Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring

Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZR-YJV 3×95mm²+1×50mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring Cable Designation & Meaning Code Meaning ZC Flame retardant Class C YJ Cross-linked polyethylene (XLPE) insulation V Polyvinyl chloride (PVC) sheath 3×95 mm² + 1×50 mm² Three phase cores of 95 mm² + one neutral ...

Product Details

Highlight:

xlpe cable zr-yjv

,

copper xlpe cable

,

copper 4 cores cable

Phase conductor (×3):
Bare Annealed Copper, Class 2 Stranded, 19×∅2.52 Mm, Conductor Ø ≈ 12.6–13.2 Mm Depending On Compaction
Neutral conductor (×1):
Bare Annealed Copper, Class 2 Stranded, 19×∅1.78 Mm (also 7×∅3.00 Mm Compact), Conductor Ø ≈ 9.0–9.5 Mm Depending On Compaction
Phase conductor nominal area:
95 Mm²
Neutral conductor nominal area:
50 Mm²
Number of cores:
4 (3+1)
Phase conductor construction:
Class 2, 19×∅2.52 Mm,IEC 60228 / GB/T 3956
Neutral conductor construction:
Class 2, 19×∅1.78 Mm,IEC 60228 / GB/T 3956
Phase conductor diameter (approx.):
12.6–13.2 Mm
Neutral conductor diameter (approx.):
9.0–9.5 Mm
Insulation (×4):
XLPE
Phase insulation thickness:
1.1 Mm (95 Mm² Class)
Neutral insulation thickness:
1.0 Mm (50 Mm² Class)
Diameter over phase insulated core:
14.8–15.4 Mm
Diameter over neutral insulated core:
11.0–11.5 Mm
Filler / binder:
FR PP Filler + FR Tape
Sheath thickness:
1.8 Mm
Overall cable diameter:
27.5 – 33.0 Mm
Design outer diameter:
≈ 30.0 Mm
Approx. weight:
1250 – 1550 Kg/km
Design weight:
≈ 1370 Kg/km
Cable shape:
Round

Product Description

Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring

Cable Designation & Meaning

Code

Meaning

ZC

Flame retardant Class C 

YJ

Cross-linked polyethylene (XLPE) insulation 

V

Polyvinyl chloride (PVC) sheath

3×95 mm² + 1×50 mm²

Three phase cores of 95 mm² + one neutral core of 50 mm² copper conductor


Construction: Three 95 mm² copper conductors (phase) + one 50 mm² copper conductor (neutral), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).




Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring


ZC-YJV 3×95+1×50 mm² — LV Flame-Retardant 3+1 Power Cable — Specification

1. Overview & Ratings. ZC-YJV 3×95+1×50 is a 3+1 LV sub-main equipment feeder cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C PVC sheath: three 95 mm² compacted copper phase cores plus a reduced 50 mm² neutral, dry-cured XLPE, unarmored. OD ≈ 28 mm, ≈ 3200 kg/km (est.), ≈ 200 A per phase free air at 30 °C (est.). Scope: building sub-mains, machine tools, HVAC chillers/compressors, pump stations and light-industry branches — not 950°C fire duty.


2. Construction Stack (Inner → Outer, expanded).


Layer / Feature Build Function
Phase conductors L1/L2/L3 3×95 compacted Cu, Class 2, ≈19 strands R ≤0.206 Ω/km
Neutral N 1×50 compacted Cu, Class 2, ≈19 strands R ≤0.387 Ω/km
Strand compaction Concentric layers rolled compact per core Compact round bundle, clean lugs
XLPE phase insulation Dry-cured PE, ≈2.0 mm Uniform 90°C dielectric
XLPE neutral insulation Dry-cured PE, ≈1.8 mm Matched to neutral voltage class
3+1 core laying Three phases around the center neutral Round finished bundle
PVC ZC sheath Class C, ≈2.0 mm overall Self-extinguishes, prints clear


3. Electrical Characteristics. Phase R ≤ 0.206 Ω/km, neutral R ≤ 0.387 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 200 A per phase (est., air 30 °C); short-circuit ≈ 11 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.

