BTTRZ Flame Retardant Cable 4x150mm2+1x120mm2 Mineral Insulated Cable
Product Summary
Product Details
bttrz flame retardant cable
,flame retardant cable 4x150mm2
,1x120mm2 mineral insulated cable
Product Description
Ultra Fire Cable BTTRZ 4x150mm²+1x120mm² Mineral Insulated 0.6/1kV Fire Resistant
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
BTTRZ |
B = Wiring cable (fixed installation); T = Copper conductor (flexible); T = Copper sheath (corrugated welded tube); R = Flexible; Z = Heavy-duty (mineral insulated) |
|
0.6/1 kV |
Rated voltage U₀/U = 0.6/1 kV; Uₘ = 1.2 kV |
|
4×150 mm² + 1×120 mm² |
Four power cores 150 mm² + one protective earth core 120 mm² (5-core, 4+1 configuration) |
Construction: Flexible mineral-insulated fire-resistant cable, corrugated copper tube sheath, round profile (5-core)
Note: BTTRZ employs Class 5 fine-stranded flexible copper conductors. Each core is insulated with fire-resistant mica tape plus XLPE (or ceramic silicone rubber). Cores are assembled with mineral fillers and enclosed in a continuously welded corrugated copper tube sheath, which serves simultaneously as armour, water barrier, and PE conductor. The 4+1 configuration is designed for TN-S three-phase five-wire systems; the PE conductor is 120 mm². Per GB/T 16895 / IEC 60364, for phase conductor S > 35 mm², PE ≥ S/2. Since phase = 150 mm², S/2 = 75 mm², thus PE = 120 mm² exceeds the minimum requirement and is fully compliant (many projects specify PE = phase or PE ≈ 0.8×phase for added safety margin).

