logo
Anhui Tongdu International Trade Co., Ltd.
Online Service

Online Service

Contact Person
+86 19056002718
WeChat QR Code
Follow Us

ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring

ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 4*120mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer sheath — flame-retardant grade, ...

Product Details

Highlight:

zr-yjv 4 cores cable

,

zr-yjv 25 sq mm 4 core cable

,

copper 4 cores cable

Conductor (×4):
Bare Annealed Copper, Class 2 Stranded, Commonly 37×∅2.03 Mm (also 19×∅2.85 Mm Compact), Conductor Ø ≈ 13.5–14.5 Mm Depending On Compaction
Conductor nominal area (per core):
120 Mm²
Number of cores:
4
Conductor construction:
Class 2, 37×∅2.03 Mm,IEC 60228 / GB/T 3956, Min. 15 Wires
Conductor diameter (approx.):
13.5–14.5 Mm
Insulation (×4):
XLPE
Insulation thickness:
1.2 Mm (120 Mm² Class)
Diameter over insulated core:
15.9–16.9 Mm,conductor + 2×1.2
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
2.2 Mm (GB/T 12706 Multi-core 120 Mm² Class)
Overall cable diameter:
37.0 – 44.0 Mm
Design outer diameter:
≈ 40.0 Mm
Approx. weight:
4400 – 5800 Kg/km
Design weight:
≈ 4700 Kg/km
Cable shape:
Round

Product Description

ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×120 mm²

Four cores, nominal copper conductor area 120 mm² per core

ZR-YJV 4×120 mm² — Technical Product Note

1. Product Overview. ZR-YJV 4×120 is a four-core flame-retardant LV power cable — four 120 mm² copper conductors, XLPE insulation, PVC sheath, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz. Built to GB/T 12706.1 / IEC 60502-1; conductors per GB/T 3956 / IEC 60228; fire class ZC (ZR) per GB/T 19666 / GB/T 18380.


ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring


2. Construction Stack. Conductor → outer sheath:

Layer Build Wall Diameter
Conductor (×4) Annealed Cu, Class 2, 37 × 2.03 mm (37/2.03, 1+6+12+18) each, 120 mm² per core — ≈ 14.20 mm per core
Insulation (×4) Cross-linked polyethylene 1.2 mm ≈ 16.60 mm per core (over ins.)
Lay-up Four cores + central filler + binder tape — ≈ 40.1 mm (calc.)
Sheath Flame-retarded PVC, ST2, black 2.1 mm ≈ 46.0 mm overall

Approx. weight ≈ 5244 kg/km (Al version ≈ 2178 kg/km).


ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring


3. Electrical Ratings. DC resistance ≤ 0.153 Ω/km per core @ 20 °C; routine 3.5 kV / 5 min; XLPE volume resistivity ≥ 1×10¹² Ω·cm; finished insulation resistance ≥ 36.7 MΩ·km; capacitance ≤ 0.45 μF/km. Reference ampacity (four cores loaded) ≈ 285 A in air / 310 A direct-buried @ 25 °C — Mingda 4×120, cross-checked with Mingda 3×120 (285/310 A identical per-core values).


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.153 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.199 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core)

≈ 300–315 A

common catalogue value

Current rating in air (design)

≈ 305 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 315–355 A

common catalogue 320–350 A

Design buried rating

≈ 330 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 12.0 kA

reference

Frequency

50/60 Hz AC

—


4. Thermal & Mechanical. Continuous 90 °C; short-circuit 250 °C (≤ 5 s); ambient −20 to +45 °C; laying ≥ 0 °C; min. bend radius ≥ 15 × OD (multi-core).


