2 X 70mm2 2 Cores Cable ZR-YJV Flame Retardant PVC Insulation Jacket 0.6/1kV
Product Summary
Product Details
2 x 70mm2 2 Core Cable
,2 Core Cable ZR-YJV
,Flame Retardant pvc insulation jacket
Product Description
ZR-YJV 2*70mm² Flame Retardant 2 Core Cable, 0.6/1kV, XLPE Insulation PVC Jacket for Construction Power
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant C — IEC 60332-3-24, Category C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
PVC sheath |
|
2×70 mm² |
Two cores, 70 mm² copper conductor each |
Construction: Two Class 2 stranded copper conductors, XLPE insulation, PVC outer sheath (no armour, no shield, circular formation).

ZC-YJV 2×70 mm² — LV Flame-Retardant Twin-Core Power Cable — Specification
1. Overview & Ratings. ZC-YJV 2×70 is a twin-core (L + N) LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant PVC sheath. Two matched compacted 70 mm² copper cores, dry-cured XLPE, unarmored. OD ≈ 19.5 mm, ≈ 1500 kg/km (est.), ≈ 245 A per core free air at 30 °C (est.). Scope: 230 V rising mains, sub-distribution, machine feeds — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor L | 1×70 compacted Cu, Class 2, ≈19 strands | Phase, R ≤0.268 Ω/km |
| Conductor N | 1×70 compacted Cu, Class 2, ≈19 strands | Matched neutral |
| Strand compaction | Concentric layers rolled compact | Round bundle, clean lug entry |
| XLPE insulation (L/N) | Dry-cured PE, ≈1.5 mm per core | 90°C dielectric |
| Core identification | Color band / printed L/N | Prevents crossed wiring |
| Twin-core laying | Two cores twisted compact | Stable ≈17.8 mm sub-bundle |
| PVC ZC sheath | Class C, ≈1.7 mm overall | Binds pair, self-extinguishes |
| Jacket print | Continuous type/size/voltage/length | On-site readable spec |
3. Electrical Characteristics. Per-core R ≤ 0.268 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 245 A per core (est., air 30 °C); short-circuit ≈ 6.3 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 0.268 Ω/km per core |
GB/T 3956 Class 2 Cu max |
|
AC resistance @90 °C (est.) |
≈ 0.344 Ω/km per core |
— |
|
Current rating in air (30 °C) |
Phase: 230 A |
two-core, touching, in free air |
|
Current rating in tray (30 °C) |
Phase: 255 A |
two-core, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
Phase: 240 A |
direct buried |
|
Current rating in conduit (30 °C) |
Phase: 205 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 7.7 kA (7,700 A) per core |
— |
|
Capacitance (core-to-core, approx.) |
≈ 0.18 µF/km |
XLPE |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.20 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 2×70 at 230 A single-phase, 230 V → max load ≈ 53 kW (cos φ = 0.8). Suitable for single-phase distribution, large equipment connections, and DC circuits.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. 70 mm² Cu lugs, large glands, crimp/torque per table; bend ≥ 15×OD ≈ 293 mm; drum rolling, no dragging; derate bundled/tray runs; continuity + insulation per core after pulling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 345 mm at Ø23.0 mm |
two-core unarmoured |
|
Max. pulling tension |
1,050 N per core (70 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Excellent (cable tray, ladder, cleats) |
— |
|
Conduit ID |
≥ 40 mm |
— |
|
Fixing |
heavy-duty cleats, cable ties |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. 230 V rising mains and vertical distribution, sub-distribution board feeds, larger equipment and machine power leads, main branch to load groups, heavier single-phase industrial wiring.

7. Testing & QA Regime (16 items). Routine: DC resistance L/N, 3.5 kV withstand, insulation resistance, continuity, sheath/insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass. Type: ZC flame test, short-circuit rating, sheath mechanical, 0~90°C cycle.
