ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZC-YJV 4x50mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution Cable Designation & Meaning Code Meaning ZC Flame retardant Category C​ (GB/T 18380.3) YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath 4×50 mm² Four cores, each 50 mm² copper (3 phases + 1 ...

Product Details

Highlight:

4 Cores Cable

,

4 Cores Cable

,

Copper Power Cable

Conductor (×4):
Copper, Class 2 Stranded Circular, Typical 19×∅1.83 Mm (50 Mm²), Conductor Ø ≈ 9.2–10.5 Mm
Conductor screen:
None (for ≤1.8/3 KV, Semi-con Screen Optional)
Insulation:
XLPE (cross-linked Polyethylene), Nominal Thickness 1.0 Mm​ (0.6/1 KV Class)
Filler:
PVC Filler (flame-retardant Grade), Round Profile
Inner bedding:
PVC Tape Wrap Or Extruded (flame-retardant), Thickness ≈ 1.0 Mm
Outer sheath:
PVC​ (polyvinyl Chloride), Flame-retardant Category C, Nominal Thickness 2.0 Mm (typical), Colour: Black
Conductor nominal area:
50 Mm² (Cu)
Number of cores:
4
Conductor material:
Copper (Cu)
Conductor class:
Class 2 Stranded
Conductor construction:
19×∅1.83 Mm (typical)
Conductor diameter (approx.):
9.2–10.5 Mm
Insulation thickness:
1.0 Mm
Diameter over insulated core (approx.):
11.2–12.5 Mm
Filler & bedding thickness:
1.0 Mm
Outer sheath thickness:
2.0 Mm
Overall cable diameter:
28 – 34 Mm
Design outer diameter:
≈ 30.5 Mm
Approx. weight:
2.8 – 3.4 Kg/m (2800–3400 Kg/km)
Design weight:
≈ 3050 Kg/km

Product Description

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

Cable Designation & Meaning

 

Code

Meaning

ZC

Flame retardant Category C​ (GB/T 18380.3)

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath

4×50 mm²

Four cores, each 50 mm² copper (3 phases + 1 neutral, no separate earth)

 

Construction: XLPE insulated, copper conductor, PVC sheathed, flame-retardant Category C, four-core low-voltage power cable.

 

ZC-YJV 4×50 mm² (C-class flame-retardant XLPE/PVC LV power cable) — Specification & Engineering Data

1. Overview & Ratings. ZC-YJV 4×50 — flame-retarding four-core LV power cable, four 50 mm² compacted Cu Class 2 conductors, XLPE insulation (90 °C), PVC outer sheath (ST2, black), rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; built and proof-tested per GB/T 12706.1 / IEC 60502-1, stranding per GB/T 3956, ZC fire class per GB/T 19666. Ø ≈ 28.5 mm, ≈ 2380 kg/km, 100 m wooden drums.

 

2. Construction Stack (Conductor → Outer Sheath).

Layer Build Wall Diameter
Conductors (×4) Compacted stranded Cu, Class 2, 7 × 3.0 mm each — ≈ 9.5 mm each
XLPE insulation (×4) Cross-linked polyethylene, 90 °C rated 1.4 mm ≈ 12.3 mm each
Bedding / filler PVC bedding + binder tape — ≈ 25.5 mm
Outer sheath PVC, ST2, flame-retardant, black 2.0 mm ≈ 28.5 mm (finished)

 

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

 

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

 

3. Electrical Characteristics. R ≤ 0.387 Ω/km at 20 °C per core; routine test 3.5 kV AC / 5 min; insulation resistance ≥ 3.67 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km. Reference ampacity (4 cores loaded) ≈ 175 A air / ≈ 185 A buried at 30 °C.

Electrical Parameters

 

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage Uₘ

1.2 kV

—

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4 kV

—

DC resistance @20 °C

≤ 0.387 Ω/km

GB/T 3956 Class 2 Cu max, 50 mm²

AC resistance @90 °C (est.)

≈ 0.493 Ω/km

per core

Capacitance (approx.)

