BTLY Fire Rated Cable 4x35mm2 + 1x16mm2 Aluminum Sheath Cable For Emergency
Product Summary
Product Details
fire rated cable 4x35mm2
,aluminum sheath cable for emergency
,btly fire rated cable
Product Description
NG-A BTLY 4x35+1x16mm2 Mineral Insulated Fire Resistant Aluminum Sheath Cable for Emergency
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
NG-A |
New Generation A-class fire-resistant (Chinese designation) |
|
(BTLY) |
Building wire, Thin copper conductor, Lightweight Y— alternative naming convention indicating: Copper conductor + Aluminium sheath + XLPO/LSZH insulation + LSZH sheath |
|
4×35 mm² + 1×16 mm² |
Four 35 mm² phase/neutral cores + one 16 mm² earth core (5-core: 3P+1N+1PE) |
Construction: Copper conductors, XLPO (cross-linked polyolefin) or mineral ceramic insulation, continuous corrugated aluminium sheath, LSZH outer sheath, flexible design.


NG-A(BTLY) 4×35+1×16 mm² (flexible mica-tape mineral-insulated Al-sheathed fire-resistant cable) — Specification & Engineering Data
1. Overview & Ratings. NG-A(BTLY) 4×35+1×16 — flexible mineral-insulated fire-resistant cable with corrugated aluminum tube sheath, four 35 mm² copper power cores (L1/L2/L3/N) plus one 16 mm² PE core, wrapped in synthetic phlogopite mica tape and enclosed in a continuous corrugated aluminum tube, rated 0.6/1 kV; built and tested per GB/T 19216 / GB/T 13033. The cable maintains circuit integrity at 750 °C for 90 minutes. Ø ≈ 36.5 mm, ≈ 2450 kg/km, wooden drums.
2. Construction Stack (Conductor → Outer).
| Layer | Build | Wall | Diameter |
|---|---|---|---|
| Conductors (×5) | Cu: 4×35 mm² (L1/L2/L3/N) + 1×16 mm² (PE) | — | ≈ 7.5 / 5.5 mm |
| Mica tape insulation | Synthetic phlogopite mica, double-wrapped | ≈ 0.7 around each | — |
| Corrugated Al tube | Continuous welded corrugated aluminum | ≈ 0.6 mm | ≈ 34.5 mm |
| Outer PVC sheath | PVC, black/red (corrosion protection) | ≈ 1.2 mm | ≈ 36.5 mm (finished) |
3. Electrical Characteristics. R ≤ 0.524 Ω/km (35 mm²) / ≤ 1.15 Ω/km (16 mm²) at 20 °C; routine test 3.5 kV AC / 5 min; insulation resistance ≥ 100 MΩ·km. Reference ampacity ≈ 130 A (4×35 loaded, free air, 30 °C).
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPO (cross-linked polyolefin), halogen-free, fire-resistant |
|
Outer sheath material |
LSZH (low-smoke zero-halogen) |
|
Long-term service temp. |
90 °C (continuous) |
|
Short-circuit temp. (≤5 s) |
250 °C (Cu conductor limit; Al sheath stable to 660 °C) |
|
Emergency overload temp. |
200 °C (short term) |
|
Fire survival temp. |
950 °C for ≥ 180 min (BS 6387 CWZ) |
|
Water resistance |
Excellent (aluminium sheath is impermeable with proper termination) |
|
Radiation resistance |
Excellent |
|
Weather resistance |
Excellent (Al sheath + LSZH outer) |
|
Flame retardant |
Inherent — non-combustible sheath + halogen-free insulation |
|
Smoke density |
Zero (LSZH outer sheath) |
|
Halogen content |
Zero (XLPO + LSZH) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 13033 / IEC 60702 |
|
Max. system voltage Uₘ |
1.2 kV |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C (35 mm²) |
≤ 0.524 Ω/km |
GB/T 3956 Class 2 Cu max |
|
DC resistance @20 °C (16 mm²) |
≤ 1.15 Ω/km |
GB/T 3956 Class 2 Cu max |
|
AC resistance @90 °C (est., 35 mm²) |
≈ 0.667 Ω/km |
per core |
|
AC resistance @90 °C (est., 16 mm²) |
≈ 1.46 Ω/km |
earth core |
|
Capacitance (approx.) |
≈ 0.20 µF/km |
core to sheath |
|
Inductive reactance (approx.) |
≈ 0.07 Ω/km |
at 50 Hz, 5-core |
|
Current rating in air (30 °C) |
140 A |
3-phase loaded, 4×35 mm² (derated for 5-core) |
|
Current rating buried (20 °C) |
115 A |
direct buried (Al sheath heat dissipation) |
|
Current rating in conduit (30 °C) |
110 A |
3-phase, 5-core |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 3.5 kA (3500 A) |
35 mm² Cu |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 35 mm² Cu at 140 A, 3-phase 400 V → max balanced load ≈ 97 kVA. Voltage drop at 140 A ≈ 93.4 V/km per core (≈3.8% per 100 m at 400 V).
