logo
Anhui Tongdu International Trade Co., Ltd.
Online Service

Online Service

Contact Person
+86 19056002718
WeChat QR Code
Follow Us

ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath

ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 4×25mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath Code Mean:ZR-Flame Retardant,YJ-XLPE Insulated,V-PVC Sheath ZR-YJV 4×25 mm² — Product Engineering File 1. Product Summary. ZR-YJV 4×25 is a four-core flame-retardant low-voltage cable — four 25 mm² copper conductors...

Product Details

Highlight:

zr-yjv 4 cores cable

,

zr-yjv 25 sq mm 4 core cable

,

copper 4 cores cable

Conductor (×4):
Bare Annealed Copper, Class 2 Stranded, 7×∅2.14 Mm, Conductor Ø ≈ 6.4 Mm
Conductor nominal area (per core):
25 Mm²
Number of cores:
4
Conductor construction:
Class 2, 7×∅2.14 Mm,min. 7 Wires
Conductor diameter (approx.):
6.4mm
Insulation (×4):
XLPE
Insulation thickness:
0.9 Mm (25 Mm² Class)
Diameter over insulated core:
8.2 Mm,6.4 + 2×0.9
Filler / binder:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.8 Mm (multi-core Rule, ≥1.8 Mm)
Overall cable diameter:
20.5 – 22.0 Mm
Approx. weight:
620 – 700 Kg/km
Long-term service temp.:
90 °C
Short-circuit temp. (≤5 s):
250 °C
Emergency overload:
105–130 °C
Routine test:
3.5 KV AC / 5 Min; Type Test 4.0 KV
Volume resistivity @90 °C:
≥ 10¹² Ω·cm

Product Description

ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


Code Mean:ZR-Flame Retardant,YJ-XLPE Insulated,V-PVC Sheath

ZR-YJV 4×25 mm² — Product Engineering File

1. Product Summary. ZR-YJV 4×25 is a four-core flame-retardant low-voltage cable — four 25 mm² copper conductors, XLPE insulation, PVC sheath, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz. Standards: GB/T 12706.1 / IEC 60502-1, conductors GB/T 3956 / IEC 60228, fire rating GB/T 19666 / GB/T 18380 (default ZC).


2. Construction Overview. Layer stack, conductor to jacket:

Layer Build Wall Diameter
Conductor (×4) Annealed copper, Class 2, 7 × 2.14 mm (7/2.14) each, 25 mm² per core — ≈ 6.40 mm per core
Insulation (×4) Cross-linked polyethylene 0.9 mm ≈ 8.20 mm per core (over ins.)
Lay-up Four cores + central filler + binder tape — ≈ 19.8 mm
Sheath Flame-retarded PVC, ST2, black 1.8 mm ≈ 24.3 mm overall

Approx. weight ≈ 1222 kg/km (Al version ≈ 577.6 kg/km).


ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


3. Electrical Ratings. DC resistance ≤ 0.727 Ω/km per core @ 20 °C; routine 3.5 kV / 5 min; XLPE volume resistivity ≥ 1×10¹² Ω·cm; typical insulation resistance ≥ 36.7 MΩ·km; capacitance ≤ 0.45 μF/km per core. Reference ampacity (all four cores loaded) ≈ 105 A in air / 125 A direct-buried @ 25 °C (Mingda; Lvbao 5×25 agrees at 105/125 A, Tongding 3×25+2×16 ≈ 107/130 A) — derate per GB/T 16895 / IEC 60364.


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.749 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.973 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core)

≈ 75 – 85 A

design ≈ 80 A

Direct buried (20 °C, soil 1.0 K·m/W, 0.7 m)

≈ 92 – 105 A

design ≈ 98 A

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 2.50 kA

reference

Frequency

50/60 Hz AC

—


4. Thermal & Bending. Continuous 90 °C; short-circuit 250 °C (≤ 5 s); ambient −20 to +45 °C; laying ≥ 0 °C; minimum bend radius ≥ 15 × OD (multi-core).


ZR-YJV 4×25 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV, Four-Core)
Construction: CU / XLPE / PVC, 4 cores  •  Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance)  •  Nominal values for reference — confirm against factory test certificate
No. Category Parameter Value Unit Notes / Standard Reference
A. Product Identification
1 Identification Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable (four-core) — Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing)
2 Identification Model designation ZR-YJV 4×25 — 4 cores × 25 mm²; Cu / XLPE / PVC
3 Identification Design standards GB/T 12706.1; IEC 60502-1 — Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380
4 Identification Rated voltage U0/U 0.6/1 kV Max system voltage Um = 1.2 kV
5 Identification Rated frequency 50 Hz AC power distribution
6 Identification Number of cores 4 — Four-core cable; three phase conductors (L1/L2/L3) + neutral (N)
7 Identification Nominal cross-sectional area 25 mm² Per core; nominal cross-section per GB/T 3956
B. Cable Construction (from conductor to outer sheath)
8 Conductor Material Plain annealed copper (Cu) — High-conductivity electrolytic / oxygen-free copper
9 Conductor Conductor class Class 1 or Class 2 (typical: Class 2, stranded) — GB/T 3956 / IEC 60228
10 Conductor Typical stranding construction (per core) 7 wires × 2.14 mm (7/2.14) — Class 2 round stranded; nominal section 25 mm² per core
11 Conductor Conductor diameter (per core) ≈ 6.40 mm Ø of the 7/2.14 stranded core (6.3–6.5 mm across practice)
12 Conductor Max. DC resistance of conductor at 20 °C 0.727 Ω/km GB/T 3956, Class 2 copper; acceptance criterion for 25 mm²
13 Insulation Material Cross-linked polyethylene (XLPE) — Thermally cross-linked; natural/transparent colour
14 Insulation Nominal insulation thickness 0.9 mm GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 25 mm²)
15 Insulation Diameter over insulation (per core) ≈ 8.20 mm ≈ 6.40 + 2 × 0.9 (calculated)
16 Lay-up Core assembly Four insulated cores laid up around a central non-hygroscopic filler; binder tape over the bundle — Round construction, right-hand lay; classic 4-core geometry
17 Sheath Material Flame-retardant polyvinyl chloride (PVC, ST2 type) — Colour: black (or as ordered)
18 Sheath Nominal sheath thickness 1.8 mm GB/T 12706.1 / IEC 60502-1 (Mingda four-core table)
19 Dimensions Approx. overall diameter ≈ 24.3 mm Mingda 24.3 (four-core unarmored)
20 Dimensions Approx. cable weight ≈ 1222 kg/km Mingda 1222 (aluminium version ≈ 577.6 kg/km)
C. Electrical Performance
21 Electrical Max. DC conductor resistance at 20 °C 0.727 Ω/km GB/T 3956; routine measurement (per core)
22 Electrical Power-frequency withstand voltage (routine test) 3.5 kV / 5 min, no breakdown — AC 50 Hz; per GB/T 12706.1 / IEC 60502-1
23 Electrical Insulation resistance (finished cable, 20 °C) ≥ 36.7 MΩ·km Typical finished-cable reference for 0.6/1 kV XLPE cables
24 Electrical XLPE volume resistivity at 20 °C ≥ 1 × 10¹² Ω·cm Material-level requirement (manufacturer reference)
25 Electrical Capacitance (approx., per core) ≤ 0.45 μF/km Manufacturer reference value
26 Electrical Reference ampacity — in air, 25 °C, four cores loaded ≈ 105 A Mingda 105 A; Lvbao 5×25 also 105 A @25 °C — derate per GB/T 16895 / IEC 60364
27 Electrical Reference ampacity — direct burial, 25 °C ≈ 125 A Mingda 125 A; Lvbao 5×25 125 A; Tongding 3×25+2×16 ≈ 130 A — depends on soil thermal resistivity
D. Thermal Performance
28 Thermal Max. continuous conductor temperature 90 °C XLPE insulation temperature class
29 Thermal Max. conductor temperature under short-circuit (≤ 5 s) 250 °C Per GB/T 12706.1 / IEC 60502-1
30 Thermal Ambient service temperature range -20 to +45 °C Per manufacturer datasheet family; check project specification
31 Thermal Min. installation (laying) temperature 0 °C Pre-heat the cable if ambient is below 0 °C
E. Flame Retardance (ZR)
32 Flame retardance Flame-retardant class ZC (class C) by default for "ZR" — GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH)
33 Flame retardance Single-cable vertical flame-spread test Pass — GB/T 18380.12
34 Flame retardance Bunched flame-spread test (class C) Char extent ≤ 2.5 m above burner bottom edge — GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min
35 Flame retardance Halogen content Halogen-containing (PVC) — For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type
F. Installation
36 Installation Min. bending radius — multi-core cable ≥ 15 × OD — GB 50168 practice for multi-core XLPE cables; OD = actual cable diameter
37 Installation Laying methods Conduit, tray, cable trench, duct, building trunking, supported/suspended aerial — Also direct burial with mechanical protection where permitted
38 Installation Site withstand test after installation DC 4U0 = 2.4 kV, 15 min (recommended) — Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project
G. Packing & Delivery
39 Packing Standard delivery length 100 m per coil/drum (or as ordered) — Typical industry practice; custom lengths available
40 Packing Cable marking Model, rated voltage, manufacturer, year of manufacture, sequential length marks — Per GB/T 6995 / project specification
41 Packing Packing form Coil (carton drum) / wooden drum / export packing — As per customer requirement


