Flame Retardant Copper Cable ZR-YJV 3×150mm²+1×70mm² for Commercial Building Power System Technical Datasheet — ZR-YJV 0.6/1 kV 3×150+1×70 mm² Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE ...

Product Details

Highlight:

Copper power cable 4 core

,

power cable 4 core 3×150mm2

,

Power System xlpe copper cable

Phase conductor (×3):
Bare Annealed Copper, Class 2 Stranded, 37×∅2.27 Mm, Conductor Ø ≈ 15.9–16.8 Mm Depending On Compaction
Neutral conductor (×1):
Bare Annealed Copper, Class 2 Stranded, 19×∅2.14 Mm, Conductor Ø ≈ 10.7–11.2 Mm Depending On Compaction
Phase conductor nominal area:
150 Mm²
Neutral conductor nominal area:
70 Mm²
Number of cores:
4 (3+1)
Phase conductor construction:
Class 2, 37×∅2.27 Mm,IEC 60228 / GB/T 3956
Neutral conductor construction:
Class 2, 19×∅2.14 Mm,IEC 60228 / GB/T 3956
Phase conductor diameter (approx.):
15.9–16.8 Mm
Neutral conductor diameter (approx.):
10.7–11.2 Mm
Insulation (×4):
XLPE
Phase insulation thickness:
1.4 Mm (150 Mm² Class)
Neutral insulation thickness:
1.1 Mm (70 Mm² Class)
Diameter over phase insulated core:
18.7–19.6 Mm
Diameter over neutral insulated core:
12.9–13.4 Mm
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.9 Mm (GB/T 12706 Multi-core 120–185 Mm² Range)
Overall cable diameter:
34.5 – 41.0 Mm
Design outer diameter:
≈ 37.0 Mm
Approx. weight:
1850 – 2300 Kg/km
Design weight:
≈ 2050 Kg/km
Cable shape:
Round

Product Description

Flame Retardant Copper Cable ZR-YJV 3×150mm²+1×70mm² for Commercial Building Power System

 

Technical Datasheet — ZR-YJV 0.6/1 kV 3×150+1×70 mm²

Cable Designation & Meaning

 

Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

3×150+1×70 mm²

Three phase cores of 150 mm² copper + one reduced neutral core of 70 mm² copper

ZR-YJV 3×150+1×70 mm² — Cable Specification & Engineering Data

1. Overview & Ratings. ZR-YJV 3×150+1×70 is a high-capacity flame-retarding 3+1-core cable: three 150 mm² copper phase conductors and one 70 mm² copper neutral conductor, XLPE insulation and one ST2 PVC jacket, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; manufactured and proof-tested to GB/T 12706.1 / IEC 60502-1, stranding to GB/T 3956, ZC fire class to GB/T 19666. Finished diameter ≈ 42.9 mm, mass ≈ 5326 kg/km (Zhongce 3+1 table), supplied in 100 m coils or wooden drums.

 

2. Construction Stack. Conductor → outer jacket:

Layer Build Wall Diameter
Phase conductor (×3) Annealed Cu, Class 2 compact, 37 × 2.29 mm (1+6+12+18) each — ≈ 16.2 mm
Neutral conductor (×1) Annealed Cu, Class 2 compact, 19 × 2.14 mm (1+6+12) — ≈ 10.7 mm
Phase insulation (×3) XLPE 1.4 mm ≈ 19.0 mm
Neutral insulation (×1) XLPE 1.1 mm ≈ 12.9 mm
Core assembly Central neutral + 3 phase cores around + PP filler + polyester binder — ≈ 37.9 mm (derived)
Outer jacket Flame-retarded PVC, ST2 compound, black 2.5 mm ≈ 42.9 mm (Zhongce)

 

3. Electrical Ratings. Phase R ≤ 0.124 Ω/km (≈ 0.158 Ω/km @ 90 °C), neutral R ≤ 0.268 Ω/km @ 20 °C; factory proof 3.5 kV AC / 5 min; finished-cable insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.35 μF/km; inductance ≈ 0.25 mH/km; AC impedance ≈ 0.15 Ω/km; short-circuit current ≈ 17.3 kA for 1 s. Reference current (3 phase cores loaded) ≈ 440 A in air @ 30 °C / 400 A buried @ 25 °C — Zhongce 3+1 table basis.

