RVVP 2x4.0mm² Heavy Duty Shielded Motor Drive Cable Braided Copper EMI Protection 300/500V
Product Summary
Product Details
Product Description
RVVP 2x4.0mm² Heavy Duty Shielded Motor Drive Cable Braided Copper EMI Protection 300/500V
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
R |
Flexible conductor (Class 5 fine-stranded) |
|
V |
PVC insulation |
|
V |
PVC sheath |
|
P |
Copper wire shield (braid or braid+tape) |
|
2×4.0 mm² |
Two cores, each 4.0 mm² copper |
Construction: Two fine-stranded flexible copper conductors, each PVC insulated, laid up with fillers to form a round core assembly, wrapped with copper braid shield (typically 85%–90% coverage), and extruded with a common round PVC outer sheath.
Applicable Standards
- JB/T 8734.5-2016 — Rated voltages up to and including 450/750 V PVC insulated cables and cords for fixed wiring and flexible applications — Part 5: Shielded flexible cables
- GB/T 5023.5-2008 / IEC 60227-5 — Polyvinyl chloride insulated cables — Flexible cables (cords)
- GB/T 3956 / IEC 60228 — Conductors (Class 5 flexible copper)
- GB/T 2951 / IEC 60811 — Insulating and sheathing materials — Common test methods
- GB/T 18380 / IEC 60332-1 — Flame retardant (single cable, passes)
- GB/T 5441 — Communication cable test methods (shielding effectiveness reference)

RVVP 2×4.0 mm² — Heavy Shielded Flexible PVC Control Cable — Specification & Engineering Data
1. Overview & Ratings. RVVP 2×4.0 is a heavy shielded flexible PVC control cable rated 300/500 V, 70 °C continuous. Built per GB/T 9330 / IEC 60227. Two 4.0 mm² large flexible copper conductors (~56×0.30 mm) enclosed in a heavy copper wire braid shield (≥ 80% coverage) and PVC outer sheath. Designed for motor power and heavy control circuits. Finished OD ≈ 10.0 mm, ≈ 190 kg/km, 100 m coils.
2. Construction Stack (Conductor → Outer).
| Layer | Build | Wall | Diameter |
|---|---|---|---|
| Conductors (×2) | Large flexible Cu, Class 5, 2×4.0 mm² | — | ≈ 2.5 mm each |
| PVC insulation | Polyvinyl chloride, per core | ≈ 0.8 mm | ≈ 4.2 mm each |
| Heavy copper braid shield | Tinned copper wire braid, ≥ 80% coverage | ≈ 0.6 mm | ≈ 8.5 mm |
| PVC outer sheath | PVC, dark brown | ≈ 1.4 mm | ≈ 10.0 mm (finished) |
3. Electrical Characteristics. DC resistance ≤ 4.61 Ω/km at 20 °C (flexible Cu 4.0 mm²); test voltage 2.0 kV AC / 5 min; insulation resistance ≥ 20 MΩ·km. Shield resistance ≤ 15 Ω/km. Nominal ampacity ≈ 23 A (heavy control). Mutual capacitance ≤ 200 pF/m.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
PVC (polyvinyl chloride), Type TI1/TI2 |
|
Outer sheath material |
PVC (polyvinyl chloride), Type TM1/TM2 |
|
Long-term service temp. |
70 °C (continuous, both insulation & sheath) |
|
Short-circuit temp. (≤5 s) |
160 °C (Cu conductor limit for PVC) |
|
Emergency overload temp. |
105 °C (short term) |
|
Test voltage AC (5 min) |
2.0 kV (routine test, 300/500 V class) |
|
Dielectric strength |
≥ 15 kV/mm (room temp.) |
|
Shielding effectiveness |
≥ 60 dB at 30 MHz – 100 MHz (typical copper braid) |
|
Transfer impedance |
≤ 100 mΩ/m at 10 MHz (typical) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
300 / 500 V |
JB/T 8734.5 / GB/T 5023.5 |
|
Max. system voltage |
500 V AC |
— |
|
Test voltage AC (5 min) |
2.0 kV |
Routine test (core-to-core, core-to-shield) |
|
DC resistance @20 °C |
≤ 4.95 Ω/km |
GB/T 3956 Class 5 Cu max, 4.0 mm² |
|
AC resistance @70 °C (est.) |
≈ 6.3 Ω/km |
per core |
|
Current rating in air (30 °C) |
25 A |
2-core, open air, reference value |
|
Current rating in tray (30 °C) |
22 A |
bundled with other cables |
|
Current rating in conduit (30 °C) |
19 A |
enclosed |
|
Short-circuit current (1 s, Cu, 160 °C) |
≈ 0.44 kA (440 A) |
4.0 mm² Cu |
|
Capacitance (core-to-core, approx.) |
≈ 125 pF/m |
PVC insulation |
|
Capacitance (core-to-shield, approx.) |
≈ 185 pF/m |
collective shield |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC (signal up to ~10 MHz) |
— |
Reference values: 2×4.0 mm² at 19–25 A, single-phase 230 V → max load ≈ 4.4–5.8 kW. Suitable for signal + substantial power applications (control signals plus motor, solenoid, or heater loads up to ~5 A per core continuously).
