3+1 Core Flame Retardant 4 Cores Cable For Factory Three Phase Main Power
Product Summary
Product Details
Three Phase 4 Cores Cable
,4 Cores Cable 1.5mm sheath
,10 sq mm copper cable 4 core
Product Description
ZR-YJV 3+1 Core Flame Retardant Copper Cable 3x16mm²+1x10mm² for Factory Three-Phase Main Power
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZR |
Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC outer sheath — flame-retardant grade, contains halogen (Cl) |
|
0.6/1 kV |
Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV |
|
3×16+1×10 mm² |
Three phase cores of 16 mm² copper + one reduced neutral core of 10 mm² copper |

ZC-YJV 3×16+1×10 mm² — LV Flame-Retardant 3+1 Power Cable — Specification
1. Overview & Ratings. ZC-YJV 3×16+1×10 is a 3+1 LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant PVC sheath: three 16 mm² compacted copper phase cores plus one 10 mm² compacted neutral, dry-cured XLPE, unarmored. OD ≈ 14 mm, ≈ 900 kg/km (est.), ≈ 85 A per phase free air at 30 °C (est.). Scope: 380/400 V small motor groups, control panel feeds and mixed branches — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor L1/L2/L3 | 3×16 compacted Cu, Class 2, ≈7 strands | Phases, R ≤1.15 Ω/km |
| Conductor N | 1×10 compacted Cu, Class 2, ≈7 strands | Reduced neutral, R ≤1.91 Ω/km |
| Strand compaction | Concentric layers rolled compact per core | Round bundles, clean lug entry |
| XLPE insulation (phases) | Dry-cured PE, ≈1.2 mm | 90°C phase dielectric |
| XLPE insulation (neutral) | Dry-cured PE, ≈1.0 mm | Neutral dielectric |
| Core identification | L1/L2/L3/N color code | Phase sequence + neutral |
| 3+1 core laying | 3 phases around neutral | Stable round bundle |
| PVC ZC sheath | Class C, ≈1.3 mm overall | Binds bundle, self-extinguishes |
| Jacket print | Continuous type/size/voltage/length | On-site readable spec |
3. Electrical Characteristics. Phase R ≤ 1.15 Ω/km, neutral R ≤ 1.91 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 85 A per phase (est., air 30 °C); short-circuit ≈ 2.4 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C (phase) |
≤ 1.15 Ω/km per core |
GB/T 3956 Class 2 Cu max (16 mm²) |
|
DC resistance @20 °C (neutral) |
≤ 1.83 Ω/km per core |
GB/T 3956 Class 2 Cu max (10 mm²) |
|
AC resistance @90 °C (est., phase) |
≈ 1.47 Ω/km per core |
— |
|
AC resistance @90 °C (est., neutral) |
≈ 2.35 Ω/km per core |
— |
|
Current rating in air (30 °C) |
3-phase: 75 A |
3×16+1×10, touching, in free air |
|
Current rating in tray (30 °C) |
3-phase: 85 A |
3×16+1×10, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
3-phase: 80 A |
direct buried |
|
Current rating in conduit (30 °C) |
3-phase: 65 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C, phase) |
≈ 1.8 kA (1,800 A) per core |
— |
|
Short-circuit current (1 s, Cu, 250 °C, neutral) |
≈ 1.1 kA (1,100 A) per core |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.14 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 3×16+1×10 at 75 A three-phase, 400 V → max load ≈ 45 kW (cos φ = 0.8). Suitable for small-to-medium three-phase distribution with reduced neutral, balanced loads, and small-to-medium motors.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. 16 mm² phase lugs, 10 mm² neutral lug, glands sized to 14 mm OD, crimp/torque per table; bend ≥ 15×OD ≈ 210 mm; derate bundled/conduit runs; keep the 3+1 bundle round; continuity, phase sequence, neutral + insulation after pulling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 233 mm at Ø15.5 mm |
four-core unarmoured |
|
Max. pulling tension (phase) |
240 N per core (16 mm² × 15 N/mm²) |
Cu conductor limit |
|
Max. pulling tension (neutral) |
150 N per core (10 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Excellent (cable tray, ladder, cleats) |
— |
|
Conduit ID |
≥ 25 mm |
— |
|
Fixing |
cable ties, cleats |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. 380/400 V small three-phase motor group leads, control panel and distribution board branch feeds, mixed lighting-and-power circuits in workshops, commercial rooms and light industry.

