OEM Copper Xlpe Cable 4 Core Heat Resistant Flex 3×50mm2+1×25mm2 For Heavy Duty
Product Summary
Product Details
OEM 4 core heat resistant flex
,4 core heat resistant flex 900kg/km
,Heavy Duty copper xlpe cable
Product Description
Flame Retardant Copper Conductor ZR-YJV 3×50mm²+1×25mm² for Heavy-Duty Three Phase Supply
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
3×50 mm² + 1×25 mm² |
Three phase cores of 50 mm² + one neutral core of 25 mm² copper conductor |
Construction: Three 50 mm² copper conductors (phase) + one 25 mm² copper conductor (neutral), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).
ZC-YJV 3×50+1×25 mm² — LV Flame-Retardant 3+1 Power Cable — Specification
1. Overview & Ratings. ZC-YJV 3×50+1×25 is a compact 3+1 LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant PVC sheath: three 50 mm² compacted copper phase cores plus one reduced 25 mm² neutral, dry-cured XLPE, unarmored (armor/screen optional). OD ≈ 16 mm, ≈ 1450 kg/km (est.), ≈ 120 A per phase free air at 30 °C (est.). Scope: 380/400 V motor branches, machine supplies and panel feeders — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Phase conductors L1/L2/L3 | 3×50 compacted Cu, Class 2, ≈19 strands | Phases, R ≤0.387 Ω/km |
| Neutral conductor N | 1×25 compacted Cu, Class 2, ≈7 strands | Reduced neutral, R ≤0.741 Ω/km |
| Strand compaction | Concentric layers rolled compact per core | Compact round bundles, clean lugs |
| XLPE insulation (phases) | Dry-cured PE, ≈1.6 mm | 90°C phase dielectric |
| XLPE insulation (neutral) | Dry-cured PE, ≈1.4 mm | Matched neutral dielectric |
| 3+1 core laying | 3 phases around 1 neutral | Stable compact round bundle |
| PVC ZC sheath | Class C, ≈1.5 mm overall | Binds bundle, self-extinguishes |
| Jacket print | Continuous type/size/voltage/length | On-site readable spec |
3. Electrical Characteristics. Phase R ≤ 0.387 Ω/km, neutral R ≤ 0.741 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 120 A per phase (est., air 30 °C); short-circuit ≈ 4.2 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C (phase) |
≤ 0.387 Ω/km per core |
GB/T 3956 Class 2 Cu max (50 mm²) |
|
DC resistance @20 °C (neutral) |
≤ 0.727 Ω/km per core |
GB/T 3956 Class 2 Cu max (25 mm²) |
|
AC resistance @90 °C (est., phase) |
≈ 0.496 Ω/km per core |
— |
|
AC resistance @90 °C (est., neutral) |
≈ 0.932 Ω/km per core |
— |
|
Current rating in air (30 °C) |
3-phase: 165 A |
3×50+1×25, touching, in free air |
|
Current rating in tray (30 °C) |
3-phase: 185 A |
3×50+1×25, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
3-phase: 175 A |
direct buried |
|
Current rating in conduit (30 °C) |
3-phase: 145 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C, phase) |
≈ 5.5 kA (5,500 A) per core |
— |
|
Short-circuit current (1 s, Cu, 250 °C, neutral) |
≈ 2.8 kA (2,800 A) per core |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.18 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 3×50+1×25 at 165 A three-phase, 400 V → max load ≈ 99 kW (cos φ = 0.8). Suitable for medium three-phase distribution with reduced neutral, industrial motors, and building sub-main feeders.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands repeated motor start-stop 0~90°C cycles; indoor; UV-grade jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. 50 mm² phase lugs, 25 mm² neutral lug, glands to ≈16 mm OD, hydraulic crimp/torque per table; bend ≥ 15×OD ≈ 240 mm; apply conduit/bundle derating; keep the 3+1 bundle round; three-phase continuity, sequence, neutral + insulation after pulling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 368 mm at Ø24.5 mm |
four-core unarmoured |
|
Max. pulling tension (phase) |
750 N per core (50 mm² × 15 N/mm²) |
Cu conductor limit |
|
Max. pulling tension (neutral) |
375 N per core (25 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Heavy-duty cable tray, ladder, cleats |
— |
|
Conduit ID |
≥ 50 mm |
— |
|
Fixing |
heavy-duty cleats, cable ties |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. 380/400 V motor branch circuits, compressors, pumps, fans, machine-tool power feeds, panel-to-equipment feeders and general three-phase machine supplies.