Insulation & Sheath Data

Property

Value

Insulation material

XLPE (cross-linked polyethylene)

Outer sheath material

PVC (ST₂)

Long-term service temp.

90 °C (continuous)

Max. conductor temp. (normal)

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Test voltage AC (5 min)

3.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹⁴ Ω·cm

Shield

None as standard (can be added)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage

1.2 kV AC

—

Test voltage AC (5 min)

3.5 kV

Routine test

DC resistance @20 °C (phase)

≤ 0.193 Ω/km per core

GB/T 3956 Class 2 Cu max (95 mm²)

DC resistance @20 °C (neutral)

≤ 0.387 Ω/km per core

GB/T 3956 Class 2 Cu max (50 mm²)

AC resistance @90 °C (est., phase)

≈ 0.247 Ω/km per core

—

AC resistance @90 °C (est., neutral)

≈ 0.496 Ω/km per core

—

Current rating in air (30 °C)

3-phase: 245 A​

3×95+1×50, touching, in free air

Current rating in tray (30 °C)

3-phase: 270 A​

3×95+1×50, spaced 2×OD

Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W)

3-phase: 255 A​

direct buried

Current rating in conduit (30 °C)

3-phase: 220 A​

—

Short-circuit current (1 s, Cu, 250 °C, phase)

≈ 10.5 kA (10,450 A) per core

—

Short-circuit current (1 s, Cu, 250 °C, neutral)

≈ 5.5 kA (5,500 A) per core

—

Capacitance (core-to-sheath, approx.)

≈ 0.22 µF/km

XLPE

Inductive reactance (approx.)

≈ 0.08 Ω/km

at 50 Hz

Frequency

50/60 Hz AC

—


Reference values: 3×95+1×50 at 245 A three-phase, 400 V → max load ≈ 147 kW​ (cos φ = 0.8). Suitable for large three-phase distribution with reduced neutral, industrial motors, and building sub-main feeders.


4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; survives equipment start-stop cycling; indoor preferred, UV jacket optional.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Min. installation ambient temp.

0 °C (below 0 °C requires preheating)

Service ambient range

−20 °C to +90 °C

Flexing temp. range

0 °C to +90 °C

Fire Performance (ZC-YJV — Flame Retardant C)

Property

Value / Requirement

Flame retardant

GB/T 18380.12 / IEC 60332-1-2​ (single cable, self-extinguishing)

Flame retardant class

Class C​ (ZC) per GB/T 19666

Halogen content

Contains halogen (PVC sheath)

Smoke density

Not low-smoke (PVC)

Corrosivity

Corrosive (PVC)

Toxicity

Toxic fumes when burned (PVC)

EMI shielding

None (no metallic screen/armour)


5. Installation Practice & Handling. Hydraulic crimp 95 mm² phase lugs and a 50 mm² neutral lug, glands to ≈28 mm OD, torque per table; bend ≥ 15×OD ≈ 420 mm; apply conduit/tray derating; keep the bundle round; verify three-phase continuity, phase sequence, neutral and insulation before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 480 mm at Ø32.0 mm

four-core unarmoured

Max. pulling tension (phase)

1,425 N per core (95 mm² × 15 N/mm²)

Cu conductor limit

Max. pulling tension (neutral)

750 N per core (50 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Suitable (with sand bedding)

—

Surface mounting

Heavy-duty cable tray, ladder, cleats

—

Conduit ID

≥ 65 mm

—

Fixing

heavy-duty cleats, cable ties

—

Impact resistance

Moderate

—

Water resistance

Good (PVC sheath)

—

UV resistance

Fair (PVC degrades outdoors, use UV-resistant PVC or conduit)

—

Flex life

Good (Class 2 stranded)

fixed installation

Termination note

Standard compression lugs or mechanical connectors

—


6. Typical Service Applications. Building sub-mains, machine tools, HVAC chillers and compressors, pump stations, and commercial light-industry branch circuits.

Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring


7. Testing & QA Regime (16 items). Routine: phase and neutral DC resistance, 3.5 kV withstand, insulation resistance, continuity, phase/neutral insulation thickness, sheath thickness, dimensional check, strand construction, eccentricity, print legibility, mass, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.