4. Thermal & Fire. 90 °C continuous conductor temperature; short-circuit 250 °C; fire rating 750 °C / 90 min per GB/T 19216 — the cable remains energised during fire with impact and water spray. Mica tape is non-combustible; PVC outer sheath contains halogen (LSZH outer available for halogen-free).
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C (Cu conductor; Al sheath stable to 660 °C) |
|
Emergency overload temp. |
200 °C (XLPO/mineral insulation stable) |
|
Min. installation ambient temp. |
−20 °C (LSZH sheath, flexible corrugated Al) |
|
Service ambient range |
−20 °C to +90 °C (continuous); 950 °C fire survival |
|
Fire survival |
BS 6387 Category CWZ — circuit integrity ≥ 180 min at 950 °C, water jet test (W), mechanical impact (Z) |
Fire Performance (NG-A / BTLY — Mineral Insulated, Fire Resistant)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
Inherent — non-combustible (Al sheath + halogen-free insulation) |
|
Halogen content |
Zero (XLPO insulation + LSZH sheath) |
|
Smoke density |
Zero (IEC 61034, LSZH) |
|
Corrosivity |
Non-corrosive (IEC 60754) |
|
Fire survival (circuit integrity) |
BS 6387 CWZ — passes C (950 °C, 180 min), W (water jet during fire), Z (mechanical impact during fire) |
|
Toxicity |
Zero (inorganic materials) |
|
Heat release |
Near zero (non-combustible sheath) |
BS 6387 Classification:
|
Category |
Test Condition |
NG-A (BTLY) Result |
|---|---|---|
|
C |
950 °C, 180 min, circuit integrity |
✅ Pass |
|
W |
Water jet during fire test |
✅ Pass |
|
Z |
Mechanical impact during fire test |
✅ Pass |
5. Installation Practice & Handling. Install fire cable end seals at both ends. Bend ≥ 12 × OD ≈ 440 mm fixed. Use Cu compression lugs + end sealing kits. The Al tube is the primary fire barrier; the thin PVC outer sheath is for corrosion protection. Lighter than Cu-sheathed BTTRZ — easier to handle.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 6 × OD → ≈ 174 mm at Ø29 mm |
flexible corrugated Al sheath |
|
Max. pulling tension |
3500 N |
Cu conductor + Al sheath |
|
Direct burial |
Excellent (Al sheath impermeable with proper seal) |
use warning tape |
|
Conduit ID |
≥ 1.5 × OD → ≥ 44 mm; use 50 mm or 63 mm |
— |
|
Fixing |
Al-compatible clamps (avoid galvanic corrosion with steel) |
use isolation pads if steel clamps |
|
Impact resistance |
High (corrugated Al sheath provides mechanical protection) |
— |
|
Water resistance |
Excellent (gas-tight Al sheath) |
suitable for wet/submerged |
|
UV resistance |
Excellent (Al sheath + LSZH) |
outdoor exposed |
|
Termination note |
Compression glands or cold-shrink seals onto Al sheath; easier than rigid BTTZ/BTTRZ |
standard electrical tools; no potting required |
6. Typical Service Applications. Fire pump power supply, emergency lighting circuits, smoke control systems, fire alarm circuits, evacuation signalling, critical life-safety power — any circuit that must remain operational during a fire.

7. Testing & QA Regime. Routine: conductor DC resistance, 3.5 kV AC withstand, insulation resistance ≥ 100 MΩ·km. Type: GB/T 19216 fire test (750 °C / 90 min with impact and water spray), crush resistance, halogen test, end seal integrity.