7. Testing & QA Regime (16 items). Routine: phase DC resistance (16), neutral DC resistance (10), 3.5 kV withstand, insulation resistance, continuity, sheath/phase/neutral insulation thickness, dimensional check, strand construction, eccentricity, print legibility, mass. Type: ZC flame test, short-circuit rating, sheath mechanical.
Cable Parameters
| ZC-YJV 3×16+1×10 mm² — LV Flame-Retardant 3+1 Power Cable — Full Parameter Sheet | |||
| 3×16 Cu phase / 1×10 Cu neutral · XLPE / PVC ZC · 0.6/1 kV · ≈14 mm · 3-phase + neutral for 380/400 V small motor group, control panel and mixed feeder | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — Cu/XLPE/PVC, flame-retardant class C | — | ZC-YJV denotes a copper conductor with cross-linked polyethylene insulation and a PVC outer sheath; ZC marks a class C flame-retardant PVC compound that self-extinguishes after the ignition source is removed. |
| Rated voltage (U0/U) | 0.6/1 | kV | 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines a general low-voltage cable suited to 380/400 V distribution. |
| Maximum operating voltage (Um) | 1.2 | kV | The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service. |
| Core configuration | 3×16 phase + 1×10 neutral (3+1) | — | Three 16 mm² compacted copper phase cores around one 10 mm² compacted neutral core, laid 3+1 for small balanced three-phase loads with a reduced neutral. |
| Conductor material | Compacted stranded annealed copper | — | Soft annealed copper strands are layer-compacted into round bundles: 16 mm² on phases, 10 mm² on the neutral, for clean lug entry. |
| Insulation | XLPE cross-linked polyethylene | — | Chemically cross-linked polyethylene bonds into a heat-resistant dielectric retaining properties at the 90 °C operating temperature. |
| Sheath | PVC, flame-retardant class C (ZC) | — | An overall PVC jacket binds the 3+1 bundle and carries the class C flame-retardant formulation; deep chestnut brown finish. |
| Flame retardancy | ZC class C (self-extinguishing, not fire-rated) | — | On removal of a flame the cable stops propagating fire; this is flame retardancy, not 950 °C/180 min circuit-integrity fire resistance. |
| Suitable for | Fixed indoor tray, conduit, trunking, 3-phase+N | — | Designed for fixed three-phase-plus-neutral wiring serving small motor groups, control panel feeds and mixed lighting/power branches. |
| Application | 380V small motor group / panel feeder | — | Typically runs three phases plus a reduced neutral from a sub-board to a small motor group, control panel or mixed branch circuit. |
| Application note | Not for 950°C circuit-integrity fire duty | — | Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire. |
| 02 · Conductors | |||
| Phase cores count / area | 3 × 16 | mm² | Three 16 mm² phase conductors carry the three phases of a small-to-medium 400 V branch or group load. |
| Neutral core count / area | 1 × 10 | mm² | One 10 mm² reduced neutral returns unbalanced current on small motor and mixed resistive three-phase loads. |
| Conductor type | Compacted stranded Cu, Class 2 | — | Class 2 stranded compacted construction gives fixed-wiring conductors that round into stable bundles for clean lug termination. |
| DC resistance (16 phase) @ 20°C | ≤ 1.15 | Ω/km | Maximum permitted DC resistance of a 16 mm² phase copper conductor at 20 °C. |
| DC resistance (10 neutral) @ 20°C | ≤ 1.91 | Ω/km | Maximum permitted DC resistance of a 10 mm² neutral copper conductor at 20 °C; neutral drop on long branch runs. |
| Stranding | Layer-compacted concentric bundle | — | Concentric layers of strands are compacted radially per core to reduce gaps, tighten the bundle and present a clean round lug entry. |
| Strands (nom., est.) | 16 ≈7 / 10 ≈7 | — | Approximate strand counts: about 7 compacted strands in a 16 mm² core and about 7 in the 10 mm² core; exact count follows the standard. |