7. Testing & QA Regime (16 items). Routine: phase DC resistance (50), neutral DC resistance (25), 3.5 kV withstand, insulation resistance, 3-phase+neutral continuity, phase/neutral insulation thickness, sheath thickness, dimensional check, strand construction, eccentricity, print legibility, mass, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.
Cable Parameters
| ZC-YJV 3×50+1×25 mm² — LV Flame-Retardant 3+1 Power Cable — Full Parameter Sheet | |||
| 3×50 phase Cu + 1×25 neutral Cu · XLPE insulation / PVC sheath · ZC · 0.6/1 kV · ≈16 mm · 3+1 lay · 380/400 V motor branch, machine supply and panel feeder | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — Cu/XLPE/PVC, flame-retardant class C | — | ZC-YJV denotes a copper conductor with cross-linked polyethylene insulation and a PVC outer sheath; ZC marks a class C flame-retardant PVC compound that self-extinguishes after the ignition source is removed. |
| Rated voltage (U0/U) | 0.6/1 | kV | 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines a general low-voltage cable suited to 380/400 V branch and panel distribution. |
| Maximum operating voltage (Um) | 1.2 | kV | The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service. |
| Core configuration | 3×50 phase + 1×25 neutral (3+1) | — | Three 50 mm² compacted copper phase cores plus one 25 mm² compacted neutral core, laid in a 3+1 arrangement for motor and panel branch circuits. |
| Conductor material | Compacted stranded annealed copper | — | Soft annealed copper strands are layer-compacted into round 50 mm² phase and 25 mm² neutral bundles for clean lug entry. |
| Insulation | XLPE cross-linked polyethylene | — | Chemically cross-linked polyethylene bonds into a heat-resistant dielectric retaining properties at the 90 °C operating temperature. |
| Sheath | PVC, flame-retardant class C (ZC) | — | An overall PVC jacket binds the 3+1 bundle and carries the class C flame-retardant formulation; deep aubergine purple finish. |
| Flame retardancy | ZC class C (self-extinguishing, not fire-rated) | — | On removal of a flame the cable stops propagating fire; this is flame retardancy, not 950 °C/180 min circuit-integrity fire resistance. |
| Suitable for | Fixed motor branch, machine supply, panel feeder | — | Designed for fixed three-phase-plus-neutral branch feeders serving motors, machines and distribution panel groups. |
| Application | 380V motor branch / machine power feeder | — | Typically runs from a panel breaker to a three-phase motor, compressor, pump or machine tool with a reduced neutral. |
| Application note | Not for 950°C circuit-integrity fire duty | — | Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire. |
| 02 · Conductors | |||
| Phase cores count / area | 3 × 50 (L1/L2/L3) | mm² | Three 50 mm² phase conductors carrying the three-phase load current to the motor or machine. |
| Neutral core count / area | 1 × 25 (N) | mm² | One 25 mm² neutral conductor sized for the branch neutral and limited harmonic current on balanced motor loads. |
| Conductor type | Compacted stranded Cu, Class 2 | — | Class 2 stranded compacted construction gives fixed-wiring conductors that round into stable bundles for lug termination. |
| DC resistance (50 phase) @ 20°C | ≤ 0.387 | Ω/km | Maximum permitted DC resistance of a 50 mm² copper phase conductor at 20 °C, applied to L1/L2/L3. |
| DC resistance (25 neutral) @ 20°C | ≤ 0.741 | Ω/km | Maximum permitted DC resistance of the 25 mm² neutral conductor at 20 °C; higher than phases by design of the reduced neutral. |
| Stranding | Layer-compacted concentric bundle | — | Concentric layers of strands are compacted radially per core to reduce gaps, tighten the bundle and present a clean round lug entry. |
| Strands (nom., est.) | 50 ≈19; 25 ≈7 strands per core | — | Approximate compacted strand counts; exact count follows the conductor standard for each section. |
| Surface | Bare copper; tinned optional | — | Bare copper suits most indoor use; optional tinned plating improves corrosion resistance in damp or chemically mild sites. |
