termination kits (indoor/outdoor / separable connectors) and field-joint kits at both ends. Always request the factory test certificate, which must include the partial-discharge and impulse-withstand reports, to confirm the actual diameter, weight and conductor resistances for the production batch.

 

11. Cable Industry FAQ.

  • Q1: How does 35 mm² differ from 25 mm² in 10 kV service? 35 mm² raises the reference ampacity from about 120 A to about 150 A, and the short-circuit rating from about 3.6 kA to about 5.1 kA. It is the standard feeder for 630–1000 kVA transformers and 10 kV motors up to about 200 kW, whereas 25 mm² serves 315–500 kVA transformers and smaller motor branches.
  • Q2: What does the "22" in YJV22 mean? The first "2" = double-steel-tape armour; the second "2" = PVC outer sheath. YJV22 is therefore a Cu conductor / XLPE insulation / double-steel-tape armour / PVC jacket MV cable. Without the "22" suffix, YJV would be unarmoured.
  • Q3: When do I choose 8.7/10 kV vs 8.7/15 kV? Choose 8.7/10 kV for nominal 10 kV distribution networks (Um = 12 kV). Choose 8.7/15 kV for nominal 15 kV networks (Um = 17.5 kV) or where the system may be up-rated — the thicker 5.5 mm XLPE gives a larger safety margin.
  • Q4: Why is there no separate neutral core? At MV distribution voltages, three-phase currents are balanced and the system is typically solidly or resistance-earthed; the copper-tape screen provides the earth path. A separate neutral is not required in standard 3-core MV construction.
  • Q5: Why is the triple-extrusion process important? Conductor screen, XLPE insulation and insulation screen are co-extruded in one pass to avoid air gaps and contamination at the interfaces. Even tiny voids cause partial discharge at MV voltages and lead to early insulation failure.
  • Q6: Why is there a copper-tape screen? The copper tape (0.1 × 25 mm lapped) provides an equipotential outer surface around each core, equalises the electric field, and carries capacitive and fault currents to earth.
  • Q7: Can this cable be directly buried? Yes — the double-steel-tape armour provides crush protection, and the PVC jacket is moisture-resistant. Direct burial depth and covering must follow the local MV cable installation code.
  • Q8: What is partial discharge and why is it tested? Partial discharge (PD) is tiny electrical sparks inside the insulation caused by voids or contaminants. At 1.5 U0, PD must be ≤ 20 pC. High PD values predict early insulation failure and are the most sensitive factory-quality indicator.
  • Q9: Why is the routine test 21.5 kV and not 10 kV? Routine tests apply a power-frequency withstand voltage higher than the rated voltage (typically 2.5 U0 = 21.75 kV, rounded to 21.5 kV) to catch manufacturing defects before site installation.
  • Q10: Can the steel armour be used as the earth? The steel armour provides mechanical protection but is not sized or certified as the primary fault-current earth conductor. The copper-tape screen and dedicated earthing conductors carry fault currents; the armour must be bonded to earth for safety.
  • Q11: What service life can be expected? When installed, terminated and operated within the stated temperature, voltage and current ratings, XLPE-insulated MV cables are designed for a service life of around 30 years in fixed installation. The dominant failure mode is moisture or PD at terminations, so professional jointing is critical.