| Surface | Bare copper; tinned optional | — | Bare copper suits most indoor use; optional tinned plating improves corrosion resistance in damp sites. |
| Core identification | L1/L2/L3 phase + N neutral by color | — | Phases and neutral are color-coded so phase sequence and neutral match at the panel or equipment terminal. |
| Nominal area tolerance | Within conductor class 2 band | — | Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count. |
| 03 · Insulation | |||
| Insulation material | XLPE (cross-linked polyethylene) | — | Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than PVC insulation for the same size. |
| Insulation thickness (phase 16, nom.) | ≈ 1.2 | mm | Nominal radial insulation wall on each 16 mm² phase core; gauged to withstand the 3.5 kV routine test. |
| Insulation thickness (neutral 10, nom.) | ≈ 1.0 | mm | Reduced wall on the 10 mm² neutral core, still gauged for the routine withstand test. |
| Working conductor temp. | 90 | °C | Maximum continuous conductor temperature under rated current without shortening insulation life. |
| Short-circuit temp. | 250 | °C | Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs. |
| Insulation resistance | High and stable | MΩ·km | XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on 3-phase branches. |
| Color | L1/L2/L3/N color on request | — | Insulation colors are matched to local 3-phase convention or supplied natural with printed marking. |
| Cure type | Chemical / dry-cured XLPE | — | A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat. |
| 04 · Sheath & Flame Retardancy | |||
| Sheath material | PVC, flame-retardant ZC | — | The class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface. |
| Sheath thickness (nom.) | ≈ 1.3 | mm | Nominal overall jacket wall sized to shield the four cores from abrasion, dust and occasional moisture in trunking. |
| Finished outer diameter | ≈ 14 | mm | Overall 3+1 finished diameter used to size conduit fill, trunking and gland entry. |
| Flame behavior | Self-extinguishing, class C | — | After the test flame is removed the sample extinguishes without propagating; it is not 950°C fire-rated. |
| Sheath color | Deep chestnut brown (black/gray on request) | — | Standard deep chestnut brown; black or dark gray jackets are supplied for industrial aesthetics on request. |
| Surface finish | Smooth, continuous print | — | A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length. |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | Low-voltage rating matching 380/400 V distribution systems. |
| Max voltage (Um) | 1.2 | kV | Continuous upper system voltage for phase-to-earth insulation stress. |
| Nominal current (per 16 phase, est.) | ≈ 85 | A | Approximate ampacity of a single 16 mm² phase core in free air at 30 °C; reduce for bundling, conduit fill and high ambient. |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine dielectric withstand applied between each conductor and sheath for five minutes without breakdown. |
| Insulation resistance | High, XLPE | MΩ·km | Measured after conditioning; confirms no void, crack or contamination in the cured insulation. |
| Short-circuit current (16 phase, 1s, est.) | ≈ 2.4 | kA | Approximate 1-second copper short-time withstand on the 16 mm² phase core; branch fault duty. |
| Frequency | 50 / 60 | Hz | Compatible with both 50 Hz and 60 Hz three-phase power systems. |
| Dielectric | XLPE, low loss | — | Low dielectric loss keeps heating down under continuous small motor-group and branch load. |
| 06 · Thermal & Environment | |||
| Normal conductor temp. | 90 | °C | Sustained operating temperature the XLPE insulation is rated for under full load. |
| Installed ambient | 0 ~ +40 | °C | Recommended continuous ambient around the cable; higher rooms require ampacity derating. |