4. Thermal & Mechanical. 70 °C continuous; 160 °C short-circuit (≤ 5 s); ambient −15~+70 °C. Bend ≥ 6 × OD ≈ 60 mm. Handles up to ~23 A for motor power and drive interconnection.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
70 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
160 °C (Cu conductor, PVC limit) |
|
Emergency overload temp. |
105 °C (not recommended for continuous) |
|
Min. installation ambient temp. |
0 °C (PVC); below 0 °C pre-heating required |
|
Service ambient range |
−15 °C to +70 °C (PVC insulation & sheath) |
|
Flexing temp. range |
+5 °C to +70 °C (recommended for repeated bending) |
|
Fire survival |
Standard (flame retardant single cable) |
Fire Performance (RVVP — Standard)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
IEC 60332-1 (single cable, passes) |
|
Halogen content |
Contains halogen (PVC insulation & sheath) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC) |
|
Fire survival (circuit integrity) |
Not applicable (standard version) |
|
EMI shielding |
Yes (copper braid, 85%–90% coverage) |
Shielding Performance
|
Parameter |
Value |
Note |
|---|---|---|
|
Shield type |
Copper wire braid (bare or tinned) |
— |
|
Coverage |
85%–90% (typical) |
>90% available on request |
|
Optional |
Copper braid + aluminium polyester tape (dual shield) |
for high EMI environments |
|
Drain wire |
Not required (braid is continuous) |
— |
|
Shielding effectiveness |
≥ 60 dB @ 30–100 MHz |
typical braid |
|
Transfer impedance |
≤ 100 mΩ/m @ 10 MHz |
— |
|
Application |
EMI/RFI protection for signal and control circuits |
— |

5. Installation Practice & Handling. Use crimp lugs and heavy terminal blocks. Ground shield at both ends for high-frequency VFD noise. At 190 kg/km, heavy — 46% heavier than RVVP 2×2.5. Indoor use.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 6 × OD → ≈ 67 mm at Ø11.2 mm |
flexible conductor, shielded |
|
Max. pulling tension |
320 N |
fine-stranded Cu (handle gently) |
|
Direct burial |
Not recommended (no mechanical protection; use conduit) |
— |
|
Surface mounting |
Good (round profile, cable ties or clips) |
— |
|
Conduit ID |
≥ 20 mm |
— |
|
Fixing |
cable ties, clamps, trunking |
— |
|
Impact resistance |
Low (PVC sheath only) |
protect with conduit in exposed areas |
|
Water resistance |
Moisture-resistant (PVC) |
not waterproof |
|
UV resistance |
Poor (PVC degrades in sunlight) |
indoor use only |
|
Flex life |
High (Class 5 fine-stranded, designed for occasional flexing) |
— |
|
Termination note |
Strip sheath, fold braid back over outer sheath, use heat-shrink or copper strap for shield termination; ferrules recommended for fine-stranded conductors |
shield must be grounded at one end (or both, depending on application) |
6. Typical Service Applications. Motor power leads, VFD drive interconnection, heavy control circuits, equipment power distribution, shielded power runs in noisy industrial environments.

7. Testing & QA Regime. Routine: conductor DC resistance, 2.0 kV AC withstand, insulation resistance, shield coverage check, dimensional check. Type: heating test, bending test, flame retardancy, mutual capacitance measurement.