 

Electrical Parameters

 

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (phase, per core)

≤ 0.124 Ω/km

GB/T 3956 max, 150 mm²

DC resistance @20 °C (neutral, per core)

≤ 0.268 Ω/km

GB/T 3956 max, 70 mm²

AC resistance @90 °C (est., phase)

≈ 0.161 Ω/km

per core

AC resistance @90 °C (est., neutral)

≈ 0.349 Ω/km

per core

Current rating in air (30 °C, single circuit, 3-core+1)

≈ 300–335 A

based on 150 mm² phase

Current rating in air (design)

≈ 315 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 335–365 A

common catalogue 342–355 A

Design buried rating

≈ 348 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, phase)

≈ 15.0 kA

150 mm² reference

Short-circuit current (1 s, Cu, 250 °C, neutral)

≈ 7.0 kA

70 mm² reference

Frequency

50/60 Hz AC

—

 

4. Cable Parameters & Test Parameters

 

Copper Power Cable 4 Core ZR-YJV 3×150mm2+1×70mm2 For Power System

 

ZR-YJV 3×150+1×70 mm² — Test & Verification Schedule (GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Phase conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.124 Ω/km @ 20 °C (150 mm²) Every production length
Routine Neutral conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.268 Ω/km @ 20 °C (70 mm²) Every production length
Routine Power-frequency withstand GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor to earth/water bath
Routine Dimensional inspection GB/T 2951 Phase ins. ≥ 1.4 mm; neutral ins. ≥ 1.1 mm; sheath ≥ 2.5 mm; OD within tolerance Wall & diameter check
Routine Conductor continuity Visual / electrical All cores continuous, no break Every length
Sample XLPE hot-set test GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking verification
Sample XLPE tensile & elongation GB/T 2951 Tensile ≥ 12.5 MPa; elongation ≥ 200 % Aged and unaged
Sample PVC sheath tensile & elongation GB/T 2951 Tensile ≥ 10.0 MPa; elongation ≥ 125 % Aged and unaged
Sample PVC thermal stability GB/T 2951 (Congo-red) ≥ 200 min @ 200 °C HCI evolution test
Sample Conductor geometry GB/T 3956 Phase: 37 × 2.29 mm Ø ≈ 16.2; neutral: 19 × 2.14 mm Ø ≈ 10.7 Per batch
Type Single-cable flame test GB/T 18380.12 No flame to upper reference mark ZR property
Type Bunched flame test — C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m Class C compliance
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core bending rule
Type Insulation resistance Factory method ≥ 36.7 MΩ·km @ 20 °C Not routine under GB/T 12706.1
Post-install DC withstand commissioning Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown Required for new installations
Post-install Phase identification Visual / continuity L1/L2/L3/N correctly labelled at both ends Before energisation

 

5. Cable Cross Section Structure

 

Copper Power Cable 4 Core ZR-YJV 3×150mm2+1×70mm2 For Power System

 

ZR-YJV 3×150+1×70 mm² — Cross-Section Construction Diagram (Schematic)
Layered 3+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · primary data from Zhongce 3+1 table
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Phase conductor (Cu) × 3 Annealed copper, Class 2 compact strand — 37 wires of 2.29 mm per core (37/2.29, 1+6+12+18 layout), nominal area 150 mm² each — ≈ 16.2 (Ø each phase core) Line-current carrying phase conductors; DC resistance capped at 0.124 Ω/km at 20 °C
2 Neutral conductor (Cu) × 1 Annealed copper, Class 2 compact strand — 19 wires of 2.14 mm (19/2.14, 1+6+12 layout), nominal area 70 mm² — ≈ 10.7 (Ø neutral core) Return / neutral path; DC resistance capped at 0.268 Ω/km at 20 °C
3 Phase insulation (XLPE) × 3 Cross-linked polyethylene dielectric 1.4 ≈ 19.0 (Ø each phase core, incl. insulation) Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min
4 Neutral insulation (XLPE) × 1 Cross-linked polyethylene dielectric 1.1 ≈ 12.9 (Ø neutral core, incl. insulation) Electrical isolation for the neutral conductor
5 Core assembly Neutral core at centre + three phase cores cabled around + PP filler + polyester binder tape — ≈ 37.9 (Ø over assembled cores) 3+1 configuration; derived from Zhongce OD − 2×sheath
6 Outer jacket (PVC) Flame-retardant PVC, ST2 compound, black 2.5 ≈ 42.9 (Ø finished cable, Zhongce) Mechanical and moisture protection; ZC flame retardance per GB/T 19666
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 42.9 mm Zhongce 3+1 unarmored table    
Approximate cable mass ≈ 5326 kg/km Zhongce copper-conductor figure    
Nominal voltage rating 0.6/1 kV AC 50 Hz; maximum system voltage Um = 1.2 kV    
Conductor temperature limits 90 / 250 °C Continuous service / short-circuit (≤ 5 s)    
Minimum bend radius (multi-core) ≥ 15 × OD ≈ 644 mm OD = actual finished cable diameter    
Flame-retardant classification ZC (ZR) — Per GB/T 19666    
Short-circuit current (1 s) ≈ 17.3 kA I = k·A/√t, k=115 for Cu/XLPE (est.)    
AC impedance @ 50 Hz ≈ 0.15 Ω/km √(R² + X²); R-dominant (est.)    
Capacitance (typical) ≤ 0.35 μF/km Per phase core (est.)    
Inductance (typical) ≈ 0.25 mH/km Three-core cable (est.)    
Air ampacity @ 30 °C ≈ 440 A Zhongce basis; Cu, 3 phase loaded    
Buried ampacity @ 25 °C ≈ 400 A Zhongce basis; Cu, 3 phase loaded    
Schematic — not to exact scale. Primary data (OD, weight, ampacity) from Zhongce 3+1 table; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1. Values marked (est.) are engineering estimates.

