BVR 2.5mm² Flexible Copper Wire PVC Insulated Easy Routing for Indoor Building Electrical Wiring
Product Summary
Product Details
Product Description
BVR 2.5mm² Flexible Copper Wire PVC Insulated Easy Routing for Indoor Building Electrical Wiring
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
B |
Fixed wiring |
|
V |
PVC insulation |
|
R |
Flexible— stranded conductor |
|
1×2.5 mm² |
Single core of 2.5 mm² copper conductor |
Construction: One 2.5 mm² stranded copper conductor (Class 2 or Class 5), PVC insulation applied directly over the conductor.

BVR 1×2.5 mm² — Single-Core Stranded PVC Insulated Flexible Building Wire
1. Overview & Ratings
BVR 1×2.5 is a single-core PVC insulated flexible building wire rated 450/750 V. It uses pure annealed bare copper (not tinned) in a Class 5 stranded lay-up, chosen for high conductivity and easy bending in panels and tight runs. One 2.5 mm² copper bundle is covered by a continuous PVC insulation; there is no braid shield, no inner sheath and no outer jacket. Finished OD ≈ 3.6 mm, ≈ 30 kg/km (est.), ≈ 20–25 A in conduit. Max conductor temperature 70 °C, -15 to +70 °C. Intended for fixed indoor and panel wiring; not for trailing drag chains, outdoor UV exposure or direct burial.
2. Construction Stack (Inner → Outer, expanded)
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor | Pure annealed Cu, stranded Class 5, 49×0.25 mm | R ≤ 7.41 Ω/km, flexible fixed wiring |
| Insulation | PVC ≈ 0.8 mm wall, colour-coded | 450/750 V dielectric, circuit identification |
| Shield | None | Single-core unshielded wire |
| Outer jacket | None | Insulation forms the outer layer |
3. Electrical Characteristics
DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956 Class 5 pure copper. Rated voltage 450/750 V. Estimated ampacity ≈ 20–25 A in conduit at 30 °C, up to ≈ 32 A in free air, with derating for grouping and enclosure. Insulation resistance ≥ 20 MΩ·km. Routine AC withstand test at 2000 V for 5 minutes. Typical capacitance ≈ 150 pF/m at 1 kHz. As a single-core wire it carries one phase, neutral or earth conductor per run; circuit identification is handled by insulation colour rather than internal pairing.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
PVC (Type TI1 or TI2) |
|
Outer sheath material |
None (non-sheathed) |
|
Shield material |
None |
|
Long-term service temp. |
70 °C (continuous, TI1/TI2) |
|
Max. conductor temp. (normal) |
70 °C |
|
Short-circuit temp. (≤5 s) |
160 °C |
|
Emergency overload temp. |
100 °C (≤1 h) |
|
Test voltage AC (5 min) |
2.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹² Ω·cm |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
450 / 750 V |
GB/T 5023.3 (fixed wiring) |
|
Max. system voltage |
500 V AC / 750 V DC |
— |
|
Test voltage AC (5 min) |
2.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 7.41 Ω/km (Class 2) / ≤ 7.98 Ω/km (Class 5) |
GB/T 3956 max |
|
AC resistance @70 °C (est.) |
≈ 9.28 Ω/km (Class 2) |
— |
|
Current rating in air (30 °C) |
25 A (reference, single-core open) |
typical |
|
Current rating in conduit (30 °C) |
21 A (reference, 2-core conduit) |
typical installation |
|
DC current capacity |
24 A |
— |
|
Short-circuit current (1 s, Cu, 160 °C) |
≈ 275 A |
— |
|
Capacitance (core-to-ambient, approx.) |
≈ 0.11 µF/km |
PVC |
|
Inductive reactance (approx.) |
≈ 0.10 Ω/km |
at 50 Hz (single-core) |
|
Frequency |
50/60 Hz AC, DC |
— |
Reference values: BVR 2.5 at 21–25 A, 230 V AC → max load ≈ 4,830–5,750 VA (typical lighting/socket/control circuit). At 24 V DC → max load ≈ 576 W.
4. Thermal & Flame Behaviour
Operating range -15 to +70 °C continuous. Short-circuit withstand up to 160 °C for ≤ 5 seconds. The PVC insulation is flame-retardant per IEC 60332-1 and self-extinguishing after the ignition source is removed. The cable is halogen-containing (PVC), emitting HCl gas on burning — avoid in enclosed public or high-density spaces where LSZH wiring is required. The insulation surface is smooth and oil-limited; protect it from direct sunlight, solvents and prolonged moisture. Bare copper should be terminated in dry, enclosed locations.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
70 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
160 °C |
|
Emergency overload temp. |
100 °C (≤1 h) |
|
Min. installation ambient temp. |
−15 °C |
|
Service ambient range |
−15 °C to +70 °C |
|
Flexing temp. range |
−5 °C to +70 °C (Class 5); 0 °C to +70 °C (Class 2) |
Fire Performance (BVR — PVC, Non-Low-Smoke)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.3 / IEC 60332-3 (Category A/B/C as specified) |
|
Halogen content |
Contains halogen (PVC) |
|
Smoke density |
Not low-smoke (IEC 61034-2 not applicable) |
|
Corrosivity |
Corrosive (HCl emission from PVC) |
|
Toxicity |
Toxic fumes when burned (CO, HCl) |
|
EMI shielding |
None |
|
UV resistance |
Poor (PVC degrades outdoors, use conduit) |
|
Water resistance |
Limited (PVC insulation only) |
5. Installation Practice & Handling
Minimum bending radius ≥ 4×OD ≈ 14 mm. The Class 5 stranded core is suppler than a solid wire, so it dresses around panel corners, terminal rows and tight duct bends without kinking. Terminate by stripping the insulation, terminating the bundle in a ferrule, lug or terminal block, and tightening to the rated torque. Group live, neutral and earth conductors in the same conduit; keep green-yellow earth wires separate in identification. After installation, verify insulation resistance and continuity before energizing. Do not use as a trailing appliance cord or drag-chain cable.
Mechanical & Installation Parameters
|
Parameter |
Value (Class 2) |
Value (Class 5) |
Remarks |
|---|---|---|---|
|
Minimum bending radius |
≥ 4 × OD → ≈ 16 mm |
≥ 4 × OD → ≈ 18 mm |
stranded conductor |
|
Max. pulling tension |
37.5 N (2.5 mm² × 15 N/mm²) |
37.5 N (2.5 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Not recommended (PVC, no sheath) |
Not recommended |
— |
|
Surface mounting |
Conduit, trunking, cable tray, DIN rail |
Conduit, trunking, cable tray |
— |
|
Conduit ID |
≥ 16 mm (single), ≥ 20 mm (multiple) |
≥ 16 mm (single), ≥ 20 mm (multiple) |
— |
|
Fixing |
cable ties, clips, staples |
cable ties, clips, staples |
— |
|
Impact resistance |
Low (PVC) |
Low (PVC) |
— |
|
Water resistance |
Limited (no sheath) |
Limited (no sheath) |
— |
|
UV resistance |
Poor (indoor/conduit only) |
Poor (indoor/conduit only) |
— |
|
Flex life |
Good (Class 2, occasional bending) |
Excellent (Class 5, frequent bending) |
— |
|
Termination note |
Compression lugs (2.5 mm²), crimp terminals, screw terminals |
Compression lugs (2.5 mm²), crimp terminals, screw terminals |
— |
6. Typical Service Applications
Panel internal wiring and switchboard connections, vibrating equipment and motor terminal leads where flexibility matters, tight-bend runs in control cabinets, distribution board internal conductors, and fixed indoor lighting and socket branch circuits. The stranded construction is preferred where the wire must bend around obstructions or connect to equipment subject to vibration, while still serving as a fixed wiring conductor. Typical installation: conduit, trunking, cable tray and panel raceway. It is not designed for: shielded signal transmission, trailing or moving equipment, outdoor UV-exposed runs, submersible or buried circuits, or high-temperature heater wiring.
.

7. Testing & Quality Assurance Regime
Routine tests (100% production): DC resistance, AC voltage withstand (2000 V/5 min), insulation resistance, conductor construction, insulation thickness, dimensional check, print legibility, mass per length, visual appearance, and packing. Type tests (per batch / material change): heat aging (100 °C/7 days), cold bend (-15 °C), insulation tensile and elongation, flame retardancy, conductor flexibility under repeated bending, and wall thickness uniformity. Every coil ships with mill test certificate, ROHS and REACH declarations. The 450/750 V rating uses a 2000 V withstand test.
The Wire Parameters
| BVR 1×2.5 mm² — Full Parameter Sheet | ||||
| Single-core PVC insulated flexible building wire · 450/750 V · pure annealed Cu stranded Class 5 · PVC insulation · no shield, no outer jacket · GB/T 5023 / IEC 60227 | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | BVR | — | Single-core, PVC insulated, stranded pure Cu | |
| Rated voltage (U0/U) | 450/750 | V | Fixed indoor / panel wiring | |
| Number of cores | 1 | — | Single core, stranded | |
| Nominal cross-section | 2.5 | mm² | Per core, Class 5 flexible | |
| Conductor material | Pure annealed copper (bare) | — | Class 5 per GB/T 3956, not tinned | |
| Insulation material | PVC | — | 70 °C rated, 0.8 mm wall | |
| Shield | None | — | No braid / foil on single-core wire | |
| Outer jacket | None | — | Insulation forms the outer layer | |
| Standard reference | GB/T 5023 / IEC 60227 / JB/T 8734 | — | PVC insulated flexible wiring wire | |
| 02 · Conductor | ||||
| Conductor form | Stranded (flexible) | — | Class 5 | |
| Stranding | 49 × 0.25 mm | — | Pure copper wires per core | |
| Conductor bundle Ø | ≈ 2.05 | mm | Strand-lay diameter | |
| DC resistance @ 20 °C | ≤ 7.41 | Ω/km | Maximum per GB/T 3956 (pure Cu) | |
| Conductor surface | Bare pure copper | — | Not tinned; fixed indoor use | |
| 03 · Insulation | ||||
| Insulation type | PVC | — | Soft PVC, 70 °C | |
| Insulation thickness | ≈ 0.8 | mm | Nominal | |
| Finished diameter | ≈ 3.6 | mm | Insulation outer Ø | |
| Insulation resistance | ≥ 20 | MΩ·km | At 20 °C | |
| 04 · Lay-Up & Shield | ||||
| Core lay-up | Not applicable | — | Single-core wire | |
| Filler / bedding | None | — | No inner sheath on BVR | |
| Shield type | None | — | Unshielded building wire | |
| Shield coverage | — | — | Not applicable | |
| 05 · Insulation Finish | ||||
| Outer surface | Smooth PVC extrusion | — | Colour-coded | |
| Printing | Designation / size / voltage / metre mark | — | At regular intervals | |
| Insulation colours | Red, yellow, blue, green-yellow, black, white | — | Order colour at purchase | |
| 06 · Electrical | ||||
| Rated voltage | 450/750 | V | Fixed wiring | |
| Test voltage (AC) | 2000 | V AC | 5 min routine | |
| DC resistance @ 20 °C | ≤ 7.41 | Ω/km | Per GB/T 3956 (pure Cu) | |
| Ampacity (conduit, est.) | ≈ 20–25 | A | 2.5 mm², 70 °C | |
| Ampacity (free air, est.) | Up to ≈ 32 | A | Derate for grouping / enclosure | |
| Capacitance | ≈ 150 | pF/m | At 1 kHz | |
| 07 · Thermal & Mechanical | ||||
| Max continuous conductor temp. | 70 | °C | Normal service | |
| Short-circuit temp. (≤5 s) | 160 | °C | Copper limit | |
| Min. ambient temp. | -15 | °C | Fixed installation | |
| Min. bending radius | ≥ 4 × OD ≈ 14 | mm | Flexible stranded core | |
| Halogen content | Halogen-containing | — | PVC compound | |
| 08 · Flame & Environment | ||||
| Flame retardancy | IEC 60332-1 | — | Single vertical flame | |
| Oil resistance | Limited | — | PVC insulation | |
| UV resistance | Limited | — | Indoor / conduit use | |
| Corrosion resistance | Limited (bare Cu) | — | Dry indoor only; use tinned variant for damp/outdoor | |
| ROHS / REACH | Compliant | — | EU 2011/65/EU | |
The Wire Test Parameters
| Test Parameters — BVR 1×2.5 mm² | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 7.41 Ω/km | Routine |
| 2 | AC voltage withstand | 2000 V AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | 500 V megohmmeter | ≥ 20 MΩ·km | Routine |
| 4 | Conductor construction | Visual + strand count | 49 × 0.25 mm pure Cu stranded | Routine |
| 5 | Insulation thickness | Micrometer cross-section | ≈ 0.8 mm | Routine |
| 6 | Dimensional check | Caliper | OD ≈ 3.6 mm | Routine |
| 7 | Print legibility | Visual + rubbing | Marks legible | Routine |
| 8 | Mass per unit length | Weighing | ≈ 30 kg/km | Routine |
| 9 | Appearance | Visual | Smooth, uniform colour, no blisters | Routine |
| 10 | Packing | Visual | Coil, sealed ends, labelled | Routine |
| 11 | Heat aging test | 7 days at 100 °C | Retention ≥ 70% | Type |
| 12 | Cold bend test | -15 °C, 4 h mandrel | No cracking | Type |
| 13 | Insulation tensile & elongation | Universal tester | Meets GB/T 5023 min. | Type |
| 14 | Flame retardancy | IEC 60332-1 | Self-extinguish | Type |
| 15 | Conductor flexibility | Mandrel bend, repeat cycles | No strand break, no insulation damage | Type |