≈ 0.25 µF/km

core to core / core to screen

Inductive reactance (approx.)

≈ 0.08 Ω/km

at 50 Hz, 4-core

Current rating in air (30 °C)

165 A​

3-phase loaded, 4-core (3P+1N)

Current rating buried (20 °C)

140 A​

direct buried, 4-core

Current rating in conduit (30 °C)

130 A​

3-phase, 4-core

Short-circuit current (1 s, Cu, 250 °C)

≈ 5.0 kA (5000 A)

50 mm² Cu

Frequency

50/60 Hz AC

—

Reference values: 50 mm² Cu at 165 A, 3-phase 400 V → max balanced load ≈ 114 kVA. Voltage drop at 165 A ≈ 81.3 V/km per core (≈3.3% per 100 m at 400 V).

Insulation Data

Property

Value

Material

XLPE (cross-linked polyethylene)

Nominal thickness

1.0 mm

Long-term service temp.

90 °C

Short-circuit temp. (≤5 s)

250 °C​ (Cu conductor limit per IEC 60228)

Emergency overload temp.

130 °C

Routine test voltage (AC, 5 min)

3.5 kV (0.6/1 kV)

Type-test voltage (AC)

4 kV (0.6/1 kV)

Partial discharge test

Not required for ≤1.8/3 kV

Tan δ (dissipation factor)

≤ 0.004 at 20 °C

 

4. Thermal & Fire. 90 °C continuous, 250 °C short-circuit (≤ 5 s); -20~+45 °C ambient, ≥ 0 °C laying; ZC per GB/T 19666 — GB/T 18380.35 class-C bunched flame test (char ≤ 2.5 m). PVC sheath is halogen-bearing → WDZ-YJY for LSZH.

Fire Performance (ZC-YJV — Flame Retardant Category C)

 

Property

Value / Requirement

Flame retardant

GB/T 18380.3 Category C (ZC)​ — passes flame propagation test for bundled cables

Halogen content

Contains halogen (PVC sheath & XLPE insulation)

Smoke density

Standard (non-low-smoke); optional ZC-YJY for low-smoke zero-halogen

Corrosivity

Corrosive (PVC)

Fire survival (circuit integrity)

Not applicable (standard ZC version); use NH-ZC-YJV for circuit integrity

 

Flame Retardant Category Comparison:

 

Category

Test Condition

Application

ZA

Most stringent (≥80 min burn resistance)

Critical safety circuits, nuclear, metro

ZB

High (≥40 min)

High-rise buildings, data centres

ZC​

Standard (≥20 min)​

Commercial buildings, industrial plants​

ZD

Basic (≥10 min)

General residential

 

5. Installation Practice & Handling. Bend ≥ 15 × OD ≈ 430 mm fixed; DC site test 4U0 = 2.4 kV / 15 min before energising; use Cu compression lugs for 50 mm² terminations; lay in tray, trench, duct, conduit. De-rate 175/185 A for ambient, grouping, burial.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 458 mm at Ø30.5 mm

static installation

Max. pulling tension

5000 N

Cu conductor, use proper pulling grips

Direct burial

Suitable (with warning tape)

unarmoured — protect from mechanical damage

Conduit ID

≥ 1.5 × OD → ≥ 46 mm; use 50 mm, 63 mm or 75 mm

—

Fixing

cable clamps, cable ties, tray

—

Impact resistance

Low–Moderate

unarmoured; avoid sharp objects

Water resistance

Moisture-resistant (PVC sheath)

not watertight; use armoured or screened for wet

Termination note

Cu conductors — standard lugs (compression or mechanical)

strip length 12–15 mm

 

6. Typical Service Applications. Main distribution risers, transformer secondaries, industrial feeders, commercial building power, machine tool supply — tray, trench, duct, conduit, trunking; indoor or sheltered outdoor.