ZR-YJV 4×120 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV, Four-Core)
Construction: CU / XLPE / PVC, 4 cores  •  Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance)  •  Nominal values for reference — confirm against factory test certificate
No. Category Parameter Value Unit Notes / Standard Reference
A. Product Identification
1 Identification Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable (four-core) — Designation ZR-YJV; "ZR" = flame-retardant, halogen-containing
2 Identification Model designation ZR-YJV 4×120 — 4 cores × 120 mm²; Cu / XLPE / PVC
3 Identification Design standards GB/T 12706.1; IEC 60502-1 — Conductor: GB/T 3956 / IEC 60228; fire rating: GB/T 19666, GB/T 18380
4 Identification Rated voltage U0/U 0.6/1 kV Max system voltage Um = 1.2 kV
5 Identification Rated frequency 50 Hz AC power distribution
6 Identification Number of cores 4 — Three phases (L1/L2/L3) + neutral (N)
7 Identification Nominal cross-sectional area 120 mm² Per core; nominal section per GB/T 3956
B. Cable Construction (from conductor to outer sheath)
8 Conductor Material Plain annealed copper (Cu) — High-conductivity copper
9 Conductor Conductor class Class 1 or Class 2 (typical: Class 2, stranded) — GB/T 3956 / IEC 60228
10 Conductor Typical stranding construction (per core) 37 wires × 2.03 mm (37/2.03) — Class 2 round stranded (1+6+12+18 concentric); nominal 120 mm² per core
11 Conductor Conductor diameter (per core) ≈ 14.20 mm Ø of the 37/2.03 stranded core (7 × 2.03)
12 Conductor Max. DC resistance of conductor at 20 °C 0.153 Ω/km GB/T 3956, Class 2 copper
13 Insulation Material Cross-linked polyethylene (XLPE) — Thermally cross-linked; natural/transparent
14 Insulation Nominal insulation thickness 1.2 mm GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 120 mm²)
15 Insulation Diameter over insulation (per core) ≈ 16.60 mm ≈ 14.20 + 2 × 1.2 (calculated)
16 Lay-up Core assembly Four insulated cores laid up around a central non-hygroscopic filler; binder tape over the bundle — Round construction; classic 4-core geometry
17 Sheath Material Flame-retardant polyvinyl chloride (PVC, ST2 type) — Colour: black (or as ordered)
18 Sheath Nominal sheath thickness 2.1 mm GB/T 12706.1 / IEC 60502-1 (Mingda four-core table)
19 Dimensions Approx. overall diameter ≈ 46.0 mm Mingda 46.0 (four-core unarmored)
20 Dimensions Approx. cable weight ≈ 5244 kg/km Mingda 5244 (aluminium version ≈ 2178 kg/km)
C. Electrical Performance
21 Electrical Max. DC conductor resistance at 20 °C 0.153 Ω/km GB/T 3956; routine measurement (per core)
22 Electrical Power-frequency withstand voltage (routine test) 3.5 kV / 5 min, no breakdown — AC 50 Hz; per GB/T 12706.1 / IEC 60502-1
23 Electrical Insulation resistance (finished cable, 20 °C) ≥ 36.7 MΩ·km Typical finished-cable reference for 0.6/1 kV XLPE cables
24 Electrical XLPE volume resistivity at 20 °C ≥ 1 × 10¹² Ω·cm Material-level requirement (manufacturer reference)
25 Electrical Capacitance (approx., per core) ≤ 0.45 μF/km Manufacturer reference value
26 Electrical Reference ampacity — in air, 25 °C, four cores loaded ≈ 285 A Mingda 285 A; Mingda 3×120 agrees per-core @25 °C
27 Electrical Reference ampacity — direct burial, 25 °C ≈ 310 A Mingda 310 A; 3×120 also 310 A; soil thermal resistivity dependent
D. Thermal Performance
28 Thermal Max. continuous conductor temperature 90 °C XLPE insulation temperature class
29 Thermal Max. conductor temperature under short-circuit (≤ 5 s) 250 °C Per GB/T 12706.1 / IEC 60502-1
30 Thermal Ambient service temperature range -20 to +45 °C Per manufacturer datasheet family; check project specification
31 Thermal Min. installation (laying) temperature 0 °C Pre-heat the cable if ambient is below 0 °C
E. Flame Retardance (ZR)
32 Flame retardance Flame-retardant class ZC (class C) by default for "ZR" — GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH)
33 Flame retardance Single-cable vertical flame-spread test Pass — GB/T 18380.12
34 Flame retardance Bunched flame-spread test (class C) Char extent ≤ 2.5 m above burner bottom edge — GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min
35 Flame retardance Halogen content Halogen-containing (PVC) — For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type
F. Installation
36 Installation Min. bending radius — multi-core cable ≥ 15 × OD — GB 50168 practice for multi-core XLPE cables
37 Installation Laying methods Conduit, tray, cable trench, duct, building trunking, supported/suspended aerial — Direct burial with mechanical protection where permitted
38 Installation Site withstand test after installation DC 4U0 = 2.4 kV, 15 min (recommended) — Per utility procurement standard Q/GDW 13244.1-2018
G. Packing & Delivery
39 Packing Standard delivery length 100 m per coil/drum (or as ordered) — Typical industry practice; custom lengths available
40 Packing Cable marking Model, rated voltage, manufacturer, year of manufacture, sequential length marks — Per GB/T 6995 / project specification
41 Packing Packing form Coil (carton drum) / wooden drum / export packing — As per customer requirement



