0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZC-YJV 3x70+1x35mm²‌

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits Technical Datasheet — ZC-YJV 0.6/1 kV 3×70+1×35 mm² 1. Cable Designation & Meaning Code Meaning ZC​ Flame retardant, Class C​ (bundled combustion test per GB/T 18380.3 / GB/T 19666) YJ​ ...

Product Details

Highlight:

1kv 4 cores cable

,

1kv 25 sq mm 4 core cable

,

copper 4 cores cable

Phase conductors (×3):
Bare Annealed Copper, Class 2 Stranded Compacted Circular, 19×∅2.14 Mm​
Neutral conductor (×1)​:
Bare Annealed Copper, Class 2 Stranded, 7×∅2.52 Mm​
Conductor screen:
Not Required For 0.6/1 KV; Omitted
Insulation (×4)​:
XLPE Compound
Phase cores (70 mm²):
Nominal Thickness 1.4 Mm​ (GB/T 12706, 70–95 Mm² Class)
Neutral core (35 mm²):
Nominal Thickness 1.0 Mm​ (GB/T 12706, 35–50 Mm² Class)
Filler:
Flame-retardant Non-hygroscopic PP/PE Filler​ (ZC Grade) To Form Round Assembly
Binder:
Flame-retardant Glass-fibre / FR Tape​ (ZC Grade) Over Laid-up Cores
Outer sheath:
Flame-retardant PVC​ Compound (ZC Grade)
Sheath thickness:
1.9 Mm​ (multi-core, 35 Mm² And Above, 2–5 Cores)
Conductor construction (70 mm²):
19×∅2.14 Mm
Conductor construction (35 mm²):
7×∅2.52 Mm
Diameter over phase core (approx.):
12.8 Mm
Diameter over neutral core (approx.):
9.0 Mm
Sheath nominal thickness:
1.9 Mm
Overall cable diameter:
35.2 – 38.0 Mm
Approx. weight:
3009 – 3520 Kg/km

Product Description

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits


Technical Datasheet — ZC-YJV 0.6/1 kV 3×70+1×35 mm²

1. Cable Designation & Meaning

Code

Meaning

ZC​

Flame retardant, Class C​ (bundled combustion test per GB/T 18380.3 / GB/T 19666)

YJ​

XLPE (cross-linked polyethylene) insulation

V​

PVC (polyvinyl chloride) outer sheath (flame-retardant ZC grade)

0.6/1 kV​

Rated voltage U₀/U = 600/1000 V; maximum system voltage Uₘ = 1.2 kV

3×70+1×35 mm²​

3 phase cores​ of 70 mm² + 1 neutral core​ of 35 mm² (three-phase four-wire, 3+1 configuration); no separate PE core

2. Applicable Standards

  • GB/T 12706.1-2020​ (equivalent to IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
  • GB/T 3956 / IEC 60228​ — Conductors (Class 2)
  • GB/T 19666-2019​ — Flame retardant & fire resistant cables (ZC = Class C)
  • GB/T 18380.3​ — Bunched flame propagation test, Class C (char ≤ 2.5 m above burner)
  • GB/T 16895.15 / IEC 60364-5-52​ — Current-carrying capacity reference for installation


3. Product Components / Construction (inside → outside)

  1. Phase conductors (×3)​ — Bare annealed copper, Class 2 stranded compacted circular, 19×∅2.14 mm​ (typical), conductor Ø ≈ 10.0 mm
  2. Neutral conductor (×1)​ — Bare annealed copper, Class 2 stranded, 7×∅2.52 mm​ (typical), conductor Ø ≈ 7.0–7.5 mm
  3. Conductor screen​ — Not required for 0.6/1 kV; omitted
  4. Insulation (×4)​ — XLPE compound, extruded:
    • Phase cores (70 mm²):​ nominal thickness 1.4 mm​ (GB/T 12706, 70–95 mm² class)
    • Neutral core (35 mm²):​ nominal thickness 1.0 mm​ (GB/T 12706, 35–50 mm² class)
    • Colours: phases L1/L2/L3 (brown/black/grey), neutral N (blue)
  5. Filler​ — Flame-retardant non-hygroscopic PP/PE filler​ (ZC grade) to form round assembly
  6. Binder​ — Flame-retardant glass-fibre / FR tape​ (ZC grade) over laid-up cores
  7. Outer sheath​ — Flame-retardant PVC​ compound (ZC grade)
  8. Sheath thickness (nominal)​ — 1.9 mm​ (multi-core, 35 mm² and above, 2–5 cores)
  9. Sheath colour​ — Black (standard); other colours available on request
  10. Armour​ — None
  11. Metallic screen​ — None