 

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

 

7. Testing & QA Regime. Routine: conductor DC resistance ≤ 0.387 Ω/km, 3.5 kV AC / 5 min withstand, dimensional check (XLPE ≥ 1.4 mm, sheath ≥ 2.0 mm, OD ≈ 28.5 mm). Type: heat ageing at 135 °C / 168 h, short-circuit 250 °C / 5 s, heat shock at 150 °C, insulation resistance at 90 °C, ZC bunched flame test GB/T 18380.35 class C.

 

Cable Parameters

 

ZC-YJV 4×50 mm² — Flame-Retardant XLPE-Insulated PVC-Sheathed LV Power Cable — Full Parameter Sheet 
C-class flame-retardant XLPE-insulated PVC-sheathed power cable · 4 cores × 50 mm² Class 2 stranded Cu · XLPE insulation (90 °C) + PVC outer sheath (ST2) · 0.6/1 kV · GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 28.5 mm
Section Parameter Value Unit Remarks / Standard
01 · Identification
  Cable type ZC-YJV (Flame-retardant C-class XLPE/PVC power cable) — Distribution / feeder
  Rated voltage (U0/U) 0.6/1 kV (Um=1.2 kV) LV power distribution
  Number of cores 4 × 50 — 4 cores, 50 mm² each
  Conductor material Annealed stranded copper — Class 2 compacted per GB/T 3956
  Inner insulation material Cross-linked polyethylene (XLPE) — 90 °C rated
  Outer sheath material Polyvinyl chloride (PVC), ST2 — Flame-retardant, black
  Outer sheath colour Black — Standard
  Flame retardancy class ZC (C-class) — Per GB/T 19666 / GB/T 18380.35
  Standard GB/T 12706.1 / IEC 60502-1 — LV power cable
02 · Conductor (Stranded Copper)
  Conductor type Compacted stranded copper — Class 2 per GB/T 3956
  Strand construction (per core) 7 × 3.0 mm 7 strands of 3.0 mm (compact)
  Conductor diameter (per core) ≈ 9.5 mm Compacted bundle
  Cross-sectional area (per core) 50 mm² Nominal
  DC resistance @ 20 °C (per core) ≤ 0.387 Ω/km Max per GB/T 3956 Class 2
  Conductor weight per km ≈ 1780 kg/km 4 × 50 mm² Cu
03 · Insulation & Sheath
  Inner insulation type Cross-linked polyethylene (XLPE) — 90 °C rated
  Inner insulation thickness 1.4 mm Nominal per core
  Core colours Red / yellow / blue (L1/L2/L3) — 4-core = 3P+N  
  Bedding / filler PVC bedding + binder tape — Filler for roundness
  Outer sheath type PVC, ST2 — Flame-retardant, black
  Outer sheath thickness 2.0 mm Nominal
  Finished outer diameter ≈ 28.5 mm 4 cores laid up + sheath
04 · Electrical
  Rated voltage (AC) 0.6/1 kV LV power distribution
  DC resistance @ 20 °C (per core) ≤ 0.387 Ω/km 50 mm² Cu Class 2
  Insulation resistance ≥ 3.67 MΩ·km XLPE
  XLPE volume resistivity ≥ 1×10¹² Ω·cm At 90 °C
  Routine test voltage (AC) 3.5 kV / 5 min — Power-frequency withstand
  Capacitance ≤ 0.45 μF/km XLPE at 50 Hz
05 · Thermal & Fire
  Max continuous conductor temp. 90 °C XLPE rated
  Short-circuit temp. 250 °C XLPE limit (≤ 5 s)
  Min installation temp. 0 °C XLPE/PVC
  Service ambient range -20 to +45 °C LV distribution
  Flame retardancy (ZC) GB/T 18380.35 class C — Bunched cable flame test
  Halogen-free No — PVC sheath contains halogen
  Fire performance Self-extinguishing — ZC = C-class
06 · Mechanical
  Min bending radius (fixed) ≥ 15 × OD ≈ 430 mm LV multi-core power
  Min bending radius (flexed) ≥ 20 × OD ≈ 570 mm Repeated flexing
  Tensile strength (XLPE) ≥ 12.5 MPa XLPE
  Abrasion resistance Good — PVC sheath
07 · Ampacity
  Air ampacity (4 cores loaded) ≈ 175 A Free air, 30 °C (est.)
  Buried ampacity (4 cores) ≈ 185 A Direct burial, 25 °C
  Voltage drop (per 100 m @ 175 A) ≈ 0.68 V Per core
08 · Installation
  Laying methods Tray, trench, duct, conduit, indoor/outdoor — LV distribution
  Connectors Cu lugs, compression terminals — 50 mm² Cu crimp
  Polarity Colour-coded cores — Red/yellow/blue = L1/L2/L3, blue=N
  Site test (DC) 4U0 = 2.4 kV / 15 min — Before energising
09 · Packing
  Standard supply length 100 m / drum m LV power cable
  Reel / packing type Wooden drum — Heavy cable
  Surface marking ZC-YJV, 4×50, 0.6/1 kV, GB/T 12706.1, metre marks — Continuous printing
  Storage conditions Dry, indoor, 0 to +40 °C — Protect from UV / moisture
10 · Applications
  Typical use Main distribution risers, transformer secondaries, industrial feeders, commercial building power, machine tool supply — LV power distribution
  Max system voltage 1.2 kV (Um) 0.6/1 kV rated
  Circuit current rating Up to 175 A per circuit 4 cores loaded