Cable Parameters


ZR-YJV 3×95+1×50 mm² — Flame-Retardant 3+1-Core Power Cable (0.6/1 kV) · Comprehensive Parameter Sheet
Copper conductor · XLPE insulation · PVC sheath · 3 phase cores @ 95 mm² + 1 neutral core @ 50 mm² · conforms to GB/T 12706.1, IEC 60502-1, GB/T 3956, GB/T 19666 · primary data from Zhongce 3+1 table
Code Parameter Value Unit Remarks
01 · Identification
Ref: GB/T 12706.1 / IEC 60502-1; fire class GB/T 19666; Um = 1.2 kV; 50 Hz
1-A Product designation Copper-conductor XLPE-insulated PVC-sheathed flame-retardant power cable, 3+1 core — ZR-YJV series; PVC sheath contains halogen
1-B Type reference ZR-YJV 3×95+1×50 — Three 95 mm² phase cores + one 50 mm² neutral core
1-C Applicable standards GB/T 12706.1; IEC 60502-1 — Conductor per GB/T 3956
1-D Voltage rating U0/U 0.6/1 kV Highest voltage for equipment Um = 1.2 kV; AC 50 Hz
1-E Core layout Three phase cores (L1/L2/L3) surrounding a central neutral core (N) — Three-phase four-wire (TN-C) configuration
1-F Nominal conductor areas 3 × 95 (phase) + 1 × 50 (neutral) mm² Phase cores carry line current; neutral per GB/T 12706.1
1-G Fire performance level Class C (ZC) — standard for "ZR" marking — ZA/ZB available on request
1-H Dielectric system XLPE insulation / PVC sheath (ST2) — 90 °C XLPE class; flame-retarded PVC jacket
02 · Conductor
Ref: GB/T 3956 / IEC 60228 Class 2 — phase 95 mm² = 19 wires; neutral 50 mm² = 7 wires
2-A Conductor material Annealed electrolytic copper (high conductivity) — ≥ 97% IACS conductivity
2-B Stranding class Class 2 (compact stranded) — GB/T 3956 / IEC 60228
2-C Phase stranding (×3) 19 × 2.52 mm (19/2.52) each — 1+6+12 concentric rings; nominal 95 mm²
2-D Neutral stranding (×1) 7 × 3.00 mm (7/3.00) — 1+6 concentric rings; nominal 50 mm²
2-E Phase conductor diameter ≈ 12.6 mm Per phase core (19 × 2.52)
2-F Neutral conductor diameter ≈ 9.0 mm Neutral core (7 × 3.00)
2-G Phase DC resistance @ 20 °C 0.193 Ω/km GB/T 3956 Class 2 Cu (95 mm²)
2-H Neutral DC resistance @ 20 °C 0.387 Ω/km GB/T 3956 Class 2 Cu (50 mm²)
2-I Phase conductor mass ≈ 845 kg/km per core 95 mm² × 8.89 g/cm³ (est.)
2-J Neutral conductor mass ≈ 445 kg/km 50 mm² × 8.89 g/cm³ (est.)
03 · Insulation
Ref: Zhongce 3+1 table — phase 1.1 mm (95 mm²); neutral 1.0 mm (50 mm²)
3-A Dielectric material Cross-linked polyethylene (XLPE) — Chemically cross-linked during extrusion
3-B Phase insulation thickness 1.1 mm Zhongce 3+1 table for 95 mm²
3-C Neutral insulation thickness 1.0 mm Zhongce 3+1 table for 50 mm²
3-D Diameter over phase insulation ≈ 14.8 mm Per phase core (calculated)
3-E Diameter over neutral insulation ≈ 11.0 mm Neutral core (calculated)
3-F Insulation mass (total) ≈ 275 kg/km 3 phase + 1 neutral, density 0.92 g/cm³ (est.)
3-G XLPE tensile strength ≥ 12.5 MPa GB/T 12706.1 / GB/T 2951
3-H XLPE elongation at break ≥ 200 % GB/T 12706.1 / GB/T 2951
04 · Assembly
Ref: 3+1 cabling — neutral at centre, three phase cores around; round bundle
4-A Lay-up configuration Central neutral core + three phase cores in triangular ring + non-hygroscopic filler + binder tape — Forms round, stable cable bundle
4-B Filler material Polypropylene (PP) rope / non-hygroscopic filler — Maintains roundness; water-resistant
4-C Binder tape Polyester tape, single helical wrap — Secures cores during sheathing
4-D Lay ratio (typical) 12 : 1 to 16 : 1 — Cabling pitch / assembly diameter
4-E Diameter over cabled assembly ≈ 29.8 mm Derived: Zhongce Ø 34.8 − 2 × 2.5 sheath
05 · Sheath
Ref: Zhongce 3+1 table (Ø 34.8; 3718 kg/km; sheath 2.5 mm)
5-A Jacket material Flame-retardant PVC, ST2 compound — Black standard; other colours on request