Cable Parameters
| ZC-YJV 2×70 mm² — LV Flame-Retardant Twin-Core Power Cable — Full Parameter Sheet | |||
| 2×Cu / XLPE / PVC · ZC class C · 0.6/1 kV · ≈19.5 mm · phase + neutral twin-core for 230V rising mains, larger equipment feeds, sub-distribution & machine power | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — Cu/XLPE/PVC, flame-retardant class C | — | ZC-YJV denotes a copper-conductor cable with cross-linked polyethylene insulation and a PVC outer sheath; the leading ZC marks a Chinese flame-retardant class C compound that self-extinguishes after the ignition source is removed. |
| Rated voltage (U0/U) | 0.6/1 | kV | 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines this as a general low-voltage power cable suited to 230/400 V building and industrial distribution. |
| Maximum operating voltage (Um) | 1.2 | kV | The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service. |
| Core configuration | 2×70 (L + N) | — | Two equal 70 mm² compacted copper cores twisted together — one phase (L) and one neutral (N) — for heavier single-phase 230 V rising mains, sub-distribution and machine feeds. |
| Conductor material | Compacted stranded annealed copper | — | Soft annealed copper strands are layer-compacted into a round bundle to lower skin effect, reduce overall diameter and give a stable entry into a 70 mm² lug. |
| Insulation | XLPE cross-linked polyethylene | — | Chemically cross-linked polyethylene bonds into a heat-resistant dielectric that keeps its properties at the 90 °C operating temperature. |
| Sheath | PVC, flame-retardant class C (ZC) | — | An overall PVC jacket protects the twisted cores from abrasion, dust and moisture and carries the class C flame-retardant formulation; deep wine burgundy finish. |
| Flame retardancy | ZC class C (self-extinguishing, not fire-rated) | — | On removal of a flame the cable stops propagating fire; this is flame-retardancy, not 950 °C/180 min circuit-integrity fire resistance. |
| Suitable for | Fixed indoor/outdoor tray, conduit, trunking, rising main | — | Designed for fixed heavier single-phase wiring: rising mains, sub-distribution boards, larger equipment and machine power leads. |
| Application | 230V rising main, sub-distribution, machine feed | — | Typically runs a phase-and-neutral heavy branch from a distribution board to a sub-board, large machine or load group. |
| Application note | Not for 950°C circuit-integrity fire duty | — | Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire. |
| 02 · Conductors | |||
| Power core count / area | 2 × 70 | mm² | Two identical 70 mm² conductors provide balanced phase and neutral paths for heavier single-phase power transfer. |
| Conductor type | Compacted stranded Cu, Class 2 | — | Class 2 stranded compacted construction gives a fixed-wiring conductor that rounds into a stable bundle for clean lug termination. |
| DC resistance (70) @ 20°C | ≤ 0.268 | Ω/km | Maximum permitted DC resistance of a 70 mm² copper conductor at 20 °C; lower than 16 for high-current, low-loss rising mains. |
| Stranding | Layer-compacted concentric bundle | — | Concentric layers of strands are compacted radially to reduce gaps, tighten the bundle and present a clean round entry into the lug. |
| Strands (nom., est.) | ≈ 19 compacted | — | Approximate number of compacted strands in a 70 mm² Class 2 bundle; exact count follows the conductor standard and factory drawing. |
| Surface | Bare copper; tinned optional | — | Bare copper suits most indoor use; optional tinned plating improves corrosion resistance where humidity or chemicals are present. |
| Core identification | L phase / N neutral by color or marking | — | Cores are distinguished by insulation color or printed marking so phase and neutral are wired consistently at both ends. |
| Nominal area tolerance | Within conductor class 2 band | — | Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count. |
| 03 · Insulation | |||
| Insulation material | XLPE (cross-linked polyethylene) | — | Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than ordinary PVC insulation for the same size. |
| Insulation thickness (nom.) | ≈ 1.5 | mm | Nominal radial insulation wall on each core; thicker than 16 to withstand the 3.5 kV routine test and 90 °C heat on a heavier core. |