5.Test Parameters


ZR-YJV 4×25 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Test Stage Test Item Method / Standard Requirement / Acceptance Criterion Notes
Routine test Conductor DC resistance measurement GB/T 3956 (IEC 60228) ≤ 0.727 Ω/km at 20 °C (per core) Measured on every production length
Routine test Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC, 5 min, no breakdown Applied between each conductor and earth/water; 50 Hz
Routine test Construction check — insulation & sheath thickness, outer diameter GB/T 2951 Within GB/T 12706.1 tolerances Insulation ≥ 0.9 mm nominal; sheath ≥ 1.8 mm nominal
Sample test Hot set (thermal elongation) test — XLPE insulation GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % Verifies degree of cross-linking
Sample test Conductor construction & diameter check GB/T 3956 Class 2; 7 × 2.14 mm; Ø ≈ 6.40 mm Sampled per batch
Type test Single-cable vertical flame-spread test (flame retardance) GB/T 18380.12 No flame spread; charring does not reach top reference point ZR / ZC flame-retardant property
Type test Bunched flame-spread test, class C GB/T 18380.35 Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m Class ZC per GB/T 19666
Type test Bending test (mechanical) GB/T 12706.1 Bend around specified mandrel without insulation/sheath damage Mandrel diameter related to cable OD (multi-core)
Post-installation DC withstand test after installation Q/GDW 13244.1-2018 (recommended practice) 4U0 = 2.4 kV DC, 15 min, no breakdown For new installations; verify project specification
Optional Insulation resistance measurement at 20 °C Manufacturer test method ≥ 36.7 MΩ·km (typical finished-cable value) Not a routine item in GB/T 12706.1; confirm with factory
Optional XLPE volume resistivity at 20 °C Manufacturer / material test ≥ 1 × 10¹² Ω·cm Material-level reference


6. Fire Behaviour. Passes GB/T 18380.12 single burn and class-C bunched burn GB/T 18380.35 (char ≤ 2.5 m) → ZC per GB/T 19666. PVC is halogen-containing — select WDZ-YJY for zero-halogen projects.