5-B Nominal sheath thickness 2.5 mm Zhongce 3+1 table
5-C Overall finished diameter ≈ 34.8 mm Zhongce 3+1 unarmored table
5-D Approximate cable mass ≈ 3718 kg/km Zhongce copper-conductor figure
5-E Sheath colour Black (standard) — Custom colours available
5-F PVC tensile strength ≥ 10.0 MPa GB/T 12706.1 / GB/T 2951
5-G PVC elongation at break ≥ 125 % GB/T 12706.1 / GB/T 2951
5-H PVC thermal stability ≥ 200 min 200 °C Congo-red test (GB/T 2951)
06 · Electrical
Ref: Zhongce 3+1 table (air 320 / buried 315 A Cu @ 25–30 °C)
6-A Phase conductor DC resistance 0.193 Ω/km GB/T 3956 @ 20 °C, each phase
6-B Neutral conductor DC resistance 0.387 Ω/km GB/T 3956 @ 20 °C, neutral
6-C Routine voltage proof 3.5 kV AC / 5 min — No breakdown; 50 Hz sine wave
6-D Insulation resistance (finished) ≥ 36.7 MΩ·km @ 20 °C on completed cable
6-E XLPE volume resistivity ≥ 1 × 10¹² Ω·cm Material-level property
6-F Capacitance (typical) ≤ 0.38 μF/km Per phase core to earth/neutral (est.)
6-G Inductance (typical) ≈ 0.26 mH/km Three-core cable, 50 Hz (est.)
6-H AC impedance @ 50 Hz ≈ 0.20 Ω/km √(R² + X²); R-dominant (est.)
6-I Short-circuit current (1 s) ≈ 10.9 kA I = k·A/√t, k=115 for Cu/XLPE (est.)
6-J Buried ampacity @ 25 °C ≈ 315 A Zhongce basis; Cu, 3 phase loaded
6-K Air ampacity @ 30 °C ≈ 320 A Zhongce basis; Cu, 3 phase loaded
6-L Earth-fault loop impedance Per project calculation — Depends on cable length & upstream system
07 · Thermal
Ref: XLPE class per GB/T 12706.1 / IEC 60502-1
7-A Continuous conductor temperature 90 °C XLPE insulation class rating
7-B Short-circuit temperature (≤ 5 s) 250 °C GB/T 12706.1 / IEC 60502-1
7-C Ambient operating range -20 to +45 °C Per manufacturer datasheet family
7-D Minimum installation temperature 0 °C Pre-heat drums if colder than 0 °C
7-E Maximum soil temperature (direct burial) 25 °C Reference for buried ampacity
7-F Thermal resistance (insulation+sheath) ≈ 3.2 K·m/W Typical for XLPE/PVC 0.6/1 kV (est.)
08 · Fire (ZR)
Ref: GB/T 19666; GB/T 18380.12; GB/T 18380.35 (20 min, ≥ 1.5 L/m)
8-A Flame-retardant grade Class C (ZC) — default for "ZR" — PVC sheath is halogen-containing
8-B Single-cable vertical flame test Compliant — Method per GB/T 18380.12
8-C Bunched-cable flame test — C Char height ≤ 2.5 m — Method per GB/T 18380.35
8-D Halogen status Halogenated (not LSZH) — Use WDZ-YJY for low-smoke zero-halogen
8-E Smoke density (PVC) Higher than LSZH — PVC emits smoke under fire
8-F Oxygen index (FR-PVC) ≥ 28 % Typical flame-retardant PVC compound (est.)
09 · Installation
Ref: Q/GDW 13244.1-2018; GB 50168
9-A Minimum bending radius (multi-core) ≥ 15 × actual OD — ≈ 522 mm for Ø 34.8 mm
9-B Approved laying methods Conduit, tray, trench, duct, trunking, direct burial — Mechanical protection required for direct burial
9-C Post-install commissioning test DC 4U0 = 2.4 kV / 15 min — Per Q/GDW 13244.1-2018
9-D Maximum pulling tension ≤ 4000 N Rule of thumb: 40 N/mm² of conductor area (est.)
9-E Storage conditions Dry, covered, −20 to +45 °C — Avoid direct sunlight and moisture
9-F Cold-weather pre-heating Warm to ≥ 0 °C before pulling — Prevents jacket cracking
10 · Packing
Ref: custom lengths; marking per GB/T 6995 / project spec
10-A Standard supply length 100 m per coil or wooden drum — Custom lengths available on request
10-B Cable surface marking Type, voltage, manufacturer, year, metre marks — Per GB/T 6995 and project requirements
10-C Recommended drum size ≥ Ø 1400 mm flange — For 100 m of Ø 34.8 mm cable (est.)
10-D Approx. net weight per 100 m drum ≈ 372 kg 100 m × 3718 kg/km


