ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution

ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 4*150mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath — flame-retardant grade, ...

Product Details

Highlight:

zr-yjv 4 cores cable

,

zr-yjv 25 sq mm 4 core cable

,

copper 4 cores cable

Conductor (×4):
Bare Annealed Copper, Class 2 Stranded, Commonly 37×∅2.25 Mm (also 19×∅3.20 Mm Compact / 30×2.55 Mm), Conductor Ø ≈ 15.0–16.5 Mm Depending On Compaction
Conductor nominal area (per core):
150 Mm²
Number of cores:
4
Conductor construction:
Class 2, 37×∅2.25 Mm,IEC 60228 / GB/T 3956, Min. 15 Wires
Conductor diameter (approx.):
15.0–16.5 Mm
Insulation (×4):
XLPE
Insulation thickness:
1.4 Mm (150 Mm² Class)
Diameter over insulated core:
17.8–19.3 Mm,conductor + 2×1.4
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
2.3 Mm (GB/T 12706 Multi-core 150 Mm² Class)
Overall cable diameter:
41.0 – 48.0 Mm
Design outer diameter:
≈ 44.0 Mm
Approx. weight:
5200 – 6600 Kg/km
Design weight:
≈ 5600 Kg/km

Product Description

ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×150 mm²

Four cores, nominal copper conductor area 150 mm² per core


ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution

ZR-YJV 4×150 mm² — Specification Data Sheet

1. Cable General Description. ZR-YJV 4×150 — halogen-containing, flame-retarding four-core cable, four 150 mm² Cu conductors, XLPE dielectric, ST2 PVC jacket, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; designed and type-tested per GB/T 12706.1 / IEC 60502-1, conductor grading per GB/T 3956, ZC flame class per GB/T 19666. Measures ≈ 50.9 mm, weighs ≈ 6435 kg/km (Al ≈ 2669), 100 m coils/drums.


2. Construction Stack. Conductor → outer sheath:

Layer Build Wall Diameter
Conductor (×4) Annealed Cu, Class 2, 37 × 2.26 mm (1+6+12+18) each — ≈ 15.80 mm
Insulation (×4) XLPE 1.4 mm ≈ 18.60 mm
Lay-up Four cores + central filler + binder tape — ≈ 44.9 mm (calc.)
Sheath Flame-retarded PVC, ST2, black 2.3 mm ≈ 50.9 mm


3. Electrical Ratings. R ≤ 0.124 Ω/km @ 20 °C; routine 3.5 kV / 5 min; insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km. Reference ampacity (four cores loaded) ≈ 325 A air / 345 A buried @ 25 °C — Mingda 4×150, cross-checked with 3×150 (identical per-core values).


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.124 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.161 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core)

≈ 340–365 A

common catalogue value

Current rating in air (design)

≈ 350 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 360–410 A

common catalogue 370–400 A

Design buried rating

≈ 380 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 15.0 kA

reference

Frequency

50/60 Hz AC

—


4. Thermal & Fire. 90 °C continuous, 250 °C short-circuit (≤ 5 s); −20~+45 °C ambient, ≥ 0 °C laying; ZC per GB/T 19666 — passes GB/T 18380.12 single-burn and GB/T 18380.35 class-C bunched (char ≤ 2.5 m); halogen-bearing PVC → WDZ-YJY for LSZH.


ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution


5.Test Parameters


ZR-YJV 4×150 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.124 Ω/km @ 20 °C (per core) Every production length
Routine Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor-to-earth/water
Routine Construction check GB/T 2951 Ins. ≥ 1.4 mm; sheath ≥ 2.3 mm; OD within tolerance Thickness & diameter
Sample Hot set test — XLPE GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking degree
Sample Conductor construction & diameter GB/T 3956 Class 2; 37 × 2.26 mm; Ø ≈ 15.80 mm Per batch
Type Single-cable flame test GB/T 18380.12 No flame spread to top reference ZR property
Type Bunched flame test — class C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m ZC class
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core rule
Post-install DC withstand test Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown New installations
Optional Insulation resistance @ 20 °C Factory method ≥ 36.7 MΩ·km Not routine in GB/T 12706.1
Optional XLPE volume resistivity Material test ≥ 1 × 10¹² Ω·cm Material reference


6. Installation & Care. Bend ≥ 15 × OD; DC site test 4U0 = 2.4 kV / 15 min before energising (Q/GDW 13244.1-2018); pre-heat drums below 0 °C; de-rate 325/345 A for ambient, grouping, burial; lugs/glands for the 15.80 mm core.