BTTRZ 4×150 + 1×120 mm² — Cable Specification & Engineering Data
1. Product Overview & Rating Summary. BTTRZ 4×150+1×120 is a flexible mineral-insulated fire-resistant power cable rated 0.6/1 kV (Um = 1.2 kV) at 50 Hz, built around four 150 mm² tinned-copper Class 5 flexible phase conductors and one 120 mm² neutral/earth conductor. Unlike rigid magnesium-oxide mineral-insulated cables, BTTRZ uses mica-tape wrapped insulation enclosed in a continuously corrugated copper tube, then jacketed in a low-smoke zero-halogen (LSZH) outer sheath. The cable maintains circuit integrity for at least 90 minutes at 950 °C open-flame exposure (GB/T 19216.21 / IEC 60331-21). Finished diameter is about 55 mm and nominal mass about 4800 kg/km (≈ 480 kg per 100 m), supplied on 500 m or 1000 m wooden-steel drums. With four 150 mm² cores loaded, the cable carries about 365 A in free air at 25 °C (engineering estimate), making it the standard fire-rated main feeder for super-high-rise building fire pump main rooms, central emergency switchboard incoming cables and critical life-safety power bus ties between main and secondary switchboards.
2. Layer-by-Layer Construction (Conductor to Outer Jacket).
| Layer | Construction | Wall | Diameter |
|---|---|---|---|
| Conductor (Cu) ×5 | Tinned annealed Cu, Class 5 — 1225×0.40 mm (150 mm², ×4) + 960×0.40 mm (120 mm², ×1) | — | ≈ 18.5 / ≈ 16.5 mm |
| Mica-tape insulation ×5 | Muscovite/phlogopite mica tape, overlapping wrap, glass-fibre reinforced | ≈ 0.7 mm | ≈ 19.9 / ≈ 17.9 mm per core |
| Filler & binder | Fire-resistant glass-fibre rope + glass-fibre binder tape | — | ≈ 49 mm bundle |
| Corrugated Cu sheath | Continuously corrugated (spiralled) copper tube, longitudinal welded | ≈ 0.5 mm | ≈ 50 mm |
| LSZH outer jacket | Low-smoke zero-halogen polyolefin, flame-retardant, orange/red | 2.5 mm | ≈ 55 mm (finished) |
3. Electrical Characteristics. Each 150 mm² phase conductor is held to a maximum DC resistance of 0.124 Ω/km at 20 °C, rising to about 0.162 Ω/km at the 90 °C operating point. The 120 mm² neutral/earth conductor holds R ≤ 0.153 Ω/km at 20 °C. Every length survives the routine 3.5 kV AC power-frequency proof held for five minutes. Finished-cable insulation resistance remains above 36.7 MΩ·km (mica-rated, very high), and typical figures include per-core capacitance ≈ 0.70 μF/km and 50 Hz AC impedance ≈ 0.124 Ω/km. With four 150 mm² cores energised, reference loading is about 365 A in free air at 25 °C.
Insulation Data
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) or ceramic silicone rubber over mica tape |
|
Nominal thickness |
1.6 mm (power), 1.6 mm (PE) |
|
Long-term service temp. |
90 °C (XLPE) / 125 °C (ceramic silicone) |
|
Short-circuit temp. (≤5 s) |
250 °C (XLPE), 350 °C (ceramic) |
|
Emergency overload temp. |
130 °C |
|
Fire survival |
950 °C / 180 min (GB/T 19216.21, IEC 60331) |
|
Routine test voltage |
3.5 kV AC / 5 min |
|
Type-test voltage |
6.5 kV AC |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine |
|
Type-test voltage |
6.5 kV |
— |
|
DC resistance @20 °C (power core) |
≤ 0.124 Ω/km |
GB/T 3956 Class 5 max, 150 mm² |
|
DC resistance @20 °C (PE core) |
≤ 0.153 Ω/km |
GB/T 3956 Class 5 max, 120 mm² |
|
AC resistance @90 °C (est., power) |
≈ 0.158 Ω/km |
per core |
|
AC resistance @90 °C (est., PE) |
≈ 0.196 Ω/km |
per core |
|
Current rating in air (single-phase, 30 °C) |
≈ 320 – 385 A |
per core |
|
Current rating (design, per power core) |
≈ 340 A |
GB/T 16895 / manufacturer data |
|
Current rating (3-phase+N+PE, balanced) |
≈ 245 – 340 A per phase |
derated due to bundling |
|
Direct buried |
Applicable (copper sheath waterproof) |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 15.0 kA (15000 A) |
150 mm² |
|
Short-circuit current (1 s, Cu, 250 °C, PE) |
≈ 12.0 kA (12000 A) |
120 mm² |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 150 mm² at 340 A, 3-phase 400 V → max balanced load ≈ 235.9 kW. Voltage drop at 340 A ≈ 1.6 V/km per core (≈0.4% per 100 m).
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
−20 °C (flexible construction) |
|
Service ambient range |
−20 °C to +90 °C |
|
Fire survival |
950 °C / 180 min (circuit integrity maintained) |
4. Thermal Response & Flame Behaviour. Mica insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −15 and +70 °C. The defining property is fire resistance: under GB/T 19216.21 / IEC 60331-21, the cable maintains circuit integrity at rated voltage for at least 90 minutes when directly exposed to a 950 °C open flame. The corrugated copper sheath provides both a fire barrier and a mechanical shield against flame penetration. The LSZH outer jacket emits low smoke and no acid gas (halogen-free), meeting the requirements for tunnels, metro systems, hospitals and high-rise public buildings.
Fire Performance (BTTRZ — Mineral Insulated)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.33 Category B (ZB available) |
|
Halogen content |
Zero halogen (IEC 60754-1) |
|
Smoke density |
Low smoke (IEC 61034, light transmittance >60%) |
|
Corrosivity |
Non-corrosive (IEC 60754-2) |
|
Fire survival (circuit integrity) |
950 °C / 180 min (IEC 60331) |
|
Toxicity |
Low toxicity (IEC 62821) |
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 825 mm for this size. The corrugated copper sheath must be earthed at both ends to provide protective-earth continuity. Special sealing glands and termination kits are required at both ends to keep moisture out of the hygroscopic mica layer — improperly terminated ends are the most common failure point on mineral-insulated cables. Reels held below 0 °C in storage must be warmed indoors before uncoiling. The 365 A reference requires derating whenever ambient temperature, grouping or burial depth deviates from reference conditions. At about 480 kg per 100 m, the cable requires drum jacks, rated pulling gear and at least five fitters.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 6 × OD → ≈ 297 mm at Ø49.5 mm |
flexible installation |
|
Max. pulling tension |
9500 N |
use proper grips on copper sheath |
|
Direct burial |
Suitable |
copper sheath waterproof; add PVC paint for soil corrosion protection |
|
Conduit ID |
≥ 1.5 × OD → ≥ 75 mm; use 90 mm or 100 mm |
— |
|
Fixing |
heavy-duty cable clamps, stainless steel ties (compatible with copper sheath) |
— |
|
Flexing |
suitable for fixed installation with limited flexing during installation |
not for continuous flexing |
|
Impact resistance |
High |
corrugated copper tube absorbs mechanical shock |
|
Water resistance |
Excellent |
continuous welded copper tube |
6. Typical Service Applications. This 4×150+1×120 BTTRZ cable is the fire-rated main feeder for very large emergency and safety-critical circuits: main fire-pump and sprinkler-pump feeds up to about 92 kW, main smoke-exhaust and pressurisation fan feeds up to about 25 kW, central emergency switchboard incoming cables, fire-alarm system main power bus ties, emergency elevator main power supply, hospital central emergency switchboard feeders, metro and tunnel emergency power main distribution, high-rise building fire-fighting main risers, data-centre UPS main emergency feeders, oil and gas platform fire-resistant power cables, stadium and large-venue emergency main distribution, industrial furnace and oven emergency main power, and any circuit where continued operation during a 90-minute fire event is mandated by building code. Approved installation methods include heavy-duty cable tray, direct tray in fire-protected zones, and fire-rated conduit.

