Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution

Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZR-YJV 3×70mm²+1×35mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath ...

Product Details

Highlight:

zr-yjv 4 cores cable

,

zr-yjv 25 sq mm 4 core cable

,

industrial 4 cores cable

Phase conductor (×3):
Bare Annealed Copper, Class 2 Stranded, 19×∅2.14 Mm, Conductor Ø ≈ 10.7–11.2 Mm Depending On Compaction
Neutral conductor (×1):
Bare Annealed Copper, Class 2 Stranded, 7×∅2.52 Mm (also 19×∅1.53 Mm Compact), Conductor Ø ≈ 7.6–8.0 Mm Depending On Compaction
Phase conductor nominal area:
70 Mm²
Neutral conductor nominal area:
35 Mm²
Number of cores:
4 (3+1)
Phase conductor construction:
Class 2, 19×∅2.14 Mm,IEC 60228 / GB/T 3956
Neutral conductor construction:
Class 2, 7×∅2.52 Mm,IEC 60228 / GB/T 3956
Phase conductor diameter (approx.):
10.7–11.2 Mm
Neutral conductor diameter (approx.):
7.6–8.0 Mm
Insulation (×4):
XLPE
Phase insulation thickness:
1.1 Mm (70 Mm² Class)
Neutral insulation thickness:
0.9 Mm (35 Mm² Class)
Diameter over phase insulated core:
12.9–13.4 Mm
Diameter over neutral insulated core:
9.4–9.8 Mm
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.7 Mm (GB/T 12706 Multi-core 50–95 Mm² Range)
Overall cable diameter:
24.5 – 29.5 Mm
Design outer diameter:
≈ 26.5 Mm
Approx. weight:
950 – 1200 Kg/km
Design weight:
≈ 1040 Kg/km

Product Description

Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution


Cable Designation & Meaning


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

3×70+1×35 mm²

Three phase cores of 70 mm² copper + one reduced neutral core of 35 mm² copper

ZR-YJV 3×70+1×35 mm² — Cable Specification & Engineering Data

1. Overview & Ratings. ZR-YJV 3×70+1×35 is a flame-retarding 3+1-core cable: three 70 mm² copper phase conductors and one 35 mm² copper neutral conductor, XLPE insulation and one ST2 PVC jacket, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; manufactured and proof-tested to GB/T 12706.1 / IEC 60502-1, stranding to GB/T 3956, ZC fire class to GB/T 19666. Finished diameter ≈ 39.6 mm (est.), mass ≈ 2800 kg/km (est.), supplied in 100 m coils or wooden drums. Note: this size is not in the Zhongce 3+1 table — dimensions and ampacity are engineering estimates interpolated between 3×50+1×25 and 3×95+1×50; confirm against the factory test certificate.


2. Construction Stack. Conductor → outer jacket:

Layer Build Wall Diameter
Phase conductor (×3) Annealed Cu, Class 2 compact, 19 × 2.14 mm (1+6+12) each — ≈ 10.7 mm
Neutral conductor (×1) Annealed Cu, Class 2 compact, 7 × 2.52 mm (1+6) — ≈ 7.56 mm
Phase insulation (×3) XLPE 1.1 mm ≈ 12.9 mm
Neutral insulation (×1) XLPE 0.9 mm ≈ 9.36 mm
Core assembly Central neutral + 3 phase cores around + PP filler + polyester binder — ≈ 35.2 mm (est.)
Outer jacket Flame-retarded PVC, ST2 compound, black 2.2 mm ≈ 39.6 mm (est.)


Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution


3. Electrical Ratings. Phase R ≤ 0.268 Ω/km, neutral R ≤ 0.524 Ω/km @ 20 °C; factory proof 3.5 kV AC / 5 min; finished-cable insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.40 μF/km; inductance ≈ 0.27 mH/km; AC impedance ≈ 0.27 Ω/km; short-circuit current ≈ 8.05 kA for 1 s. Reference current (3 phase cores loaded) ≈ 245 A in air @ 30 °C / 255 A buried @ 25 °C — engineering estimate based on 70 mm² three-core references.