Insulation Test Data
ZR-YJV  0.6/1 kV  4 × 150 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Item Description Standard / Note
Designation ZR-YJV 0.6/1 kV 4×150 mm² GB/T 12706.1-2020
Conductor Bare annealed copper, Class 2 stranded, 37×∅2.25 mm GB/T 3956 / IEC 60228
Insulation XLPE (cross-linked polyethylene), 1.4 mm nominal GB/T 12706.1-2020
Outer sheath Flame-retardant PVC (ZR grade), 2.3 mm nominal, black GB/T 19666-2019
Rated voltage U₀/U 0.6 / 1 kV (Uₘ = 1.2 kV) IEC 60502-1
Number of cores 4 (three-phase L1+L2+L3+N or L1+L2+L3+PE, equal sizes) —
2.  Insulation Design Data  (CORE)
Parameter Value Remarks
Insulation material XLPE (cross-linked polyethylene) —
Nominal thickness (eₙ) 1.4 mm 150 mm² class
Minimum allowable thickness (e_min) 1.12 mm eₙ − 0.28 mm (GB/T 12706.1-2020, Table 3)
Insulator colours Brown/black/grey/blue or red/yellow/blue/green-yellow (or as specified) IEC 60446
Volume resistivity @ 90 °C ≥ 10¹² Ω·cm —
Dielectric loss factor (tan δ) @ 20 °C ≤ 1 × 10⁻³ reference
Relative permittivity (εᵣ) ≈ 2.3 – 2.5 reference
Long-term service temp. 90 °C GB/T 12706.1-2020
Short-circuit temp. (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 – 130 °C transient
Diameter over insulated core 17.8–19.3 mm conductor 15.0–16.5 + 2×1.4
3.  Thermal Characteristics
Property Value Remarks
Max. conductor operating temp. (normal) 90 °C long-term
Max. conductor temp. — short-circuit (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) —
Min. installation ambient temp. 0 °C (pre-heat below 0 °C) —
Service ambient range (PVC sheath) −15 °C to +90 °C —
Flame retardant class (sheath) Class C (ZR per GB/T 19666) —
4.  Insulation Test Schedule
Test Item Test Value / Condition Result
Routine withstand test (AC) 3.5 kV AC, 5 min — no breakdown PASS
Type test voltage 4.0 kV AC PASS (IEC 60502-1)
Partial discharge test ≤ 10 pC @ 1.73 U₀ (1.73 kV) PASS (XLPE)
Insulation resistance (IR) ≥ 10⁴ MΩ·km @ 20 °C (reference) PASS
Hot-set test (XLPE cross-linking) 200 °C, 15 min, load 0.2 N/mm² — elongation ≤ 175 %, permanent set ≤ 15 % PASS (IEC 60811-507)
Aging test (air oven) 135 °C, 168 h — tensile strength / elongation retained ≥ 80 % PASS
Tensile strength (insulation) ≥ 12.5 MPa (XLPE, before aging) PASS
Elongation at break (insulation) ≥ 200 % (XLPE, before aging) PASS
Cold bend test −15 °C, 4 h — no cracking PASS
Water absorption ≤ 1 mg/cm² (85 °C, 336 h, reference) PASS
Breakdown voltage (insulation) ≥ 20 kV/mm (reference) PASS
DC resistance of conductor @ 20 °C ≤ 0.124 Ω/km (Class 2 Cu, per core) PASS (GB/T 3956)
Dielectric loss (tan δ) measurement ≤ 1 × 10⁻³ @ 20 °C PASS (reference)
Spark test (during production) 6 – 10 kV (online), pinhole detection PASS
Thickness measurement (microscopic) eₙ = 1.4 mm; e_min ≥ 1.12 mm PASS
5.  Electrical Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.124 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.161 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 340–365 A (design ≈ 350 A) 4-core
Current rating — direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) ≈ 360–410 A (design ≈ 380 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 15.0 kA reference
Frequency 50/60 Hz AC —
6.  Dimensional / Inspection Result
Item Design / Limit Measured (example)
Conductor construction Class 2, 37×∅2.25 mm 37×2.25 mm
Conductor diameter 15.0–16.5 mm 15.8 mm
Insulation thickness (each core) 1.4 mm (min. 1.12 mm) 1.42 / 1.40 / 1.41 / 1.38 mm
Diameter over insulated core 17.8–19.3 mm 18.6 mm
Sheath thickness 2.3 mm (min. 2.0 mm) 2.31 mm
Overall cable diameter ≈ 42.0–46.0 mm (range 41.0–48.0) 44.2 mm
DC resistance @ 20 °C (per core) ≤ 0.124 Ω/km 0.122 Ω/km
Approx. weight 5200 – 6600 kg/km (design ≈ 5600) 5580 kg/km
Footnotes
1. All tests performed at ambient 20 ± 5 °C and 45–75 % RH unless otherwise stated.
2. Routine tests: withstand (3.5 kV / 5 min), conductor resistance, dimensional check. Type tests: 4.0 kV, partial discharge, hot-set, aging, mechanical (per IEC 60502-1).
3. Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.
4. Insulation thickness for 150 mm² class = 1.4 mm nominal (GB/T 12706.1-2020, Table 3); minimum = 1.4 − 0.28 = 1.12 mm. Sheath thickness = 2.3 mm for 150 mm² class.
5. For low-smoke halogen-free → use WDZ-YJY 4×150; for fire-survival → NH-ZR-YJV / WDZN-YJY 4×150; for armoured → ZR-YJV22 4×150.
6. Plain-round 150 mm² shows maker-to-maker dimensional variance (OD 41–48 mm, weight 5200–6600 kg/km); design values are mid-range estimates — verify with manufacturer catalog.


7. Flame Retardant Test Parameters


ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution


8.Cross Section Structure


ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution


ZR-YJV 4×150 mm² — Cable Cross-Section Structure (Schematic)
Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 4 Annealed copper, Class 2 stranded — 37 × 2.26 mm per core (37/2.26, 1+6+12+18), nominal 150 mm² per core — ≈ 15.80 (Ø per core) Current-carrying element; max DC resistance ≤ 0.124 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 4 Cross-linked polyethylene 1.4 ≈ 18.60 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Four insulated cores laid up around central non-hygroscopic filler; binder tape — ≈ 44.9 (Ø over lay-up, calc.) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 2.3 ≈ 50.9 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter ≈ 50.9 mm Mingda four-core unarmored table

Approx. cable weight ≈ 6435 kg/km Mingda 6435 (Al ≈ 2669)

Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV

Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)

Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter

Flame-retardant class ZC (ZR) — GB/T 19666

Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.


ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution


9. Application. Heavy distribution risers, plant switchboards, motor sub-feeds, transformer secondaries — conduit, tray, trench, duct, trunking; indoor or sheltered outdoor.


ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution


10. Ordering. ZR-YJV 0.6/1 kV 4×150 + length/drum + marking; confirm against factory test certificate.


ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution