YJV22 3x150mm2 Copper HV High Voltage Power Cable XLPE Armored 26 35kV Underground

YJV22 3x150mm2 Copper HV High Voltage Power Cable XLPE Armored 26 35kV Underground

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
YJV22 3x150mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

YJV22 3x150mm² Copper XLPE Armored HV Cable 26/35kV High Voltage Underground Cable Designation & Meaning Code Meaning 26/35 kV Rated voltage: U₀ = 26 kV (phase-to-earth), U = 35 kV (phase-to-phase) YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath 22 Steel tape armoured (double steel ...

Product Details

Highlight:

3x150mm2 High Voltage Power Cable

,

HV Cable 26kV

,

35kV armored copper cable

Conductor (×3):
Copper, Class 2 Stranded Sector-shaped, Nominal 37×∅2.27 Mm (150 Mm²), Conductor Ø ≈ 16–18 Mm (sector Width)
Conductor screen:
Semi-conductive Compound Layer, Thickness ≈ 0.5 Mm
Insulation:
XLPE (cross-linked Polyethylene), Nominal Thickness 10.5 Mm​ (for 26/35 KV Class Per IEC 60502-2)
Insulation screen:
Semi-conductive Compound Layer, Thickness ≈ 0.5 Mm
Metallic screen:
Copper Tape Screen Over Each Core (standard For 26/35 KV)
Filler & bedding:
PVC Filler, Round Profile, Inner PVC Bedding Thickness ≈ 1.5 Mm
Armour:
Double Steel Tape, Thickness 0.5 Mm × 2 Layers (overlapped)
Outer sheath:
PVC​ (polyvinyl Chloride), Nominal Thickness 3.0 Mm (typical), Colour: Black
Conductor nominal area:
150 Mm² (Cu)
Number of cores:
3
Conductor material:
Copper (Cu)
Conductor class:
Class 2 Stranded Sector
Conductor construction:
37×∅2.27 Mm (typical)
Conductor diameter (approx.):
16–18 Mm (sector Width)
Insulation thickness:
10.5 Mm
Diameter over insulation (approx.):
37–41 Mm
Bedding thickness:
1.5 Mm
Armour (steel tape):
0.5 Mm × 2 Layers
Outer sheath thickness:
3.0 Mm
Overall cable diameter:
82 – 95 Mm
Design outer diameter:
≈ 88 Mm
Approx. weight:
8.5 – 10.5 Kg/m (8500–10500 Kg/km)
Design weight:
≈ 9200 Kg/km
Cable shape:
Round

Product Description

YJV22 3x150mm² Copper XLPE Armored HV Cable 26/35kV High Voltage Underground

Cable Designation & Meaning

 

Code

Meaning

26/35 kV

Rated voltage: U₀ = 26 kV (phase-to-earth), U = 35 kV (phase-to-phase)

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath

22

Steel tape armoured (double steel tape)

3×150 mm²

Three cores, each 150 mm² copper

 

Construction: Copper conductor, XLPE insulation, semi-con screens, steel tape armour, PVC sheath, three-core medium voltage power cable.

 

YJV22 3x150mm2 Copper HV High Voltage Power Cable XLPE Armored 26 35kV Underground

 

YJV22-3×150 mm² (26/35 kV) — High-Voltage XLPE Insulated Steel-Tape Armored Copper Power Cable — Specification & Engineering Data

1. Overview & Ratings. YJV22-3×150 is a high-voltage (26/35 kV) XLPE-insulated, double steel-tape armored, copper-conductor power cable, three 150 mm² compacted copper conductors (L1/L2/L3), rated 26/35 kV (Um = 40.5 kV), 50 Hz; built and tested per GB/T 12701 / IEC 60840. Designed for 35 kV primary grid transmission. Ø ≈ 78 mm, ≈ 7200 kg/km, steel drums.

