ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution
Product Summary
Product Details
zr-yjv 4 cores cable
,zr-yjv 25 sq mm 4 core cable
,copper 4 cores cable
Product Description
ZR-YJV 4*150mm² Flame Retardant Copper Power Cable for Industrial Power Distribution
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
4×150 mm² |
Four equal cores of 150 mm² copper conductor |
Construction: Four 150 mm² copper conductors (3 phase + 1 neutral), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).

ZC-YJV 4×150 mm² — LV Flame-Retardant Four-Core Power Cable — Specification
1. Overview & Ratings. ZC-YJV 4×150 is a heavy four-wire LV main feeder cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C PVC sheath: four equal 150 mm² compacted copper cores (L1/L2/L3 + N), dry-cured XLPE, unarmored, 2+2 lay. OD ≈ 35 mm, ≈ 5600 kg/km (est.), ≈ 300 A per core free air at 30 °C (est.). Scope: heavy main feeders, large motor banks, transformer secondaries and plant distribution trunks — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Conductors L1/L2/L3/N | 4×150 compacted Cu, Class 2, ≈37 strands | R ≤0.124 Ω/km all cores |
| Strand compaction | Concentric layers rolled compact per core | Compact heavy bundle, clean lugs |
| XLPE insulation | Dry-cured PE, ≈1.8 mm | Uniform 90°C dielectric |
| Core identification | L1/L2/L3/N color-coded insulation | Correct sequence at switchboard |
| 2+2 core laying | Four equal cores in two pairs | Round heavy finished bundle |
| PVC ZC sheath | Class C, ≈1.8 mm overall | Self-extinguishes, prints clear |
3. Electrical Characteristics. All 150 cores R ≤ 0.124 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 300 A per core (est., air 30 °C); short-circuit ≈ 16 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 0.124 Ω/km per core |
GB/T 3956 Class 2 Cu max (150 mm²) |
|
AC resistance @90 °C (est.) |
≈ 0.159 Ω/km per core |
— |
|
Current rating in air (30 °C) |
3-phase: 330 A |
4×150, touching, in free air |
|
Current rating in tray (30 °C) |
3-phase: 360 A |
4×150, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
3-phase: 340 A |
direct buried |
|
Current rating in conduit (30 °C) |
3-phase: 290 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 16.5 kA (16,500 A) per core |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.26 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 4×150 at 330 A three-phase, 400 V → max load ≈ 198 kW (cos φ = 0.8). Suitable for extra-large three-phase distribution with full-size neutral, heavy industrial equipment, and main building feeders.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; survives large-unit start-stop cycling; indoor preferred, UV jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. Hydraulic crimp 150 mm² lugs on all four cores, heavy glands to ≈35 mm OD, torque per table; bend ≥ 15×OD ≈ 525 mm; apply conduit-fill and tray-grouping derating; keep the bundle tidy; verify four-core continuity, phase sequence, neutral and insulation before energizing.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 578 mm at Ø38.5 mm |
four-core unarmoured |
|
Max. pulling tension |
2,250 N per core (150 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Heavy-duty cable tray, ladder, cleats |
— |
|
Conduit ID |
≥ 80 mm |
— |
|
Fixing |
heavy-duty cleats, cable ties |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. Heavy main feeders, large motor banks, transformer secondaries, plant distribution trunks and large-unit supply circuits.

7. Testing & QA Regime (16 items). Routine: DC resistance on all cores, 3.5 kV withstand, insulation resistance, continuity, insulation and sheath thickness, dimensional check, strand construction, eccentricity, color ID, print legibility, mass, jacket finish, packing inspection. Type: ZC flame test, short-circuit rating.