5. Fire Behaviour. Passes GB/T 18380.12 single-burn and class-C bunched GB/T 18380.35 (char ≤ 2.5 m) → ZC per GB/T 19666. PVC is halogen-containing — select WDZ-YJY where LSZH is mandatory.


Technical Datasheet — Flame-Retardant (FR) Characteristics
ZR-YJV  0.6/1 kV  4 × 120 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Code / Item Meaning / Value Standard / Note
ZR Flame Retardant (legacy prefix); under GB/T 19666-2019 defaults to Class C; modern equivalent = ZC GB/T 19666-2019
YJ XLPE — cross-linked polyethylene insulation —
V PVC outer sheath — flame-retardant grade, contains halogen (Cl) GB/T 19666-2019
0.6/1 kV Rated voltage U₀/U = 600/1000 V; maximum Uₘ = 1.2 kV IEC 60502-1
4 × 120 mm² Four cores, nominal copper conductor area 120 mm² per core (all cores equal) —
Construction Unarmoured, non-screened, round multi-core —
Application note Four-core → three-phase AC with neutral (L1+L2+L3+N) or with PE (L1+L2+L3+PE), equal conductor sizes —
2.  Flame-Retardant & Fire Performance  (CORE)
Property Value / Requirement Standard
Flame Retardant Class Class C (bundled cables, char length ≤ 2.5 m) GB/T 19666-2019; GB/T 18380.3 / IEC 60332-3-24
Legacy designation ZR (= ZC); modern prefix preferred: ZC GB/T 19666-2019
Test method — flame Bunched flame test (category C), char ≤ 2.5 m after flame removal GB/T 18380.3 (IEC 60332-3-24)
Halogen content Contains halogen — Cl from PVC sheath; releases HCl on burning GB/T 17650 / IEC 60754-1/-2
Smoke density Heavy dark smoke — NOT low-smoke (no LSZH certification) GB/T 17651 / IEC 61034
Corrosivity Corrosive — HCl gas generated during fire GB/T 17650 / IEC 60754-2
pH / conductivity of gases Not certified (PVC base — acidic / conductive combustion gases) GB/T 17650 / IEC 60754-2
Limited Oxygen Index (LOI) PVC typical ≈ 45–49 % O₂ (reference, design value) ASTM D2863 / GB/T 2406, reference
Max. conductor operating temp. 90 °C (long-term service) GB/T 12706.1-2020
Max. short-circuit temp. (≤5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) IEC 60502-1
Service ambient range (PVC sheath) −15 °C to +90 °C —
Min. installation ambient temp. 0 °C (pre-heat required below 0 °C) —
Note: ZR = Flame Retardant only — it does NOT imply low-smoke (LSZH) or fire-survival. PVC sheath is halogenated; upgrade to WDZ-YJY / WDZN-YJY for LSZH or NH-ZR-YJV for fire-survival circuits.
3.  Fire Test Summary
Test Requirement ZR-YJV 4×120 Verdict
Bunched flame test (Class C) Char length ≤ 2.5 m PASS (design, Class C)
Single flame test (IEC 60332-1) Self-extinguishing PASS (XLPE/PVC FR)
Smoke density (IEC 61034) Light transmittance ≥ 60 % for LSZH N/A (PVC = heavy smoke)
Halogen content (IEC 60754) ≤ 0.5 % HCl for LSZH N/A (contains Cl)
Acidity / corrosivity (IEC 60754-2) pH ≥ 4.3; conductivity ≤ 10 µS/mm for LSZH N/A (corrosive HCl)
Fire-survival (BS 6387 / IEC 60331) Circuit integrity during/after fire N/A — use NH-ZR-YJV / WDZN-YJY
4.  Key Electrical & Thermal Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.153 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.199 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 300–315 A (design ≈ 305 A) 4-core
Current rating — direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) ≈ 315–355 A (design ≈ 330 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 12.0 kA reference