 

Cable Test Parameters

 

Test Parameters — ZC-YJV 4×50 mm²
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C, per core ≤ 0.387 Ω/km (50 mm² Cu Class 2) Routine
2 Power-frequency withstand 3.5 kV AC, 5 min, between cores No breakdown Routine
3 Insulation thickness test Micrometer XLPE ≥ 1.4 mm, sheath ≥ 2.0 mm Routine
4 Dimensional check Micrometer OD ≈ 28.5 mm Routine
5 Flame retardancy (ZC) GB/T 18380.35 class C bunched Char ≤ 2.5 m, self-extinguishing Type
6 Heat ageing 168 h at 135 °C (XLPE) No cracking after bend test Type
7 Short-circuit test 250 °C, 5 s No deformation Type
8 Heat shock (XLPE) 2 h at 150 °C No cracking Type
9 Insulation resistance At 500 V DC, 90 °C ≥ 3.67 MΩ·km Type
10 Conductor continuity Per GB/T 3956 All 4 cores continuous Routine
11 Core colour check Visual Red/yellow/blue cores Routine
12 Bundled flame test GB/T 18380.35 class C Vertical bunched flame test Type

 

Cable Cross Section Structure

 

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

ZC-YJV 4×50 mm² — Cross-Section Construction Diagram (Schematic)
LV power cable build-up: 4 Cu Class 2 cores (red/yellow/blue) → XLPE insulation → PVC bedding → PVC outer sheath · 0.6/1 kV · ZC C-class flame-retardant · finished Ø ≈ 28.5 mm
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductors (×4) Compacted stranded copper, Class 2, 7 × 3.0 mm per core — ≈ 9.5 each 4 cores; R ≤ 0.387 Ω/km
2 XLPE insulation (×4) Cross-linked polyethylene, 90 °C rated 1.4 ≈ 12.3 each XLPE — 90 °C, better than PVC
3 Bedding / filler PVC bedding + binder tape — ≈ 25.5 Roundness and mechanical fill
4 Outer sheath PVC, ST2, flame-retardant, black 2.0 ≈ 28.5 (finished) ZC C-class flame-retardant
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 28.5 mm 4 cores laid up + bedding + sheath    
Approx. cable mass ≈ 2380 kg/km 4 × 50 mm² Cu + XLPE + PVC    
Nominal voltage rating 0.6/1 kV LV power distribution    
Max continuous conductor temp. 90 °C XLPE rated    
Short-circuit temp. (≤5 s) 250 °C XLPE limit    
Min installation temp. 0 °C XLPE/PVC    
Min bending radius (fixed) ≥ 15 × OD ≈ 430 mm LV multi-core power    
DC resistance @ 20 °C (per core) ≤ 0.387 Ω/km 50 mm² Cu Class 2    
Insulation resistance ≥ 3.67 MΩ·km XLPE    
Routine test voltage (AC) 3.5 kV / 5 min — Power-frequency withstand    
Air ampacity @ 30 °C ≈ 175 A 4 cores loaded (est.)    
Buried ampacity @ 25 °C ≈ 185 A Direct burial    
Flame retardancy (ZC) GB/T 18380.35 class C — Bunched cable flame test    
Halogen-free No — PVC sheath contains halogen    
Schematic — not to exact scale. Finished Ø ≈ 28.5 mm and weight ≈ 2380 kg/km from cross-referenced industry samples; conductor/insulation dimensions per GB/T 12706.1 and GB/T 3956; ampacity 175 A (air) / 185 A (buried) is an engineering estimate for 4 cores loaded. ZC-YJV is the C-class flame-retardant version of YJV — XLPE-insulated (90 °C) PVC-sheathed LV power cable rated 0.6/1 kV for distribution trunking and feeder circuits. Unlike BV (single-core PVC 70 °C building wire), YJV uses XLPE insulation (90 °C), has 4 colour-coded power cores, and is designed for high-current distribution. Values marked (est.) require confirmation against the factory test certificate.