Cable Parameter
| ZR-YJV 4×150 mm² — Flame-Retardant Four-Core Power Cable (0.6/1 kV) · Product Parameters | ||||
| CU / XLPE / PVC · 4 × 150 mm² · GB/T 12706.1, IEC 60502-1, GB/T 3956, GB/T 19666 · nominal values for reference | ||||
| Overall Ø ≈ 50.9 mm | Approx. weight ≈ 6435 kg/km (Al ≈ 2669) | |||
| DC resistance ≤ 0.124 Ω/km @ 20 °C (per core) | Ampacity ≈ 325 A (air) / 345 A (buried) @ 25 °C | |||
| No. | Parameter | Value | Unit | Notes / Standard Reference |
| 1 · Identification | ||||
| 1 | Product name | Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable (four-core) | — | ZR-YJV; halogen-containing flame-retardant |
| 2 | Model | ZR-YJV 4×150 | — | 4 cores × 150 mm²; CU / XLPE / PVC |
| 3 | Design standards | GB/T 12706.1; IEC 60502-1 | — | Conductor GB/T 3956; fire GB/T 19666 |
| 4 | Rated voltage U0/U | 0.6/1 | kV | Um = 1.2 kV; AC 50 Hz |
| 5 | Core arrangement | 4 cores (L1/L2/L3 + N) | — | Three phases + neutral |
| 6 | Nominal cross-section | 150 | mm² | Per core, GB/T 3956 |
| 2 · Conductor | ||||
| 1 | Material | Plain annealed copper | — | High conductivity |
| 2 | Class | Class 2 (stranded) | — | GB/T 3956 / IEC 60228 |
| 3 | Stranding (per core) | 37 × 2.26 mm (37/2.26) | — | 1+6+12+18 concentric rings |
| 4 | Conductor diameter | ≈ 15.80 | mm | Per core (7 × 2.26) |
| 5 | Max. DC resistance @ 20 °C | 0.124 | Ω/km | GB/T 3956 Class 2 Cu |
| 3 · Insulation | ||||
| 1 | Material | Cross-linked polyethylene (XLPE) | — | Thermally cross-linked |
| 2 | Nominal thickness | 1.4 | mm | GB/T 12706.1 (150 mm² step) |
| 3 | Diameter over insulation | ≈ 18.60 | mm | Per core (calculated) |
| 4 · Assembly | ||||
| 1 | Core lay-up | Four cores around dry central filler + binder tape | — | Round bundle |
| 2 | Diameter over lay-up | ≈ 44.9 | mm | Calculated |
| 5 · Sheath | ||||
| 1 | Material | Flame-retardant PVC, ST2 | — | Black (or as ordered) |
| 2 | Nominal thickness | 2.3 | mm | GB/T 12706.1 / Mingda four-core table |
| 3 | Overall diameter | ≈ 50.9 | mm | Mingda 50.9 |
| 4 | Approx. cable weight | ≈ 6435 | kg/km | Mingda 6435 (Al ≈ 2669) |
| 6 · Electrical | ||||
| 1 | DC conductor resistance | 0.124 | Ω/km | GB/T 3956 @ 20 °C, per core |
| 2 | Routine voltage test | 3.5 kV / 5 min | — | No breakdown; 50 Hz AC |
| 3 | Insulation resistance | ≥ 36.7 | MΩ·km | Finished cable @ 20 °C |
| 4 | XLPE volume resistivity | ≥ 1 × 10¹² | Ω·cm | Material level |
| 5 | Capacitance (approx.) | ≤ 0.45 | μF/km | Per core |
| 6 | Ampacity — air @ 25 °C (4 cores) | ≈ 325 | A | Mingda; 3×150 agrees |
| 7 | Ampacity — buried @ 25 °C | ≈ 345 | A | Mingda; soil resistivity dependent |
| 7 · Thermal | ||||
| 1 | Continuous conductor temperature | 90 | °C | XLPE class |
| 2 | Short-circuit temperature (≤ 5 s) | 250 | °C | GB/T 12706.1 / IEC 60502-1 |
| 3 | Ambient service range | -20 to +45 | °C | Per datasheet family |
| 4 | Min. laying temperature | 0 | °C | Pre-heat below 0 °C |
| 8 · Fire (ZR) | ||||
| 1 | Flame-retardant class | ZC by default ("ZR") | — | GB/T 19666; halogen-containing PVC |
| 2 | Single-cable flame test | Pass | — | GB/T 18380.12 |
| 3 | Bunched flame test — class C | Char ≤ 2.5 m | — | GB/T 18380.35; 20 min; ≥ 1.5 L/m |
| 4 | Halogen content | Halogen-containing | — | LSZH needs WDZ-YJY |
| 9 · Installation | ||||
| 1 | Min. bending radius (multi-core) | ≥ 15 × OD | — | GB 50168 practice |
| 2 | Laying methods | Conduit, tray, trench, duct, trunking | — | Mechanical protection where buried |
| 3 | Site test after installation | DC 4U0 = 2.4 kV / 15 min | — | Q/GDW 13244.1-2018 |
| 10 · Packing | ||||
| 1 | Standard delivery length | 100 m per coil/drum | — | Custom lengths available |