Frequency 50/60 Hz AC —
Design recommendation: ≈ 305 A in air / ≈ 330 A buried, then apply grouping & ambient + soil-thermal-resistivity correction. Buried rating often > air rating due to better heat dissipation under reference conditions. Catalogue values vary by maker — confirm before specification.
5.  Construction & Material Specification
Layer (inside → out) Description / Specification FR Contribution
Conductor (×4) Bare annealed copper, Class 2 stranded, 37×∅2.03 mm, conductor Ø ≈ 13.5–14.5 mm None (Cu non-combustible)
Conductor screen Omitted (not required for 0.6/1 kV) —
Insulation (×4) XLPE, colours: brown/black/grey/blue etc., 1.2 mm nominal XLPE — low flame spread
Filler Flame-retardant PP / PE to form round assembly FR additive
Binder Flame-retardant tape over laid-up cores FR barrier
Outer sheath Flame-retardant PVC (ZR grade), 2.2 mm nominal, black Primary FR layer (halogenated)
Armour None —
Metallic screen None —
6.  Dimensional Data
Item Typical Value Remarks
Conductor nominal area (per core) 120 mm² —
Number of cores 4 —
Conductor construction Class 2, 37×∅2.03 mm IEC 60228 / GB/T 3956, min. 15 wires
Conductor diameter (approx.) 13.5–14.5 mm compact vs solid-round
Insulation thickness 1.2 mm 120 mm² class
Diameter over insulated core 15.9–16.9 mm conductor + 2×1.2
Sheath thickness 2.2 mm GB/T 12706, 120 mm² class
Overall cable diameter ≈ 38.0–42.0 mm (catalogue range 37.0–44.0 mm) plain-round design
Design outer diameter ≈ 40.0 mm common Chinese maker value
Approx. weight 4400 – 5800 kg/km (plain YJV Cu ≈ 4500–4800) design ≈ 4700 kg/km
Cable shape Round —
7.  Mechanical & Installation Parameters
Parameter Value Note
Minimum bending radius (unarmoured multi-core) ≥ 15 × OD ≈ 555–600 mm @ Ø37–40 mm (≈ 600 mm @ 40 mm) —
Max. pulling tension (Cu only) 50 N/mm² × 120 mm² × 4 = 24,000 N = 24 kN total use conductor sock, avoid sheath grip
Direct burial Allowed in non-aggressive soil; for mechanical load / road crossing use ZR-YJV22 4×120 —
Conduit ID ≥ 1.5 × OD → ≥ 56–60 mm (use 63 mm or 75 mm conduit) —
Fixing spacing Horizontal tray ≈ 800 mm; vertical ≈ 1500 mm —
Elevation difference limit None (XLPE) —
8.  Selection Guide — When FR Matters
Scenario Recommended Cable Reason
Flame-retardant, halogenated acceptable (standard) ZR-YJV 4×120 (this cable) Class C FR, PVC sheath, cost-effective
Low-smoke halogen-free required (LSZH) WDZ-YJY 4×120 LSZH sheath — IEC 61034 / IEC 60754 compliant
Fire-survival circuit (circuit integrity) NH-ZR-YJV / WDZN-YJY 4×120 BS 6387 / IEC 60331 fire-survival grade
Heavy mechanical load / buried under roads ZR-YJV22 4×120 Steel-tape armoured version
Separate PE and N required 5-core version (e.g. 5×120 or 4×120+1×70) 4×120 has combined/shared PE-N only
Applicable standards: GB/T 12706.1-2020 (equiv. IEC 60502-1) · GB/T 3956 / IEC 60228 · GB/T 19666-2019 · GB/T 18380.3 · GB/T 17651 / IEC 61034 · GB/T 17650 / IEC 60754.  |  Packing: steel-wooden drum or coil, 100–500 m typical.  |  HS code (China): 8544 4921.
Values are typical / design reference. Plain-round 120 mm² shows maker-to-maker dimensional variance (OD 37–44 mm, weight 4400–5800 kg/km) — always confirm with manufacturer test reports & relevant local regulations before final specification.