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (phase, per core)

≤ 0.268 Ω/km

GB/T 3956 max, 70 mm²

DC resistance @20 °C (neutral, per core)

≤ 0.524 Ω/km

GB/T 3956 max, 35 mm²

AC resistance @90 °C (est., phase)

≈ 0.349 Ω/km

per core

AC resistance @90 °C (est., neutral)

≈ 0.682 Ω/km

per core

Current rating in air (30 °C, single circuit, 3-core+1)

≈ 180–205 A

based on 70 mm² phase

Current rating in air (design)

≈ 190 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 205–225 A

common catalogue 210–218 A

Design buried rating

≈ 214 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, phase)

≈ 7.0 kA

70 mm² reference

Short-circuit current (1 s, Cu, 250 °C, neutral)

≈ 3.5 kA

35 mm² reference

Frequency

50/60 Hz AC

—


4.Cable Parameters & Test Parameters


Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution


ZR-YJV 3×70+1×35 mm² — Test & Verification Schedule (GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Phase conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.268 Ω/km @ 20 °C (70 mm²) Every production length
Routine Neutral conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.524 Ω/km @ 20 °C (35 mm²) Every production length
Routine Power-frequency withstand GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor to earth/water bath
Routine Dimensional inspection GB/T 2951 Phase ins. ≥ 1.1 mm; neutral ins. ≥ 0.9 mm; sheath ≥ 2.2 mm; OD within tolerance Wall & diameter check
Routine Conductor continuity Visual / electrical All cores continuous, no break Every length
Sample XLPE hot-set test GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking verification
Sample XLPE tensile & elongation GB/T 2951 Tensile ≥ 12.5 MPa; elongation ≥ 200 % Aged and unaged
Sample PVC sheath tensile & elongation GB/T 2951 Tensile ≥ 10.0 MPa; elongation ≥ 125 % Aged and unaged
Sample PVC thermal stability GB/T 2951 (Congo-red) ≥ 200 min @ 200 °C HCI evolution test
Sample Conductor geometry GB/T 3956 Phase: 19 × 2.14 mm Ø ≈ 10.7; neutral: 7 × 2.52 mm Ø ≈ 7.56 Per batch
Type Single-cable flame test GB/T 18380.12 No flame to upper reference mark ZR property
Type Bunched flame test — C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m Class C compliance
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core bending rule
Type Insulation resistance Factory method ≥ 36.7 MΩ·km @ 20 °C Not routine under GB/T 12706.1
Post-install DC withstand commissioning Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown Required for new installations
Post-install Phase identification Visual / continuity L1/L2/L3/N correctly labelled at both ends Before energisation


5.Cable Cross Section Structure


Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution


ZR-YJV 3×70+1×35 mm² — Cross-Section Construction Diagram (Schematic)
Layered 3+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · dimensions marked (est.) are engineering estimates — confirm with factory certificate
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Phase conductor (Cu) × 3 Annealed copper, Class 2 compact strand — 19 wires of 2.14 mm per core (19/2.14, 1+6+12 layout), nominal area 70 mm² each — ≈ 10.7 (Ø each phase core) Line-current carrying phase conductors; DC resistance capped at 0.268 Ω/km at 20 °C
2 Neutral conductor (Cu) × 1 Annealed copper, Class 2 compact strand — 7 wires of 2.52 mm (7/2.52, 1+6 layout), nominal area 35 mm² — ≈ 7.56 (Ø neutral core) Return / neutral path; DC resistance capped at 0.524 Ω/km at 20 °C
3 Phase insulation (XLPE) × 3 Cross-linked polyethylene dielectric 1.1 ≈ 12.9 (Ø each phase core, incl. insulation) Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min
4 Neutral insulation (XLPE) × 1 Cross-linked polyethylene dielectric 0.9 ≈ 9.36 (Ø neutral core, incl. insulation) Electrical isolation for the neutral conductor
5 Core assembly Neutral core at centre + three phase cores cabled around + PP filler + polyester binder tape — ≈ 35.2 (Ø over assembled cores, est.) 3+1 configuration; forms a round, stable bundle
6 Outer jacket (PVC) Flame-retardant PVC, ST2 compound, black 2.2 ≈ 39.6 (Ø finished cable, est.) Mechanical and moisture protection; ZC flame retardance per GB/T 19666
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 39.6 mm Engineering estimate (not in Zhongce table)

Approximate cable mass ≈ 2800 kg/km Cu + XLPE + PVC + filler (est.)

