3×120mm2+1×70mm2 4 Cores Cable Power Distribution Flame Retardant XLPE Insulated Copper

3×120mm2+1×70mm2 4 Cores Cable Power Distribution Flame Retardant XLPE Insulated Copper

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZR-YJV 3×120mm²+1×70mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

Power Distribution Cable ZR-YJV 3×120mm²+1×70mm², Flame Retardant XLPE Insulated Copper Wire Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer ...

Product Details

Highlight:

IEC 60228 4 Cores Cable

,

annealed copper 4 Cores Cable

,

Power Distribution Cable Insulated

Phase conductor (×3):
Bare Annealed Copper, Class 2 Stranded, 37×∅2.03 Mm, Conductor Ø ≈ 14.2–15.0 Mm Depending On Compaction
Neutral conductor (×1):
Bare Annealed Copper, Class 2 Stranded, 19×∅2.14 Mm, Conductor Ø ≈ 10.7–11.2 Mm Depending On Compaction
Phase conductor nominal area:
120 Mm²
Neutral conductor nominal area:
70 Mm²
Number of cores:
4 (3+1)
Phase conductor construction:
Class 2, 37×∅2.03 Mm,IEC 60228 / GB/T 3956
Neutral conductor construction:
Class 2, 19×∅2.14 Mm,IEC 60228 / GB/T 3956
Phase conductor diameter (approx.):
14.2–15.0 Mm
Neutral conductor diameter (approx.):
10.7–11.2 Mm
Insulation (×4):
XLPE
Phase insulation thickness:
1.2 Mm (120 Mm² Class)
Neutral insulation thickness:
1.1 Mm (70 Mm² Class)
Diameter over phase insulated core:
16.6–17.4 Mm
Diameter over neutral insulated core:
12.9–13.4 Mm
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.8 Mm (GB/T 12706 Multi-core 95–150 Mm² Range)
Overall cable diameter:
31.0 – 37.0 Mm
Design outer diameter:
≈ 33.5 Mm
Approx. weight:
1550 – 1950 Kg/km
Design weight:
≈ 1710 Kg/km
Cable shape:
Round

Product Description

Power Distribution Cable ZR-YJV 3×120mm²+1×70mm², Flame Retardant XLPE Insulated Copper Wire

 

Cable Designation & Meaning

 

Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

3×120+1×70 mm²

Three phase cores of 120 mm² copper + one reduced neutral core of 70 mm² copper

ZR-YJV 3×120 mm²+1×70 mm² — Cable Specification & Engineering Data

1. Overview & Ratings. ZR-YJV 3×120+1×70 is a large-section flame-retarding 3+1-core cable: three 120 mm² copper phase conductors and one 70 mm² copper neutral conductor, XLPE insulation and one ST2 PVC jacket, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; manufactured and proof-tested to GB/T 12706.1 / IEC 60502-1, stranding to GB/T 3956, ZC fire class to GB/T 19666. Finished diameter ≈ 39.7 mm, mass ≈ 4443 kg/km (Zhongce 3+1 table), supplied in 100 m coils or wooden drums.

 

2. Construction Stack. Conductor → outer jacket:

Layer Build Wall Diameter
Phase conductor (×3) Annealed Cu, Class 2 compact, 37 × 2.06 mm (1+6+12+18) each — ≈ 14.4 mm
Neutral conductor (×1) Annealed Cu, Class 2 compact, 19 × 2.14 mm (1+6+12) — ≈ 10.7 mm
Phase insulation (×3) XLPE 1.2 mm ≈ 16.8 mm
Neutral insulation (×1) XLPE 1.1 mm ≈ 12.9 mm
Core assembly Central neutral + 3 phase cores around + PP filler + polyester binder — ≈ 34.7 mm (derived)
Outer jacket Flame-retarded PVC, ST2 compound, black 2.5 mm ≈ 39.7 mm (Zhongce)

 

3×120mm2+1×70mm2 4 Cores Cable Power Distribution Flame Retardant XLPE Insulated Copper

 

3. Electrical Ratings. Phase R ≤ 0.153 Ω/km, neutral R ≤ 0.268 Ω/km @ 20 °C; factory proof 3.5 kV AC / 5 min; finished-cable insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.36 μF/km; inductance ≈ 0.25 mH/km; AC impedance ≈ 0.16 Ω/km; short-circuit current ≈ 13.8 kA for 1 s. Reference current (3 phase cores loaded) ≈ 380 A in air @ 30 °C / 360 A buried @ 25 °C — Zhongce 3+1 table basis.