6. Verification Plan. Routine: resistance, 3.5 kV/5 min, construction (ins. ≥ 1.2 mm, sheath ≥ 2.1 mm). Sample: XLPE hot-set (200 ± 3 °C / 15 min / 0.2 MPa). Type: flame + bending. Site: DC 4U0 = 2.4 kV / 15 min (Q/GDW 13244.1-2018).


ZR-YJV 4×120 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Test Stage Test Item Method / Standard Requirement / Acceptance Criterion Notes
Routine test Conductor DC resistance measurement GB/T 3956 (IEC 60228) ≤ 0.153 Ω/km at 20 °C (per core) Measured on every production length
Routine test Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC, 5 min, no breakdown Applied between each conductor and earth/water; 50 Hz
Routine test Construction check — insulation & sheath thickness, outer diameter GB/T 2951 Within GB/T 12706.1 tolerances Insulation ≥ 1.2 mm nominal; sheath ≥ 2.1 mm nominal
Sample test Hot set (thermal elongation) test — XLPE insulation GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % Verifies degree of cross-linking
Sample test Conductor construction & diameter check GB/T 3956 Class 2; 37 × 2.03 mm; Ø ≈ 14.20 mm Sampled per batch
Type test Single-cable vertical flame-spread test (flame retardance) GB/T 18380.12 No flame spread; charring does not reach top reference point ZR / ZC flame-retardant property
Type test Bunched flame-spread test, class C GB/T 18380.35 Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m Class ZC per GB/T 19666
Type test Bending test (mechanical) GB/T 12706.1 Bend around specified mandrel without insulation/sheath damage Mandrel diameter related to cable OD (multi-core)
Post-installation DC withstand test after installation Q/GDW 13244.1-2018 (recommended practice) 4U0 = 2.4 kV DC, 15 min, no breakdown For new installations; verify project specification
Optional Insulation resistance measurement at 20 °C Manufacturer test method ≥ 36.7 MΩ·km (typical finished-cable value) Not a routine item in GB/T 12706.1; confirm with factory
Optional XLPE volume resistivity at 20 °C Manufacturer / material test ≥ 1 × 10¹² Ω·cm Material-level reference