 

2. Construction Stack (Conductor → Outer).

Layer Build Wall Diameter
Conductors (×3) Compacted stranded Cu, Class 2, 3×150 mm² — ≈ 14.5 mm
Conductor screen Extruded semi-conducting — —
XLPE insulation Cross-linked polyethylene (thick) ≈ 8.8 mm ≈ 32 mm
Insulation screen Semi-conducting + Cu tape ≈ 0.12 mm Cu —
Inner PVC bedding PVC over cored assembly ≈ 2.0 mm ≈ 70 mm
Steel tape armor (22) Double galvanized steel tape ≈ 2×0.5 mm ≈ 74 mm
Outer PVC sheath PVC ST2, black, UV-resistant ≈ 2.8 mm ≈ 78 mm (finished)

 

3. Electrical Characteristics. R ≤ 0.124 Ω/km at 20 °C (Cu 150 mm²); routine test 63 kV AC / 5 min; partial discharge ≤ 10 pC at 26 kV; insulation resistance ≥ 2000 MΩ·km; capacitance ≈ 0.18 μF/km; tan δ ≤ 0.0004 at 90 °C. Reference ampacity ≈ 230 A (free air, 25 °C).

Insulation Data

Property

Value

Material

XLPE (cross-linked polyethylene)

Nominal thickness

10.5 mm (26/35 kV class)

Long-term service temp.

90 °C

Short-circuit temp. (≤5 s)

250 °C​ (Cu conductor limit per IEC 60228)

Emergency overload temp.

130 °C

Routine test voltage (AC, 5 min)

65 kV (for 26/35 kV)

Type-test voltage (AC)

91 kV (for 26/35 kV)

Partial discharge test

≤ 10 pC at 1.5 U₀ (39 kV)

Tan δ (dissipation factor)

≤ 0.004 at 20 °C

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

26 / 35 kV

GB/T 12706.2 / IEC 60502-2

Max. system voltage Uₘ

40.5 kV

—

Test voltage AC (5 min)

65 kV

Routine test (26/35 kV)

DC resistance @20 °C

≤ 0.124 Ω/km

GB/T 3956 Class 2 Cu max, 150 mm²

AC resistance @90 °C (est.)

≈ 0.158 Ω/km

per core

Capacitance (approx.)

≈ 0.20 µF/km

core to screen

Inductive reactance (approx.)

≈ 0.11 Ω/km

at 50 Hz, 3-core armoured

Current rating in air (30 °C)

295 A​

3-core, 26/35 kV (derated from lower voltage due to larger insulation thickness)

Current rating buried (20 °C)

260 A​

direct buried, 3-core

Current rating in conduit (30 °C)

245 A​

3-core

Short-circuit current (1 s, Cu, 250 °C)

≈ 15.0 kA (15000 A)

150 mm² Cu

Frequency

50/60 Hz AC

—

Reference values: 150 mm² Cu at 295 A, 3-phase 35 kV → max balanced load ≈ 17.9 MVA. Voltage drop at 295 A ≈ 46.6 V/km per core (≈0.13% per km at 35 kV).

 

4. Thermal & Mechanical. 90 °C continuous conductor temperature; 250 °C short-circuit (≤ 5 s); 105 °C overload short duration; operating ambient −40~+50 °C; lay ≥ 0 °C. Double steel tape armor provides crush protection for direct burial in 35 kV grid trenches.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C (Cu conductor)

Emergency overload temp.

130 °C

Min. installation ambient temp.

0 °C (PVC sheath); below 0 °C pre-heating required

Service ambient range

−20 °C to +90 °C (with PVC sheath)

Fire survival

Standard (flame retardant single cable)

Fire Performance (YJV22 — Standard)

Property

Value / Requirement

Flame retardant

IEC 60332-1 (single cable, passes)

Halogen content

Contains halogen (PVC sheath & XLPE)

Smoke density

Standard (non-low-smoke)

Corrosivity

Corrosive (PVC)

Fire survival (circuit integrity)

Not applicable (standard version); use NH-YJV22 for circuit integrity

 