| 16 | Wall thickness uniformity | Micrometer at 4 points | Min. wall ≥ nominal − tolerance | Type |
Cross Section Structure

| BVR 1×2.5 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Layered build-up: pure copper stranded Class 5 conductor (single core) → PVC insulation · 450/750 V single-core PVC insulated flexible building wire · panel internal wiring / vibrating equipment / tight bends · no shield, no outer jacket · -15~+70 °C | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor | Pure annealed copper, stranded Class 5 — 49 × 0.25 mm wires | — | ≈ 2.05 (strand bundle) | Flexible fixed wiring; R ≤ 7.41 Ω/km; bare pure copper for high conductivity |
| 2 | Insulation | PVC compound, extruded over the stranded conductor, colour-coded | ≈ 0.8 | ≈ 3.6 (finished) | Primary electrical insulation; 450/750 V rated; colour identifies circuit polarity |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 3.6 | mm | Single-core stranded flexible wire (est.) | ||
| Approximate cable mass | ≈ 30 | kg/km | Pure Cu stranded + PVC insulation | ||
| Nominal voltage rating | 450/750 | V | Fixed indoor / panel wiring | ||
| Max continuous conductor temp. | 70 | °C | Normal service | ||
| Min. ambient / installation temp. | -15 | °C | Fixed installation | ||
| DC resistance @ 20 °C | ≤ 7.41 | Ω/km | Class 5 pure copper, GB/T 3956 | ||
| Core count × cross-section | 1 × 2.5 | mm² | Single core, stranded | ||
| Shielding | None | — | Single-core wire, no braid / foil | ||
| Insulation resistance | ≥ 20 | MΩ·km | PVC at 20 °C | ||
| Test voltage (AC) | 2000 V AC / 5 min | — | Routine withstand test | ||
| Flame retardancy | IEC 60332-1 | — | Single vertical flame | ||
| Insulation colours | Red / yellow / blue / green-yellow / black / white | — | Order colour at purchase | ||
| Jacket colour | — | — | BVR has no outer jacket; insulation is the outer layer | ||
| Mass per 100 m | ≈ 3.0 | kg/100 m | For coil loading | ||
| Reference standard | GB/T 5023 / IEC 60227 / JB/T 8734 | — | PVC insulated flexible fixed wiring wire | ||
| Schematic — not to exact scale. Finished Ø ≈ 3.6 mm and weight ≈ 30 kg/km from cross-referenced industry samples; stranded pure copper conductor 49/0.25 mm, 0.8 mm PVC insulation. Pure copper (not tinned). Est. values confirmed against factory type certificate. | |||||
Construction Description
| Construction Description — BVR 1×2.5 mm² | |||
| Layer-by-layer build-up narrative · 450/750 V single-core PVC insulated flexible building wire · GB/T 5023 / IEC 60227 · pure annealed copper stranded Class 5 conductor / PVC insulation | |||
| 1. Product Identity & Ratings | |||
| BVR 1×2.5 is a single-core PVC insulated flexible building wire rated 450/750 V. The conductor is pure annealed bare copper (not tinned), stranded in a Class 5 flexible lay-up for easy bending in panels and tight runs. One 2.5 mm² stranded copper core is insulated by a continuous PVC extrusion. There is no braid shield, no inner sheath and no outer jacket. OD ≈ 3.6 mm, ≈ 30 kg/km. Max 70 °C, -15 to +70 °C. Intended for fixed indoor and panel wiring; not for moving drag chains or outdoor UV exposure. | |||
| 2. Pure Copper Stranded Conductor | |||
| The 2.5 mm² conductor is stranded from 49 pure annealed copper wires of 0.25 mm in a Class 5 flexible lay-up. Stranding keeps the wire supple around panel corners, terminal rows and tight duct bends, while DC resistance stays ≤ 7.41 Ω/km at 20 °C per GB/T 3956. Pure bare copper provides high conductivity for fixed installation; for damp or outdoor locations a tinned or insulated variant should be considered. | |||
| 3. PVC Insulation | |||
| A 0.8 mm PVC compound is extruded continuously over the stranded copper bundle, forming the only insulating and outer layer. The insulation provides the primary electrical barrier for 450/750 V circuits, with insulation resistance ≥ 20 MΩ·km at 20 °C. The PVC surface is smooth, uniform in wall thickness, and available in standard circuit colours. | |||
| 4. Lay-Up & Colour Coding | |||
| As a single-core wire there is no stranding of multiple cores, fillers or bedding. Colour coding identifies the circuit: red for live/phase, blue for neutral, green-yellow for protective earth, with yellow, black and white as supplementary colours. Customers specify the required colour at order time; mixed-colour lots are cut and packaged separately to avoid installation errors. | |||