 

Construction Description

 

Construction Description — ZC-YJV 4×50 mm² (LV power cable)
Layer-by-layer LV power cable build-up · 4 compacted Cu Class 2 cores (7×3.0) / XLPE insulation (90 °C) / PVC bedding / PVC outer sheath (ST2) · 0.6/1 kV · ZC C-class flame-retardant · finished Ø ≈ 28.5 mm
1. Product Identity & Ratings
ZC-YJV 4×50 is the C-class flame-retardant version of YJV — a flame-retardant XLPE-insulated PVC-sheathed LV power cable rated 0.6/1 kV (Um=1.2 kV) at 50 Hz, built and tested per GB/T 12706.1 / IEC 60502-1. It has 4 colour-coded cores (red/yellow/blue), each 50 mm² compacted stranded copper (Class 2, 7×3.0 mm), insulated with 1.4 mm XLPE (90 °C rated), laid up with PVC bedding, and enclosed in a 2.0 mm PVC outer sheath (ST2, black). Unlike BV (single-core PVC 70 °C building wire), YJV uses XLPE insulation (90 °C), has 4 power cores, and is designed for high-current distribution. Finished Ø ≈ 28.5 mm, mass ≈ 2380 kg/km, supplied on wooden drums in 100 m lengths.
2. Compacted Stranded Copper Conductors (4 cores)
Each of the 4 cores uses 7 strands of 3.0 mm annealed copper wire, compacted to a near-circular bundle (Class 2 per GB/T 3956), giving a maximum DC resistance of 0.387 Ω/km per core at 20 °C. The 4 cores are colour-coded: red (L1), yellow (L2), blue (L3 and N). The compacted conductor reduces the overall cable diameter compared with a non-compacted bundle. Always use Cu compression lugs for 50 mm² terminations.
3. XLPE Insulation (90 °C rated)
Each core is insulated with 1.4 mm of cross-linked polyethylene (XLPE), rated for 90 °C continuous conductor temperature (up to 250 °C for ≤ 5 s short-circuit). XLPE has much better thermal and electrical properties than PVC — it can carry more current for the same cross-section, has higher dielectric strength, and lower insulation resistance. This is the key difference from BV (PVC 70 °C).
4. PVC Bedding & Outer Sheath
The 4 insulated cores are laid up in a triangular formation with PVC bedding and binder tape to ensure roundness. The cable is then enclosed in a 2.0 mm PVC outer sheath (ST2, black), which provides mechanical protection and is flame-retardant to ZC (C-class). The ZC designation means the cable passes the bunched cable flame test (GB/T 18380.35 class C) — char length ≤ 2.5 m.
5. Site Handling & Operational Notes
• Lay in tray, trench, duct, conduit, or indoor/outdoor fixed installations.  • Observe the 15 × OD minimum bend radius (≈ 430 mm) for fixed installation.  • Service range -20 to +45 °C; conductor up to 90 °C continuous.  • Routine test 3.5 kV AC / 5 min between cores.  • DC site test 4U0 = 2.4 kV / 15 min before energising.  • PVC sheath contains halogen — use WDZ-YJY for LSZH.  • At about 2380 kg/km, the cable is supplied on wooden drums.  • Use Cu compression lugs for 50 mm² terminations.  • ZC = C-class flame-retardant for bunched cable installations.