5. Installation Practice & Handling. Bend ≥ 15 × OD ≈ 1170 mm fixed. Use HV cold-shrink / heat-shrink terminations rated 26/35 kV. Certified HV personnel only — 35 kV jointing requires specialized training. At 7200 kg/km, heavy steel drums require mechanical handling.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 1320 mm at Ø88 mm

static installation

Max. pulling tension

15000 N

Cu conductor, use proper pulling grips

Direct burial

Excellent​ (steel tape armour protects from mechanical damage)

use warning tape

Conduit ID

≥ 1.5 × OD → ≥ 132 mm; use 150 mm or larger

—

Fixing

cable clamps, tray, direct buried

—

Impact resistance

High​ (steel tape armour)

—

Water resistance

Good (PVC sheath + armour)

not watertight; use lead-sheathed for submerged

UV resistance

Good (black PVC, outdoor rated)

—

Termination note

Cu conductors — standard compression lugs or mechanical lugs; requires 35 kV class terminations (cold-shrink or heat-shrink)

strip length 35–40 mm per core

 

6. Typical Service Applications. 35 kV primary grid transmission, industrial primary substations, large plant feeders, urban ring main units, wind/solar farm main collector circuits — high-voltage power distribution.

 

YJV22 3x150mm2 Copper HV High Voltage Power Cable XLPE Armored 26 35kV Underground

 

7. Testing & QA Regime. Routine: conductor DC resistance, 63 kV AC / 5 min withstand, partial discharge ≤ 10 pC at 26 kV, insulation resistance. Type: impulse voltage 200 kV, tan δ at 90 °C, bending test, heating cycle, dimensional check.

 

Cable Parameters

 

YJV22-3×150 mm² (26/35 kV) — High-Voltage XLPE Insulated Steel-Tape Armored Copper Power Cable — Full Parameter Sheet 
HV power cable · Cu conductor / thick XLPE insulation / Cu tape screen / inner PVC / double steel tape armor (22) / outer PVC · 3×150 mm² · 26/35 kV · 90 °C · GB/T 12701 / IEC 60840 · finished Ø ≈ 78 mm
Section Parameter Value Unit Remarks / Standard
01 · Identification
  Cable type YJV22 — XLPE insulated, steel tape armored, PVC sheathed, Cu conductor — HV power transmission
  Rated voltage (U0/U) 26/35 (Um=40.5) kV High-voltage power
  Number of cores 3 × 150 — 3-phase (L1/L2/L3)
  Conductor material Annealed copper — Class 2 compacted per GB/T 3956
  Insulation material XLPE (cross-linked polyethylene) — 90 °C rated, triple-layer extrusion
  Armor type Double steel tape (22) — Mechanical / crush protection
  Outer sheath material PVC (ST2), black — UV / weather protection
  Standard GB/T 12701 / IEC 60840 — HV XLPE cable
  Shielding Cu tape screen over insulation — Corona / partial discharge control
02 · Conductor (Copper)
  Conductor type Compacted stranded copper — Class 2 per GB/T 3956
  Conductor area 3 × 150 mm² 3-phase power
  Stranding construction 30 × 2.52 mm (approx.) — Compacted round
  DC resistance @ 20 °C ≤ 0.124 Ω/km Cu 150 mm² max per GB/T 3956
  Conductor screen Extruded semi-conducting — Stress control at conductor
  Conductor weight per km ≈ 4050 kg/km 3×150 Cu
03 · Insulation & Screening
  Insulation type XLPE (cross-linked polyethylene) — 90 °C rated
  Insulation thickness ≈ 8.8 mm 26/35 kV level (thick)
  Insulation screen Extruded semi-conducting + Cu tape — Cu tape ≈ 0.12 mm
  Inner sheath (bedding) PVC ≈ 2.0 Over cored assembly
  Steel tape armor Double galvanized steel tape ≈ 2×0.5 22 armor
  Outer PVC sheath PVC ST2, black ≈ 2.8 UV / weather resistant
  Finished outer diameter ≈ 78 mm Overall
04 · Electrical
  Rated voltage (U0/U) 26/35 kV High voltage
  Max system voltage (Um) 40.5 kV Temporary overvoltage
  DC resistance @ 20 °C ≤ 0.124 Ω/km Cu 150 mm²
  Insulation resistance ≥ 2000 MΩ·km XLPE — very high
  Routine test voltage (AC) 63 kV / 5 min — Power-frequency withstand
  Partial discharge test ≤ 10 pC at 26 kV — HV cable requirement
  Capacitance ≈ 0.18 μF/km XLPE HV
  Dielectric loss (tan δ) ≤ 0.0004 at 90 °C — HV quality
05 · Thermal
  Max continuous conductor temp. 90 °C XLPE rated
  Short-circuit temp. 250 °C Max 5 s duration
  Overload temp. 105 °C Short duration
  Ambient operating range -40 ~ +50 °C Outdoor / buried
  Laying temperature ≥ 0 °C Pre-heat below 0 °C
06 · Mechanical
  Min bending radius (fixed) ≥ 15 × OD ≈ 1170 mm Armed HV cable
  Min bending radius (flexed) ≥ 20 × OD ≈ 1560 mm Repeated flexing
  Crush resistance Good — Steel tape armor
  Tensile strength Per GB/T 12701 — Installation pull
07 · Ampacity
  Air ampacity (3×150 Cu) ≈ 230 A 25 °C ambient (est.)
  Buried ampacity ≈ 215 A Direct burial, 25 °C soil
  Free air current ≈ 250 A Open tray
08 · Installation
  Laying methods Tray, direct burial, duct, trench — HV transmission
  Terminations HV cold-shrink / heat-shrink terminations — 26/35 kV rated
  Joints HV straight joints / branch joints — 26/35 kV rated
  Special tools HV jointing kits, torque wrenches — Certified HV personnel only
09 · Packing
  Standard supply length 500 m / drum m HV cable on steel drums
  Reel / packing type Steel drum, sealed ends — Ends must be sealed
  Surface marking YJV22, 3×150, 26/35kV, GB/T 12701, metre marks — Continuous printing
  Storage conditions Dry, indoor, sealed ends — Protect from moisture
10 · Applications
  Typical use HV power transmission, 35 kV grid, industrial primary substations, large plant feeders, urban ring main units — High-voltage power
  Max system voltage 40.5 kV (Um) 26/35 kV rated
  Application level High voltage — Transmission / primary distribution