Technical Datasheet — Flame-Retardant (FR) Characteristics
ZR-YJV  0.6/1 kV  4 × 25 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Code / Item Meaning / Value Standard / Note
ZR Flame Retardant (legacy prefix); under GB/T 19666-2019 defaults to Class C; modern equivalent = ZC GB/T 19666-2019
YJ XLPE — cross-linked polyethylene insulation —
V PVC outer sheath — flame-retardant grade, contains halogen (Cl) GB/T 19666-2019
0.6/1 kV Rated voltage U₀/U = 600/1000 V; maximum Uₘ = 1.2 kV IEC 60502-1
4 × 25 mm² Four cores, nominal copper conductor area 25 mm² per core (all cores equal) —
Construction Unarmoured, non-screened, round multi-core —
Application note Four-core → three-phase AC with neutral (L1+L2+L3+N) or with PE (L1+L2+L3+PE), equal conductor sizes —
2.  Flame-Retardant & Fire Performance  (CORE)
Property Value / Requirement Standard
Flame Retardant Class Class C (bundled cables, char length ≤ 2.5 m) GB/T 19666-2019; GB/T 18380.3 / IEC 60332-3-24
Legacy designation ZR (= ZC); modern prefix preferred: ZC GB/T 19666-2019
Test method — flame Bunched flame test (category C), char ≤ 2.5 m after flame removal GB/T 18380.3 (IEC 60332-3-24)
Halogen content Contains halogen — Cl from PVC sheath; releases HCl on burning GB/T 17650 / IEC 60754-1/-2
Smoke density Heavy dark smoke — NOT low-smoke (no LSZH certification) GB/T 17651 / IEC 61034
Corrosivity Corrosive — HCl gas generated during fire GB/T 17650 / IEC 60754-2
pH / conductivity of gases Not certified (PVC base — acidic / conductive combustion gases) GB/T 17650 / IEC 60754-2
Limited Oxygen Index (LOI) PVC typical ≈ 45–49 % O₂ (reference, design value) ASTM D2863 / GB/T 2406, reference
Max. conductor operating temp. 90 °C (long-term service) GB/T 12706.1-2020
Max. short-circuit temp. (≤5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) IEC 60502-1
Service ambient range (PVC sheath) −15 °C to +90 °C —
Min. installation ambient temp. 0 °C (pre-heat required below 0 °C) —
3.  Fire Test Summary
Test Requirement ZR-YJV 4×25 Verdict
Bunched flame test (Class C) Char length ≤ 2.5 m PASS (design, Class C)
Single flame test (IEC 60332-1) Self-extinguishing PASS (XLPE/PVC FR)
Smoke density (IEC 61034) Light transmittance ≥ 60 % for LSZH N/A (PVC = heavy smoke)
Halogen content (IEC 60754) ≤ 0.5 % HCl for LSZH N/A (contains Cl)
Acidity / corrosivity (IEC 60754-2) pH ≥ 4.3; conductivity ≤ 10 µS/mm for LSZH N/A (corrosive HCl)
Fire-survival (BS 6387 / IEC 60331) Circuit integrity during/after fire N/A — use NH-ZR-YJV