| 2 | Marking | Model, voltage, maker, year, length marks | — | GB/T 6995 / project spec |
Cable Test Parameter
| ZR-YJV 4×150 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1) | ||||
| Stage | Test Item | Method / Standard | Acceptance Criterion | Notes |
| Routine | Conductor DC resistance | GB/T 3956 (IEC 60228) | ≤ 0.124 Ω/km @ 20 °C (per core) | Every production length |
| Routine | Power-frequency withstand voltage | GB/T 12706.1 / IEC 60502-1 | 3.5 kV AC / 5 min, no breakdown | Conductor-to-earth/water |
| Routine | Construction check | GB/T 2951 | Ins. ≥ 1.4 mm; sheath ≥ 2.3 mm; OD within tolerance | Thickness & diameter |
| Sample | Hot set test — XLPE | GB/T 12706.1 §16.3.13 / GB/T 2951.11 | 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % | Cross-linking degree |
| Sample | Conductor construction & diameter | GB/T 3956 | Class 2; 37 × 2.26 mm; Ø ≈ 15.80 mm | Per batch |
| Type | Single-cable flame test | GB/T 18380.12 | No flame spread to top reference | ZR property |
| Type | Bunched flame test — class C | GB/T 18380.35 | Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m | ZC class |
| Type | Bending test | GB/T 12706.1 | No damage on specified mandrel | Multi-core rule |
| Post-install | DC withstand test | Q/GDW 13244.1-2018 | 2.4 kV DC / 15 min, no breakdown | New installations |
| Optional | Insulation resistance @ 20 °C | Factory method | ≥ 36.7 MΩ·km | Not routine in GB/T 12706.1 |
| Optional | XLPE volume resistivity | Material test | ≥ 1 × 10¹² Ω·cm | Material reference |
Cable Cross Section Structure

| ZR-YJV 4×150 mm² — Cable Cross-Section Structure (Schematic) | |||||
| Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Cu) × 4 | Annealed copper, Class 2 stranded — 37 × 2.26 mm per core (37/2.26, 1+6+12+18), nominal 150 mm² per core | — | ≈ 15.80 (Ø per core) | Current-carrying element; max DC resistance ≤ 0.124 Ω/km @ 20 °C (per core) |
| 2 | Insulation (XLPE) × 4 | Cross-linked polyethylene | 1.4 | ≈ 18.60 (Ø per core, over insulation) | Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min |
| 3 | Core lay-up | Four insulated cores laid up around central non-hygroscopic filler; binder tape | — | ≈ 44.9 (Ø over lay-up, calc.) | Forms a round assembly for sheathing |
| 4 | Outer sheath (PVC) | Flame-retardant PVC, ST2 type, black | 2.3 | ≈ 50.9 (Ø overall) | Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666 |
| Key Dimensions & Properties | |||||
| Overall diameter | ≈ 50.9 | mm | Mingda four-core unarmored table | ||
| Approx. cable weight | ≈ 6435 | kg/km | Mingda 6435 (Al ≈ 2669) | ||
| Rated voltage | 0.6/1 | kV | AC 50 Hz; max system voltage Um = 1.2 kV | ||
| Max conductor temperature | 90 / 250 | °C | Continuous / short-circuit (≤ 5 s) | ||
| Min. bending radius (multi-core) | ≥ 15 × OD | — | OD = actual cable diameter | ||
| Flame-retardant class | ZC (ZR) | — | GB/T 19666 | ||
| Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate. | |||||
Product Structure Introduction
| Product Structure Introduction — ZR-YJV 4×150 mm² | |||
| Four-core layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV | |||
| 1. Cable General Description | |||
| ZR-YJV 4×150 is a halogen-containing flame-retarding four-core cable, rated 0.6/1 kV, with four 150 mm² copper conductors, XLPE dielectric and an ST2 PVC outer cover. It is designed and type-tested per GB/T 12706.1 / IEC 60502-1, uses GB/T 3956 conductor grading and carries a ZC flame class under GB/T 19666. It measures ≈ 50.9 mm over the sheath, weighs ≈ 6435 kg/km, and 100 m coils or drums are customary. | |||
| The four loaded cores pass roughly 325 A in air at 25 °C, which suits heavy risers, plant switchboards and motor sub-feeds. | |||
| 2. Conductor Design & Build | |||