 

Cable Test Parameters

 

Test Parameters — YJV22-3×150 mm² (26/35 kV)
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 0.124 Ω/km (Cu 150 mm²) Routine
2 Power-frequency withstand 63 kV AC, 5 min No breakdown Routine
3 Partial discharge test 26 kV, 5 min ≤ 10 pC Routine
4 Insulation resistance 5000 V DC ≥ 2000 MΩ·km Routine
5 Dielectric loss (tan δ) 90 °C, U0 voltage ≤ 0.0004 Type
6 Impulse voltage test 200 kV lightning impulse, 10 shots No breakdown Type
7 Bending test 15× OD, 3 cycles No damage Type
8 Dimensional check Micrometer / caliper OD ≈ 78 mm, XLPE ≈ 8.8 mm Routine
9 Heating cycle test 90 °C ↔ ambient, 10 cycles No damage Type
10 Torsion / armor check Visual + dimensional Steel tape intact Routine
11 Conductor continuity Per GB/T 3956 All 3 cores continuous Routine
12 Sheath thickness Micrometer PVC ≥ 2.8 mm Routine

 

Cable Cross Section Structure

 

YJV22 3x150mm2 Copper HV High Voltage Power Cable XLPE Armored 26 35kV Underground

 

YJV22-3×150 mm² (26/35 kV) — Cross-Section Construction Diagram (Schematic)
HV power cable: Cu conductors → thick XLPE insulation → Cu tape screen → inner PVC → double steel tape armor (22) → outer PVC · 26/35 kV · 90 °C · finished Ø ≈ 78 mm
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductors (×3) Compacted stranded copper, Class 2, 3 × 150 mm² — ≈ 14.5 R ≤ 0.124 Ω/km
2 Insulation screen Extruded semi-conducting + Cu tape ≈ 0.12 (Cu tape) — Partial discharge control
3 XLPE insulation Cross-linked polyethylene (thick) ≈ 8.8 ≈ 32 90 °C rated, 26/35 kV
4 Inner sheath (bedding) PVC over cored assembly ≈ 2.0 ≈ 70 Bed over cores
5 Steel tape armor (22) Double galvanized steel tape ≈ 2×0.5 ≈ 74 Mechanical / crush protection
6 Outer PVC sheath PVC ST2, black, UV-resistant ≈ 2.8 ≈ 78 (finished) Weather / UV protection
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 78 mm Overall    
Approx. cable mass ≈ 7200 kg/km Cu conductors + thick XLPE + armor + PVC    
Nominal voltage rating 26/35 kV High-voltage power    
Max system voltage (Um) 40.5 kV Temporary overvoltage    
Max continuous conductor temp. 90 °C XLPE rated    
Short-circuit temp. 250 °C Max 5 s    
Min bending radius (fixed) ≥ 15 × OD ≈ 1170 mm Armed HV cable    
DC resistance @ 20 °C ≤ 0.124 Ω/km Cu 150 mm²    
Routine test voltage (AC) 63 kV / 5 min — Power-frequency withstand    
Partial discharge ≤ 10 pC at 26 kV — HV requirement    
Air ampacity @ 25 °C ≈ 230 A 3 cores loaded (est.)    
Buried ampacity ≈ 215 A Direct burial    
Impulse test voltage 200 kV — Lightning impulse    
Conductor material Copper — High conductivity    
Schematic — not to exact scale. Finished Ø ≈ 78 mm and weight ≈ 7200 kg/km from cross-referenced industry samples. YJV22-3×150 is a high-voltage (26/35 kV) XLPE-insulated, steel-tape-armored, copper-conductor power cable. Compared to YJLV22-3×400 (8.7/10 kV, aluminum conductor, 400 mm², Ø85 mm, 6200 kg/km, 410 A, 21 kV test), this cable operates at a much higher voltage (26/35 kV vs 8.7/10 kV), uses much thicker XLPE insulation (8.8 mm vs 5.5 mm), requires a higher routine test voltage (63 kV vs 21 kV), and is designed for 35 kV primary grid transmission rather than 10 kV distribution. Values marked (est.) require confirmation against the factory test certificate.

 

Construction Description

 

Construction Description — YJV22-3×150 mm² (26/35 kV HV armored cable)
Layer-by-layer HV power cable: Cu conductors / thick XLPE insulation / Cu tape screen / inner PVC / double steel tape armor / outer PVC · 26/35 kV · 90 °C · finished Ø ≈ 78 mm
1. Product Identity & Ratings
YJV22-3×150 is a high-voltage (26/35 kV) XLPE-insulated, steel-tape-armored, copper-conductor power cable built and tested per GB/T 12701 / IEC 60840. It has 3 copper conductors (150 mm² each, L1/L2/L3), thick XLPE insulation (8.8 mm) with copper tape screening, inner PVC bedding, double steel tape armor, and outer PVC sheath. Rated 90 °C continuous. Unlike YJLV22-3×400 (8.7/10 kV distribution, aluminum, 400 mm²), this is a 35 kV primary grid transmission cable. Finished Ø ≈ 78 mm, mass ≈ 7200 kg/km, steel drums.
2. Copper Conductors (3×150)
The 3 conductors use 150 mm² compacted stranded copper (R ≤ 0.124 Ω/km). At 35 kV, the current is lower than at 10 kV for the same power, so 150 mm² Cu is sufficient for 35 kV primary distribution. Each conductor has an extruded semi-conducting screen to control electrical stress.
3. Thick XLPE Insulation (8.8 mm)
XLPE insulation ≈ 8.8 mm thick — much thicker than the 8.7/10 kV version (5.5 mm). This is required to withstand the 26 kV phase-to-ground voltage. Over the insulation is a semi-conducting layer plus copper tape screen (≈ 0.12 mm). Routine test voltage is 63 kV / 5 min. Partial discharge ≤ 10 pC at 26 kV.
4. Steel Tape Armor (22)
Double galvanized steel tape (≈ 2×0.5 mm) over inner PVC bedding provides crush protection for direct burial in 35 kV grid trenches. The armor does not carry current — it is purely mechanical protection. At 35 kV, cable fault energy is higher, so robust armor is essential.
5. Site Handling & Operational Notes
• Bend radius 15×OD (≈ 1170 mm) fixed.  • Use HV cold-shrink / heat-shrink terminations rated 26/35 kV.  • 63 kV AC routine withstand test.  • Partial discharge ≤ 10 pC at 26 kV.  • Impulse test 200 kV.  • At 7200 kg/km, heavy steel drums.  • Store with ends sealed.  • For 35 kV primary grid, industrial substations.

 

8. Standards & Conformity. GB/T 12701 (HV plastic-insulated power cables up to 35 kV); IEC 60840 (XLPE HV cables); GB/T 3956 (conductors). Rated 26/35 kV (Um = 40.5 kV).

 

9. Packaging, Storage & Logistics. 500 m per steel drum with sealed ends. Continuous marking: YJV22, 3×150, 26/35 kV, GB/T 12701, metre marks. Store dry, indoor, ends sealed.

 

YJV22 3x150mm2 Copper HV High Voltage Power Cable XLPE Armored 26 35kV Underground

 

10. Procurement Specification. State "YJV22-3×150, 26/35 kV" + length. Order matching HV terminations/joints rated 26/35 kV. Confirm against factory test certificate (partial discharge + impulse test).

 

11. Cable Industry FAQ.

  • Q1: What is the difference between 26/35 kV and 8.7/10 kV? 26/35 kV is high-voltage primary grid transmission (35 kV phase-to-phase), while 8.7/10 kV is medium-voltage distribution (10 kV phase-to-phase). The HV cable requires much thicker insulation (8.8 mm vs 5.5 mm), higher test voltage (63 kV vs 21 kV), and higher impulse rating (200 kV vs 75 kV).
  • Q2: Why is the insulation so thick (8.8 mm)? At 26 kV phase-to-ground, the electrical stress on the insulation is much higher than at 8.7 kV. The thicker XLPE wall prevents dielectric breakdown and keeps partial discharge below 10 pC.
  • Q3: What is the routine test voltage for 26/35 kV? 63 kV AC for 5 minutes — this is 2.4× the rated phase voltage (26 kV). This proves the thick XLPE has no manufacturing defects.
  • Q4: What is the impulse voltage test? 200 kV lightning impulse — simulates switching surges and lightning strikes on the 35 kV grid. The cable must withstand 10 positive and 10 negative impulses without breakdown.
  • Q5: Why use copper at 35 kV? At 35 kV, current is lower than at 10 kV for the same power, so a smaller conductor (150 mm² Cu) is sufficient. Copper also has better short-circuit withstand and lower connection resistance.
  • Q6: What does "22" mean? 22 = inner PVC bedding + double steel tape armor + outer PVC sheath. Standard for buried HV cables where crush protection is needed.
  • Q7: Can YJV22-35kV be used outdoors? Yes — the outer PVC sheath is UV-resistant. For direct burial, the steel tape armor provides crush protection.
  • Q8: What bending radius is required? 15×OD ≈ 1170 mm for fixed installation. HV cables require larger bend radii because the thick XLPE insulation is rigid.
  • Q9: What is partial discharge at 26 kV? Tiny electrical sparks inside the insulation at defects. HV cables must have ≤ 10 pC at rated voltage (26 kV) to ensure 30-year service life.
  • Q10: Can YJV22 be used for fire pump circuits? No — YJV22 is not fire-resistant. Fire pump circuits must use mineral-insulated fire cables (BTTRZ/BTLY). YJV22 is for standard HV power transmission.
  • Q11: How is the cable terminated? HV cold-shrink or heat-shrink terminations rated 26/35 kV. The termination must carefully strip the thick XLPE insulation, insulation screen, and conductor screen in the correct order. Only certified HV personnel should terminate 35 kV cables.