| Working conductor temp. | 90 | °C | Maximum continuous conductor temperature under rated current without shortening insulation life. |
| Short-circuit temp. | 250 | °C | Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs. |
| Insulation resistance | High and stable | MΩ·km | XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault and leakage detection. |
| Color | Phase / neutral color on request | — | Insulation colors are matched to local wiring convention (e.g. brown/blue) or supplied natural with printed marking. |
| Cure type | Chemical / dry-cured XLPE | — | A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat. |
| 04 · Sheath & Flame Retardancy | |||
| Sheath material | PVC, flame-retardant ZC | — | The class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface. |
| Sheath thickness (nom.) | ≈ 1.7 | mm | Nominal overall jacket wall sized to shield the two heavier twisted cores from abrasion, dust and occasional moisture. |
| Finished outer diameter | ≈ 19.5 | mm | Overall twin-core finished diameter used to size heavy trunking fill, conduit and large gland entry. |
| Flame behavior | Self-extinguishing, class C | — | After the test flame is removed the sample extinguishes without propagating along the cable; it is not 950°C fire-rated. |
| Sheath color | Deep wine burgundy (black/gray on request) | — | Standard deep wine burgundy; black or dark gray jackets are supplied for outdoor and industrial aesthetics on request. |
| Surface finish | Smooth, continuous print | — | A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length. |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | Low-voltage rating matching 230/400 V distribution systems. |
| Max voltage (Um) | 1.2 | kV | Continuous upper system voltage for phase-to-earth insulation stress. |
| Nominal current (per 70 core, est.) | ≈ 245 | A | Approximate ampacity of a single 70 mm² core in free air at 30 °C; reduce for bundling, duct fill and high ambient. |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine dielectric withstand applied between conductor and sheath for five minutes without breakdown. |
| Insulation resistance | High, XLPE | MΩ·km | Measured after conditioning; confirms no void, crack or contamination in the cured insulation. |
| Short-circuit current (70, 1s, est.) | ≈ 6.3 | kA | Approximate 1-second copper short-time withstand; the heavier core carries more fault energy before protection trips. |
| Frequency | 50 / 60 | Hz | Compatible with both 50 Hz and 60 Hz low-voltage power systems. |
| Dielectric | XLPE, low loss | — | Low dielectric loss keeps heating down under continuous load and supports efficient rising-main transfer. |
| 06 · Thermal & Environment | |||
| Normal conductor temp. | 90 | °C | Sustained operating temperature the XLPE insulation is rated for under full load. |
| Installed ambient | 0 ~ +40 | °C | Recommended continuous ambient around the cable; higher rooms require ampacity derating. |
| Min install temp. | 0 | °C | Avoid cold bending below 0 °C where the heavier PVC jacket and insulation may stiffen and crack. |
| Burning | Self-extinguishing, ZC class C | — | Class C vertical flame test behavior: flame stops once the external burner is removed. |
| Outdoor / UV | Indoor preferred; UV-grade jacket optional | — | Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor runs. |
| Oil / chemicals | Resistant to common oils; check aggressive media | — | Withstands typical machine oils and grease; verify against specific solvents or acid fumes before use. |
| Temperature cycle | Withstands repeated 0~90°C duty | — | The insulation and jacket survive repeated heating/cooling cycles without cracking or delamination. |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 293 | mm | Fixed-installation minimum bend radius for the heavy twin-core cable; tighter bends strain insulation and jacket. |
| Flexibility | Stranded, crane-assisted on site | — | Compacted strands keep the heavy cable workable but the mass requires drum rolling and careful handling on site. |
| Shielding / Armor | None / unarmored | — | No copper braid screen and no armor; add screening or armor where EMI or mechanical protection is required. |
| Cable weight per km (est.) | ≈ 1500 | kg/km | Approximate mass per kilometer used for heavy tray loading and drum sizing. |