| Core identification | L1/L2/L3 phase colors + N neutral | — | Phase cores and the smaller neutral are color-coded so phase sequence and neutral match at the motor terminal box. |
| Neutral sizing logic | Reduced neutral for balanced motor load | — | The 25 mm² neutral suits predominantly balanced three-phase motor circuits; enlarge the neutral where high third harmonics exist. |
| Compaction benefit | Round bundle, lower OD, clean crimp | — | Radial compaction reduces overall diameter versus loose stranding and gives a flat, even lug crimp on both sections. |
| 03 · Insulation | |||
| Insulation material | XLPE (cross-linked polyethylene) | — | Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than PVC insulation for the same size. |
| Insulation thickness (50 phase, nom.) | ≈ 1.6 | mm | Nominal radial insulation wall on each 50 mm² phase core; gauged to withstand the 3.5 kV routine test. |
| Insulation thickness (25 neutral, nom.) | ≈ 1.4 | mm | Nominal insulation wall on the smaller 25 mm² neutral core, matched to its voltage class. |
| Working conductor temp. | 90 | °C | Maximum continuous conductor temperature under rated current without shortening insulation life. |
| Short-circuit temp. | 250 | °C | Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs. |
| Insulation resistance | High and stable | MΩ·km | XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on branch feeders. |
| Color | L1/L2/L3/N color on request | — | Insulation colors are matched to local 3-phase convention or supplied natural with printed marking. |
| Cure type | Chemical / dry-cured XLPE | — | A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat. |
| 04 · Sheath & Flame Retardancy | |||
| Sheath material | PVC, flame-retardant ZC | — | The class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface. |
| Sheath thickness (nom.) | ≈ 1.5 | mm | Nominal overall jacket wall sized to shield the 3+1 bundle from abrasion, mechanical handling and duct damage. |
| Finished outer diameter | ≈ 16 | mm | Overall 3+1 finished diameter used to size glands, trunking and conduit for motor branch runs. |
| Flame behavior | Self-extinguishing, class C | — | After the test flame is removed the sample extinguishes without propagating; it is not 950°C fire-rated. |
| Sheath color | Deep aubergine purple (black/gray on request) | — | Standard deep aubergine purple; black or dark gray jackets are supplied for industrial aesthetics on request. |
| Surface finish | Smooth, continuous print | — | A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length. |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | Low-voltage rating matching 380/400 V motor and panel branch systems. |
| Max voltage (Um) | 1.2 | kV | Continuous upper system voltage for phase-to-earth insulation stress. |
| Nominal current (per 50 phase, est.) | ≈ 120 | A | Approximate ampacity of a 50 mm² phase core in free air at 30 °C; reduce for bundling, conduit fill and high ambient. |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine dielectric withstand applied between each conductor and sheath for five minutes without breakdown. |
| Insulation resistance | High, XLPE | MΩ·km | Measured after conditioning; confirms no void, crack or contamination in the cured insulation. |
| Short-circuit current (50 phase, 1s, est.) | ≈ 4.2 | kA | Approximate 1-second copper short-time withstand on the 50 mm² phase core; branch fault coordination. |
| Frequency | 50 / 60 | Hz | Compatible with both 50 Hz and 60 Hz three-phase power systems. |
| Dielectric | XLPE, low loss | — | Low dielectric loss keeps heating down under continuous motor branch and machine feeder load. |
| 06 · Thermal & Environment | |||
| Normal conductor temp. | 90 | °C | Sustained operating temperature the XLPE insulation is rated for under full load. |
| Installed ambient | 0 ~ +40 | °C | Recommended continuous ambient around the cable; hot motor rooms and crowded trays require ampacity derating. |