 

Copper Power Cable 4 Core ZR-YJV 3×150mm2+1×70mm2 For Power System

 

6. Thermal & Fire. 90 °C continuous conductor, 250 °C short-circuit (≤ 5 s); service ambient −20 to +45 °C, minimum laying temp 0 °C; max burial soil temp 25 °C; ZC per GB/T 19666 — GB/T 18380.12 single-cable + GB/T 18380.35 category-C bunched (char ≤ 2.5 m); PVC jacket is halogenated and emits smoke under fire — specify WDZ-YJY for LSZH.

 

Copper Power Cable 4 Core ZR-YJV 3×150mm2+1×70mm2 For Power System

 

7. Installation & Care. Minimum bend ≥ 15 × OD (≈ 644 mm); commissioning DC test 4U0 = 2.4 kV / 15 min before first energisation (Q/GDW 13244.1-2018); warm drums below 0 °C before pulling; max pulling tension ≤ 6000 N; derate the 440/400 A references for ambient, grouping and soil; fit lugs and glands sized for the 16.2 mm phase core, 10.7 mm neutral core and 42.9 mm jacket; verify short-circuit rating against protective device settings.

 

Insulation Test Data — ZR-YJV 3×150+1×70 mm²
ZR-YJV 3×150+1×70 mm²  (Cu / XLPE / FR-PVC)   ·   0.6/1 kV
1.  Cable Identification
Item Description Standard / Note
Designation ZR-YJV 3×150+1×70 mm² GB/T 12706.1-2020
Conductor Bare annealed copper, Class 2 stranded — phase 3×37ר2.03 mm, neutral 1×19ר2.14 mm GB/T 3956 / IEC 60228
Insulation XLPE (cross-linked polyethylene), phase 1.4 mm / neutral 1.0 mm nominal (150 / 70 mm² respectively) GB/T 12706.1-2020
Insulator colours L1/L2/L3 = brown/black/grey (150 mm²); N = blue (70 mm²) IEC 60446
Outer sheath Flame-retardant PVC (ZR grade), 1.6 mm (multi-core, 3+1 rule), Black (standard) GB/T 19666-2019
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Number of cores 4 (3×150 mm² phase + 1×70 mm² neutral, 3+1) —
2.  Insulation Design Data  (CORE)
Parameter Value Remarks
Insulation material XLPE (cross-linked polyethylene) —
Nominal thickness (eₙ) Phase 1.4 mm (150 mm²); Neutral 1.0 mm (70 mm²) two core sizes
Minimum allowable thickness (e_min) Phase 1.12 mm; Neutral 0.80 mm eₙ − 0.28 / eₙ − 0.28 (GB/T 12706.1-2020, Table 3)
Insulator colours L1/L2/L3 = brown/black/grey (150 mm²); N = blue (70 mm²) IEC 60446
Volume resistivity @ 90 °C ≥ 10¹² Ω·cm —
Dielectric loss factor (tan δ) @ 20 °C ≤ 1 × 10⁻³ reference
Relative permittivity (εᵣ) ≈ 2.3 – 2.5 reference
Long-term service temp. 90 °C GB/T 12706.1-2020
Short-circuit temp. (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 – 130 °C transient
Diameter over insulated core Phase 15.8 mm; Neutral 9.8 mm phase 13.0 + 2×1.4 / neutral 7.80 + 2×1.0
3.  Thermal Characteristics
Property Value Remarks
Max. conductor operating temp. (normal) 90 °C long-term
Max. conductor temp. — short-circuit (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) —
Min. installation ambient temp. 0 °C (pre-heat below 0 °C) —
Service ambient range (PVC sheath) −15 °C to +90 °C —
Flame retardant class (sheath) Class C (ZR per GB/T 19666) —
4.  Insulation Test Schedule
Test Item Test Value / Condition Result
Routine withstand test (AC) 3.5 kV AC, 5 min — no breakdown PASS
Type test voltage 4.0 kV AC PASS (IEC 60502-1)
Partial discharge test ≤ 10 pC @ 1.73 U₀ (1.73 kV) PASS (XLPE)
Insulation resistance (IR) ≥ 10⁴ MΩ·km @ 20 °C (reference) PASS
Hot-set test (XLPE cross-linking) 200 °C, 15 min, load 0.2 N/mm² — elongation ≤ 175 %, permanent set ≤ 15 % PASS (IEC 60811-507)
Aging test (air oven) 135 °C, 168 h — tensile strength / elongation retained ≥ 80 % PASS