Cable Test Parameters


ZR-YJV 3×95+1×50 mm² — Test & Verification Schedule (GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Phase conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.193 Ω/km @ 20 °C (95 mm²) Every production length
Routine Neutral conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.387 Ω/km @ 20 °C (50 mm²) Every production length
Routine Power-frequency withstand GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor to earth/water bath
Routine Dimensional inspection GB/T 2951 Phase ins. ≥ 1.1 mm; neutral ins. ≥ 1.0 mm; sheath ≥ 2.5 mm; OD within tolerance Wall & diameter check
Routine Conductor continuity Visual / electrical All cores continuous, no break Every length
Sample XLPE hot-set test GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking verification
Sample XLPE tensile & elongation GB/T 2951 Tensile ≥ 12.5 MPa; elongation ≥ 200 % Aged and unaged
Sample PVC sheath tensile & elongation GB/T 2951 Tensile ≥ 10.0 MPa; elongation ≥ 125 % Aged and unaged
Sample PVC thermal stability GB/T 2951 (Congo-red) ≥ 200 min @ 200 °C HCI evolution test
Sample Conductor geometry GB/T 3956 Phase: 19 × 2.52 mm Ø ≈ 12.6; neutral: 7 × 3.00 mm Ø ≈ 9.0 Per batch
Type Single-cable flame test GB/T 18380.12 No flame to upper reference mark ZR property
Type Bunched flame test — C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m Class C compliance
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core bending rule
Type Insulation resistance Factory method ≥ 36.7 MΩ·km @ 20 °C Not routine under GB/T 12706.1
Post-install DC withstand commissioning Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown Required for new installations
Post-install Phase identification Visual / continuity L1/L2/L3/N correctly labelled at both ends Before energisation


Cable Cross Section Structure


Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring

ZR-YJV 3×95+1×50 mm² — Cross-Section Construction Diagram (Schematic)
Layered 3+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · primary data from Zhongce 3+1 table
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Phase conductor (Cu) × 3 Annealed copper, Class 2 compact strand — 19 wires of 2.52 mm per core (19/2.52, 1+6+12 layout), nominal area 95 mm² each — ≈ 12.6 (Ø each phase core) Line-current carrying phase conductors; DC resistance capped at 0.193 Ω/km at 20 °C
2 Neutral conductor (Cu) × 1 Annealed copper, Class 2 compact strand — 7 wires of 3.00 mm (7/3.00, 1+6 layout), nominal area 50 mm² — ≈ 9.0 (Ø neutral core) Return / neutral path; DC resistance capped at 0.387 Ω/km at 20 °C
3 Phase insulation (XLPE) × 3 Cross-linked polyethylene dielectric 1.1 ≈ 14.8 (Ø each phase core, incl. insulation) Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min
4 Neutral insulation (XLPE) × 1 Cross-linked polyethylene dielectric 1 ≈ 11.0 (Ø neutral core, incl. insulation) Electrical isolation for the neutral conductor
5 Core assembly Neutral core at centre + three phase cores cabled around + PP filler + polyester binder tape — ≈ 29.8 (Ø over assembled cores) 3+1 configuration; derived from Zhongce OD − 2×sheath
6 Outer jacket (PVC) Flame-retardant PVC, ST2 compound, black 2.5 ≈ 34.8 (Ø finished cable, Zhongce) Mechanical and moisture protection; ZC flame retardance per GB/T 19666
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 34.8 mm Zhongce 3+1 unarmored table