7.Insulation Test Parameters


Insulation Test Data
ZR-YJV  0.6/1 kV  4 × 120 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Item Description Standard / Note
Designation ZR-YJV 0.6/1 kV 4×120 mm² GB/T 12706.1-2020
Conductor Bare annealed copper, Class 2 stranded, 37×∅2.03 mm GB/T 3956 / IEC 60228
Insulation XLPE (cross-linked polyethylene), 1.2 mm nominal GB/T 12706.1-2020
Outer sheath Flame-retardant PVC (ZR grade), 2.2 mm nominal, black GB/T 19666-2019
Rated voltage U₀/U 0.6 / 1 kV (Uₘ = 1.2 kV) IEC 60502-1
Number of cores 4 (three-phase L1+L2+L3+N or L1+L2+L3+PE, equal sizes) —
2.  Insulation Design Data  (CORE)
Parameter Value Remarks
Insulation material XLPE (cross-linked polyethylene) —
Nominal thickness (eₙ) 1.2 mm 120 mm² class
Minimum allowable thickness (e_min) 0.96 mm eₙ − 0.24 mm (GB/T 12706.1-2020, Table 3)
Insulator colours Brown/black/grey/blue or red/yellow/blue/green-yellow (or as specified) IEC 60446
Volume resistivity @ 90 °C ≥ 10¹² Ω·cm —
Dielectric loss factor (tan δ) @ 20 °C ≤ 1 × 10⁻³ reference
Relative permittivity (εᵣ) ≈ 2.3 – 2.5 reference
Long-term service temp. 90 °C GB/T 12706.1-2020
Short-circuit temp. (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 – 130 °C transient
Diameter over insulated core 15.9–16.9 mm conductor 13.5–14.5 + 2×1.2
3.  Thermal Characteristics
Property Value Remarks
Max. conductor operating temp. (normal) 90 °C long-term
Max. conductor temp. — short-circuit (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) —
Min. installation ambient temp. 0 °C (pre-heat below 0 °C) —
Service ambient range (PVC sheath) −15 °C to +90 °C —
Flame retardant class (sheath) Class C (ZR per GB/T 19666) —
4.  Insulation Test Schedule
Test Item Test Value / Condition Result
Routine withstand test (AC) 3.5 kV AC, 5 min — no breakdown PASS
Type test voltage 4.0 kV AC PASS (IEC 60502-1)
Partial discharge test ≤ 10 pC @ 1.73 U₀ (1.73 kV) PASS (XLPE)
Insulation resistance (IR) ≥ 10⁴ MΩ·km @ 20 °C (reference) PASS
Hot-set test (XLPE cross-linking) 200 °C, 15 min, load 0.2 N/mm² — elongation ≤ 175 %, permanent set ≤ 15 % PASS (IEC 60811-507)
Aging test (air oven) 135 °C, 168 h — tensile strength / elongation retained ≥ 80 % PASS
Tensile strength (insulation) ≥ 12.5 MPa (XLPE, before aging) PASS
Elongation at break (insulation) ≥ 200 % (XLPE, before aging) PASS
Cold bend test −15 °C, 4 h — no cracking PASS
Water absorption ≤ 1 mg/cm² (85 °C, 336 h, reference) PASS
Breakdown voltage (insulation) ≥ 20 kV/mm (reference) PASS
DC resistance of conductor @ 20 °C ≤ 0.153 Ω/km (Class 2 Cu, per core) PASS (GB/T 3956)
Dielectric loss (tan δ) measurement ≤ 1 × 10⁻³ @ 20 °C PASS (reference)
Spark test (during production) 6 – 10 kV (online), pinhole detection PASS
Thickness measurement (microscopic) eₙ = 1.2 mm; e_min ≥ 0.96 mm PASS
5.  Electrical Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.153 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.199 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 300–315 A (design ≈ 305 A) 4-core
Current rating — direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) ≈ 315–355 A (design ≈ 330 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 12.0 kA reference
Frequency 50/60 Hz AC —
6.  Dimensional / Inspection Result
Item Design / Limit Measured (example)
Conductor construction Class 2, 37×∅2.03 mm 37×2.03 mm
Conductor diameter 13.5–14.5 mm 14.2 mm
Insulation thickness (each core) 1.2 mm (min. 0.96 mm) 1.22 / 1.20 / 1.21 / 1.18 mm
Diameter over insulated core 15.9–16.9 mm 16.6 mm
Sheath thickness 2.2 mm (min. 1.9 mm) 2.21 mm
Overall cable diameter ≈ 38.0–42.0 mm (range 37.0–44.0) 40.5 mm
DC resistance @ 20 °C (per core) ≤ 0.153 Ω/km 0.150 Ω/km
Approx. weight 4400 – 5800 kg/km (design ≈ 4700) 4680 kg/km
Footnotes
1. All tests performed at ambient 20 ± 5 °C and 45–75 % RH unless otherwise stated.
2. Routine tests: withstand (3.5 kV / 5 min), conductor resistance, dimensional check. Type tests: 4.0 kV, partial discharge, hot-set, aging, mechanical (per IEC 60502-1).
3. Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.
4. Insulation thickness for 120 mm² class = 1.2 mm nominal (GB/T 12706.1-2020, Table 3); minimum = 1.2 − 0.24 = 0.96 mm. Sheath thickness = 2.2 mm for 120 mm² class.
5. For low-smoke halogen-free → use WDZ-YJY 4×120; for fire-survival → NH-ZR-YJV / WDZN-YJY 4×120; for armoured → ZR-YJV22 4×120.
6. Plain-round 120 mm² shows maker-to-maker dimensional variance (OD 37–44 mm, weight 4400–5800 kg/km); design values are mid-range estimates — verify with manufacturer catalog.


