ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath

ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 4×35mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath Cable Designation & Meaning Code Meaning ZC Flame retardant Class C YJ Cross-linked polyethylene (XLPE) insulation V Polyvinyl chloride (PVC) sheath 4×35 mm² Four equal cores of 35 mm² copper conductor Construction: ...

Product Details

Highlight:

zr-yjv 4 cores cable

,

zr-yjv 25 sq mm 4 core cable

,

copper 4 cores cable

Currentrating:
25A
Insulationmaterial:
PVC
Numberofcores:
4
Shielding:
None
Cablediameter:
10mm
Flameretardant:
Yes
Cabletype:
Multi-core Power Cable
Colorcode:
Red, Yellow, Blue, Black
Standardcompliance:
IEC 60502
Conductormaterial:
Copper
Outersheathmaterial:
PVC
Temperaturerating:
-20°C To 70°C
Productname:
4 Cores Cable
Voltagerating:
600/1000V
Application:
Power Distribution, Industrial Wiring

Product Description

ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath

Cable Designation & Meaning

Code

Meaning

ZC

Flame retardant Class C 

YJ

Cross-linked polyethylene (XLPE) insulation 

V

Polyvinyl chloride (PVC) sheath 

4×35 mm²

Four equal cores of 35 mm² copper conductor


Construction: Four 35 mm² copper conductors (3 phase + 1 neutral), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).



ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath

ZC-YJV 4×35 mm² — LV Flame-Retardant Four-Core Power Cable — Specification 

1. Overview & Ratings. ZC-YJV 4×35 is a mid four-core LV feeder cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C PVC sheath: four equal 35 mm² compacted copper cores (L1/L2/L3 phases plus a full neutral), dry-cured XLPE, unarmored. OD ≈ 18 mm, ≈ 1900 kg/km (est.), ≈ 110 A per core free air at 30 °C (est.). Scope: mid power distribution, workshop feeders, mid motors and trunk branches — not 950°C fire duty.


2. Construction Stack (Inner → Outer, expanded).


Layer / Feature Build Function
Conductors L1/L2/L3/N 4×35 compacted Cu, Class 2, ≈12 strands R ≤0.524 Ω/km
Strand compaction Concentric layers rolled compact per core Compact bundle, clean lugs
XLPE insulation (all cores) Dry-cured PE, ≈1.4 mm Uniform 90°C dielectric
2+2 core laying Four equal cores in two rows Round finished bundle
PVC ZC sheath Class C, ≈1.4 mm overall Self-extinguishes, prints clear
Jacket print Continuous type/size/voltage/length On-site readable spec


3. Electrical Characteristics. All four cores R ≤ 0.524 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 110 A per core (est., air 30 °C); short-circuit ≈ 4.0 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.

Insulation & Sheath Data

Property

Value

Insulation material

XLPE (cross-linked polyethylene)

Outer sheath material

PVC (ST₂)

Long-term service temp.

90 °C (continuous)

Max. conductor temp. (normal)

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Test voltage AC (5 min)

3.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹⁴ Ω·cm

Shield

None as standard (can be added)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage

1.2 kV AC

—

Test voltage AC (5 min)

3.5 kV

Routine test

DC resistance @20 °C

≤ 0.524 Ω/km per core

GB/T 3956 Class 2 Cu max (35 mm²)

AC resistance @90 °C (est.)

≈ 0.671 Ω/km per core

—

Current rating in air (30 °C)

3-phase: 115 A​

4×35, touching, in free air

Current rating in tray (30 °C)

3-phase: 130 A​

4×35, spaced 2×OD

Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W)

3-phase: 125 A​

direct buried

Current rating in conduit (30 °C)

3-phase: 100 A​

—

Short-circuit current (1 s, Cu, 250 °C)

≈ 3.9 kA (3,900 A) per core

—

Capacitance (core-to-sheath, approx.)

≈ 0.17 µF/km

XLPE

Inductive reactance (approx.)

≈ 0.08 Ω/km

at 50 Hz

Frequency

50/60 Hz AC

—


Reference values: 4×35 at 115 A three-phase, 400 V → max load ≈ 69 kW​ (cos φ = 0.8). Suitable for medium three-phase distribution with full-size neutral, medium industrial motors, and building sub-main feeders.


4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; survives motor start-stop and feeder cycling; indoor preferred, UV jacket optional.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Min. installation ambient temp.