Approximate cable mass ≈ 3718 kg/km Zhongce copper-conductor figure

Nominal voltage rating 0.6/1 kV AC 50 Hz; maximum system voltage Um = 1.2 kV

Conductor temperature limits 90 / 250 °C Continuous service / short-circuit (≤ 5 s)

Minimum bend radius (multi-core) ≥ 15 × OD ≈ 522 mm OD = actual finished cable diameter

Flame-retardant classification ZC (ZR) — Per GB/T 19666

Short-circuit current (1 s) ≈ 10.9 kA I = k·A/√t, k=115 for Cu/XLPE (est.)

AC impedance @ 50 Hz ≈ 0.20 Ω/km √(R² + X²); R-dominant (est.)

Capacitance (typical) ≤ 0.38 μF/km Per phase core (est.)

Inductance (typical) ≈ 0.26 mH/km Three-core cable (est.)

Air ampacity @ 30 °C ≈ 320 A Zhongce basis; Cu, 3 phase loaded

Buried ampacity @ 25 °C ≈ 315 A Zhongce basis; Cu, 3 phase loaded

Schematic — not to exact scale. Primary data (OD, weight, ampacity) from Zhongce 3+1 table; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1. Values marked (est.) are engineering estimates.


Construction Description


Construction Description — ZR-YJV 3×95mm²+1×50 mm²
Layer-by-layer build-up narrative, conductor through outer jacket · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV class · primary data from Zhongce 3+1 table
1. Product Identity & Ratings
ZR-YJV 3×95+1×50 is a heavy-duty flame-retardant 3+1-core cable: it combines three 95 mm² copper phase conductors with a single 50 mm² copper neutral conductor, all insulated in XLPE and enclosed in one ST2 PVC jacket, for 0.6/1 kV service. Manufacturing and type testing follow GB/T 12706.1 / IEC 60502-1, conductor stranding follows GB/T 3956, and the ZR marking corresponds to class ZC under GB/T 19666. The finished cable measures 34.8 mm across (Zhongce 3+1 table) and weighs 3718 kg per kilometre; supply is in 100 m coils or wooden drums.
This 3+1 build follows the conventional three-phase four-wire format: the reduced neutral core sits in the centre while the three phase cores are laid up around it. With all three phase cores energised, the cable supports 320 A in free air at 30 °C and 315 A when directly buried at 25 °C (Zhongce basis) — suited to main distribution risers, transformer secondaries and large industrial feeders.
2. Copper Stranded Conductors
Each 95 mm² phase core is formed from nineteen 2.52 mm annealed wires in the 1+6+12 compact arrangement (19/2.52) — the Class 2 standard for this cross-section — yielding an outside diameter of about 12.6 mm and a DC resistance ceiling of 0.193 Ω/km at 20 °C. The 50 mm² neutral core uses seven 3.00 mm wires (7/3.00) to about 9.0 mm Ø, with resistance capped at 0.387 Ω/km. Both are compact Class 2 strands that deliver clean circular profiles and dependable crimp terminations; the 19-wire phase construction provides good flexibility for this large section.
3. XLPE Dielectric Insulation
XLPE is extruded at 1.1 mm onto the phase cores (the wall Zhongce's 3+1 table assigns to 95 mm² conductors) and at 1.0 mm onto the 50 mm² neutral core — producing approximately 14.8 mm per phase core and 11.0 mm for the neutral core over the insulation. The dielectric is rated for 90 °C continuous duty and 250 °C for five seconds, maintains volume resistivity above 1×10¹² Ω·cm, passes the routine 3.5 kV AC five-minute voltage proof, and offers tensile strength ≥ 12.5 MPa with elongation ≥ 200 %.
4. Cabling & PVC Outer Jacket
After insulation, the neutral core is placed at the centre and the three phase cores are cabled around it in a triangular ring with polypropylene filler and a polyester binder tape, forming a bundle of about 29.8 mm diameter (derived from the finished OD). A 2.5 mm layer of flame-retarded ST2 PVC is then extruded over the assembly to the Zhongce 34.8 mm finish. The jacket provides ZC behaviour through GB/T 18380.12 and GB/T 18380.35, offers tensile strength ≥ 10 MPa and elongation ≥ 125 %; because PVC is halogenated, low-smoke zero-halogen projects should specify WDZ-YJY instead.
5. Site Handling & Operational Notes
• Observe the 15 × OD minimum bending radius (≈ 522 mm).  • Perform the DC 4U0 = 2.4 kV / 15 min commissioning test before first energisation.  • Service ambient spans −20 to +45 °C; warm drums below 0 °C before pulling.  • Derate the 320 A (air) / 315 A (buried) references for ambient temperature, grouping and soil conditions.  • Maximum pulling tension ≤ 4000 N; use appropriate pulling grips and lubricant.  • Select lugs and glands matched to the 12.6 mm phase core, 9.0 mm neutral core and 34.8 mm jacket diameter.  • Short-circuit rating ≈ 10.9 kA for 1 second — verify against protective device settings.