Tensile strength (insulation) ≥ 12.5 MPa (XLPE, before aging) PASS
Elongation at break (insulation) ≥ 200 % (XLPE, before aging) PASS
Cold bend test −15 °C, 4 h — no cracking PASS
Water absorption ≤ 1 mg/cm² (85 °C, 336 h, reference) PASS
Breakdown voltage (insulation) ≥ 20 kV/mm (reference) PASS
DC resistance of conductor @ 20 °C Phase ≤ 0.124 Ω/km; Neutral ≤ 0.268 Ω/km (Class 2 Cu) PASS (GB/T 3956)
Dielectric loss (tan δ) measurement ≤ 1 × 10⁻³ @ 20 °C PASS (reference)
Spark test (during production) 6 – 10 kV (online), pinhole detection PASS
Thickness measurement (microscopic) Phase eₙ = 1.1 / 1.0 mm; e_min ≥ 1.12 / 0.80 mm PASS
5.  Electrical Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (phase, 150 mm²) ≤ 0.124 Ω/km GB/T 3956 / IEC 60228, Class 2 max
DC resistance @ 20 °C (neutral, 70 mm²) ≤ 0.268 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (phase, est.) ≈ 0.161 Ω/km per phase core
Current rating — in air (30 °C, single circuit) ≈ 400–430 A (design ≈ 410 A) 3+1 core
Current rating — direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) ≈ 485–515 A (design ≈ 500 A) 3+1 core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 15.0 kA (per phase core) reference; neutral ≈ 7.0 kA
Frequency 50/60 Hz AC —
6.  Dimensional / Inspection Result
Item Design / Limit Measured (example)
Conductor construction Phase 3×37ר2.03 mm; Neutral 1×19ר2.14 mm 11.20 / 7.70 mm
Conductor diameter Phase ≈ 13.0 mm; Neutral ≈ 7.80 mm 11.25 / 7.72 mm
Insulation thickness (per core) Phase 1.4 mm / Neutral 1.0 mm (min. 1.12 / 0.80 mm) — all 4 cores 1.13 / 1.11 / 1.10 / 1.02 mm (L1/L2/L3/N)
Diameter over insulated core Phase 15.8 mm; Neutral 9.8 mm 13.65 / 9.75 mm
Sheath thickness 1.6 mm (multi-core, 3+1 rule) (min. 1.3 mm) 1.63 mm
Overall cable diameter 26.0 – 32.0 mm (design ≈ 29.0 mm) 26.2 mm
Approx. weight 1500 – 1900 kg/km (use ≈ 1750/km) ≈ 1520 kg/km
DC resistance @ 20 °C Phase ≤ 0.124 Ω/km; Neutral ≤ 0.268 Ω/km 0.150 / 0.264 Ω/km
50 N/mm² × (3×150 + 1×70) = 26,000 N total 50 N/mm² × (3×150 + 1×70) = 26,000 N total conductor sock
Minimum bending radius: ≥ 15 × OD ≈ 435 mm @ Ø ≈ 29.0 mm (unarmoured, multi-core)
Conduit inner diameter: ≥ 1.5 × OD → use 50 mm or 63 mm conduit (≥ 44 mm clear)
Notes
1. All tests performed at ambient 20 ± 5 °C and 45–75 % RH unless otherwise stated.
2. Routine tests: withstand (3.5 kV / 5 min), conductor resistance, dimensional check. Type tests: 4.0 kV, partial discharge, hot-set, aging, mechanical (per IEC 60502-1).
3. Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.
4. Insulation thickness: phase 150 mm² = 1.4 mm (e_min = 1.4 − 0.28 = 1.12 mm); neutral 70 mm² = 1.0 mm (e_min = 1.0 − 0.20 = 0.80 mm) (GB/T 12706.1-2020, Table 3).
5. 3×150+1×70 mm² = three 150 mm² phase cores (L1+L2+L3) + one 70 mm² neutral (N), total 4 cores (3+1); neutral is reduced. Four thickness readings (L1/L2/L3/N) are recorded at inspection.
6. For low-smoke halogen-free → WDZ-YJY 3×150+1×70; for fire-survival → NH-ZR-YJV / WDZN-YJY 3×150+1×70; for armoured → ZR-YJV22 3×150+1×70; for separate PE → 5-core cable.

 

8. Application. Heavy three-phase four-wire distribution, transformer secondaries, large building mains and industrial feeders requiring a dedicated neutral conductor in a single cable (TN-C style) — conduit, tray, trench, duct, trunking, direct burial; indoor or sheltered outdoor.

 