4. Dimensional Data

Item

Typical value

Remarks

Phase conductor nominal area

70 mm² (×3)

Class 2, 19×2.14 mm

Neutral conductor nominal area

35 mm² (×1)

Class 2, 7×2.52 mm

Conductor construction (70 mm²)

19×∅2.14 mm

conductor Ø ≈ 10.0 mm

Conductor construction (35 mm²)

7×∅2.52 mm

conductor Ø ≈ 7.0 mm

Insulation thickness (70 mm² phase)

1.4 mm​


Insulation thickness (35 mm² neutral)

1.0 mm​


Diameter over phase core (approx.)

12.8 mm

10.0 + 2×1.4

Diameter over neutral core (approx.)

9.0 mm

7.0 + 2×1.0

Sheath nominal thickness

1.9 mm​


Overall cable diameter

35.2 – 38.0 mm​

35.2 (Nexans 4×70), 36.7 , 38.0 ; use 36.7 mm for design​

Approx. weight

3009 – 3520 kg/km​

3009 , 3364 , 3520 ; use ≈ 3300 kg/km​

Cable shape

Round

—

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

5. Insulation Data

  • Material:​ XLPE (cross-linked polyethylene)
  • Nominal thickness:​ Phase 70 mm² → 1.4 mm; Neutral 35 mm² → 1.0 mm​
  • Long-term service temperature:​ 90 °C​ (all cores)
  • Short-circuit temperature (≤5 s):​ 250 °C​
  • Emergency overload:​ 105–130 °C (limited duration, general XLPE practice)
  • Routine test:​ 3.5 kV AC / 5 min; type test 4.0 kV
  • Volume resistivity @90 °C:​ ≥ 10¹² Ω·cm (typical XLPE)
  • Insulation resistance constant:​ ≈ 3.67 MΩ·km @90 °C

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

6. Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV​

Routine test

Type-test voltage

4.0 kV

IEC 60502 practice

DC resistance @20 °C (Class 2 Cu)​

70 mm² ≤ 0.268 Ω/km; 35 mm² ≤ 0.524 Ω/km​

GB/T 3956 / IEC 60228 max

AC resistance @90 °C (est.)

70 mm² ≈ 0.349 Ω/km; 35 mm² ≈ 0.682 Ω/km

copper temp. coefficient

Recommended current rating — in air (30 °C, single circuit, 4-core equivalent)

≈ 178 – 222 A​

178 (3+1, 30℃), 222 (Nexans 4×70, 20℃); design ≈ 195 A​

In air — per common Chinese sample (3+1)

195 A

conservative design value

Direct buried / in soil (20 °C, soil thermal res. 1.0 K·m/W, depth 0.7 m)

≈ 205 – 260 A​

205 (Nexans), 220 (4×70 ref.), 260 (3+1, 20℃); design ≈ 230 A​

Short-circuit current capacity (1 s adiabatic, Cu, 250 °C)

70 mm² ≈ 8.2 kA; 35 mm² ≈ 4.1 kA

reference

Frequency

50/60 Hz AC (DC usable)

—

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

7. Temperature Characteristics

  • Max. conductor operating temp. (continuous):​ 90 °C​
  • Max. short-circuit temp. (≤5 s):​ 250 °C​
  • Emergency overload temp.:​ 105 °C (limited duration)
  • Min. ambient temp. during installation:​ 0 °C​ (pre-heat below 0 °C)
  • Service ambient temperature range:​ −20 °C to +90 °C (sheath/environment)
  • Flame retardant class:​ Category C​ per GB/T 19666 (bundled, self-extinguishing, char ≤ 2.5 m)

8. Mechanical & Installation Parameters

  • Minimum bending radius (unarmoured multi-core):​ ≥ 15 × overall diameter​ → ≈ 550 mm at Ø36.7 mm
  • Maximum pulling tension (copper conductor only):​ 50 N/mm² × (3×70 + 1×35) = 12,250 N total​ (distribute to all 4 cores via pulling eye/sock)
  • PVC sheath pulling limit:​ significantly lower — avoid direct sheath grip; use conductor pulling sock
  • Direct burial:​ Allowed in non-aggressive soil; sand bed + warning tape, depth ≥ 0.7 m, conduit/duct under roads
  • Conduit / duct size:​ Cable OD ≈ 37 mm; use duct ID ≥ 1.5 × OD → ≥ 55 mm (typically 63 mm or larger)
  • Cable tray / duct:​ 4-core is stiff at 70 mm²; observe 15D bend radius to avoid core deformation
  • Elevation difference:​ No limitation for XLPE insulated cable