Nominal voltage rating 0.6/1 kV AC 50 Hz; maximum system voltage Um = 1.2 kV

Conductor temperature limits 90 / 250 °C Continuous service / short-circuit (≤ 5 s)

Minimum bend radius (multi-core) ≥ 15 × OD ≈ 594 mm OD = actual finished cable diameter

Flame-retardant classification ZC (ZR) — Per GB/T 19666

Short-circuit current (1 s) ≈ 8.05 kA I = k·A/√t, k=115 for Cu/XLPE (est.)

AC impedance @ 50 Hz ≈ 0.27 Ω/km √(R² + X²); R-dominant (est.)

Capacitance (typical) ≤ 0.40 μF/km Per phase core (est.)

Inductance (typical) ≈ 0.27 mH/km Three-core cable (est.)

Air ampacity @ 30 °C ≈ 245 A Engineering estimate; Cu, 3 phase loaded

Buried ampacity @ 25 °C ≈ 255 A Engineering estimate; Cu, 3 phase loaded

Schematic — not to exact scale. Values marked (est.) are engineering estimates interpolated between 3×50+1×25 and 3×95+1×50; confirm against factory test certificate.


Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution


6. Thermal & Fire. 90 °C continuous conductor, 250 °C short-circuit (≤ 5 s); service ambient −20 to +45 °C, minimum laying temp 0 °C; max burial soil temp 25 °C; ZC per GB/T 19666 — GB/T 18380.12 single-cable + GB/T 18380.35 category-C bunched (char ≤ 2.5 m); PVC jacket is halogenated and emits smoke under fire — specify WDZ-YJY for LSZH.