Cable Parameters
| NG-A(BTLY) 4×35+1×16 mm² — Flexible Mineral-Insulated (Mica Tape) Al-Sheathed Fire-Resistant Cable — Full Parameter Sheet | ||||
| Mica tape insulated fire cable · Cu conductors / mica tape / corrugated Al tube / PVC outer sheath · 4×35 + 1×16 mm² · 0.6/1 kV · 750 °C fire-rated · GB/T 19216 / GB/T 13033 · finished Ø ≈ 36.5 mm | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | NG-A(BTLY) — Flexible mineral-insulated Al-sheathed fire-resistant cable | — | Fire-rated emergency power | |
| Rated voltage (U0/U) | 0.6/1 | kV (Um=1.2 kV) | Fire-rated power circuit | |
| Number of cores | 4×35 + 1×16 | — | 3P+N+PE (PE=16 mm²) | |
| Conductor material | Annealed copper | — | Class 1/2 per GB/T 3956 | |
| Insulation material | Mica tape (synthetic phlogopite) | — | Fire-resistant, 750 °C | |
| Sheath material | Corrugated aluminum tube + PVC outer | — | Al tube = fire barrier | |
| Outer sheath colour | Black / red | — | Fire cable identification | |
| Fire rating | 750 °C / 90 min | — | GB/T 19216 / GB/T 13033 | |
| Standard | GB/T 19216 / GB/T 13033 | — | Mineral fire cable | |
| 02 · Conductor (Copper) | ||||
| Conductor type (power cores) | Solid/stranded copper | — | Class 1/2 per GB/T 3956 | |
| Conductor area (power) | 4 × 35 | mm² | L1/L2/L3/N | |
| Conductor area (PE) | 1 × 16 | mm² | Protective earth | |
| DC resistance @ 20 °C (35 mm²) | ≤ 0.524 | Ω/km | Max per GB/T 3956 | |
| DC resistance @ 20 °C (16 mm²) | ≤ 1.15 | Ω/km | PE core | |
| Conductor weight per km | ≈ 1560 | kg/km | 4×35 + 1×16 Cu | |
| 03 · Insulation & Sheath | ||||
| Insulation type | Synthetic mica tape (phlogopite), double-wrapped | — | Non-combustible fire barrier | |
| Insulation thickness (around conductor) | ≈ 0.7 | mm | Mica tape wrap | |
| Aluminum tube wall | ≈ 0.6 | mm | Corrugated, welded | |
| Outer PVC sheath | ≈ 1.2 | mm | Corrosion protection | |
| Finished outer diameter | ≈ 36.5 | mm | Al tube + PVC | |
| 04 · Electrical | ||||
| Rated voltage (AC) | 0.6/1 | kV | Fire-rated power | |
| DC resistance @ 20 °C (35 mm²) | ≤ 0.524 | Ω/km | Power cores | |
| Insulation resistance | ≥ 100 | MΩ·km | Mica tape | |
| Routine test voltage (AC) | 3.5 kV / 5 min | — | Power-frequency withstand | |
| Fire circuit test | 750 °C / 90 min | — | Cable remains energised | |
| Circuit integrity | GB/T 19216 | — | Fire resistance standard | |
| 05 · Thermal & Fire | ||||
| Max continuous conductor temp. | 90 | °C | Mica tape rated | |
| Short-circuit temp. | 250 | °C | Cu conductor limit | |
| Fire rating | 750 | °C / 90 min | GB/T 19216 | |
| Flame spread | None | — | Mica + Al tube non-combustible | |
| Toxic gas emission | Low | — | PVC outer (halogen-bearing) | |
| Halogen-free option | Yes (LSZH outer) | — | BTLY with LSZH outer | |
| Water resistance | Good | — | Al tube is water-tight | |
| 06 · Mechanical | ||||
| Min bending radius (fixed) | ≥ 12 × OD ≈ 440 | mm | Corrugated Al tube | |
| Min bending radius (flexed) | ≥ 15 × OD ≈ 550 | mm | Repeated flexing | |
| Crush resistance | Good | — | Al tube rigid | |
| Outer sheath | PVC corrosion protection | — | Al tube main protection | |
| 07 · Ampacity | ||||
| Air ampacity (4×35 loaded) | ≈ 130 | A | 30 °C (est.) | |
| Buried ampacity | ≈ 135 | A | Direct burial | |
| Fire circuit derating | 80% | — | For fire-rated circuits | |
| 08 · Installation | ||||
| Laying methods | Tray, conduit, vertical riser, fire-rated enclosure | — | Emergency power | |
| Terminations | Special fire cable end seals | — | Mica + Al tube sealing | |
| Connectors | Cu lugs + end sealing kits | — | Moisture barrier required | |