7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance verification (150 mm² ≤ 0.124; 120 mm² ≤ 0.153 Ω/km) at 20 °C, the 3.5 kV AC / 5 min withstand, insulation resistance ≥ 36.7 MΩ·km, conductor continuity across all five cores, corrugated copper sheath electrical continuity, and dimensional inspection covering mica ≈ 0.7 mm, Cu sheath ≈ 0.5 mm, LSZH jacket ≥ 2.5 mm and overall diameter ≈ 55 mm. Sample and type tests comprise the 950 °C / 90 min fire-resistance test (GB/T 19216.21), vertical flame spread GB/T 18380.34 class A, smoke density GB/T 17651, halogen acid gas content GB/T 17650, sheath moisture-tightness / water-immersion leak test, bending at ≥ 15 × OD, short-circuit to 250 °C, and voltage re-test after fire exposure. A factory test certificate accompanies each drum.
Cable Parameters

Cable Test Parameters

Cable Cross Section Structure


Cable Construction Description

8. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type, voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −15 to +40 °C, shielded from direct sunlight, moisture, oils and sharp objects; drum end seals must remain intact until installation. Because mica is hygroscopic, any drum whose end seal has been damaged must be re-tested for insulation resistance before use. During transit, drums must be secured against rolling and impact.
9. Procurement Specification. State "BTTRZ 0.6/1 kV 4×150+1×120" together with the required length or drum arrangement, and specify whether the corrugated copper sheath is to be used as the protective earth (PE) or whether a separate green-yellow 120 mm² conductor is required. Always order the matching sealing gland and termination kit at both ends. Always request the factory test certificate, which must include the 950 °C / 90 min fire-resistance report, to confirm the actual diameter (≈ 55 mm), weight (≈ 4800 kg/km) and conductor resistances for the production batch.
10. Cable Industry FAQ.
- Q1: When should I choose 150 mm² over 120 mm² for fire-rated circuits? Choose 150 mm² when the emergency load carries up to about 365 A (vs about 310 A for 120 mm²), such as main fire pumps up to 92 kW, central emergency switchboard incoming cables, or main bus ties between main and secondary switchboards where voltage drop is critical. 120 mm² is sufficient for branch-level fire-rated main feeders.
- Q2: Why is the neutral/earth core only 120 mm² while phases are 150 mm²? In typical three-phase balanced loads the neutral carries little current, so it is derated to 120 mm². The corrugated copper sheath additionally provides a continuous protective-earth path, so the separate 120 mm² core serves primarily as a system neutral.
- Q3: What does "950 °C / 90 min" actually guarantee? During the GB/T 19216.21 / IEC 60331-21 test, the cable is laid in a test furnace, energised at rated voltage, and directly exposed to a 950 °C flame for 90 minutes. The cable must continue to carry the load without electrical breakdown. This is the rating that justifies its use on fire pumps, emergency lighting and escape-route circuits.
- Q4: Why is the corrugated copper sheath necessary? The copper sheath serves three purposes: (i) physical flame barrier protecting the mica layer; (ii) moisture barrier — mica is hygroscopic and must stay dry; (iii) continuous electrical path that can double as the protective earth (PE).
- Q5: Why is the jacket LSZH instead of PVC? In a fire, PVC releases dense smoke and hydrochloric acid gas, which are the dominant causes of death in fires. LSZH jacket releases low smoke and no acid gas — essential in tunnels, metros, hospitals and high-rise public buildings where evacuation is slow.
- Q6: Why must the termination kit be special? Mica tape is hygroscopic: if moisture enters the cable end, the insulation resistance collapses. Standard PVC cable glands are not air- and moisture-tight. The BTTRZ termination kit uses a sealed brass gland with epoxy sealing compound and a heat-shrink boot.
- Q7: Can the copper sheath replace the separate earth conductor? Yes — the corrugated copper sheath is electrically continuous and can be sized as the protective earth (PE), provided its cross-sectional area and fault-current capacity meet the installation code.
- Q8: How heavy is this cable compared to ordinary PVC? At ≈ 4800 kg/km it is roughly twice the mass of an ordinary RVV 4×150 flexible cord, because of the corrugated copper sheath and mica layers. This is normal for fire-rated cables and must be planned for in tray loading and pulling.
- Q9: Can BTTRZ be used outdoors or buried directly? Yes — the LSZH jacket is UV-resistant and the copper sheath is an effective moisture barrier, so BTTRZ can be installed outdoors, in trays or directly in buried trenches.
- Q10: Which tests confirm acceptability on delivery and before energisation? At delivery, verify the factory fire-resistance certificate (950 °C / 90 min), conductor resistance (150 ≤ 0.124; 120 ≤ 0.153 Ω/km), dimensions (≈ 55 mm), and the drum end-seal integrity. After installation, complete an insulation-resistance test, a 3.5 kV AC / 5 min withstand, and verify both ends of the corrugated copper sheath are properly earthed before energising.
- Q11: What service life can be expected? When installed, terminated and operated within the stated temperature, voltage and fire ratings, BTTRZ cable is designed for a service life of around 30–40 years in fixed installation. The two failure modes to watch are moisture ingress through improperly sealed terminations and mechanical damage to the corrugated sheath.