| Min install temp. | 0 | °C | Avoid cold bending below 0 °C where the PVC jacket and insulation may stiffen and crack. |
| Burning | Self-extinguishing, ZC class C | — | Class C vertical flame test behavior: flame stops once the external burner is removed. |
| Outdoor / UV | Indoor preferred; UV-grade jacket optional | — | Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor machine runs. |
| Oil / chemicals | Resistant to common oils; check aggressive media | — | Withstands typical machine oils; verify against specific solvents, cutting fluids or acid fumes before use. |
| Temperature cycle | Withstands repeated 0~90°C duty | — | The insulation and jacket survive repeated motor start-stop heating/cooling cycles without cracking. |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 240 | mm | Fixed-installation minimum bend radius for the 3+1 cable; tight bends risk insulation and jacket damage. |
| Flexibility | Stranded, easy to route to machines | — | Compacted strands remain flexible enough for panel-to-machine runs without large rollers. |
| Shielding / Armor | None / unarmored (armor optional) | — | No copper braid screen and no armor as standard; add braid screen for VFD EMI and armor for ground-crushing ducts. |
| Cable weight per km (est.) | ≈ 1450 | kg/km | Moderate mass per kilometer used for tray loading and drum sizing on branch circuits. |
| Circularity | 3+1 bundle, stable compact OD | — | Three phases around the reduced neutral form a compact round bundle after sheathing. |
| Tensile / elongation | Jacket meets PVC grade | — | Jacket tensile strength and elongation satisfy the PVC compound grade for machine-room pulling. |
| 08 · Factory Advantages | |||
| Balanced 3+1 sizing | 3×50 phases with 1×25 neutral for motor loads | — | Right-sized neutral avoids excess copper cost on predominantly balanced three-phase branches. |
| Stable XLPE cure | Even cross-linking keeps the 90°C dielectric consistent | — | Controlled cure prevents soft spots in insulation under repeated motor start-stop cycles. |
| Dosed ZC compound | Flame-retardant PVC self-extinguishes to class C | — | Self-extinguishing jacket protects machine rooms and panel wiring spaces. |
| Length-on-demand | Cut to exact machine/branch meter, sealed ends | — | Custom cut lengths match the measured panel-to-machine route and reduce waste. |
| Dual-section resistance log | Phase 50 and neutral 25 R logged to lot | — | Both conductor sections are recorded for incoming inspection and traceability. |
| Continuous print line | Type, size, ZC, voltage and length along jacket | — | Clear continuous marking lets installers read phase and neutral section on short branch runs. |
| Phase-color option | L1/L2/L3/N insulation colors matched to convention | — | Pre-colored cores reduce wiring errors at the motor terminal box. |
| Compact drum pack | Standard wooden drum with sealed ends | — | Moderate branch length wound on a manageable drum for site handling. |
| Certified QA pack | Routine + type test record shipped per batch | — | A complete QA packet supports buyer inspection and machine commissioning sign-off. |
| 09 · Installation | |||
| Laying | Panel-to-machine branch, tray, conduit, 3-phase+N | — | Route in trays, conduit or direct to motor terminal boxes; keep the 3+1 bundle round and observe bend radius. |
| Connectors | 50 mm² phase lugs; 25 mm² neutral lug | — | Crimp 50 mm² lugs on L1/L2/L3 and a 25 mm² lug on N; select glands sized to ≈16 mm OD. |
| Bend radius | ≥ 15×OD ≈ 240 mm | — | Maintain the minimum radius around panel elbows and machine entry points. |
| Parallel runs | Derating in bundles and conduit | — | Adjacent loaded cores share heat; apply conduit and bundle derating before breaker selection. |
| Site test | Continuity + insulation post-laying | — | After pulling, verify three-phase continuity, phase sequence, neutral continuity and insulation resistance. |