| Min install temp. | 0 | °C | Avoid cold bending below 0 °C where the PVC jacket and insulation may stiffen and crack. |
| Burning | Self-extinguishing, ZC class C | — | Class C vertical flame test behavior: flame stops once the external burner is removed. |
| Outdoor / UV | Indoor preferred; UV-grade jacket optional | — | Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor runs. |
| Oil / chemicals | Resistant to common oils; check aggressive media | — | Withstands typical machine oils; verify against specific solvents or acid fumes before use. |
| Temperature cycle | Withstands repeated 0~90°C duty | — | The insulation and jacket survive repeated heating/cooling cycles without cracking or delamination. |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 210 | mm | Fixed-installation minimum bend radius for the 3+1 cable; tighter bends strain insulation and jacket. |
| Flexibility | Stranded, easy to pull on site | — | Compacted strands keep the cable flexible enough to route through conduit and trunking. |
| Shielding / Armor | None / unarmored | — | No copper braid screen and no armor; add screening or armor where EMI or mechanical protection is required. |
| Cable weight per km (est.) | ≈ 900 | kg/km | Approximate mass per kilometer used for tray loading and coil/drum sizing. |
| Circularity | 3+1 core bundle, stable OD | — | Three phase cores plus one neutral lay into a round bundle so the finished OD stays consistent. |
| Tensile / elongation | Jacket meets PVC grade | — | Sheath tensile strength and elongation satisfy the PVC compound grade for durable pulling. |
| 08 · Factory Advantages | |||
| Balanced 3+1 sizing | 3×16 phases with 1×10 neutral matches group load | — | Reduced neutral avoids excess copper while carrying normal unbalanced current. |
| Stable XLPE cure | Even cross-linking keeps the 90°C dielectric consistent lot to lot | — | Controlled cure removes soft spots in insulation that would age faster under panel duty. |
| Dosed ZC compound | Flame-retardant PVC self-extinguishes to class C | — | Dosed flame inhibitors give a safety margin in panel rooms and cable trenches. |
| Length-on-demand | Cut to exact meter, sealed ends, minimal offcut | — | Custom cut lengths match the measured branch route and reduce waste. |
| Batch resistance log | Phase R (16) and neutral R (10) logged against lot | — | Both phase and neutral resistances are recorded against batch ID for traceability. |
| Continuous print line | Type, size, ZC, voltage and length along jacket | — | Clear continuous marking lets installers read the spec without a certificate on site. |
| Phase-color option | L1/L2/L3/N insulation colors matched to convention | — | Pre-colored phases and neutral remove wiring guesswork at the panel terminal. |
| Coil or drum pack | Coil for branches; drum for longer feeds | — | Pack choice matched to the length and handling method. |
| Certified QA pack | Routine + type test record shipped per batch | — | A complete QA packet supports buyer audit and commissioning sign-off. |
| 09 · Installation | |||
| Laying | Tray, conduit, trunking, 3-phase+N | — | Route in fixed supports; keep the 3+1 bundle round and bending above 15×OD. |
| Connectors | 16 mm² phase lugs, 10 mm² neutral lug | — | Crimp matched 16 mm² lugs on phases and a 10 mm² lug on the neutral; select a gland sized to 14 mm OD. |
| Bend radius | ≥ 15×OD ≈ 210 mm | — | Maintain the minimum radius around corners to prevent insulation cold-working. |
| Parallel runs | Derate when bundled in conduit/tray | — | Adjacent heating cores share heat; apply bundle derating before sizing the group breaker. |
| Site test | Continuity + insulation post-laying | — | After pulling, verify three-phase continuity, neutral, phase sequence and insulation resistance. |
| Termination | Strip, crimp lug, torque per table | — | Strip insulation without nicking strands, crimp each lug fully, and torque per the lug table. |