8. Factory Advantages.

  • Balanced 3+1 feeder sizing — reduced 50 neutral avoids excess copper cost on balanced equipment loads.
  • Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent under feeder load.
  • Dosed ZC compound — self-extinguishing jacket protects distribution rooms and wiring spaces.
  • Length-on-demand — cut to exact feeder meter with sealed ends.
  • Dual-section resistance log — phase 95 and neutral 50 R recorded to lot for traceability.
  • Continuous print line — type, size, ZC, voltage and length readable along feeder runs.
  • Phase-color option — L1/L2/L3/N colors reduce wiring errors at distribution boards.
  • Drum pack — wound on a rated drum with moisture-sealed ends.
  • Certified QA pack — routine + type test record shipped per batch for commissioning.

Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring


9. Packaging, Storage & Logistics. Cut to measured feeder length on a wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.


Copper Conductor Flame Retardant XLPE Cable ZR-YJV 3×95mm²+1×50mm² for Site Power Wiring


10. Procurement Specification. State "ZC-YJV 3×95+1×50", length, class C, phase colors; note the reduced neutral suits balanced loads (enlarge for high harmonics) and not fire-rated; request the dual-section resistance log and 16-item QA record. Est. values confirmed against the factory certificate.


11. Cable Industry FAQ.

  • Q1: How does 3×95+1×50 differ from 4×70? Different architecture: a 3+1 变截面 (reduced-neutral) build rather than four equal cores — phases 95 vs 70 mm², neutral 50 vs 70; phase R 0.206 vs 0.268 Ω/km, phase current ≈200 vs 175 A; aimed at building sub-mains and equipment feeders rather than a balanced four-core branch.
  • Q2: Why a 50 mm² neutral here? Balanced motor/equipment loads draw little neutral current; a reduced neutral saves copper. Enlarge it where VFD/rectifier harmonics are high.
  • Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
  • Q4: DC resistance values? 95 phases ≤0.206; 50 neutral ≤0.387 Ω/km at 20°C.
  • Q5: Screen or armor? Unscreened standard; add braid near VFD EMI; steel-tape armor for buried ground-crushing duty.
  • Q6: Current per phase? ≈200 A (est.) free air 30°C; derate in crowded conduit and trays.
  • Q7: Bending? ≈420 mm (15×OD); standard pulling tools suffice on this section.
  • Q8: Connectors? 95 mm² phase lugs and a 50 mm² neutral lug; gland to ≈28 mm OD.
  • Q9: Indoor or outdoor? Indoor preferred; specify UV-stabilized jacket for exposed runs.
  • Q10: Packing? Wooden drum with moisture-sealed ends.
  • Q11: What proof ships? Dual-section resistance log + 16-test record; est. values confirmed against certificate.