| 5. Surface Marking & Application Range | |||
| The insulation surface is printed at regular intervals with the designation BVR, cross-section, voltage rating, manufacturer and metre mark. The wire is designed for fixed installation and flexible internal connections: panel internal wiring, vibrating equipment terminals, tight-bend runs, switchboard and distribution board connections. It is not a trailing appliance cable, not a shielded signal cable and not a submersible or direct-burial wire. |
8. Factory Advantages
Pure annealed stranded copper delivers stable conductivity with a flexible, supple core that resists kinking in tight panels. Class 5 stranding keeps the wire dressable around corners and terminal rows. Continuous PVC extrusion gives a smooth, uniform wall with consistent colour and diameter. Standard circuit colours are available to prevent wiring errors at site. Ferrules seat cleanly on the stranded bundle, reducing loose-connection risk. 100% routine electrical QA on every coil. Cut-to-length packaging with sealed ends reduces waste. Lightweight ≈ 30 kg/km for easy coil handling. Full traceability with MTC and certification support for panel-build and building-wiring tenders.

9. Packaging, Storage & Logistics
Cut to customer-specified length on export-grade coils, with both ends sealed to prevent moisture ingress. Coils wrapped in waterproof film and cardboard, labelled with designation BVR, cross-section, colour, length, weight, production date and reel number. Standard lengths 100/200/500/1000 m; custom lengths available. Store dry indoor, -10 to +40 °C, below 75% RH, away from direct sunlight, solvents and chemical fumes. FOB Shanghai/Nanjing/Qingdao; CIF and DAP available. Sample lead time 5–7 days; bulk production 15–25 days. Mixed-colour lots are packed and labelled separately.

10. Procurement Specification
State wire designation "BVR 1×2.5 pure copper", required colour (red/blue/yellow/green-yellow/black/white), and length per coil. Request the routine AC withstand test record (2000 V) and DC resistance certificate for the specific batch. Note this is a pure copper (bare) flexible fixed-wiring variant for dry indoor use — for damp or outdoor locations, specify a tinned or appropriate insulated variant. Specify any regional certification requirements (CE, etc.) at order time. Payment: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list.
11. Cable Industry FAQ
Q1: What does "BVR" mean? B denotes a copper conductor, V denotes PVC insulation, and R denotes a stranded flexible construction; BVR is the stranded flexible version of the BV building wire in IEC 60227 practice.
Q2: Why choose BVR over BV? The stranded Class 5 core is suppler and bends tighter than a solid wire, making BVR the preferred choice in panels, cabinets and vibrating equipment where BV solid would kink or fatigue.
Q3: Is the conductor solid or stranded? Stranded: 49 wires of 0.25 mm pure annealed copper in a Class 5 lay-up, DC resistance ≤ 7.41 Ω/km at 20 °C.
Q4: What is the voltage rating? 450/750 V, suitable for low-voltage fixed indoor and panel wiring.
Q5: What current can 2.5 mm² carry? ≈ 20–25 A in conduit, up to ≈ 32 A in free air, derated for grouping and enclosure; confirm against local wiring rules and circuit protection.
Q6: Why pure copper instead of tinned? Bare pure copper gives the highest conductivity for fixed indoor contacts; tinned copper is normally chosen where moisture or outdoor corrosion is a concern.
Q7: What do the colours mean? Red = live/phase, blue = neutral, green-yellow = protective earth; yellow, black and white are supplementary colours.
Q8: Does BVR have a shield? No — BVR is an unshielded single-core wire. For EMI-sensitive signal circuits, use a shielded RVVP-type multiconductor cable.
Q9: Can it be used outdoors? Not directly — limited UV resistance and bare copper oxidize in humidity. Install inside UV-protected conduit or choose an outdoor-rated cable.
Q10: What proof ships? Routine AC test record (2000 V) + DC resistance certificate + MTC.
Q11: What is the temperature range? -15 to +70 °C continuous. For high-temperature or flexible trailing-duty duty, a dedicated flexible or high-temperature cable should be specified instead.