| 10 · Packing & Applications | |||
| Supply length | Custom / coil or drum | m | Cut to the measured branch length; coil or drum packing. |
| Length tolerance | Per trade standard for cut lengths | — | Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise. |
| Reel type | Coil / wooden drum | — | Coil for short panel leads; drum for longer group feeds. |
| Surface marking | ZC-YJV, 3×16+1×10, 0.6/1kV, ZC, length | — | Jacket prints type, 3+1 core size, voltage, flame class and cumulative meter length. |
| Typical use | Small motor group, control panel, mixed branch | — | Runs three phases plus neutral to panels and small motor groups. |
| Storage | Dry indoor, avoid direct UV | — | Store on a pallet, dry and shaded, to keep the jacket intact. |
Cable Test Parameters
| Test Parameters — ZC-YJV 3×16+1×10 LV Flame-Retardant 3+1 Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Phase DC resistance | 20 °C, each L1/L2/L3 (16 mm²) | 16 ≤1.15 Ω/km | Routine |
| 2 | Neutral DC resistance | 20 °C, N (10 mm²) | 10 ≤1.91 Ω/km | Routine |
| 3 | Voltage test (AC) | 3.5 kV AC, 5 min, core-to-sheath | No breakdown | Routine |
| 4 | Insulation resistance | XLPE, 20°C, per core | High & stable | Routine |
| 5 | Continuity | Each core L1/L2/L3/N | Continuous | Routine |
| 6 | Flame retardancy | Class C vertical test | Self-extinguish | Type |
| 7 | Sheath thickness | Micrometer, cross-section | Nominal ≥1.3 mm | Routine |
| 8 | Phase insulation thickness | Micrometer, 16 mm² cores | Nominal ≥1.2 mm | Routine |
| 9 | Neutral insulation thickness | Micrometer, 10 mm² core | Nominal ≥1.0 mm | Routine |
| 10 | Dimensional check | Caliper, overall OD | OD ≈ 14 mm | Routine |
| 11 | Conductor construction | Visual / strand count per core | Class 2 compacted | Routine |
| 12 | Short-circuit rating | Calculated / type | 2.4 kA / 1 s (phase) | Type |
| 13 | Insulation eccentric test | Cross-section measure per core | Within tolerance | Routine |
| 14 | Printing legibility | Visual | Marking readable | Routine |
| 15 | Mass per unit length | Weigh / calculate | ≈ 900 kg/km | Routine |
| 16 | Sheath mechanical | Tensile / elongation check | Meets PVC grade | Type |
Cable Cross Section Structure

| ZC-YJV 3×16+1×10 — 3+1 Cross-Section Construction Diagram | |||||
| 3×16 phase Cu + 1×10 neutral Cu / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈14 mm · 380/400 V small motor group, control panel & mixed branches | |||||
| No. | Layer / Feature | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Detailed Function / Remarks |
| 1 | Conductor L1 — phase | 1×16 compacted Cu, Class 2, ≈7 strands | — | ≈ 4.4 | Phase 1 core, DC R ≤1.15 Ω/km @20°C; group motor current. |
| 2 | Conductor L2 — phase | 1×16 compacted Cu, Class 2, ≈7 strands | — | ≈ 4.4 | Phase 2 core, same size/resistance for balanced impedance. |
| 3 | Conductor L3 — phase | 1×16 compacted Cu, Class 2, ≈7 strands | — | ≈ 4.4 | Phase 3 core, same spec; color-coded for phase sequence. |
| 4 | Conductor N — neutral | 1×10 compacted Cu, Class 2, ≈7 strands | — | ≈ 3.6 | Reduced neutral, DC R ≤1.91 Ω/km; returns unbalanced current. |
| 5 | Strand compaction | Concentric layers rolled compact per core | — | — | Radial compaction closes strand gaps for round bundles and clean lug entry. |
| 6 | XLPE insulation (phases) | Dry-cured cross-linked PE, ≈1.2 mm | ≈ 1.2 | ≈ 6.8 | 90°C dielectric on each 16 mm² phase core, low loss, stable R-insulation. |
| 7 | XLPE insulation (neutral) | Dry-cured cross-linked PE, ≈1.0 mm | ≈ 1.0 | ≈ 5.6 | Matching neutral insulation; N distinguished by color from phases. |
| 8 | 3+1 laying & PVC ZC sheath | 3 phases + 1 neutral, class C jacket | ≈ 1.3 | ≈ 14 | Three phases around the neutral; jacket binds bundle and self-extinguishes. |