 

Electrical Parameters

 

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (phase, per core)

≤ 0.153 Ω/km

GB/T 3956 max, 120 mm²

DC resistance @20 °C (neutral, per core)

≤ 0.268 Ω/km

GB/T 3956 max, 70 mm²

AC resistance @90 °C (est., phase)

≈ 0.199 Ω/km

per core

AC resistance @90 °C (est., neutral)

≈ 0.349 Ω/km

per core

Current rating in air (30 °C, single circuit, 3-core+1)

≈ 260–290 A

based on 120 mm² phase

Current rating in air (design)

≈ 272 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 290–320 A

common catalogue 298–310 A

Design buried rating

≈ 304 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, phase)

≈ 12.0 kA

120 mm² reference

Short-circuit current (1 s, Cu, 250 °C, neutral)

≈ 7.0 kA

70 mm² reference

Frequency

50/60 Hz AC

—

 

4.Cable Parameters & Test Parameters

 

3×120mm2+1×70mm2 4 Cores Cable Power Distribution Flame Retardant XLPE Insulated Copper

 

ZR-YJV 3×120+1×70 mm² — Test & Verification Schedule (GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Phase conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.153 Ω/km @ 20 °C (120 mm²) Every production length
Routine Neutral conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.268 Ω/km @ 20 °C (70 mm²) Every production length
Routine Power-frequency withstand GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor to earth/water bath
Routine Dimensional inspection GB/T 2951 Phase ins. ≥ 1.2 mm; neutral ins. ≥ 1.1 mm; sheath ≥ 2.5 mm; OD within tolerance Wall & diameter check
Routine Conductor continuity Visual / electrical All cores continuous, no break Every length
Sample XLPE hot-set test GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking verification
Sample XLPE tensile & elongation GB/T 2951 Tensile ≥ 12.5 MPa; elongation ≥ 200 % Aged and unaged
Sample PVC sheath tensile & elongation GB/T 2951 Tensile ≥ 10.0 MPa; elongation ≥ 125 % Aged and unaged
Sample PVC thermal stability GB/T 2951 (Congo-red) ≥ 200 min @ 200 °C HCI evolution test
Sample Conductor geometry GB/T 3956 Phase: 37 × 2.06 mm Ø ≈ 14.4; neutral: 19 × 2.14 mm Ø ≈ 10.7 Per batch
Type Single-cable flame test GB/T 18380.12 No flame to upper reference mark ZR property
Type Bunched flame test — C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m Class C compliance
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core bending rule
Type Insulation resistance Factory method ≥ 36.7 MΩ·km @ 20 °C Not routine under GB/T 12706.1
Post-install DC withstand commissioning Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown Required for new installations
Post-install Phase identification Visual / continuity L1/L2/L3/N correctly labelled at both ends Before energisation

 

5. Cable Cross Section Structure

 

3×120mm2+1×70mm2 4 Cores Cable Power Distribution Flame Retardant XLPE Insulated Copper

 