 

8. Standards & Conformity. GB/T 12706.1 / IEC 60502-1 (LV XLPE power cables); GB/T 3956 (Class 2 compacted conductors); GB/T 19666 / GB/T 18380.35 (ZC C-class flame retardancy). Rated 0.6/1 kV LV power distribution.

 

9. Packaging, Storage & Logistics. 100 m per wooden drum. Continuous marking: ZC-YJV, 4×50, 0.6/1 kV, GB/T 12706.1, supplier identity, production year, metre marks. Store dry, indoor, 0 to +40 °C, protect from UV.

 

ZC-YJV 4x50mm² Class C Flame Retardant XLPE Copper Power Cable for Building Distribution

 

10. Procurement Specification. State "ZC-YJV 0.6/1 kV 4×50" + length/drum + marking; confirm against factory test certificate. Use Cu compression lugs for 50 mm². For LSZH, specify WDZ-YJY 4×50 instead.

 

11. Cable Industry FAQ.

  • Q1: What is the difference between YJV and BV? YJV uses XLPE insulation (90 °C, 0.6/1 kV, multi-core power cable for distribution). BV uses PVC insulation (70 °C, 450/750 V, single-core building wire for conduit). YJV is for high-current power; BV is for low-current building wiring.
  • Q2: What does "ZC" mean? ZC = C-class flame-retardant per GB/T 19666 / GB/T 18380.35. The cable passes the bunched vertical flame test at class C (char length ≤ 2.5 m). ZA and ZB are higher classes; ZC is the most common for general LV distribution.
  • Q3: Why XLPE instead of PVC? XLPE can run at 90 °C continuous (vs PVC 70 °C), so a 50 mm² XLPE cable carries ~175 A vs ~130 A for PVC. XLPE also has better dielectric strength and lower insulation loss.
  • Q4: Can YJV be buried directly? Unarmored YJV should be laid in trench, duct, or conduit. For direct burial, use YJV22 (steel tape armored) or YJV32 (steel wire armored).
  • Q5: What is YJV22? YJV22 adds a double steel tape armor layer between the bedding and outer sheath, providing crush protection for direct burial and underground installations.
  • Q6: What is the difference between YJV and YJLV? YJV uses copper conductors. YJLV uses aluminum conductors (lighter, cheaper, lower ampacity). For the same cross-section, aluminum has higher resistance.
  • Q7: Why is the routine test 3.5 kV and not 2 kV? For 0.6/1 kV cables, the power-frequency withstand test is 3.5 kV (3.5×U0), vs 2.0 kV for 300/500 V control cables. Higher rated voltage requires higher test voltage.
  • Q8: Can YJV be used outdoors? YJV's black PVC sheath is UV-resistant enough for sheltered outdoor use, but for long-term direct outdoor exposure, use a UV-stabilized sheath or armored cable.
  • Q9: What size lugs do I need for 50 mm²? Use 50 mm² copper compression lugs (Cu tubular terminals), crimped with a hydraulic crimper. Always inspect crimp quality.
  • Q10: What is the minimum bending radius? 15 × OD for fixed installation (≈ 430 mm for 28.5 mm cable), 20 × OD for flexible installation. This is much larger than BV (4×OD) because YJV is a large multi-core power cable.
  • Q11: How do I choose between YJV and RVV? RVV is 300/500 V control/lamp cable (PVC, 70 °C, small cross-sections). YJV is 0.6/1 kV power distribution cable (XLPE, 90 °C, large cross-sections for high current). Different voltage and current ranges.