0 °C (below 0 °C requires preheating)

Service ambient range

−20 °C to +90 °C

Flexing temp. range

0 °C to +90 °C

Fire Performance (ZC-YJV — Flame Retardant C)

Property

Value / Requirement

Flame retardant

GB/T 18380.12 / IEC 60332-1-2​ (single cable, self-extinguishing)

Flame retardant class

Class C​ (ZC) per GB/T 19666

Halogen content

Contains halogen (PVC sheath)

Smoke density

Not low-smoke (PVC)

Corrosivity

Corrosive (PVC)

Toxicity

Toxic fumes when burned (PVC)

EMI shielding

None (no metallic screen/armour)


5. Installation Practice & Handling. 35 mm² lugs on all four cores, glands to ≈18 mm OD, crimp/torque per table; bend ≥ 15×OD ≈ 270 mm; apply duct/tray derating; keep the bundle tidy; verify four-core continuity, phase sequence, neutral and insulation before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 330 mm at Ø22.0 mm

four-core unarmoured

Max. pulling tension

525 N per core (35 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Suitable (with sand bedding)

—

Surface mounting

Cable tray, ladder, cleats

—

Conduit ID

≥ 40 mm

—

Fixing

cable ties, cleats

—

Impact resistance

Moderate

—

Water resistance

Good (PVC sheath)

—

UV resistance

Fair (PVC degrades outdoors, use UV-resistant PVC or conduit)

—

Flex life

Good (Class 2 stranded)

fixed installation

Termination note

Standard compression lugs or mechanical connectors

—


6. Typical Service Applications. Mid three-phase feeders, workshop motors, trunk branches, sub-distribution boards, panel-to-panel links and vertical riser branches.

ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


7. Testing & QA Regime (16 items). Routine: DC resistance on all four 35 cores, 3.5 kV withstand, insulation resistance, four-core continuity, insulation thickness, sheath thickness, dimensional check, strand construction, eccentricity, core color identification, print legibility, mass, jacket finish, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.


Cable Parameters


ZR-YJV 4×35 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV, Four-Core)
Construction: CU / XLPE / PVC, 4 cores  •  Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance)  •  Nominal values for reference — confirm against factory test certificate
No. Category Parameter Value Unit Notes / Standard Reference
A. Product Identification
1 Identification Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable (four-core) — Designation ZR-YJV; "ZR" = flame-retardant, halogen-containing
2 Identification Model designation ZR-YJV 4×35 — 4 cores × 35 mm²; Cu / XLPE / PVC
3 Identification Design standards GB/T 12706.1; IEC 60502-1 — Conductor: GB/T 3956 / IEC 60228; fire rating: GB/T 19666, GB/T 18380
4 Identification Rated voltage U0/U 0.6/1 kV Max system voltage Um = 1.2 kV
5 Identification Rated frequency 50 Hz AC power distribution
6 Identification Number of cores 4 — Three phases (L1/L2/L3) + neutral (N)
7 Identification Nominal cross-sectional area 35 mm² Per core; nominal section per GB/T 3956
B. Cable Construction (from conductor to outer sheath)
8 Conductor Material Plain annealed copper (Cu) — High-conductivity copper
9 Conductor Conductor class Class 1 or Class 2 (typical: Class 2, stranded) — GB/T 3956 / IEC 60228
10 Conductor Typical stranding construction (per core) 7 wires × 2.52 mm (7/2.52) — Class 2 round stranded; nominal section 35 mm² per core
11 Conductor Conductor diameter (per core) ≈ 7.56 mm Ø of the 7/2.52 stranded core (3 × 2.52)
12 Conductor Max. DC resistance of conductor at 20 °C 0.524 Ω/km GB/T 3956, Class 2 copper
13 Insulation Material Cross-linked polyethylene (XLPE) — Thermally cross-linked; natural/transparent
14 Insulation Nominal insulation thickness 0.9 mm GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 25–35 mm² band)
15 Insulation Diameter over insulation (per core) ≈ 9.36 mm ≈ 7.56 + 2 × 0.9 (calculated)
16 Lay-up Core assembly Four insulated cores laid up around a central non-hygroscopic filler; binder tape over the bundle — Round construction; classic 4-core geometry
17 Sheath Material Flame-retardant polyvinyl chloride (PVC, ST2 type) — Colour: black (or as ordered)
18 Sheath Nominal sheath thickness 1.8 mm GB/T 12706.1 / IEC 60502-1 (Mingda four-core table)
19 Dimensions Approx. overall diameter ≈ 27.1 mm Mingda 27.1 (four-core unarmored)
20 Dimensions Approx. cable weight ≈ 1626 kg/km Mingda 1626 (aluminium version ≈ 731.8 kg/km)
C. Electrical Performance
21 Electrical Max. DC conductor resistance at 20 °C 0.524 Ω/km GB/T 3956; routine measurement (per core)
22 Electrical Power-frequency withstand voltage (routine test) 3.5 kV / 5 min, no breakdown — AC 50 Hz; per GB/T 12706.1 / IEC 60502-1
23 Electrical Insulation resistance (finished cable, 20 °C) ≥ 36.7 MΩ·km Typical finished-cable reference for 0.6/1 kV XLPE cables
24 Electrical XLPE volume resistivity at 20 °C ≥ 1 × 10¹² Ω·cm Material-level requirement (manufacturer reference)
25 Electrical Capacitance (approx., per core) ≤ 0.45 μF/km Manufacturer reference value
26 Electrical Reference ampacity — in air, 25 °C, four cores loaded ≈ 125 A Mingda 125 A; Lvbao 4×35+1×16 also 125 A @25 °C
27 Electrical Reference ampacity — direct burial, 25 °C ≈ 155 A Mingda 155 A; Lvbao 4×35+1×16 155 A; soil thermal resistivity dependent
D. Thermal Performance
28 Thermal Max. continuous conductor temperature 90 °C XLPE insulation temperature class
29 Thermal Max. conductor temperature under short-circuit (≤ 5 s) 250 °C Per GB/T 12706.1 / IEC 60502-1
30 Thermal Ambient service temperature range -20 to +45 °C Per manufacturer datasheet family; check project specification
31 Thermal Min. installation (laying) temperature 0 °C Pre-heat the cable if ambient is below 0 °C
E. Flame Retardance (ZR)
32 Flame retardance Flame-retardant class ZC (class C) by default for "ZR" — GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH)
33 Flame retardance Single-cable vertical flame-spread test Pass — GB/T 18380.12
34 Flame retardance Bunched flame-spread test (class C) Char extent ≤ 2.5 m above burner bottom edge — GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min
35 Flame retardance Halogen content Halogen-containing (PVC) — For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type
F. Installation
36 Installation Min. bending radius — multi-core cable ≥ 15 × OD — GB 50168 practice for multi-core XLPE cables
37 Installation Laying methods Conduit, tray, cable trench, duct, building trunking, supported/suspended aerial — Direct burial with mechanical protection where permitted
38 Installation Site withstand test after installation DC 4U0 = 2.4 kV, 15 min (recommended) — Per utility procurement standard Q/GDW 13244.1-2018
G. Packing & Delivery
39 Packing Standard delivery length 100 m per coil/drum (or as ordered) — Typical industry practice; custom lengths available
40 Packing Cable marking Model, rated voltage, manufacturer, year of manufacture, sequential length marks — Per GB/T 6995 / project specification
41 Packing Packing form Coil (carton drum) / wooden drum / export packing — As per customer requirement