| Termination | Strip, hydraulic crimp lug, torque per table | — | Strip insulation without nicking strands, use matched dies on each lug, and torque per the lug table. |
| 10 · Packing & Applications | |||
| Supply length | Custom / standard wooden drum | m | Cut to the measured branch length on a standard drum. |
| Length tolerance | Per trade standard for cut lengths | — | Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise. |
| Reel type | Standard wooden drum | — | Drum for moderate branch lengths; sealed ends prevent moisture ingress. |
| Surface marking | ZC-YJV, 3×50+1×25, 0.6/1kV, ZC, length | — | Jacket prints type, phase/neutral section, voltage, flame class and cumulative meter length. |
| Typical use | Motor branch, compressor, pump, machine feeder | — | Three-phase motors, compressors, pumps, fans and machine-tool power feeds. |
| Storage | Dry indoor on drum supports, avoid UV | — | Store the drum horizontally on timber supports, dry and shaded, avoiding direct sunlight. |
Cable Test Parameters
| Test Parameters — ZC-YJV 3×50+1×25 LV Flame-Retardant 3+1 Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | DC resistance (50 phase) | 20 °C, L1/L2/L3 (50 mm²) | ≤0.387 Ω/km | Routine |
| 2 | DC resistance (25 neutral) | 20 °C, N (25 mm²) | ≤0.741 Ω/km | Routine |
| 3 | Voltage test (AC) | 3.5 kV AC, 5 min, core-to-sheath | No breakdown | Routine |
| 4 | Insulation resistance | XLPE, 20°C, per core | High & stable | Routine |
| 5 | Continuity | 3 phases + neutral | Continuous | Routine |
| 6 | Flame retardancy | Class C vertical test | Self-extinguish | Type |
| 7 | Sheath thickness | Micrometer, cross-section | Nominal ≈1.5 mm | Routine |
| 8 | Phase insulation thickness | Micrometer, 50 mm² cores | Nominal ≈1.6 mm | Routine |
| 9 | Neutral insulation thickness | Micrometer, 25 mm² core | Nominal ≈1.4 mm | Routine |
| 10 | Dimensional check | Caliper, overall OD | OD ≈ 16 mm | Routine |
| 11 | Conductor construction | Visual / strand count per core | Class 2 compacted | Routine |
| 12 | Short-circuit rating | Calculated / type | ≈4.2 kA / 1 s | Type |
| 13 | Insulation eccentric test | Cross-section measure per core | Within tolerance | Routine |
| 14 | Printing legibility | Visual | Marking readable | Routine |
| 15 | Mass per unit length | Weigh / calculate | ≈ 1450 kg/km | Routine |
| 16 | Packing & drum inspection | Visual / drum condition | Sealed ends, sound drum | Routine |
Cable Cross Section Structure

| ZC-YJV 3×50+1×25 — 3+1 Cross-Section Construction Diagram (Schematic, Expanded) | |||||
| 3×50 phase Cu + 1×25 neutral Cu / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈16 mm · motor branch, machine supply & panel feeder | |||||
| No. | Layer / Feature | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Detailed Function / Remarks |
| 1 | Conductor L1 — phase | 1×50 compacted Cu, Class 2, ≈19 strands | — | ≈ 8.0 | Phase 1 core, DC R ≤0.387 Ω/km @20°C; motor load current. |
| 2 | Conductor L2 — phase | 1×50 compacted Cu, Class 2, ≈19 strands | — | ≈ 8.0 | Phase 2 core, equal size/resistance for balanced three-phase. |
| 3 | Conductor L3 — phase | 1×50 compacted Cu, Class 2, ≈19 strands | — | ≈ 8.0 | Phase 3 core, equal spec; color-coded for phase sequence. |
| 4 | Conductor N — neutral | 1×25 compacted Cu, Class 2, ≈7 strands | — | ≈ 5.6 | Reduced neutral, R ≤0.741 Ω/km; balanced motor neutral return. |
| 5 | Strand compaction | Concentric layers rolled compact per core | — | — | Radial compaction closes gaps for compact round bundles and clean lugs. |
| 6 | XLPE insulation (50 phase) | Dry-cured cross-linked PE, ≈1.6 mm | ≈ 1.6 | ≈ 11.2 | 90°C phase dielectric; low loss, passes 3.5 kV routine test. |
| 7 | XLPE insulation (25 neutral) | Dry-cured cross-linked PE, ≈1.4 mm | ≈ 1.4 | ≈ 8.4 | Neutral dielectric matched to the smaller 25 mm² section. |
| 8 | 3+1 core laying | 3 phases around 1 reduced neutral | — | — | Compact 3+1 bundle arrangement stabilizes the round finished form. |
| 9 | PVC ZC sheath | Class C jacket, ≈1.5 mm | ≈ 1.5 | ≈ 16 | Binds the 3+1 bundle; self-extinguishes to class C; aubergine finish. |