| Circularity | Compacted twin bundle, stable OD | — | The two heavier cores lay into a compact bundle so the finished OD stays consistent along the length. |
| Tensile / elongation | Jacket meets PVC grade | — | Sheath tensile strength and elongation satisfy the PVC compound grade for durable heavy handling. |
| 08 · Factory Advantages | |||
| Matched twin cores | L and N built to the same 70 mm² spec for balanced heavy single-phase mains | — | Both cores match in size and resistance so phase and neutral drop equally across a rising main. |
| Stable XLPE cure | Even cross-linking keeps the 90°C dielectric consistent lot to lot | — | Controlled cure removes soft spots in insulation that would age faster under heavy continuous load. |
| Dosed ZC compound | Flame-retardant PVC self-extinguishes to class C | — | Dosed flame inhibitors give a safety margin against incidental ignition in rising-main and wiring spaces. |
| Length-on-demand | Cut to exact meter, sealed ends, minimal offcut | — | Custom cut lengths match the measured rising-main run and reduce waste on long branches. |
| Batch resistance log | Per-core DC R recorded against the lot number | — | Each core's resistance is logged against batch ID for procurement traceability. |
| Continuous print line | Type, size, ZC, voltage and meter length along jacket | — | Clear continuous marking lets installers read the spec without a certificate on site. |
| Phase-color option | L/N insulation colors matched to local convention | — | Pre-colored phase and neutral remove guesswork at termination and inspection. |
| Heavy drum pack | Supplied on heavy wooden drum for the mass | — | Drum supply suits the ~1500 kg/km mass and long pulls; crane/forklift handling. |
| Certified QA pack | Routine + type test record shipped per batch | — | A complete QA packet supports buyer audit and commissioning sign-off. |
| 09 · Installation | |||
| Laying | Heavy tray, conduit, trunking, rising main | — | Route on heavy supports; the mass needs drum rolling and avoid dragging the jacket. |
| Connectors | 70 mm² Cu lugs, large glands | — | Crimp matched 70 mm² copper lugs on each core; select a large gland sized to the 19.5 mm OD. |
| Bend radius | ≥ 15×OD ≈ 293 mm | — | Maintain the minimum radius around corners to prevent the heavy insulation cold-working. |
| Parallel runs | Derate when bundled in tray/duct | — | Adjacent heating cores share heat; apply bundle derating before sizing the main breaker. |
| Site test | Continuity + insulation post-laying | — | After pulling, verify L and N continuity and insulation resistance before energizing. |
| Termination | Strip, crimp lug, torque per table | — | Strip insulation without nicking strands, crimp the lug fully, and torque per the lug table. |
| 10 · Packing & Applications | |||
| Supply length | Custom / heavy wooden drum | m | Cut to the measured rising-main length; heavy drum packing for the mass. |
| Length tolerance | Per trade standard for cut lengths | — | Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise. |
| Reel type | Heavy wooden drum | — | Drum required for long heavy pulls; crane/forklift handling. |
| Surface marking | ZC-YJV, 2×70, 0.6/1kV, ZC, length | — | Jacket prints type, two-core size, voltage, flame class and cumulative meter length. |
| Typical use | Rising main, sub-distribution, machine feed | — | Runs phase+neutral to sub-boards, large machines and load groups. |
| Storage | Dry indoor, avoid direct UV | — | Store on end on a pallet, dry and shaded, to keep the jacket intact. |
Cable Test Parameters
| Test Parameters — ZC-YJV 2×70 LV Flame-Retardant Twin-Core Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | 20 °C, each core L and N | 70 ≤0.268 Ω/km | Routine |
| 2 | Voltage test (AC) | 3.5 kV AC, 5 min, core-to-sheath | No breakdown | Routine |
| 3 | Insulation resistance | XLPE, 20°C, per core | High & stable | Routine |
| 4 | Continuity | Each core L and N | Continuous | Routine |
| 5 | Flame retardancy | Class C vertical test | Self-extinguish | Type |
| 6 | Sheath thickness | Micrometer, cross-section | Nominal ≥1.7 mm | Routine |
| 7 | Insulation thickness | Micrometer, per core | Nominal ≥1.5 mm | Routine |
| 8 | Dimensional check | Caliper, overall OD | OD ≈ 19.5 mm | Routine |