Cable Test Parameters


ZR-YJV 4×35 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Test Stage Test Item Method / Standard Requirement / Acceptance Criterion Notes
Routine test Conductor DC resistance measurement GB/T 3956 (IEC 60228) ≤ 0.524 Ω/km at 20 °C (per core) Measured on every production length
Routine test Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC, 5 min, no breakdown Applied between each conductor and earth/water; 50 Hz
Routine test Construction check — insulation & sheath thickness, outer diameter GB/T 2951 Within GB/T 12706.1 tolerances Insulation ≥ 0.9 mm nominal; sheath ≥ 1.8 mm nominal
Sample test Hot set (thermal elongation) test — XLPE insulation GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % Verifies degree of cross-linking
Sample test Conductor construction & diameter check GB/T 3956 Class 2; 7 × 2.52 mm; Ø ≈ 7.56 mm Sampled per batch
Type test Single-cable vertical flame-spread test (flame retardance) GB/T 18380.12 No flame spread; charring does not reach top reference point ZR / ZC flame-retardant property
Type test Bunched flame-spread test, class C GB/T 18380.35 Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m Class ZC per GB/T 19666
Type test Bending test (mechanical) GB/T 12706.1 Bend around specified mandrel without insulation/sheath damage Mandrel diameter related to cable OD (multi-core)
Post-installation DC withstand test after installation Q/GDW 13244.1-2018 (recommended practice) 4U0 = 2.4 kV DC, 15 min, no breakdown For new installations; verify project specification
Optional Insulation resistance measurement at 20 °C Manufacturer test method ≥ 36.7 MΩ·km (typical finished-cable value) Not a routine item in GB/T 12706.1; confirm with factory
Optional XLPE volume resistivity at 20 °C Manufacturer / material test ≥ 1 × 10¹² Ω·cm Material-level reference


Cable Cross Section Structure

ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath

ZR-YJV 4×35 mm² — Cable Cross-Section Structure (Schematic)
Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 4 Annealed copper, Class 2 stranded — 7 × 2.52 mm per core (7/2.52), nominal 35 mm² per core — ≈ 7.56 (Ø per core) Current-carrying element; max DC resistance ≤ 0.524 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 4 Cross-linked polyethylene 0.9 ≈ 9.36 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Four insulated cores laid up around central non-hygroscopic filler; binder tape — ≈ 22.6 (Ø over lay-up, calc.) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.8 ≈ 27.1 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter ≈ 27.1 mm Mingda four-core unarmored table

Approx. cable weight ≈ 1626 kg/km Mingda 1626 (Al ≈ 731.8)

Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV

Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)

Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter

Flame-retardant class ZC (ZR) — GB/T 19666

Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.