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

9. Material Specification Summary

  • Phase conductors:​ Cu ≥ 99.9 % annealed, Class 2, 19×2.14 mm, IEC 60228 / GB/T 3956 (70 mm²)
  • Neutral conductor:​ Cu ≥ 99.9 % annealed, Class 2, 7×2.52 mm, IEC 60228 / GB/T 3956 (35 mm²)
  • Insulation:​ XLPE, 1.4 mm (70 mm²) / 1.0 mm (35 mm²), rated 90 °C, coloured
  • Filler:​ Flame-retardant PP/PE (ZC grade)
  • Binder:​ Flame-retardant glass fibre / FR tape
  • Outer sheath:​ Flame-retardant PVC (ZC), 1.9 mm nom.
  • No armour, no metallic screen, no separate PE core

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

10. Scope of Application / Usage Range

ZC-YJV 0.6/1 kV 3×70+1×35 mm²​ is intended for fixed installation​ in low-voltage three-phase four-wire (3L+N) power distribution & transmission systems up to 1.2 kV system voltage, where flame-retardant Class C​ performance is required.

Typical applicable locations:

  • Three-phase four-wire (TN-C) distribution feeders​ — the standard use of 3×70+1×35 (3L+N, reduced neutral) for three-phase loads with unbalanced neutral current
  • Main / sub-distribution boards, floor risers, and feeder circuits in high-rise buildings, commercial complexes, hotels, hospitals, stations and metros​ (where ZC flame-retardant grade is mandated)
  • Industrial plants, warehouses, medium machinery, HVAC (air conditioning) and pump/motor feeders​
  • Cable trays, cable ducts, cable trenches & shafts in residential / public buildings
  • Direct buried routes in non-aggressive soil with low-to-moderate mechanical impact
  • Renewable / PV and EV charging station three-phase supply feeders (earthing/neutral arrangement to be confirmed per local code)

Not suitable for:

  • Systems requiring separate PE (TN-S) → use 3×70+2×35​ (3L+N+PE) or add a separate PE conductor
  • Fire-survival / emergency circuits → use NH-ZC-YJV 3×70+1×35
  • Heavy tensile / armour-protected routes → use ZC-YJV22 3×70+1×35
  • Single-phase circuits → use 2-core or 3-core
  • Highly corrosive / hydrocarbon-rich / long-term submerged environments without extra barrier
  • High-current feeders where ~195 A / voltage drop governs → upsize to 3×95+1×50 or larger

0.6/1kV ZC-YJV 3x70+1x35mm²‌ Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits

11. Packing

  • Drum:​ Steel-wooden drum; common length 100–500 m per drum (70 mm² class, shorter lengths typical due to weight/stiffness; ≈ 3.3 t/km)
  • HS code (China):​ 8544 4921 (LV power cable, PVC sheath)

Key engineering notes for ZC-YJV 3×70+1×35 mm²

  1. 3+1 means no separate PE​ — neutral (35 mm²) is shared as PEN in TN-C, or used purely as N. For TN-S (separate PE), select 3×70+2×35.
  2. Mixed insulation thicknesses:​ 70 mm² phase = 1.4 mm​ (70–95 class); 35 mm² neutral = 1.0 mm​ (35–50 class). Do not give both cores 1.4 mm .
  3. Sheath = 1.9 mm​ (multi-core ≥ 35 mm² rule) — thicker than the 1.8 mm used for ≤16 mm² multi-core cables.
  4. Conductor resistance​ is the compliance limit: 70 mm² ≤ 0.268 Ω/km, 35 mm² ≤ 0.524 Ω/km (GB/T 3956 Class 2) .
  5. Ampacity consensus ≈ 195 A (air) / 230 A (buried)​ — source tables vary 178–260 A with laying method and reference temperature. Always correct for grouping, ambient temperature, and conduit/duct.​ At 400 V three-phase, 195 A ≈ 135 kVA theoretical.
  6. Weight ≈ 3.3 t/km​ — plan drum handling, tray loading and pulling equipment accordingly.