Cable Parameters
| RVVP 2×4.0 mm² — Heavy Shielded Flexible PVC Control Cable — Full Parameter Sheet | ||||
| Heavy shielded control · 2× large flexible Cu / PVC insulation / copper braid shield / PVC sheath · 300/500 V · 70 °C · ≈ 10.0 mm · heavy control / power | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | RVVP — heavy shielded flexible PVC control cable | — | Heavy control | |
| Rated voltage (U0/U) | 300/500 | V | Signal / control | |
| Number of cores | 2 × 4.0 | — | 2-core | |
| Conductor material | Annealed copper, fine-stranded | — | Class 5 flexible | |
| Insulation material | PVC (polyvinyl chloride) | — | Per core | |
| Shield type | Copper wire braid (P) | — | ≥ 80% coverage | |
| Sheath material | PVC (outer, dark brown) | — | Flexible | |
| Standard | GB/T 9330 / IEC 60227 | — | Control cable | |
| Application | Heavy control, motor power, drive interconnection, power control | — | Heavy | |
| 02 · Conductor (Flexible Cu) | ||||
| Conductor type | Fine-stranded annealed copper | — | Class 5 flexible | |
| Conductor area | 2 × 4.0 | mm² | 2-core heavy | |
| Stranding construction | ≈ 56 × 0.30 mm (approx.) | — | Large strands | |
| DC resistance @ 20 °C | ≤ 4.61 | Ω/km | Cu 4.0 mm² flexible | |
| Conductor weight per km | ≈ 76 | kg/km | 2×4.0 Cu | |
| Conductor diameter | ≈ 2.5 | mm | Flexible stranded | |
| 03 · Insulation & Shield | ||||
| Insulation type | PVC (per core) | — | General-purpose | |
| Insulation thickness | ≈ 0.8 | mm | 300/500 V | |
| Insulated core OD | ≈ 4.2 | mm | Per core | |
| Shield type | Copper wire braid | — | P = shield | |
| Shield coverage | ≥ 80 | % | EMI protection | |
| Shield diameter | ≈ 8.5 | mm | Over cores | |
| 04 · Sheath | ||||
| Sheath type | PVC outer sheath | — | Flexible | |
| Sheath thickness | ≈ 1.4 | mm | Heavy control | |
| Finished outer diameter | ≈ 10.0 | mm | Overall | |
| Sheath color | Dark brown | — | Standard | |
| 05 · Electrical | ||||
| Rated voltage (U0/U) | 300/500 | V | Signal / control | |
| Max voltage | 500 | V | Phase-to-phase | |
| DC resistance @ 20 °C | ≤ 4.61 | Ω/km | Flexible Cu 4.0 | |
| Test voltage (AC) | 2.0 kV / 5 min | — | Routine | |
| Insulation resistance | ≥ 20 | MΩ·km | PVC | |
| Nominal current (ampacity) | ≈ 23 | A | Heavy control | |
| Shield resistance | ≤ 15 | Ω/km | Heavy braid | |
| 06 · Thermal | ||||
| Max conductor temp. | 70 | °C | PVC rated | |
| Short-circuit temp. | 160 | °C | Max 5 s | |
| Ambient range | -15 ~ +70 | °C | Indoor | |
| Laying temperature | ≥ -10 | °C | Flexible | |
| 07 · Mechanical & Shield | ||||
| Min bending radius (fixed) | ≥ 6 × OD ≈ 60 | mm | Heavy shielded | |
| Flexibility | Moderate | — | Large flexible | |
| Shield attenuation | EMI/RFI protected | — | Copper braid | |
| Cable weight per km | ≈ 190 | kg/km | Heavy | |
| 08 · Installation | ||||
| Laying methods | Motor power, drive interconnection, heavy control, equipment power | — | Heavy | |
| Connectors | Crimp lugs / ferrules / terminal blocks | — | Shielded | |
| Shield termination | Ground at one or both ends | — | Per system | |
| Bend radius | ≥ 6 × OD ≈ 60 mm | — | Heavy | |
| 09 · Packing | ||||
| Standard supply length | 100 m / coil | m | Control cable | |
| Reel / packing type | Coil, wrapped | — | Plastic bag | |
| Surface marking | RVVP, 2×4.0, 300/500V, GB/T 9330 | — | Continuous printing | |
| Approx. cable weight | ≈ 190 | kg/km | 2-core heavy shielded | |
| 10 · Applications | ||||
