0.6/1kV ZC-YJV 3x70+1x35mm² Copper XLPE PVC Flame-Retardant Power Cable for Transformer Room LV Outgoing Circuits
Technical Datasheet — ZC-YJV 0.6/1 kV 3×70+1×35 mm²
1. Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant, Class C (bundled combustion test per GB/T 18380.3 / GB/T 19666) |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC (polyvinyl chloride) outer sheath (flame-retardant ZC grade) |
|
0.6/1 kV |
Rated voltage U₀/U = 600/1000 V; maximum system voltage Uₘ = 1.2 kV |
|
3×70+1×35 mm² |
3 phase cores of 70 mm² + 1 neutral core of 35 mm² (three-phase four-wire, 3+1 configuration); no separate PE core |
2. Applicable Standards
- GB/T 12706.1-2020 (equivalent to IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
- GB/T 3956 / IEC 60228 — Conductors (Class 2)
- GB/T 19666-2019 — Flame retardant & fire resistant cables (ZC = Class C)
- GB/T 18380.3 — Bunched flame propagation test, Class C (char ≤ 2.5 m above burner)
- GB/T 16895.15 / IEC 60364-5-52 — Current-carrying capacity reference for installation
3. Product Components / Construction (inside → outside)
- Phase conductors (×3) — Bare annealed copper, Class 2 stranded compacted circular, 19×∅2.14 mm (typical), conductor Ø ≈ 10.0 mm
- Neutral conductor (×1) — Bare annealed copper, Class 2 stranded, 7×∅2.52 mm (typical), conductor Ø ≈ 7.0–7.5 mm
- Conductor screen — Not required for 0.6/1 kV; omitted
- Insulation (×4) — XLPE compound, extruded:
- Phase cores (70 mm²): nominal thickness 1.4 mm (GB/T 12706, 70–95 mm² class)
- Neutral core (35 mm²): nominal thickness 1.0 mm (GB/T 12706, 35–50 mm² class)
- Colours: phases L1/L2/L3 (brown/black/grey), neutral N (blue)
- Filler — Flame-retardant non-hygroscopic PP/PE filler (ZC grade) to form round assembly
- Binder — Flame-retardant glass-fibre / FR tape (ZC grade) over laid-up cores
- Outer sheath — Flame-retardant PVC compound (ZC grade)
- Sheath thickness (nominal) — 1.9 mm (multi-core, 35 mm² and above, 2–5 cores)
- Sheath colour — Black (standard); other colours available on request
- Armour — None
- Metallic screen — None
4. Dimensional Data
|
Item |
Typical value |
Remarks |
|---|---|---|
|
Phase conductor nominal area |
70 mm² (×3) |
Class 2, 19×2.14 mm |
|
Neutral conductor nominal area |
35 mm² (×1) |
Class 2, 7×2.52 mm |
|
Conductor construction (70 mm²) |
19×∅2.14 mm |
conductor Ø ≈ 10.0 mm |
|
Conductor construction (35 mm²) |
7×∅2.52 mm |
conductor Ø ≈ 7.0 mm |
|
Insulation thickness (70 mm² phase) |
1.4 mm |
|
|
Insulation thickness (35 mm² neutral) |
1.0 mm |
|
|
Diameter over phase core (approx.) |
12.8 mm |
10.0 + 2×1.4 |
|
Diameter over neutral core (approx.) |
9.0 mm |
7.0 + 2×1.0 |
|
Sheath nominal thickness |
1.9 mm |
|
|
Overall cable diameter |
35.2 – 38.0 mm |
35.2 (Nexans 4×70), 36.7 , 38.0 ; use 36.7 mm for design |
|
Approx. weight |
3009 – 3520 kg/km |
3009 , 3364 , 3520 ; use ≈ 3300 kg/km |
|
Cable shape |
Round |
— |
5. Insulation Data
- Material: XLPE (cross-linked polyethylene)
- Nominal thickness: Phase 70 mm² → 1.4 mm; Neutral 35 mm² → 1.0 mm
- Long-term service temperature: 90 °C (all cores)
- Short-circuit temperature (≤5 s): 250 °C
- Emergency overload: 105–130 °C (limited duration, general XLPE practice)
- Routine test: 3.5 kV AC / 5 min; type test 4.0 kV
- Volume resistivity @90 °C: ≥ 10¹² Ω·cm (typical XLPE)
- Insulation resistance constant: ≈ 3.67 MΩ·km @90 °C

6. Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
Type-test voltage |
4.0 kV |
IEC 60502 practice |
|
DC resistance @20 °C (Class 2 Cu) |
70 mm² ≤ 0.268 Ω/km; 35 mm² ≤ 0.524 Ω/km |
GB/T 3956 / IEC 60228 max |
|
AC resistance @90 °C (est.) |
70 mm² ≈ 0.349 Ω/km; 35 mm² ≈ 0.682 Ω/km |
copper temp. coefficient |
|
Recommended current rating — in air (30 °C, single circuit, 4-core equivalent) |
≈ 178 – 222 A |
178 (3+1, 30℃), 222 (Nexans 4×70, 20℃); design ≈ 195 A |
|
In air — per common Chinese sample (3+1) |
195 A |
conservative design value |
|
Direct buried / in soil (20 °C, soil thermal res. 1.0 K·m/W, depth 0.7 m) |
≈ 205 – 260 A |
205 (Nexans), 220 (4×70 ref.), 260 (3+1, 20℃); design ≈ 230 A |
|
Short-circuit current capacity (1 s adiabatic, Cu, 250 °C) |
70 mm² ≈ 8.2 kA; 35 mm² ≈ 4.1 kA |
reference |
|
Frequency |
50/60 Hz AC (DC usable) |
— |
7. Temperature Characteristics
- Max. conductor operating temp. (continuous): 90 °C
- Max. short-circuit temp. (≤5 s): 250 °C
- Emergency overload temp.: 105 °C (limited duration)
- Min. ambient temp. during installation: 0 °C (pre-heat below 0 °C)
- Service ambient temperature range: −20 °C to +90 °C (sheath/environment)
- Flame retardant class: Category C per GB/T 19666 (bundled, self-extinguishing, char ≤ 2.5 m)
8. Mechanical & Installation Parameters
- Minimum bending radius (unarmoured multi-core): ≥ 15 × overall diameter → ≈ 550 mm at Ø36.7 mm
- Maximum pulling tension (copper conductor only): 50 N/mm² × (3×70 + 1×35) = 12,250 N total (distribute to all 4 cores via pulling eye/sock)
- PVC sheath pulling limit: significantly lower — avoid direct sheath grip; use conductor pulling sock
- Direct burial: Allowed in non-aggressive soil; sand bed + warning tape, depth ≥ 0.7 m, conduit/duct under roads
- Conduit / duct size: Cable OD ≈ 37 mm; use duct ID ≥ 1.5 × OD → ≥ 55 mm (typically 63 mm or larger)
- Cable tray / duct: 4-core is stiff at 70 mm²; observe 15D bend radius to avoid core deformation
- Elevation difference: No limitation for XLPE insulated cable

9. Material Specification Summary
- Phase conductors: Cu ≥ 99.9 % annealed, Class 2, 19×2.14 mm, IEC 60228 / GB/T 3956 (70 mm²)
- Neutral conductor: Cu ≥ 99.9 % annealed, Class 2, 7×2.52 mm, IEC 60228 / GB/T 3956 (35 mm²)
- Insulation: XLPE, 1.4 mm (70 mm²) / 1.0 mm (35 mm²), rated 90 °C, coloured
- Filler: Flame-retardant PP/PE (ZC grade)
- Binder: Flame-retardant glass fibre / FR tape
- Outer sheath: Flame-retardant PVC (ZC), 1.9 mm nom.
- No armour, no metallic screen, no separate PE core

10. Scope of Application / Usage Range
ZC-YJV 0.6/1 kV 3×70+1×35 mm² is intended for fixed installation in low-voltage three-phase four-wire (3L+N) power distribution & transmission systems up to 1.2 kV system voltage, where flame-retardant Class C performance is required.
Typical applicable locations:
- Three-phase four-wire (TN-C) distribution feeders — the standard use of 3×70+1×35 (3L+N, reduced neutral) for three-phase loads with unbalanced neutral current
- Main / sub-distribution boards, floor risers, and feeder circuits in high-rise buildings, commercial complexes, hotels, hospitals, stations and metros (where ZC flame-retardant grade is mandated)
- Industrial plants, warehouses, medium machinery, HVAC (air conditioning) and pump/motor feeders
- Cable trays, cable ducts, cable trenches & shafts in residential / public buildings
- Direct buried routes in non-aggressive soil with low-to-moderate mechanical impact
- Renewable / PV and EV charging station three-phase supply feeders (earthing/neutral arrangement to be confirmed per local code)
Not suitable for:
- Systems requiring separate PE (TN-S) → use 3×70+2×35 (3L+N+PE) or add a separate PE conductor
- Fire-survival / emergency circuits → use NH-ZC-YJV 3×70+1×35
- Heavy tensile / armour-protected routes → use ZC-YJV22 3×70+1×35
- Single-phase circuits → use 2-core or 3-core
- Highly corrosive / hydrocarbon-rich / long-term submerged environments without extra barrier
- High-current feeders where ~195 A / voltage drop governs → upsize to 3×95+1×50 or larger

11. Packing
- Drum: Steel-wooden drum; common length 100–500 m per drum (70 mm² class, shorter lengths typical due to weight/stiffness; ≈ 3.3 t/km)
- HS code (China): 8544 4921 (LV power cable, PVC sheath)
Key engineering notes for ZC-YJV 3×70+1×35 mm²
- 3+1 means no separate PE — neutral (35 mm²) is shared as PEN in TN-C, or used purely as N. For TN-S (separate PE), select 3×70+2×35.
- Mixed insulation thicknesses: 70 mm² phase = 1.4 mm (70–95 class); 35 mm² neutral = 1.0 mm (35–50 class). Do not give both cores 1.4 mm .
- Sheath = 1.9 mm (multi-core ≥ 35 mm² rule) — thicker than the 1.8 mm used for ≤16 mm² multi-core cables.
- Conductor resistance is the compliance limit: 70 mm² ≤ 0.268 Ω/km, 35 mm² ≤ 0.524 Ω/km (GB/T 3956 Class 2) .
- Ampacity consensus ≈ 195 A (air) / 230 A (buried) — source tables vary 178–260 A with laying method and reference temperature. Always correct for grouping, ambient temperature, and conduit/duct. At 400 V three-phase, 195 A ≈ 135 kVA theoretical.
- Weight ≈ 3.3 t/km — plan drum handling, tray loading and pulling equipment accordingly.