ZR-YJV 3×120+1×70 mm² — Cross-Section Construction Diagram (Schematic)
Layered 3+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · primary data from Zhongce 3+1 table
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Phase conductor (Cu) × 3 Annealed copper, Class 2 compact strand — 37 wires of 2.06 mm per core (37/2.06, 1+6+12+18 layout), nominal area 120 mm² each — ≈ 14.4 (Ø each phase core) Line-current carrying phase conductors; DC resistance capped at 0.153 Ω/km at 20 °C
2 Neutral conductor (Cu) × 1 Annealed copper, Class 2 compact strand — 19 wires of 2.14 mm (19/2.14, 1+6+12 layout), nominal area 70 mm² — ≈ 10.7 (Ø neutral core) Return / neutral path; DC resistance capped at 0.268 Ω/km at 20 °C
3 Phase insulation (XLPE) × 3 Cross-linked polyethylene dielectric 1.2 ≈ 16.8 (Ø each phase core, incl. insulation) Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min
4 Neutral insulation (XLPE) × 1 Cross-linked polyethylene dielectric 1.1 ≈ 12.9 (Ø neutral core, incl. insulation) Electrical isolation for the neutral conductor
5 Core assembly Neutral core at centre + three phase cores cabled around + PP filler + polyester binder tape — ≈ 34.7 (Ø over assembled cores) 3+1 configuration; derived from Zhongce OD − 2×sheath
6 Outer jacket (PVC) Flame-retardant PVC, ST2 compound, black 2.5 ≈ 39.7 (Ø finished cable, Zhongce) Mechanical and moisture protection; ZC flame retardance per GB/T 19666
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 39.7 mm Zhongce 3+1 unarmored table    
Approximate cable mass ≈ 4443 kg/km Zhongce copper-conductor figure    
Nominal voltage rating 0.6/1 kV AC 50 Hz; maximum system voltage Um = 1.2 kV    
Conductor temperature limits 90 / 250 °C Continuous service / short-circuit (≤ 5 s)    
Minimum bend radius (multi-core) ≥ 15 × OD ≈ 596 mm OD = actual finished cable diameter    
Flame-retardant classification ZC (ZR) — Per GB/T 19666    
Short-circuit current (1 s) ≈ 13.8 kA I = k·A/√t, k=115 for Cu/XLPE (est.)    
AC impedance @ 50 Hz ≈ 0.16 Ω/km √(R² + X²); R-dominant (est.)    
Capacitance (typical) ≤ 0.36 μF/km Per phase core (est.)    
Inductance (typical) ≈ 0.25 mH/km Three-core cable (est.)    
Air ampacity @ 30 °C ≈ 380 A Zhongce basis; Cu, 3 phase loaded    
Buried ampacity @ 25 °C ≈ 360 A Zhongce basis; Cu, 3 phase loaded    
Schematic — not to exact scale. Primary data (OD, weight, ampacity) from Zhongce 3+1 table; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1. Values marked (est.) are engineering estimates.

 

3×120mm2+1×70mm2 4 Cores Cable Power Distribution Flame Retardant XLPE Insulated Copper

 

6. Thermal & Fire. 90 °C continuous conductor, 250 °C short-circuit (≤ 5 s); service ambient −20 to +45 °C, minimum laying temp 0 °C; max burial soil temp 25 °C; ZC per GB/T 19666 — GB/T 18380.12 single-cable + GB/T 18380.35 category-C bunched (char ≤ 2.5 m); PVC jacket is halogenated and emits smoke under fire — specify WDZ-YJY for LSZH.

 