| 10 | Jacket print | Continuous type/size/voltage/length line | — | — | Marking: ZC-YJV, 3×50+1×25, 0.6/1kV, ZC, cumulative length. |
| Key Dimensions, Electrical & Mechanical Properties (expanded) | |||||
| Finished cable diameter | ≈ 16 | mm | Compact 3+1 branch OD for glands and conduit. | ||
| Approx. cable mass (est.) | ≈ 1450 | kg/km | Moderate branch feeder mass; standard drum. | ||
| Nominal voltage rating | 0.6/1 | kV | Matches 380/400 V motor and panel systems. | ||
| Max voltage (Um) | 1.2 | kV | Phase-to-earth continuous upper limit. | ||
| Normal conductor temp. | 90 | °C | Continuous load temperature of XLPE. | ||
| Short-circuit temp. | 250 | °C | Short-time fault peak before insulation damage. | ||
| DC resistance (50 phase) | ≤ 0.387 | Ω/km | Per phase core @20°C. | ||
| DC resistance (25 neutral) | ≤ 0.741 | Ω/km | Reduced neutral @20°C. | ||
| Neutral sizing | 1×25 reduced neutral | — | For balanced motor loads; enlarge on high harmonics. | ||
| Nominal phase current (est.) | ≈ 120 | A | Per 50 phase core, free air 30°C; derate in conduit. | ||
| Short-circuit rating (1s, est.) | ≈ 4.2 | kA | Branch fault coordination duty. | ||
| Flame retardancy | ZC class C, self-extinguishing | — | Not 950°C fire-rated. | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 240 | mm | Panel-to-machine bend radius. | ||
| Frequency | 50 / 60 | Hz | Compatible with both power systems. | ||
| Insulation resistance | High & stable | MΩ·km | XLPE; supports earth-fault detection. | ||
| Dielectric loss | Low | — | XLPE limits heating on motor duty. | ||
| Temperature cycle | 0~90°C repeated | — | Survives motor start-stop cycling. | ||
| Sheath mechanical | Jacket meets PVC grade | — | Tensile/elongation checked at type test. | ||
| Pack choice | Standard wooden drum | — | Sealed ends, manageable branch length. | ||
| Application | Motor branch, compressor, pump, machine | — | 380/400 V three-phase machine power feeds. | ||
| Schematic — not to exact scale. OD ≈16 mm, weight ≈1450 kg/km, phase ampacity ≈120 A free air at 30°C and ≈4.2 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 3×50+1×25 serves 380/400 V motor branches, machine supplies and panel feeders; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 3×50+1×25 LV flame-retardant 3+1 cable | |||
| 3×50 phase Cu + 1×25 neutral Cu / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈16 mm · motor branch, machine supply & panel feeder | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 3×50+1×25 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; three 50 mm² phase cores plus one 25 mm² neutral in a 3+1 lay. OD ≈16 mm, ≈1450 kg/km (est.), ≈120 A per phase free air at 30°C (est.), standard wooden drum. It is a fixed motor branch cable, not a flexible cord and not a 950°C fire-rated circuit. | |||
| 2. Copper Conductors (3×50 phase + 1×25 neutral) | |||
| Three compacted Class 2 Cu phase cores (L1/L2/L3), R ≤0.387 Ω/km @20°C, plus one 25 mm² neutral, R ≤0.741 Ω/km @20°C; reduced neutral suits balanced motor loads; tinned plating optional; phase-color insulation on request. | |||
| 3. Strand Compaction & 3+1 Bundle | |||
| Concentric strands are rolled compact per core to close gaps and give clean lug entry; three phases surround the reduced neutral to form a compact round 3+1 bundle before sheathing. | |||
| 4. XLPE Insulation | |||
| Dry-cured cross-linked PE ≈1.6 mm on phases and ≈1.4 mm on the neutral; stable 90°C dielectric, low dielectric loss, high insulation resistance; short-circuit peak 250°C; matched wall per section. | |||
| 5. Core Identification | |||
| L1/L2/L3 phases and the N neutral are identified by insulation color; the smaller neutral section also distinguishes it visually from the three phase cores at the motor terminal box. | |||
| 6. PVC ZC Sheath | |||
| Class C flame-retardant PVC ≈1.5 mm overall, self-extinguishing; deep aubergine purple standard (black/gray on request); smooth printable surface; binds the 3+1 bundle and shields from machine-room abrasion. | |||