| 9 | Conductor construction | Visual / strand count | Class 2 compacted | Routine |
| 10 | Short-circuit rating | Calculated / type | 6.3 kA / 1 s | Type |
| 11 | Insulation eccentric test | Cross-section measure per core | Within tolerance | Routine |
| 12 | Sheath appearance | Visual along length | Smooth, no flaw | Routine |
| 13 | Printing legibility | Visual | Marking readable | Routine |
| 14 | Mass per unit length | Weigh / calculate | ≈ 1500 kg/km | Routine |
| 15 | Sheath mechanical | Tensile / elongation check | Meets PVC grade | Type |
| 16 | Temperature cycle | Repeated 0~90°C duty | No cracking | Type |
Cable Cross Section Structure

| ZC-YJV 2×70 — Twin-Core Cross-Section Construction Diagram | |||||
| 2×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈19.5 mm · L+N rising mains, sub-distribution & machine feeds | |||||
| No. | Layer / Feature | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Detailed Function / Remarks |
| 1 | Conductor (L) — phase | 1×70 compacted Cu, Class 2, ≈19 strands | — | ≈ 11.8 | Phase core, DC R ≤0.268 Ω/km @20°C, low-loss heavy current. |
| 2 | Conductor (N) — neutral | 1×70 compacted Cu, Class 2, ≈19 strands | — | ≈ 11.8 | Matched neutral core, same size/resistance to balance single-phase drop. |
| 3 | Strand compaction | Concentric layers rolled compact | — | — | Radial compaction closes strand gaps for a round bundle and clean lug entry. |
| 4 | XLPE insulation (L) | Dry-cured cross-linked PE | ≈ 1.5 | ≈ 14.8 | 90°C dielectric on the phase core, low loss, high stable insulation resistance. |
| 5 | XLPE insulation (N) | Dry-cured cross-linked PE | ≈ 1.5 | ≈ 14.8 | Matching neutral insulation; L/N distinguished by color or print. |
| 6 | Core identification | Color band or printed L/N marking | — | — | Phase and neutral readable at both ends to prevent crossed wiring. |
| 7 | Twin-core laying | Two cores twisted into a compact bundle | — | ≈ 17.8 | Controlled lay keeps the pair stable and reduces OD for trunking fill. |
| 8 | PVC ZC sheath | Flame-retardant class C, smooth, overall | ≈ 1.7 | ≈ 19.5 | Binds the pair, shields from abrasion/dust, self-extinguishes to class C. |
| 9 | Jacket print | Continuous type/size/voltage/length line | — | — | Marking along the jacket: ZC-YJV, 2×70, 0.6/1kV, ZC, cumulative length. |
| Key Dimensions, Electrical & Mechanical Properties (expanded) | |||||
| Finished cable diameter | ≈ 19.5 | mm | Heavy twin-core overall OD for trunking and large gland sizing. | ||
| Approx. cable mass (est.) | ≈ 1500 | kg/km | Heavy bundle needs drum rolling and crane/forklift handling. | ||
| Nominal voltage rating | 0.6/1 | kV | Matches 230/400 V distribution systems. | ||
| Max voltage (Um) | 1.2 | kV | Phase-to-earth continuous upper limit. | ||
| Normal conductor temp. | 90 | °C | Continuous load temperature of XLPE. | ||
| Short-circuit temp. | 250 | °C | Short-time fault peak before insulation damage. | ||
| DC resistance (70) | ≤ 0.268 | Ω/km | Per core @20°C; low-loss rising main. | ||
| Nominal current (est.) | ≈ 245 | A | Per core, free air 30°C; derate bundled. | ||
| Short-circuit rating (1s, est.) | ≈ 6.3 | kA | 70 Cu, carries more fault energy. | ||
| Flame retardancy | ZC class C, self-extinguishing | — | Not 950°C fire-rated. | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 293 | mm | Fixed heavy twin-core install radius. | ||
| Frequency | 50 / 60 | Hz | Compatible with both power systems. | ||
| Insulation resistance | High & stable | MΩ·km | XLPE; supports earth-fault detection. | ||
| Dielectric loss | Low | — | XLPE keeps heating down on heavy load. | ||
| Temperature cycle | 0~90°C repeated | — | Survives heating/cooling without cracking. | ||
| Sheath mechanical | Meets PVC grade | — | Tensile/elongation checked at type test. | ||
| Pack choice | Heavy wooden drum | — | Drum suits the ~1500 kg/km mass. | ||
| Core configuration | 2×70 (L+N) | — | Balanced twin single-phase. | ||
| Application | Rising main, sub-distribution, machine | — | 230 V heavier branch power. | ||
| UV / outdoor | UV-grade optional | — | Indoor preferred; specify stabilized jacket outside. | ||
| Schematic — not to exact scale. OD ≈19.5 mm, weight ≈1500 kg/km, ≈245 A per core free air at 30°C and ≈6.3 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 2×70 serves 230 V rising mains, sub-distribution and machine feeds; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 2×70 LV flame-retardant twin-core cable | |||