Flame-Retardant (FR) Characteristics — ZR-YJV 3×120+1×70 mm²
ZR-YJV 3×120+1×70 mm²  (3 (L1+L2+L3, 120 mm²) + 1 (N, 70 mm²); 3+1 = L1+L2+L3+N)   ·   0.6/1 kV
1.  Cable Identification
Code / Item Meaning / Value Standard / Note
Designation ZR-YJV 3×120+1×70 mm² GB/T 12706.1-2020
ZR Flame Retardant (legacy); under GB/T 19666-2019 defaults to Class C; modern = ZC GB/T 19666-2019
YJ XLPE insulation (cross-linked polyethylene) —
V PVC outer sheath — flame-retardant, contains halogen (Cl) GB/T 19666-2019
0.6/1 kV U₀/U = 600/1000 V; Uₘ = 1.2 kV IEC 60502-1
3×120+1×70 mm² Three 120 mm² phase cores + one 70 mm² neutral core (reduced neutral, 3+1 construction) —
Construction Unarmoured, non-screened, round multi-core (3+1) —
Application note 3+1 core → three-phase AC with neutral (L1+L2+L3+N); neutral reduced to 70 mm². No separate PE (use 4-core or 5-core if PE required). —
2.  Flame-Retardant & Fire Performance  (CORE)
Property Value / Requirement Standard
Flame Retardant Class Class C (bundled cables, char length ≤ 2.5 m) GB/T 19666-2019; GB/T 18380.3 / IEC 60332-3-24
Legacy designation ZR (= ZC); modern prefix preferred: ZC GB/T 19666-2019
Test method — flame Bunched flame test (category C), char ≤ 2.5 m after flame removal GB/T 18380.3 (IEC 60332-3-24)
Halogen content Contains halogen — Cl from PVC sheath; releases HCl on burning GB/T 17650 / IEC 60754-1/-2
Smoke density Heavy dark smoke — NOT low-smoke (no LSZH certification) GB/T 17651 / IEC 61034
Corrosivity Corrosive — HCl gas generated during fire GB/T 17650 / IEC 60754-2
pH / conductivity of gases Not certified (PVC base — acidic / conductive combustion gases) GB/T 17650 / IEC 60754-2
Limited Oxygen Index (LOI) PVC typical ≈ 45–49 % O₂ (reference, design value) ASTM D2863 / GB/T 2406, reference
Max. conductor operating temp. 90 °C (long-term service) GB/T 12706.1-2020
Max. short-circuit temp. (≤5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) IEC 60502-1
Service ambient range (PVC sheath) −15 °C to +90 °C —
Min. installation ambient temp. 0 °C (pre-heat required below 0 °C) —
3.  Fire Test Summary
Test Requirement ZR-YJV 3×120+1×70 mm² Verdict
Bunched flame test (Class C) Char length ≤ 2.5 m PASS (design, Class C)
Single flame test (IEC 60332-1) Self-extinguishing PASS (XLPE/PVC FR)
Smoke density (IEC 61034) Light transmittance ≥ 60 % for LSZH N/A (PVC = heavy smoke)
Halogen content (IEC 60754) ≤ 0.5 % HCl for LSZH N/A (contains Cl)
Acidity / corrosivity (IEC 60754-2) pH ≥ 4.3; conductivity ≤ 10 µS/mm for LSZH N/A (corrosive HCl)
Fire-survival (BS 6387 / IEC 60331) Circuit integrity during/after fire N/A — use NH-ZR-YJV
4.  Key Electrical & Thermal Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (phase, 120 mm²) ≤ 0.153 Ω/km GB/T 3956 / IEC 60228, Class 2 max
DC resistance @ 20 °C (neutral, 70 mm²) ≤ 0.268 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (phase, est.) ≈ 0.251 Ω/km per phase core
Current rating — in air (30 °C, single circuit) ≈ 235–255 A (design ≈ 340 A) 3+1 core
Current rating — direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) ≈ 275–310 A (design ≈ 340 A) 3+1 core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 12.0 kA (per phase core) phase core; neutral ≈ 7.0 kA
5.  Construction & Material Specification (with FR Contribution)
Layer (inside → out) Description / Specification FR Contribution
Conductor (phase ×3) Bare annealed copper, Class 2 stranded, 19ר2.78 mm, Ø ≈ 11.30 mm None (Cu non-combustible)
Conductor (neutral ×1) Bare annealed copper, Class 2 stranded, 19ר2.14 mm, Ø ≈ 7.80 mm None (Cu non-combustible)
Conductor screen Omitted (not required for 0.6/1 kV) —
Insulation (×4) XLPE, phase 1.2 mm (e_min 0.98) / neutral 1.0 mm (e_min 0.80); L1/L2/L3 = brown/black/grey, N = blue XLPE — low flame spread
Filler Flame-retardant PP / PE to form round assembly FR additive