4.  Key Electrical & Thermal Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.749 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.973 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 75–85 A (design ≈ 80 A) 4-core
Current rating — direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) ≈ 92–105 A (design ≈ 98 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 2.50 kA reference
Frequency 50/60 Hz AC —
5.  Construction & Material Specification
Layer (inside → out) Description / Specification FR Contribution
Conductor (×4) Bare annealed copper, Class 2 stranded, 7×∅2.14 mm, conductor Ø ≈ 6.4 mm None (Cu non-combustible)
Conductor screen Omitted (not required for 0.6/1 kV) —
Insulation (×4) XLPE, colours: brown/black/grey/blue etc., 0.9 mm nominal XLPE — low flame spread
Filler Flame-retardant PP / PE to form round assembly FR additive
Binder Flame-retardant tape over laid-up cores FR barrier
Outer sheath Flame-retardant PVC (ZR grade), 1.8 mm nominal, black Primary FR layer (halogenated)
Armour None —
Metallic screen None —
6.  Dimensional Data
Item Typical Value Remarks
Conductor nominal area (per core) 25 mm² —
Number of cores 4 —
Conductor construction Class 2, 7×∅2.14 mm min. 7 wires
Conductor diameter (approx.) 6.4 mm —
Insulation thickness 0.9 mm 25 mm² class
Diameter over insulated core 8.2 mm 6.4 + 2×0.9
Sheath thickness 1.8 mm multi-core rule, ≥ 1.8 mm
Overall cable diameter 20.5 – 22.0 mm (use 21.2 mm for design) —
Approx. weight 620 – 700 kg/km (use ≈ 660 kg/km) —
Cable shape Round —
7.  Mechanical & Installation Parameters
Parameter Value Note
Minimum bending radius (unarmoured multi-core) ≥ 15 × OD ≈ 318 mm @ Ø21.2 mm —
Max. pulling tension (Cu only) 50 N/mm² × 25 mm² × 4 = 5,000 N total use conductor sock, avoid sheath grip
Direct burial Allowed in non-aggressive soil; for mechanical protection use ZR-YJV22 4×25 —
Conduit ID ≥ 1.5 × OD → ≥ 32 mm (use 40 mm conduit) —
Elevation difference limit None (XLPE) —
8.  Selection Guide — When FR Matters
Scenario Recommended Cable Reason
Flame-retardant, halogenated acceptable (standard) ZR-YJV 4×25 (this cable) Class C FR, PVC sheath, cost-effective
Low-smoke halogen-free required (LSZH) WDZ-YJY 4×25 LSZH sheath — IEC 61034 / IEC 60754 compliant
Fire-survival circuit (circuit integrity) NH-ZR-YJV 4×25 BS 6387 / IEC 60331 fire-survival grade
Heavy mechanical load / direct burial risk ZR-YJV22 4×25 Steel-tape armoured version
Separate PE and N required 5-core version 4×25 has combined/shared PE-N only