| A 150 mm² core consists of thirty-seven 2.26 mm annealed copper wires (37/2.26), arranged in the 1+6+12+18 concentric pattern of Class 2 and compacted to ≈ 15.80 mm. The DC resistance limit is 0.124 Ω/km at 20 °C; the four-ring pack provides a firm, round core for crimping and glanding. | |||
| 3. Insulation Design & Build | |||
| XLPE is extruded at 1.4 mm — the 150 mm² wall step of GB/T 12706.1 — making each core ≈ 18.60 mm over insulation. The compound is rated for 90 °C continuous duty and 250 °C for five seconds in fault; it keeps volume resistivity at or above 1×10¹² Ω·cm and passes the 3.5 kV AC five-minute routine proof. | |||
| 4. Assembly, Filling & Jacketing | |||
| The four cores are stranded around a dry, non-hygroscopic central filler, secured by binder tape to about 44.9 mm, and jacketed with 2.3 mm of flame-retarded ST2 PVC to close at 50.9 mm. ZC fire behaviour follows from GB/T 18380.12 and GB/T 18380.35; halogen-bearing PVC means LSZH duty should specify WDZ-YJY. | |||
| 5. Site, Storage & Maintenance Notes | |||
| • Do not bend inside 15 × OD. • Carry out the DC 4U0 = 2.4 kV / 15 min site test before switching on. • Service band −20 to +45 °C; warm drums for pulls under 0 °C. • Adjust the 325 A / 345 A reference for ambient, grouping and burial conditions. • Use lugs and glands sized for the 15.80 mm core and 50.9 mm jacket. |
8. Factory Advantages.
- Equal-size four-core build — full 150 neutral handles unbalance and harmonic return without extra selection.
- Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent on long main feeders.
- Dosed ZC compound — self-extinguishing jacket protects switchrooms and plant rooms.
- Length-on-demand — cut to exact main feeder meter with sealed ends.
- Uniform resistance log — all four cores' R recorded to lot for balanced performance.
- Continuous print line — type, size, ZC, voltage and length readable along the run.
- Phase-color option — L1/L2/L3/N colors reduce wiring errors at switchboards.
- Heavy drum pack — heavy section on a rated wooden drum, moisture-sealed ends.
- Certified QA pack — routine + type test record shipped per batch for commissioning.

9. Packaging, Storage & Logistics. Cut to measured main feeder length on a heavy wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.

10. Procurement Specification. State "ZC-YJV 4×150", length, class C, core colors; note full-size neutral suits harmonics and unbalance; request the uniform resistance log and 16-item QA record. Est. values confirmed against the factory certificate; not fire-rated.
11. Cable Industry FAQ.
- Q1: How does 4×150 differ from 4×70? Heavier section: cores 150 vs 70 mm²; OD 35 vs 26 mm, mass 5600 vs 3300 kg/km, core current 300 vs 175 A, R 0.124 vs 0.268 Ω/km; built for main feeders and motor banks rather than mid-heavy branch circuits.
- Q2: Why a full-size neutral here? A 150 neutral matches the phases to absorb large-unit unbalance and VFD/rectifier harmonics on a four-wire feeder.
- Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
- Q4: Core DC resistance? ≤0.124 Ω/km at 20°C on every 150 core.
- Q5: Screen or armor? Unscreened standard; add braid near VFD EMI; steel-tape armor for buried ground-crushing duty.
- Q6: Current per core? ≈300 A (est.) free air 30°C; derate in crowded ducts and trays.
- Q7: Bending? ≈525 mm (15×OD); use bending tools and sheaves.
- Q8: Connectors? 150 mm² lugs on all four cores; gland to ≈35 mm OD.
- Q9: Indoor or outdoor? Indoor preferred; specify UV-stabilized jacket for exposed runs.
- Q10: Packing? Heavy wooden drum with moisture-sealed ends.
- Q11: What proof ships? Uniform resistance log + 16-test record; est. values confirmed against certificate.