| 9 | Jacket print | Continuous type/size/voltage/length line | — | — | Marking: ZC-YJV, 3×16+1×10, 0.6/1kV, ZC, cumulative length. |
| Key Dimensions, Electrical & Mechanical Properties (expanded) | |||||
| Finished cable diameter | ≈ 14 | mm | 3+1 overall OD for conduit and gland sizing. | ||
| Approx. cable mass (est.) | ≈ 900 | kg/km | Light-to-medium branch cable. | ||
| Nominal voltage rating | 0.6/1 | kV | Matches 380/400 V systems. | ||
| Max voltage (Um) | 1.2 | kV | Phase-to-earth continuous upper limit. | ||
| Normal conductor temp. | 90 | °C | Continuous load temperature of XLPE. | ||
| Short-circuit temp. | 250 | °C | Short-time fault peak before insulation damage. | ||
| DC resistance (16 phase) | ≤ 1.15 | Ω/km | Per phase core @20°C. | ||
| DC resistance (10 neutral) | ≤ 1.91 | Ω/km | Neutral core @20°C. | ||
| Nominal phase current (est.) | ≈ 85 | A | Per 16 phase core, free air 30°C; derate bundled. | ||
| Short-circuit rating (1s, est.) | ≈ 2.4 | kA | 16 phase, branch fault duty. | ||
| Flame retardancy | ZC class C, self-extinguishing | — | Not 950°C fire-rated. | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 210 | mm | Fixed 3+1 install corner radius. | ||
| Frequency | 50 / 60 | Hz | Compatible with both power systems. | ||
| Insulation resistance | High & stable | MΩ·km | XLPE; supports earth-fault detection. | ||
| Dielectric loss | Low | — | XLPE keeps heating down on branch load. | ||
| Temperature cycle | 0~90°C repeated | — | Survives heating/cooling without cracking. | ||
| Sheath mechanical | Meets PVC grade | — | Tensile/elongation checked at type test. | ||
| Pack choice | Coil or drum | — | Coil for short panel leads. | ||
| Core configuration | 3×16 + 1×10 (3+1) | — | Three phases + reduced neutral. | ||
| Application | Small motor group, panel, mixed branch | — | 380/400 V small 3-phase+N power. | ||
| Schematic — not to exact scale. OD ≈14 mm, weight ≈900 kg/km, phase ampacity ≈85 A free air at 30°C and ≈2.4 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 3×16+1×10 serves 380/400 V small motor groups, control panel feeds and mixed branches; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 3×16+1×10 LV flame-retardant 3+1 cable | |||
| 3×16 phase Cu + 1×10 neutral Cu / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈14 mm · small motor group, control panel & mixed branches | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 3×16+1×10 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; three 16 mm² phases plus one 10 mm² neutral in 3+1 lay. OD ≈14 mm, ≈900 kg/km (est.), ≈85 A per phase free air at 30°C (est.), coil or drum. It is a fixed small-to-medium branch cable, not a flexible cord and not a 950°C fire-rated circuit. | |||
| 2. Copper Conductors (3×16 phases + 1×10 neutral) | |||
| Three 16 mm² compacted Class 2 Cu phase cores (L1/L2/L3), R ≤1.15 Ω/km @20°C, plus one 10 mm² compacted Cu neutral, R ≤1.91 Ω/km @20°C; reduced neutral for small balanced loads; tinned plating optional; phase-color insulation on request. | |||
| 3. Strand Compaction & 3+1 Bundle | |||
| Concentric strands are rolled compact per core to close gaps and give clean lug entry; the three phase cores lay around the neutral in a controlled 3+1 arrangement to hold a round bundle before sheathing. | |||
| 4. XLPE Insulation | |||
| Dry-cured cross-linked PE ≈1.2 mm on phases and ≈1.0 mm on the neutral; stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; phases and neutral distinguished by color. | |||
| 5. Core Identification | |||
| L1/L2/L3 phases and the N neutral are identified by insulation color so phase sequence and neutral match at the panel or equipment terminal; colors can be supplied to local 3-phase convention. | |||
| 6. PVC ZC Sheath | |||
| Flame-retardant PVC ≈1.3 mm overall, self-extinguishing class C; deep chestnut brown standard (black/gray on request); smooth printable surface; binds the 3+1 bundle and shields from abrasion and trunking dust. | |||