Flame-Retardant (FR) Characteristics — ZR-YJV 3×70+1×35 mm²
ZR-YJV 3×70+1×35 mm²  (3 (L1+L2+L3, 70 mm²) + 1 (N, 35 mm²); 3+1 = L1+L2+L3+N)   ·   0.6/1 kV
1.  Cable Identification
Code / Item Meaning / Value Standard / Note
Designation ZR-YJV 3×70+1×35 mm² GB/T 12706.1-2020
ZR Flame Retardant (legacy); under GB/T 19666-2019 defaults to Class C; modern = ZC GB/T 19666-2019
YJ XLPE insulation (cross-linked polyethylene) —
V PVC outer sheath — flame-retardant, contains halogen (Cl) GB/T 19666-2019
0.6/1 kV U₀/U = 600/1000 V; Uₘ = 1.2 kV IEC 60502-1
3×70+1×35 mm² Three 70 mm² phase cores + one 35 mm² neutral core (reduced neutral, 3+1 construction) —
Construction Unarmoured, non-screened, round multi-core (3+1) —
Application note 3+1 core → three-phase AC with neutral (L1+L2+L3+N); neutral reduced to 35 mm². No separate PE (use 4-core or 5-core if PE required). —
2.  Flame-Retardant & Fire Performance  (CORE)
Property Value / Requirement Standard
Flame Retardant Class Class C (bundled cables, char length ≤ 2.5 m) GB/T 19666-2019; GB/T 18380.3 / IEC 60332-3-24
Legacy designation ZR (= ZC); modern prefix preferred: ZC GB/T 19666-2019
Test method — flame Bunched flame test (category C), char ≤ 2.5 m after flame removal GB/T 18380.3 (IEC 60332-3-24)
Halogen content Contains halogen — Cl from PVC sheath; releases HCl on burning GB/T 17650 / IEC 60754-1/-2
Smoke density Heavy dark smoke — NOT low-smoke (no LSZH certification) GB/T 17651 / IEC 61034
Corrosivity Corrosive — HCl gas generated during fire GB/T 17650 / IEC 60754-2
pH / conductivity of gases Not certified (PVC base — acidic / conductive combustion gases) GB/T 17650 / IEC 60754-2
Limited Oxygen Index (LOI) PVC typical ≈ 45–49 % O₂ (reference, design value) ASTM D2863 / GB/T 2406, reference
Max. conductor operating temp. 90 °C (long-term service) GB/T 12706.1-2020
Max. short-circuit temp. (≤5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) IEC 60502-1
Service ambient range (PVC sheath) −15 °C to +90 °C —
Min. installation ambient temp. 0 °C (pre-heat required below 0 °C) —
3.  Fire Test Summary
Test Requirement ZR-YJV 3×70+1×35 mm² Verdict
Bunched flame test (Class C) Char length ≤ 2.5 m PASS (design, Class C)
Single flame test (IEC 60332-1) Self-extinguishing PASS (XLPE/PVC FR)
Smoke density (IEC 61034) Light transmittance ≥ 60 % for LSZH N/A (PVC = heavy smoke)
Halogen content (IEC 60754) ≤ 0.5 % HCl for LSZH N/A (contains Cl)
Acidity / corrosivity (IEC 60754-2) pH ≥ 4.3; conductivity ≤ 10 µS/mm for LSZH N/A (corrosive HCl)
Fire-survival (BS 6387 / IEC 60331) Circuit integrity during/after fire N/A — use NH-ZR-YJV
4.  Key Electrical & Thermal Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (phase, 70 mm²) ≤ 0.268 Ω/km GB/T 3956 / IEC 60228, Class 2 max
DC resistance @ 20 °C (neutral, 35 mm²) ≤ 0.524 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (phase, est.) ≈ 0.349 Ω/km per phase core
Current rating — in air (30 °C, single circuit) ≈ 175–195 A (design ≈ 185 A) 3+1 core
Current rating — direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) ≈ 210–240 A (design ≈ 225 A) 3+1 core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 7.00 kA (per phase core) phase core; neutral ≈ 3.50 kA
5.  Construction & Material Specification (with FR Contribution)
Layer (inside → out) Description / Specification FR Contribution
Conductor (phase ×3) Bare annealed copper, Class 2 stranded, 19ר2.14 mm, Ø ≈ 9.20 mm None (Cu non-combustible)
Conductor (neutral ×1) Bare annealed copper, Class 2 stranded, 19ר2.14 mm, Ø ≈ 9.20 mm None (Cu non-combustible)
Conductor screen Omitted (not required for 0.6/1 kV) —
Insulation (×4) XLPE (cross-linked polyethylene), phase 1.1 mm (e_min 0.89) / neutral 0.9 mm (e_min 0.71); L1/L2/L3 = brown/black/grey, N = blue XLPE — low flame spread
Filler Flame-retardant PP / PE to form round assembly FR additive
Binder Flame-retardant tape over laid-up cores FR barrier
Inner binder / assembly FR tape, no inner sheath required for plain YJV FR barrier
Outer sheath Flame-retardant PVC (ZR grade), 1.5 mm (multi-core, 3+1 rule), Black (standard) Primary FR layer (halogenated)
Armour None —
Metallic screen None —
6.  Dimensional Data
Item Typical Value Remarks
Conductor nominal area 3×70 mm² + 1×35 mm² phase / neutral
Number of cores 4 (3+1) —
Conductor construction Phase: Class 2, 19ר2.14 mm; Neutral: Class 2, 7ר2.52 mm min. 7 wires
Conductor diameter (approx.) Phase ≈ 9.20 mm; Neutral ≈ 7.50 mm —
Insulation thickness Phase 1.1 mm; Neutral 0.9 mm (70 / 35 mm² classes) 0.9 / 0.7 mm class
Diameter over insulated core Phase 11.4 mm; Neutral 9.3 mm conductor + 2×insulation
Sheath thickness 1.5 mm (multi-core, 3+1 rule) 3+1 multi-core rule
Overall cable diameter 20.0 – 24.5 mm (design ≈ 22.0 mm) design ≈ 22.0 mm
Approx. weight 900 – 1140 kg/km (use ≈ 1080 kg/km) —
Cable shape Round —
7.  Mechanical & Installation Parameters
Parameter Value Note
Minimum bending radius (unarmoured multi-core) ≥ 15 × OD ≈ 330 mm @ Ø≈ 22.0 mm —
Max. pulling tension (Cu only) 50 N/mm² × (3×70 + 1×35) = 12,250 N total use conductor sock, avoid sheath grip
Direct burial Allowed in non-aggressive soil; for mechanical protection use ZR-YJV22 3×70+1×35 —
Conduit ID ≥ 1.5 × OD → ≥ 33 mm (use 40 mm or 50 mm conduit) —
Fixing (horizontal / vertical tray) ≈ 800 mm / ≈ 1500 mm (horizontal / vertical tray) —
Elevation difference limit None (XLPE) —
8.  Selection Guide — When FR Matters
Scenario Recommended Cable Reason
Flame-retardant, halogenated acceptable (standard) ZR-YJV 3×70+1×35 mm² (this cable) Class C FR, PVC sheath, cost-effective
Low-smoke halogen-free required (LSZH) WDZ-YJY 3×70+1×35 LSZH sheath — IEC 61034 / IEC 60754 compliant
Fire-survival circuit (circuit integrity) NH-ZR-YJV / WDZN-YJY 3×70+1×35 BS 6387 / IEC 60331 fire-survival grade
1. ZR is the legacy GB/T 19666-2019 Class C designation; modern equivalent is ZC. Class C: char ≤ 2.5 m after bunched flame test (GB/T 18380.3).
2. PVC sheath is halogenated (contains Cl, releases HCl) → heavy smoke and corrosive gases; NOT suitable for LSZH-required routes (use WDZ-YJY).
3. 3×70+1×35 mm² = three 70 mm² phase cores (L1+L2+L3) + one 35 mm² neutral (N), total 4 cores (3+1); neutral is reduced in size. Current ratings (≈155 A air / ≈185 A buried) are design values; apply grouping, ambient temperature, soil thermal resistivity and IEC 60364-5-52 correction factors.
4. For LSZH → WDZ-YJY 3×70+1×35; for fire-survival → NH-ZR-YJV / WDZN-YJY 3×70+1×35; for armour → ZR-YJV22 3×70+1×35; for separate PE → use 5-core (e.g. 5×25).
5. DC resistance phase ≤ 0.268 Ω/km, neutral ≤ 0.524 Ω/km (GB/T 3956 Class 2 max). Test values marked "reference" are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.