| 7. Electrical Characteristics | |||
| 0.6/1 kV, Um 1.2; phase R ≤0.387, neutral R ≤0.741 Ω/km; routine 3.5 kV AC/5 min; ≈120 A per phase (est., air 30°C); short-circuit ≈4.2 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE. | |||
| 8. Factory Advantages | |||
| • Balanced 3+1 sizing (cost-effective reduced neutral). • Stable XLPE cure. • Dosed ZC self-extinguish. • Length-on-demand. • Dual-section resistance log. • Continuous clear print. • Phase-color option. • Compact drum pack. • Certified QA pack. | |||
| 9. Site Handling & Installation | |||
| • Bend 15×OD (≈240 mm). • 50 mm² phase lugs, 25 mm² neutral lug, glands to ≈16 mm OD, hydraulic crimp, torque per table. • Conduit/bundle derating. • Keep 3+1 bundle round. • Three-phase continuity, sequence, neutral + insulation after pulling. | |||
| 10. Typical Service Applications | |||
| 380/400 V motor branch circuits, compressors, pumps, fans, machine-tool power feeds, panel-to-equipment feeders and general three-phase machine supplies. | |||
| 11. Testing & QA | |||
| 16-item regime: routine phase DC resistance (50), neutral DC resistance (25), 3.5 kV withstand, insulation resistance, 3-phase+neutral continuity, phase/neutral insulation thickness, sheath thickness, dimensional check, strand construction, eccentricity, print legibility, mass, packing inspection; type ZC flame, short-circuit, sheath mechanical. | |||
| 12. Packaging, Storage & Notes | |||
| Cut to measured branch length on a standard wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated. |
8. Factory Advantages.
- Balanced 3+1 sizing — 3×50 phases with 1×25 neutral, cost-effective on motor loads.
- Stable XLPE cure — even cross-linking withstands motor start-stop cycles.
- Dosed ZC compound — self-extinguishing jacket protects machine rooms.
- Length-on-demand — exact machine/branch meter, sealed ends.
- Dual-section resistance log — phase 50 and neutral 25 R logged to lot.
- Continuous print line — type, size, ZC, voltage and length along jacket.
- Phase-color option — L1/L2/L3/N colors matched to convention.
- Compact drum pack — standard wooden drum with sealed ends.
- Certified QA pack — routine + type test record per batch.

9. Packaging, Storage & Logistics. Cut to measured branch length on a standard wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.

10. Procurement Specification. State "ZC-YJV 3×50+1×25", length, class C, phase colors, braid screen for VFD if required, drum; note reduced neutral for balanced motors and not fire-rated; request dual-section resistance log and 16-item QA record. Est. values confirmed against the factory certificate.
11. Cable Industry FAQ.
- Q1: How does 3×50+1×25 differ from 4×300? Compact 3+1 branch vs four equal heavy mains: much smaller (50/25 vs 300 mm²), slimmer (16 vs 42 mm), far lighter (1450 vs 9800 kg/km), much lower current (120 vs 510 A), and higher resistance (0.387/0.741 vs 0.0601 Ω/km). It runs motor branches, not busbar risers.
- Q2: Why a reduced 25 mm² neutral? Balanced three-phase motors draw little neutral current, so a 25 mm² neutral saves copper; enlarge it where VFD/rectifier harmonics are high.
- Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
- Q4: DC resistance values? Phase 50 ≤0.387 Ω/km; neutral 25 ≤0.741 Ω/km at 20°C.
- Q5: Braid screen or armor? Unscreened standard; add braid screen near VFD EMI and armor for ground-crushing ducts.
- Q6: Current per phase? ≈ 120 A (est.) free air 30°C; derate in conduit and crowded trays.
- Q7: Bending? ≥ 240 mm (15×OD); compact enough for panel-to-machine routing.
- Q8: Connectors? 50 mm² phase lugs, 25 mm² neutral lug, gland to ≈16 mm OD.
- Q9: Indoor or outdoor? Indoor machine rooms preferred; UV jacket for exposed outdoor runs.
- Q10: Packing? Standard wooden drum with sealed ends.
- Q11: What proof ships? Dual-section resistance log + 16-test record; est. values confirmed against certificate.