| 7. Electrical Characteristics | |||
| 0.6/1 kV, Um 1.2; phase R ≤1.15, neutral R ≤1.91 Ω/km; routine 3.5 kV AC/5 min; ≈85 A per phase (est., air 30°C); short-circuit ≈2.4 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE. | |||
| 8. Factory Advantages | |||
| • Balanced 3+1 sizing (3×16 phases + 1×10 neutral). • Stable XLPE cure lot to lot. • Dosed ZC self-extinguish. • Length-on-demand. • Phase + neutral resistance log. • Continuous clear print. • Phase-color option. • Coil or drum pack. • Certified QA pack. | |||
| 9. Site Handling & Installation | |||
| • Bend 15×OD (≈210 mm). • 16 mm² phase lugs, 10 mm² neutral lug, small glands, torque per table. • Derate bundled/conduit runs. • Keep 3+1 bundle round. • Continuity, phase sequence, neutral + insulation after pulling. | |||
| 10. Typical Service Applications | |||
| 380/400 V small three-phase motor group leads, control panel and distribution board branch feeds, mixed lighting-and-power circuits in workshops, commercial rooms and light industry. | |||
| 11. Testing & QA | |||
| 16-item regime: routine phase DC resistance (16), neutral DC resistance (10), 3.5 kV withstand, insulation resistance, continuity, sheath/phase/neutral insulation thickness, dimensional check, strand construction, eccentricity, print legibility, mass; type ZC flame, short-circuit, sheath mechanical. | |||
| 12. Packaging, Storage & Notes | |||
| Cut to measured branch length on coil or drum; continuous marking; store dry indoor on a pallet, shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated. |
8. Factory Advantages.
- Balanced 3+1 sizing — 3×16 phases with 1×10 neutral matches group load.
- Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
- Dosed ZC compound — self-extinguishes to class C.
- Length-on-demand — exact meter, sealed ends, minimal offcut.
- Phase + neutral resistance log — both recorded against lot number.
- Continuous print line — type, size, ZC, voltage and length along jacket.
- Phase-color option — L1/L2/L3/N colors matched to convention.
- Coil or drum pack — coil for short panel leads.
- Certified QA pack — routine + type test record per batch.

9. Packaging, Storage & Logistics. Cut to measured branch length on coil or drum; continuous marking; store dry indoor on a pallet, shaded, avoid direct UV.

10. Procurement Specification. State "ZC-YJV 3×16+1×10", length, class C, phase colors, pack; note flame retardant not fire-rated; request phase + neutral resistance log and 16-item QA record. Est. values confirmed against the factory certificate.
11. Cable Industry FAQ.
- Q1: How does 3×16+1×10 differ from 2×10? Three phases plus a reduced neutral (3+1) vs a twin L+N pair; larger (16 vs 10 mm²), thicker (14 vs 10.0 mm), heavier (900 vs 320 kg/km), higher current (85 vs 55 A), lower phase resistance (1.15 vs 1.91 Ω/km). It serves 400 V three-phase groups rather than 230 V twin drops.
- Q2: Why a 10 mm² neutral? Small balanced motor and resistive loads draw little neutral current, so a reduced neutral controls copper cost safely.
- Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
- Q4: DC resistance values? Phase 16 ≤1.15 Ω/km; neutral 10 ≤1.91 Ω/km at 20°C.
- Q5: When a full-size neutral? High single-phase non-linear or harmonic load; choose 4×16 instead.
- Q6: Shielded or armored? Neither standard; add on request.
- Q7: Current per phase? ≈ 85 A (est.) free air 30°C; derate in conduit/tray.
- Q8: Connectors? 16 mm² phase lugs, 10 mm² neutral lug, gland to 14 mm OD.
- Q9: Indoor or outdoor? Indoor preferred; UV-grade jacket for exposed runs.
- Q10: Packing? Coil for short panel leads; drum for longer group feeds.
- Q11: What proof ships? Phase + neutral resistance log + 16-test record; est. values confirmed against certificate.