| Special tools | Fire cable end sealing kit | — | Moisture-proof termination | |
| 09 · Packing | ||||
| Standard supply length | 100 m / drum | m | Fire cable | |
| Reel / packing type | Wooden drum, sealed ends | — | Ends must be sealed | |
| Surface marking | NG-A(BTLY), 4×35+1×16, 0.6/1kV, 750°C, metre marks | — | Continuous printing | |
| Storage conditions | Dry, indoor, sealed ends | — | Mica hygroscopic protection | |
| 10 · Applications | ||||
| Typical use | Fire pump power, emergency lighting, smoke control, fire alarm circuits, evacuation systems, critical life-safety circuits | — | Fire-rated emergency power | |
| Max system voltage | 1.2 | kV (Um) | 0.6/1 kV rated | |
| Fire duration | 750 °C / 90 min | — | GB/T 19216 | |
Cable Test Parameters
| Test Parameters — NG-A(BTLY) 4×35+1×16 mm² | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 0.524 Ω/km (35mm²), ≤ 1.15 Ω/km (16mm²) | Routine |
| 2 | Power-frequency withstand | 3.5 kV AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | 500 V DC, between Al tube and conductor | ≥ 100 MΩ·km | Routine |
| 4 | Fire resistance test | GB/T 19216: 750 °C, 90 min | Cable remains energised, no circuit failure | Type |
| 5 | Impact test during fire | GB/T 19216: mechanical impact at flame | Circuit remains intact | Type |
| 6 | Water spray during fire | GB/T 19216: water spray at flame | Circuit remains intact | Type |
| 7 | Crush test | Al tube crush resistance | No conductor exposure | Type |
| 8 | Dimensional check | Micrometer | OD ≈ 36.5 mm, Al tube ≈ 0.6 mm | Routine |
| 9 | End seal integrity | Visual + insulation resistance | Moisture-proof seals | Routine |
| 10 | Corrugation check | Visual | Uniform corrugated Al tube | Routine |
| 11 | Conductor continuity | Per GB/T 3956 | All 5 cores continuous | Routine |
| 12 | Toxicity / halogen test | IEC 60754 / IEC 60754-2 | PVC outer has halogen; LSZH option available | Type |
Cable Cross Section Structure

| NG-A(BTLY) 4×35+1×16 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Fire-resistant cable: Cu conductors → mica tape insulation → corrugated Al tube (fire barrier) → PVC outer sheath · 0.6/1 kV · 750 °C / 90 min · finished Ø ≈ 36.5 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductors (×5) | Copper: 4×35 mm² (L1/L2/L3/N) + 1×16 mm² (PE) | — | ≈ 7.5 / 5.5 | R ≤ 0.524 / 1.15 Ω/km |
| 2 | Mica tape insulation | Synthetic phlogopite mica tape, double-wrapped | ≈ 0.7 around each | — | Non-combustible, 750 °C rated |
| 3 | Corrugated Al tube | Continuous welded corrugated aluminum | ≈ 0.6 | ≈ 34.5 | Fire barrier, water-tight, lighter than Cu |
| 4 | Outer PVC sheath | PVC, black/red (corrosion protection) | ≈ 1.2 | ≈ 36.5 (finished) | Protects Al tube from corrosion |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 36.5 | mm | Al tube + PVC sheath | ||
| Approx. cable mass | ≈ 2450 | kg/km | Cu conductors + mica + Al tube + PVC | ||
| Nominal voltage rating | 0.6/1 | kV | Fire-rated power circuit | ||
| Max continuous conductor temp. | 90 | °C | Mica tape insulation | ||
| Fire rating | 750 | °C / 90 min | GB/T 19216 | ||
| Short-circuit temp. | 250 | °C | Cu conductor limit | ||
| Min bending radius (fixed) | ≥ 12 × OD ≈ 440 | mm | Corrugated Al tube | ||
| DC resistance @ 20 °C (35 mm²) | ≤ 0.524 | Ω/km | Power cores | ||
| DC resistance @ 20 °C (16 mm²) | ≤ 1.15 | Ω/km | PE core | ||
| Insulation resistance | ≥ 100 | MΩ·km | Mica tape | ||
| Routine test voltage (AC) | 3.5 kV / 5 min | — | Power-frequency withstand | ||
| Air ampacity @ 30 °C | ≈ 130 | A | 4 cores loaded (est.) | ||