8.Cross Section Structure


ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring


ZR-YJV 4×120 mm² — Cable Cross-Section Structure (Schematic)
Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 4 Annealed copper, Class 2 stranded — 37 × 2.03 mm per core (37/2.03, 1+6+12+18), nominal 120 mm² per core — ≈ 14.20 (Ø per core) Current-carrying element; max DC resistance ≤ 0.153 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 4 Cross-linked polyethylene 1.2 ≈ 16.60 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Four insulated cores laid up around central non-hygroscopic filler; binder tape — ≈ 40.1 (Ø over lay-up, calc.) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 2.1 ≈ 46.0 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter ≈ 46.0 mm Mingda four-core unarmored table

Approx. cable weight ≈ 5244 kg/km Mingda 5244 (Al ≈ 2178)

Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV

Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)

Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter

Flame-retardant class ZC (ZR) — GB/T 19666

Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.


Product Structure Introduction — ZR-YJV 4×120 mm² 
Four-core layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV
1. Cable Presentation
ZR-YJV 4×120 is a flame-retarding four-core power cable, rated 0.6/1 kV, that carries four 120 mm² copper cores under XLPE insulation and a single PVC jacket. It follows the construction rules of GB/T 12706.1 / IEC 60502-1 and carries the ZC flame classification by default under GB/T 19666. Outside diameter 46.0 mm and weight 5244 kg/km; coils and drums of 100 m are the normal supply unit.
The four cores allow a complete three-phase-plus-neutral feed in one cable, which shortens installation time on building services and industrial feeders.
2. Conductor Description
Each 120 mm² core is stranded from thirty-seven 2.03 mm annealed copper wires (37/2.03) laid in four concentric rings (1+6+12+18), Class 2 per GB/T 3956, forming a conductor of ≈ 14.20 mm. Resistance is held to 0.153 Ω/km at 20 °C. The dense ring pack keeps the core round and gives a stable termination area for lugs and glands.
3. Insulation & Dielectric
Cross-linked polyethylene is extruded at 1.2 mm, the wall for the 120 mm² step in GB/T 12706.1, bringing the over-insulation diameter to ≈ 16.60 mm per core. XLPE keeps a 90 °C continuous rating and a 250 °C five-second short-circuit ceiling, with volume resistivity ≥ 1×10¹² Ω·cm and a 3.5 kV five-minute routine proof.
4. Assembly & Jacket
The four insulated cores are laid up with a dry central filler and held with binder tape into a bundle of about 40.1 mm, then jacketed with 2.1 mm of flame-retarded ST2 PVC, closing at 46.0 mm. Fire behaviour satisfies ZC via GB/T 18380.12 and GB/T 18380.35; since PVC is halogen-bearing, LSZH projects should specify WDZ-YJY instead.
5. Handling & Application
• Keep bend radius above 15 × OD.  • Apply the DC 4U0 = 2.4 kV / 15 min site test before first energising.  • Ambient range −20 to +45 °C; warm the drum for pulls below 0 °C.  • Derate the 285 A (air) / 310 A (soil) reference for ambient, grouping and burial factors.  • Match lugs and glands to the 14.20 mm core and 46.0 mm sheath.


9. Usage Cautions. Bend ≥ 15 × OD; use rollers/stockings on long runs; guard against crushing; DC site test before energising; derate for ambient/grouping/burial; fit lugs and glands for the ≈ 14.20 mm core.


ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring


10. Application Range. Three-phase + neutral feeders, distribution boards, sub-distribution and large motor circuits at 0.6/1 kV — building risers, plant rooms, transformer secondaries, pump/HVAC circuits — in conduit, tray, trench, duct, trunking; indoor or sheltered outdoor.


ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring


9. Ordering. ZR-YJV 0.6/1 kV 4×120 + length/drum + marking. Standard 100 m; confirm against the factory test certificate.


ZR-YJV 4*120mm² Flame Retardant Copper Power Cable for Building & Industrial Wiring