Product Structure Introduction


Product Structure Introduction — ZR-YJV 4×35 mm² 
Four-core layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV
1. General Description
ZR-YJV 4×35 is a 0.6/1 kV AC flame-retarded four-core cable built on the classic copper / XLPE / PVC platform and manufactured to GB/T 12706.1 / IEC 60502-1, with stranding per GB/T 3956 / IEC 60228 and fire classification per GB/T 19666 (ZC default). Approx. outside diameter 27.1 mm and weight 1626 kg/km make it a typical rising-main and feeder cable at this section; it is delivered on 100 m coils or drums.
All four cores share the same 35 mm² section, so the neutral conductor can carry full phase current when required — a practical advantage for lighting and unbalanced single-phase loads.
2. Conductor System
Each core strands seven 2.52 mm annealed copper wires (7/2.52, Class 2) into a round conductor of ≈ 7.56 mm with a maximum DC resistance of 0.524 Ω/km at 20 °C. The stranded cross-section reduces skin-effect loss and keeps the cable flexible enough for switchgear cubicles and riser trunking.
3. Insulation System
XLPE insulation is applied at the 0.9 mm wall maintained through the 25–35 mm² band, bringing each core to ≈ 9.36 mm over insulation. Dielectric properties support a 3.5 kV AC five-minute routine test, continuous operation at 90 °C, and short-circuit peaks of 250 °C for up to five seconds, with volume resistivity ≥ 1×10¹² Ω·cm.
4. Sheath & Fire Performance
The four insulated cores are assembled around a dry central filler into a round bundle of about 22.6 mm and bound with tape, then jacketed with 1.8 mm of flame-retarded ST2 PVC to close at ≈ 27.1 mm. The ZC rating is proven through GB/T 18380.12 single and GB/T 18380.35 class-C bunched burning; because PVC carries halogen, projects demanding smoke/zero-halogen should move to WDZ-YJY.
5. Service Guidance
• Keep installation bends at or above 15 × OD.  • Prove the circuit with the DC 4U0 = 2.4 kV / 15 min test before energising.  • Ambient −20 to +45 °C in service; warm reels for pulls below 0 °C.  • Apply grouping, ambient and burial derating to the quoted ampacity.  • Terminate with lugs and glands sized for the ≈ 7.56 mm core.


8. Factory Advantages.

  • Equal-size four-core build — full neutral handles mid-motor unbalance and harmonic return without extra selection.
  • Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent on long feeder runs.
  • Dosed ZC compound — self-extinguishing jacket protects switchrooms and workshops from flame spread.
  • Length-on-demand — cut to exact feeder meter with sealed ends.
  • Uniform resistance log — all four 35 cores' R recorded to lot for balanced performance.
  • Continuous print line — type, size, ZC, voltage and length readable along the feeder run.
  • Phase-color option — L1/L2/L3/N colors reduce wiring errors at distribution boards.
  • Drum pack — section on a rated wooden drum, both ends moisture-sealed.
  • Certified QA pack — routine + type test record shipped per batch for commissioning.

ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


9. Packaging, Storage & Logistics. Cut to measured feeder length on a wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.


ZR-YJV 4×35mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


10. Procurement Specification. State "ZC-YJV 4×35", length, class C, phase colors; note the full neutral for mid-motor unbalance and not fire-rated; request the four-core resistance log and 16-item QA record. Est. values confirmed against the factory certificate.


11. Cable Industry FAQ.

  • Q1: How does 4×35 differ from 4×16? One size up: cores 35 vs 16 mm²; OD 18 vs 14 mm, mass 1900 vs 950 kg/km, current 110 vs 65 A, resistance 0.524 vs 1.15 Ω/km; built for mid workshop feeders rather than small lighting branches.
  • Q2: Why a full-size neutral? Mid motors and drives draw neutral current and harmonics; an equal 35 neutral prevents overheating.
  • Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
  • Q4: DC resistance values? All four 35 mm² cores ≤0.524 Ω/km at 20°C.
  • Q5: Screen or armor? Unscreened standard; add braid near VFD EMI; steel-tape armor for buried ground-crushing duty.
  • Q6: Current per core? ≈110 A (est.) free air 30°C; derate in crowded ducts.
  • Q7: Bending? ≈270 mm (15×OD); use bending tools and sheaves.
  • Q8: Connectors? 35 mm² lugs on L1/L2/L3/N; gland to ≈18 mm OD.
  • Q9: Indoor or outdoor? Indoor preferred; specify UV-stabilized jacket for exposed runs.
  • Q10: Packing? Wooden drum with moisture-sealed ends.
  • Q11: What proof ships? Four-core resistance log + 16-test record; est. values confirmed against certificate.