| Halogen-free option | LSZH outer available | — | PVC outer is halogen-bearing | ||
| Toxic gas emission | Low | — | Mica tape non-toxic | ||
| Schematic — not to exact scale. Finished Ø ≈ 36.5 mm and weight ≈ 2450 kg/km from cross-referenced industry samples. NG-A(BTLY) is a flexible mineral-insulated fire-resistant cable — copper conductors wrapped in synthetic mica tape, enclosed in a continuous corrugated aluminum tube. Unlike RVV-5×4.0 (PVC 70 °C, 300/500 V, 25 A, 350 kg/km, 5-core flexible PVC), NG-A(BTLY) uses mica tape insulation (750 °C fire-rated), a lightweight aluminum tube sheath (fire barrier), and is designed for emergency power circuits. The Al tube is lighter than the Cu tube of BTTRZ, making installation easier. Fire rating: 750 °C / 90 min. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — NG-A(BTLY) 4×35+1×16 mm² (mineral-insulated fire cable) | |||
| Layer-by-layer fire-resistant cable: Cu conductors / mica tape insulation / corrugated Al tube (fire barrier) / PVC outer sheath · 0.6/1 kV · 750 °C / 90 min · finished Ø ≈ 36.5 mm | |||
| 1. Product Identity & Ratings | |||
| NG-A(BTLY) 4×35+1×16 is a flexible mineral-insulated (mica tape) aluminum-sheathed fire-resistant cable rated 0.6/1 kV, built and tested per GB/T 19216 / GB/T 13033. It has 4 power cores (35 mm², L1/L2/L3/N) + 1 PE core (16 mm²), all wrapped in synthetic mica tape inside a corrugated aluminum tube. The cable maintains circuit integrity at 750 °C for 90 minutes. Unlike RVV-5×4.0 (PVC 70 °C, 300/500 V, 25 A, 350 kg/km), NG-A(BTLY) is a fire-rated emergency power cable. Finished Ø ≈ 36.5 mm, mass ≈ 2450 kg/km, wooden drums. | |||
| 2. Copper Conductors (4×35 + 1×16) | |||
| The 4 power cores use 35 mm² copper conductors (R ≤ 0.524 Ω/km), and the PE core uses 16 mm² copper (R ≤ 1.15 Ω/km). Conductors are solid or stranded per GB/T 3956. All 5 cores are wrapped in mica tape and enclosed in the aluminum tube. The copper conductors can survive temperatures above PVC/XLPE because mica tape does not melt or burn. | |||
| 3. Mica Tape Insulation | |||
| Synthetic phlogopite mica tape is double-wrapped around each conductor. Unlike PVC or XLPE (which burn, melt, and release toxic gas), mica tape remains stable at 750 °C. This is the fire-resistant insulation layer — it does not burn, does not melt, and maintains insulation during fire. The mica tape is lightweight and flexible, making BTLY easier to install than rigid MgO tubes. | |||
| 4. Corrugated Aluminum Tube (Fire Barrier) | |||
| The mica-wrapped conductors are enclosed in a continuous welded corrugated aluminum tube (≈ 0.6 mm wall). The aluminum tube serves three functions: (1) fire barrier — aluminum does not burn; (2) water-tight seal; (3) mechanical protection. Aluminum is lighter than copper, making the cable easier to handle. This is fundamentally different from RVV's PVC outer sheath, which melts and burns. | |||
| 5. Site Handling & Operational Notes | |||
| • Install fire cable end seals at both ends — mica tape and Al tube must be sealed. • Bend radius 12×OD (≈ 440 mm) fixed. • Fire rating: 750 °C / 90 min (GB/T 19216). • Use Cu compression lugs + end sealing kits. • PVC outer sheath is for corrosion protection — the Al tube is the primary barrier. • At 2450 kg/km, lighter than Cu-sheathed BTTRZ. • Store with ends sealed. • For fire pump, emergency lighting, smoke control circuits. |
8. Standards & Conformity. GB/T 19216 (fire resistance test); GB/T 13033 (mineral-insulated cables); GB/T 3956 (conductors). Rated 0.6/1 kV fire-rated power circuit.