7. Verification. Routine: resistance, 3.5 kV/5 min, construction check (ins. ≥ 0.9 mm, sheath ≥ 1.8 mm). Sample: XLPE hot-set (200 ± 3 °C / 15 min / 0.2 MPa). Type: flame + bending. Site: DC 4U0 = 2.4 kV / 15 min (Q/GDW 13244.1-2018).


Insulation Test Data
ZR-YJV  0.6/1 kV  4 × 25 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Item Description Standard / Note
Designation ZR-YJV 0.6/1 kV 4×25 mm² GB/T 12706.1-2020
Conductor Bare annealed copper, Class 2 stranded, 7×∅2.14 mm GB/T 3956 / IEC 60228
Insulation XLPE (cross-linked polyethylene), 0.9 mm nominal GB/T 12706.1-2020
Outer sheath Flame-retardant PVC (ZR grade), 1.8 mm nominal, black GB/T 19666-2019
Rated voltage U₀/U 0.6 / 1 kV (Uₘ = 1.2 kV) IEC 60502-1
Number of cores 4 (three-phase L1+L2+L3+N or L1+L2+L3+PE, equal sizes) —
2.  Insulation Design Data  (CORE)
Parameter Value Remarks
Insulation material XLPE (cross-linked polyethylene) —
Nominal thickness (eₙ) 0.9 mm 25 mm² class
Minimum allowable thickness (e_min) 0.71 mm eₙ − 0.19 mm (GB/T 12706.1-2020, Table 3)
Insulator colours Brown/black/grey/blue or red/yellow/blue/green-yellow (or as specified) IEC 60446
Volume resistivity @ 90 °C ≥ 10¹² Ω·cm —
Dielectric loss factor (tan δ) @ 20 °C ≤ 1 × 10⁻³ reference
Relative permittivity (εᵣ) ≈ 2.3 – 2.5 reference
Long-term service temp. 90 °C GB/T 12706.1-2020
Short-circuit temp. (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 – 130 °C transient
Diameter over insulated core 8.2 mm conductor 6.4 + 2×0.9
3.  Thermal Characteristics
Property Value Remarks
Max. conductor operating temp. (normal) 90 °C long-term
Max. conductor temp. — short-circuit (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) —
Min. installation ambient temp. 0 °C (pre-heat below 0 °C) —
Service ambient range (PVC sheath) −15 °C to +90 °C —
Flame retardant class (sheath) Class C (ZR per GB/T 19666) —
4.  Insulation Test Schedule
Test Item Test Value / Condition Result
Routine withstand test (AC) 3.5 kV AC, 5 min — no breakdown PASS
Type test voltage 4.0 kV AC PASS (IEC 60502-1)
Partial discharge test ≤ 10 pC @ 1.73 U₀ (1.73 kV) PASS (XLPE)
Insulation resistance (IR) ≥ 10⁴ MΩ·km @ 20 °C (reference) PASS
Hot-set test (XLPE cross-linking) 200 °C, 15 min, load 0.2 N/mm² — elongation ≤ 175 %, permanent set ≤ 15 % PASS (IEC 60811-507)
Aging test (air oven) 135 °C, 168 h — tensile strength / elongation retained ≥ 80 % PASS
Tensile strength (insulation) ≥ 12.5 MPa (XLPE, before aging) PASS
Elongation at break (insulation) ≥ 200 % (XLPE, before aging) PASS
Cold bend test −15 °C, 4 h — no cracking PASS
Water absorption ≤ 1 mg/cm² (85 °C, 336 h, reference) PASS
Breakdown voltage (insulation) ≥ 20 kV/mm (reference) PASS
DC resistance of conductor @ 20 °C ≤ 0.749 Ω/km (Class 2 Cu, per core) PASS (GB/T 3956)
Dielectric loss (tan δ) measurement ≤ 1 × 10⁻³ @ 20 °C PASS (reference)
Spark test (during production) 6 – 10 kV (online), pinhole detection PASS
Thickness measurement (microscopic) eₙ = 0.9 mm; e_min ≥ 0.71 mm PASS
5.  Electrical Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.749 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.973 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 75–85 A (design ≈ 80 A) 4-core
Current rating — direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) ≈ 92–105 A (design ≈ 98 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 2.50 kA reference
Frequency 50/60 Hz AC —
6.  Dimensional / Inspection Result
Item Design / Limit Measured (example)
Conductor construction Class 2, 7×∅2.14 mm 7×2.14 mm
Conductor diameter ≈ 6.4 mm 6.3 mm
Insulation thickness (each core) 0.9 mm (min. 0.71 mm) 0.92 / 0.90 / 0.91 / 0.88 mm
Diameter over insulated core 8.2 mm 8.1 mm
Sheath thickness 1.8 mm (min. 1.5 mm) 1.82 mm
Overall cable diameter 20.5 – 22.0 mm (design 21.2) 21.1 mm
DC resistance @ 20 °C (per core) ≤ 0.749 Ω/km 0.738 Ω/km
Approx. weight 620 – 700 kg/km (≈ 660) 658 kg/km
Footnotes
1. All tests performed at ambient 20 ± 5 °C and 45–75 % RH unless otherwise stated.
2. Routine tests: withstand (3.5 kV / 5 min), conductor resistance, dimensional check. Type tests: 4.0 kV, partial discharge, hot-set, aging, mechanical (per IEC 60502-1).
3. Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.
4. Insulation thickness for 25 mm² class = 0.9 mm nominal (GB/T 12706.1-2020, Table 3); minimum = 0.9 − 0.19 = 0.71 mm.
5. For low-smoke halogen-free → use WDZ-YJY 4×25; for fire-survival → NH-ZR-YJV 4×25; for armoured → ZR-YJV22 4×25.