7. Installation & Care. Minimum bend ≥ 15 × OD (≈ 594 mm); commissioning DC test 4U0 = 2.4 kV / 15 min before first energisation (Q/GDW 13244.1-2018); warm drums below 0 °C before pulling; max pulling tension ≤ 3000 N; derate the 245/255 A references for ambient, grouping and soil; fit lugs and glands sized for the 10.7 mm phase core, 7.56 mm neutral core and 39.6 mm jacket; verify short-circuit rating against protective device settings.


Flame Retardant Power Cable ZR-YJV 3×70mm²+1×35mm² for Industrial Power Distribution


8. Application. Heavy three-phase four-wire distribution, transformer secondaries, large building mains and industrial feeders requiring a dedicated neutral conductor in a single cable (TN-C style) — conduit, tray, trench, duct, trunking, direct burial; indoor or sheltered outdoor.


FAQs
who are we?
We are based in Anhui, China, start from 2026,sell to Africa(70.00%). There are total about 51-100 people in our office.
how can we guarantee quality?
Always a pre-production sample before mass production; Always final Inspection before shipment;
what can you buy from us?
Building Wire, Flat and Sheathed Wire, Fire Alarm and Signal Wire, Power Cable, Control Cable
why should you buy from us not from other suppliers?
OEM/ODM ready with in-house R&D and industrial design, trusted by Fortune 500 brands, offering massive stock and shipment within 15 days, featuring oxygen-free copper and flame-retardant materials for premium quality.
what services can we provide?
Accepted Delivery Terms: FOB,CFR,CIF,EXW,FAS,CIP,FCA,CPT,DEQ,DDP,DDU,Express Delivery,DAF,DES; Accepted Payment Currency: USD,EUR,JPY,CAD,AUD,HKD,GBP,CNY,CHF; Accepted Payment Type: T/T,L/C,D/P D/A,,Credit Card,PayPal,Western Union,Cash,Escrow; Language Spoken: English,Chinese,Spanish,Japanese,Portuguese,German,Arabic,French,Russian,Korean,Hindi,Italian