9. Packaging, Storage & Logistics. 100 m per wooden drum with sealed ends. Continuous marking: NG-A(BTLY), 4×35+1×16, 0.6/1 kV, 750 °C, GB/T 19216, metre marks. Store dry, indoor, with factory end seals intact.

10. Procurement Specification. State "NG-A(BTLY) 4×35+1×16, 0.6/1 kV, 750 °C/90 min" + length. Order matching end sealing kits. Confirm against factory fire test certificate. Do not substitute ordinary YJV for fire-rated circuits.
11. Cable Industry FAQ.
- Q1: What makes NG-A(BTLY) fire-resistant? Unlike RVV (PVC insulation which burns at 70 °C), NG-A(BTLY) uses synthetic mica tape (phlogopite) wrapped around each conductor, and a corrugated aluminum tube as the sheath. Neither mica tape nor aluminum burns. The cable maintains circuit integrity at 750 °C for 90 minutes.
- Q2: What is the difference between BTTRZ and NG-A(BTLY)? BTTRZ uses a copper tube + MgO powder insulation (950 °C/180 min, 105 °C, 3850 kg/km). NG-A(BTLY) uses an aluminum tube + mica tape insulation (750 °C/90 min, 90 °C, 2450 kg/km). BTTRZ has higher fire rating and higher temp, but is heavier and more expensive. BTLY is lighter, easier to install, and sufficient for most fire-rated circuits.
- Q3: Why is the aluminum tube used instead of copper? Aluminum is ~1/3 the density of copper, making the cable much lighter (2450 vs 3850 kg/km). This reduces installation labor and support structure load. Aluminum also does not burn and provides a water-tight seal.
- Q4: What is mica tape? Mica tape is a thin sheet of phlogopite mineral paper backed with glass cloth. It is non-combustible, heat-resistant to 750 °C, and flexible. It is wrapped around each conductor to provide fire-resistant insulation without the MgO powder fill of rigid mineral cables.
- Q5: Can NG-A(BTLY be used outdoors? Yes — the PVC outer sheath protects the Al tube from corrosion. For direct burial, the Al tube is water-tight. No additional armor needed.
- Q6: What is the fire rating difference between 750 °C and 950 °C? 750 °C/90 min (GB/T 19216) is the standard fire rating for most building emergency circuits. 950 °C/180 min (BS 6387 class C) is a higher rating for critical industrial fire pumps. BTTRZ meets 950 °C; NG-A(BTLY) meets 750 °C.
- Q7: Does NG-A(BTLY) need armor? No — the corrugated aluminum tube itself provides crush and impact resistance. This is why it is the standard for fire-rated circuits.
- Q8: Can RVV be used for fire pump circuits? No — RVV's PVC insulation burns at ~250 °C and releases toxic smoke. Fire pump circuits MUST use mineral-insulated cable (BTTRZ/BTLY) or fire-rated silicone cable.
- Q9: What is the difference between BTLY and BTTW? BTLY uses an aluminum tube sheath. BTTW uses a copper tube sheath (similar to BTTRZ). BTLY is lighter and cheaper; BTTW has higher fire rating.
- Q10: How do I terminate NG-A(BTLY)? Cut the cable square, remove the outer PVC, slide on the end seal gland, install the Cu lug, and crimp. The seal must be moisture-tight. Improper termination is the #1 failure point.
- Q11: Is NG-A(BTLY) halogen-free? The PVC outer sheath contains halogen. For halogen-free applications, specify the LSZH outer sheath version (BTLY with LSZH). The mica tape itself is halogen-free.