8.Cross Section Structure


ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


ZR-YJV 4×25 mm² — Cable Cross-Section Structure (Schematic)
Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale






No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 4 Annealed copper, Class 2 stranded — 7 × 2.14 mm per core (7/2.14), nominal 25 mm² per core — ≈ 6.40 (Ø per core) Current-carrying element; max DC resistance ≤ 0.727 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 4 Cross-linked polyethylene 0.9 ≈ 8.20 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Four insulated cores laid up around central non-hygroscopic filler; binder tape — ≈ 19.8 (Ø over lay-up) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.8 ≈ 24.3 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter ≈ 24.3 mm Mingda four-core unarmored table

Approx. cable weight ≈ 1222 kg/km Mingda 1222 (Al ≈ 577.6)

Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV

Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)

Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter

Flame-retardant class ZC (ZR) — GB/T 19666

Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.


ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


Product Structure Introduction — ZR-YJV 4×25 mm² 
Four-core layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV
1. Product Role
ZR-YJV 4×25 is a flame-retardant four-core power cable rated 0.6/1 kV AC, from the copper / XLPE / PVC product family. It is made to GB/T 12706.1 / IEC 60502-1, with conductors per GB/T 3956 / IEC 60228 and the flame class per GB/T 19666 (ZC default). Approx. outside diameter 24.3 mm, weight ≈ 1222 kg/km, supplied on 100 m coils or drums.
Four equal 25 mm² cores suit three-phase-plus-neutral circuits, typically balanced so the neutral carries only imbalance current.
2. Conductor Build-Up
Each 25 mm² core is stranded from seven 2.14 mm annealed copper wires — 7/2.14 Class 2 — to ≈ 6.40 mm diameter. Maximum DC resistance per core is 0.727 Ω/km at 20 °C. The heavier section still bends acceptably for risers and trunking because of the round stranded construction.
3. Insulation Build-Up
Insulation thickness steps up to 0.9 mm at this size; each core is covered and the diameter over insulation reaches ≈ 8.20 mm. XLPE gives 90 °C continuous service, 250 °C for five seconds under short-circuit, volume resistivity of at least 1×10¹² Ω·cm, and passes a routine 3.5 kV AC, five-minute withstand.
4. Assembly & Sheathing
The four insulated cores are twisted around a central dry filler into a round bundle of ≈ 19.8 mm, held by binder tape. A 1.8 mm flame-retarded PVC (ST2) jacket is extruded over the bundle to close at ≈ 24.3 mm. ZC fire performance is confirmed by GB/T 18380.12 and GB/T 18380.35; as the PVC carries halogen, WDZ-YJY is the right selection for zero-halogen projects.
5. Practical Notes
• Keep bends ≥ 15 × OD.  • Carry out the DC 4U0 = 2.4 kV / 15 min site test before energising.  • Service ambient −20 to +45 °C; warm reels when pulling below 0 °C.  • Apply ambient, grouping and burial derating — ratings are whole-cable values.  • Use lugs and glands sized for the ≈ 6.40 mm core.


9. Usage Cautions. Bend ≥ 15 × OD; pull by stocking; avoid kinking; protect from UV/impact; run the DC site test before energising; balance L1–L3 loads; size lugs for the ≈ 6.40 mm core.


ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


10. Application Range. Three-phase + neutral feeders and sub-distribution at 0.6/1 kV — building mains, distribution boards, HVAC/pump circuits — in conduit, trays, trenches, ducts, trunking; indoor or sheltered outdoor.


ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath


11. Ordering Information. ZR-YJV 0.6/1 kV 4×25, length and drum type, marking. Standard 100 m; confirm all figures against the factory test certificate.


ZR-YJV 4×25mm² Flame Retardant Copper Power Cable, 0.6/1kV XLPE Insulated PVC Sheath