| Typical use | Motor power, drive interconnection, heavy control, equipment power, shielded power | — | Heavy | |
| Max system voltage | 500 | V | 300/500 V | |
| Application level | Heavy control / power | — | High current | |
Cable Test Parameters
| Test Parameters — RVVP 2×4.0 mm² Heavy Shielded Control Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 4.61 Ω/km (flexible Cu 4.0) | Routine |
| 2 | Voltage test (AC) | 2.0 kV AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | 500 V DC | ≥ 20 MΩ·km | Routine |
| 4 | Insulation thickness | Micrometer | ≥ 0.8 mm | Routine |
| 5 | Shield coverage | Visual / microscopic | ≥ 80% braid coverage | Routine |
| 6 | Shield continuity | Per GB/T 9330 | Shield electrically continuous | Routine |
| 7 | Heating test | 70 °C conductor, 2 h | No damage | Type |
| 8 | Flexibility / bending test | 6× OD, cycles | No damage | Type |
| 9 | Flame retardancy | IEC 60332-1 | Self-extinguishing | Type |
| 10 | Dimensional check | Caliper | OD ≈ 10.0 mm | Routine |
| 11 | Mutual capacitance | Per GB/T 9330 | ≤ 200 pF/m | Type |
| 12 | Printing legibility | Visual | Marking readable | Routine |
Cable Cross Section Structure

| RVVP 2×4.0 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Heavy shielded control: 2×large flexible Cu → PVC insulation → copper braid shield → PVC sheath · 300/500 V · ≈ 10.0 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductors (×2) | Fine-stranded annealed Cu, Class 5, 2×4.0 mm² | — | ≈ 2.5 each | R ≤ 4.61 Ω/km |
| 2 | PVC insulation | Polyvinyl chloride, per core | ≈ 0.8 | ≈ 4.2 each | 300/500 V rated |
| 3 | Copper braid shield | Tinned copper wire braid, ≥ 80% coverage | ≈ 0.6 | ≈ 8.5 | EMI/RFI protection |
| 4 | PVC outer sheath | PVC, dark brown | ≈ 1.4 | ≈ 10.0 | Outer protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 10.0 | mm | Overall | ||
| Approx. cable mass | ≈ 190 | kg/km | Heavy | ||
| Nominal voltage rating | 300/500 | V | Signal / control | ||
| Max conductor temp. | 70 | °C | PVC rated | ||
| Short-circuit temp. | 160 | °C | Max 5 s | ||
| Min bending radius (fixed) | ≥ 6 × OD ≈ 60 | mm | Heavy shielded | ||
| DC resistance @ 20 °C | ≤ 4.61 | Ω/km | Flexible Cu 4.0 | ||
| Test voltage (AC) | 2.0 kV / 5 min | — | Routine | ||
| Nominal current (ampacity) | ≈ 23 | A | Heavy control | ||
| Shield coverage | ≥ 80 | % | Copper braid | ||
| Shield resistance | ≤ 15 | Ω/km | Heavy braid | ||
| Number of cores | 2 | — | Power pair | ||
| Standard | GB/T 9330 / IEC 60227 | — | Control cable | ||
| Application | Motor power / heavy control | — | High current | ||
| Schematic — not to exact scale. Finished OD ≈ 10.0 mm and weight ≈ 190 kg/km from cross-referenced industry samples. RVVP 2×4.0 is a heavy shielded flexible control cable for motor power and heavy control circuits. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — RVVP 2×4.0 mm² heavy shielded control cable | |||
| Layer-by-layer heavy shielded control cable: 2×large flexible Cu / PVC insulation / copper braid shield / PVC sheath · 300/500 V · 70 °C · ≈ 10.0 mm | |||
| 1. Product Identity & Ratings | |||
| RVVP 2×4.0 is a heavy shielded flexible PVC control cable rated 300/500 V, 70 °C continuous. Built per GB/T 9330 / IEC 60227. Two 4.0 mm² large flexible copper conductors enclosed in a copper wire braid shield (≥ 80% coverage) and PVC outer sheath. Designed for motor power and heavy control circuits. Finished OD ≈ 10.0 mm, mass ≈ 190 kg/km, 100 m coils. | |||
| 2. Two Large Flexible Copper Conductors | |||