Binder Flame-retardant tape over laid-up cores FR barrier
Inner binder / assembly FR tape, no inner sheath required for plain YJV FR barrier
Outer sheath Flame-retardant PVC (ZR grade), 1.6 mm (multi-core, 3+1 rule), Black (standard) Primary FR layer (halogenated)
Armour None —
Metallic screen None —
6.  Dimensional Data
Item Typical Value Remarks
Conductor nominal area 3×120 mm² + 1×70 mm² phase / neutral
Number of cores 4 (3+1) —
Conductor construction Phase: Class 2, 19ר2.78 mm; Neutral: Class 2, 19ר2.14 mm min. 19 wires (≥70 mm²)
Conductor diameter (approx.) Phase ≈ 11.30 mm; Neutral ≈ 7.80 mm —
Insulation thickness Phase: 1.2 mm; Neutral: 1.0 mm (120 / 70 mm² classes) 1.2 / 1.0 mm class
Diameter over insulated core Phase 13.7 mm; Neutral 9.8 mm conductor + 2×insulation
Sheath thickness 1.6 mm (multi-core, 3+1 rule) 3+1 multi-core rule
Overall cable diameter 24.0 – 29.5 mm (design ≈ 26.5 mm) design ≈ 26.5 mm
Approx. weight 1350 – 1700 kg/km (use ≈ 1550/km) —
Cable shape Round —
7.  Mechanical & Installation Parameters
Parameter Value Note
≥ 15 × OD ≈ 398 mm @ Ø ≈ 26.5 mm ≥ 15 × OD ≈ 398 mm @ Ø ≈ 26.5 mm —
50 N/mm² × (3×120 + 1×70) = 21,500 N total 50 N/mm² × (3×120 + 1×70) = 21,500 N total use conductor sock, avoid sheath grip
Direct burial Allowed in non-aggressive soil; for mechanical protection use ZR-YJV22 3×120+1×70 —
≥ 1.5 × OD → ≥ 40 mm (use 50 mm or 63 mm conduit) ≥ 1.5 × OD → ≥ 40 mm (use 50 mm or 63 mm conduit) —
Fixing (horizontal / vertical tray) ≈ 800 mm / ≈ 1500 mm horizontal / vertical
Elevation difference limit None (XLPE) —
8.  Selection Guide — When FR Matters
Scenario Recommended Cable Reason
Flame-retardant, halogenated acceptable (standard) ZR-YJV 3×120+1×70 mm² (this cable) Class C FR, PVC sheath, cost-effective
Low-smoke halogen-free required (LSZH) WDZ-YJY 3×120+1×70 LSZH sheath — IEC 61034 / IEC 60754 compliant
Fire-survival circuit (circuit integrity) NH-ZR-YJV / WDZN-YJY 3×120+1×70 BS 6387 / IEC 60331 fire-survival grade
Heavy mechanical load / direct burial ZR-YJV22 3×120+1×70 Steel tape armour for impact / road crossing
Separate PE + N required 5-core cable (e.g. 5×50 or 4×120+1×70) 3+1 has no separate PE
Notes
1. ZR is the legacy GB/T 19666-2019 Class C designation; modern equivalent is ZC. Class C: char ≤ 2.5 m after bunched flame test (GB/T 18380.3).
2. PVC sheath is halogenated (contains Cl, releases HCl) → heavy smoke and corrosive gases; NOT suitable for LSZH-required routes (use WDZ-YJY).
3. 3×120+1×70 mm² = three 120 mm² phase cores (L1+L2+L3) + one 70 mm² neutral (N), total 4 cores (3+1); neutral is reduced in size. Current ratings (≈ 435 A air / ≈ 435 A buried) are design values; apply grouping, ambient temperature, soil thermal resistivity and IEC 60364-5-52 correction factors.
4. For LSZH → WDZ-YJY 3×120+1×70; for fire-survival → NH-ZR-YJV / WDZN-YJY 3×120+1×70; for armour → ZR-YJV22 3×120+1×70; for separate PE → use 5-core.
5. DC resistance phase ≤ 0.153 Ω/km, neutral ≤ 0.268 Ω/km (GB/T 3956 Class 2 max). Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.

 

7. Installation & Care. Minimum bend ≥ 15 × OD (≈ 596 mm); commissioning DC test 4U0 = 2.4 kV / 15 min before first energisation (Q/GDW 13244.1-2018); warm drums below 0 °C before pulling; max pulling tension ≤ 5000 N; derate the 380/360 A references for ambient, grouping and soil; fit lugs and glands sized for the 14.4 mm phase core, 10.7 mm neutral core and 39.7 mm jacket; verify short-circuit rating against protective device settings.

 

3×120mm2+1×70mm2 4 Cores Cable Power Distribution Flame Retardant XLPE Insulated Copper

 

8. Application. Heavy three-phase four-wire distribution, transformer secondaries, large building mains and industrial feeders requiring a dedicated neutral conductor in a single cable (TN-C style) — conduit, tray, trench, duct, trunking, direct burial; indoor or sheltered outdoor.