| 2×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈19.5 mm · L+N rising mains, sub-distribution & machine feeds | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 2×70 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; twin L+N cores. OD ≈19.5 mm, ≈1500 kg/km (est.), ≈245 A per core free air at 30°C (est.), heavy wooden drum. It is a fixed rising-main / sub-distribution cable, not a flexible cord and not a 950°C fire-rated circuit. | |||
| 2. Copper Conductors (2×70) | |||
| Two matched 70 mm² compacted Class 2 Cu cores (L + N), ≈19 strands each; DC R ≤0.268 Ω/km @20°C; low-loss heavy current; tinned plating optional for humid sites; phase-color insulation supplied on request. | |||
| 3. Strand Compaction & Bundle | |||
| Concentric strands are rolled compact to close gaps, round the bundle and give a clean entry into a 70 mm² lug; the two cores are twisted at a controlled lay to hold a stable ≈17.8 mm sub-bundle before sheathing. | |||
| 4. XLPE Insulation | |||
| Dry-cured cross-linked PE ≈1.5 mm on each core, stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; L/N distinguished by color or printed marking. | |||
| 5. Core Identification | |||
| Phase (L) and neutral (N) are identified by insulation color band or printed marking so wiring matches at both ends; brown/blue colors can be supplied to local convention instead of natural insulation. | |||
| 6. PVC ZC Sheath | |||
| Flame-retardant PVC ≈1.7 mm overall, self-extinguishing class C; deep wine burgundy standard (black/gray on request); smooth printable surface; binds the pair and shields from abrasion, dust and occasional moisture. | |||
| 7. Electrical Characteristics | |||
| 0.6/1 kV, Um 1.2; per-core R ≤0.268 Ω/km; routine 3.5 kV AC/5 min; ≈245 A per core (est., air 30°C); short-circuit ≈6.3 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE. | |||
| 8. Factory Advantages | |||
| • Matched twin cores for balanced heavy mains. • Stable XLPE cure lot to lot. • Dosed ZC self-extinguish. • Length-on-demand. • Per-batch resistance log. • Continuous clear print. • Phase-color option. • Heavy drum pack. • Certified QA pack. | |||
| 9. Site Handling & Installation | |||
| • Bend 15×OD (≈293 mm). • 70 Cu lugs, large glands, torque per table. • Derate bundled/tray runs. • Drum rolling, no dragging. • Continuity + insulation per core after pulling. • Indoor; UV grade if exposed. | |||
| 10. Typical Service Applications | |||
| 230 V rising mains and vertical distribution, sub-distribution board feeds, larger equipment and machine power leads, main branch to load groups, heavier single-phase industrial wiring. | |||
| 11. Testing & QA | |||
| 16-item regime: routine DC resistance L/N, 3.5 kV withstand, insulation resistance, continuity, sheath/insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass; type ZC flame, short-circuit, sheath mechanical, 0~90°C cycle. | |||
| 12. Packaging, Storage & Notes | |||
| Cut to measured length on a heavy wooden drum; continuous marking; store dry indoor on end, shaded, avoid direct UV; crane/forklift handling. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated. |
8. Factory Advantages.
- Matched twin cores — L and N built to the same 70 mm² spec for balanced heavy mains.
- Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
- Dosed ZC compound — self-extinguishes to class C.
- Length-on-demand — exact meter, sealed ends, minimal offcut.
- Batch resistance log — per-core DC R recorded against lot number.
- Continuous print line — type, size, ZC, voltage and length along jacket.
- Phase-color option — L/N colors matched to local convention.
- Heavy drum pack — suited to the ~1500 kg/km mass, crane/forklift handling.
- Certified QA pack — routine + type test record per batch.

9. Packaging, Storage & Logistics. Cut to measured length on a heavy wooden drum; continuous marking; store dry indoor on end, shaded, avoid direct UV.

10. Procurement Specification. State "ZC-YJV 2×70", length, class C, L/N color, drum; note flame retardant not fire-rated; request per-batch resistance log and 16-item QA record. Est. values confirmed against the factory certificate.