| Two 4.0 mm² fine-stranded annealed copper conductors (Class 5, ~56×0.30 mm). DC resistance ≤ 4.61 Ω/km at 20 °C. The large flexible construction handles up to ~23 A for motor power and drive interconnection. | |||
| 3. Heavy Copper Braid Shield | |||
| Tinned copper wire braid woven over the insulated cores with ≥ 80% coverage. The heavier braid shield blocks EMI/RFI from VFDs, motors, and power cables — critical when carrying both power and signal in noisy industrial environments. | |||
| 4. PVC Outer Sheath | |||
| PVC outer sheath ≈ 1.4 mm thick, dark brown. Provides heavy-duty mechanical protection. The flexible sheath bends for equipment interconnection but requires a generous 6×OD bend radius. | |||
| 5. Site Handling & Operational Notes | |||
| • Bend radius 6×OD (≈ 60 mm). • Use crimp lugs and heavy terminal blocks. • Ground shield at both ends. • At 190 kg/km, heavy. • Indoor use. • Heavy control / power (≈ 23 A max). |
8. Standards & Conformity. GB/T 9330 (plastic insulated control cables); IEC 60227 (international); GB/T 3956 (Class 5 flexible conductors). Rated 300/500 V.
9. Packaging, Storage & Logistics. 100 m per coil, plastic wrapped. Continuous marking: RVVP, 2×4.0, 300/500V, GB/T 9330. Store dry, indoor.

10. Procurement Specification. State "RVVP 2×4.0" + length. Specify shield coverage requirement (≥ 80%). Confirm against factory test certificate.
11. Cable Industry FAQ.
- Q1: What is the difference between RVVP 2×4.0 and RVVP 2×2.5? The 4.0 mm² version has 60% more copper cross-section, is 25% thicker (10.0 vs 8.0 mm), 46% heavier (190 vs 130 kg/km), and carries 44% more current (23 vs 16 A). It is for motor power; the 2.5 mm² version is for general control.
- Q2: Why choose 4.0 mm²? When you need to carry up to ~23 A while maintaining EMI shielding — e.g., powering small motors, solenoids, or drives — 4.0 mm² provides the current capacity. The 2.5 mm² version is limited to ~16 A.
- Q3: Can it power a small motor? Yes — up to ~23 A at 300/500 V is enough for fractional-horsepower motors and drive inputs. The shield prevents VFD noise from radiating back into the control circuit.
- Q4: What connectors are used? Heavy crimp lugs, ferrules, or terminal blocks rated for 4 mm² conductors. The 2.5 mm conductor diameter requires larger lugs than the 2.0 mm in RVVP 2×2.5.
- Q5: Is the shield heavier? Yes — the braid is thicker (0.6 vs 0.5 mm) and shield resistance is lower (≤ 15 vs ≤ 20 Ω/km) because it wraps larger cores. Coverage remains ≥ 80%.
- Q6: Can it be used as a power cable? It can carry up to 23 A at 300/500 V, but it is not a power cable per se. For true power distribution, use RVV or YJV. RVVP 2×4.0 is for shielded power/control hybrid runs.
- Q7: What is the bending radius? 6×OD ≈ 60 mm — stiffer than the 48 mm of RVVP 2×2.5 due to the larger conductors.
- Q8: Can it be used outdoors? No — PVC sheath is not UV-resistant. For outdoor use, use outdoor-rated cable.
- Q9: How does it compare to RVVP 2×6.0? The 6.0 mm² version carries ~30 A and is for heavier motor power. The 4.0 mm² version carries 23 A and is the sweet spot for small drives and heavy control. If you need more than 23 A, step up to 6.0 mm².
- Q10: Should the shield be grounded at one or both ends? For VFD and high-frequency noise, ground at both ends. For low-frequency signals, one end only. With 4.0 mm² power/control hybrid, both ends is typical.
- Q11: What is the standard? GB/T 9330 / IEC 60227 for plastic insulated control cables, rated 300/500 V.