RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
RVVP 3x6.0mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 3×10.0 mm² Three cores of 10.0 mm² copper conductor Construction: Three 10.0 mm² fine-stranded ...

Product Details

Conductor (×3):
Copper, Flexible (Class 5), Nominal 80×∅0.40 Mm (10.0 Mm²), Conductor Ø ≈ 5.2 Mm Per Core
Insulation:
PVC (Type TI2), Nominal Thickness 1.0 Mm, Min. Thickness 0.78 Mm
Lay-up:
Three Insulated Cores Twisted Together
Shield:
Pure Copper Braid, Coverage ≥ 80%, Nominal 16×10/0.10 Mm
Outer sheath:
PVC (Type TM2), Nominal Thickness 1.4 Mm, Min. Thickness 1.08 Mm
Conductor nominal area:
10.0 Mm² (Cu) × 3
Number of cores:
3
Conductor material:
Copper (Cu)
Conductor class:
Class 5 Flexible
Conductor construction:
80×∅0.40 Mm Per Core
Conductor diameter:
≈ 5.2 Mm Per Core
Insulation thickness (nom.):
1.0 Mm
Insulation thickness (min.):
0.78 Mm
Shield coverage:
≥ 80%
Outer sheath thickness (nom.):
1.4 Mm
Outer sheath thickness (min.):
1.08 Mm
Overall cable diameter:
15.5 – 18.0 Mm
Design outer diameter:
≈ 16.8 Mm
Approx. weight:
500 – 620 Kg/km
Design weight:
≈ 560 Kg/km
Cable shape:
Round

Product Description

RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

Cable Designation & Meaning

Code

Meaning

R

Flexible cord 

V

PVC insulation 

V

PVC sheath 

P

Copper braid shield 

3×10.0 mm²

Three cores of 10.0 mm² copper conductor


Construction: Three 10.0 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥80% coverage) over the laid-up cores, PVC outer sheath.

Applicable Standards

  • GB/T 5023.5-2008 / IEC 60227-5 — Polyvinyl chloride insulated cables — Flexible cables (cords)
  • GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables (Class 5 flexible)
  • GB/T 18380.3 / IEC 60332-3 — Flame retardant (Category A/B/C as specified)
  • GB/T 5023.2-2008 / IEC 60227-2 — Test methods

RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

RVVP 3×10.0 mm² — Flexible Shielded Heavy Feeder Cable — Specification 

1. Overview & Ratings

RVVP 3×10.0 is the largest 3-core RVVP size — a shielded heavy feeder cable rated 300/500 V. It uses pure annealed bare copper (not tinned) for both the conductor and braid, maximizing conductivity. The three 10.0 mm² cores are laid up in a triangular formation and handle 3-phase main feeder runs, large motor feeds, and heavy-duty power distribution near the power cable territory. The braid suppresses EMI/RFI from nearby VFDs and servo drives. OD ≈ 20.0 mm, ≈ 380 kg/km (est.), ≈ 55–70 A. Max conductor temperature 70 °C, -15 to +70 °C. Intended for dry indoor heavy feeder circuits; for damp or outdoor duty, specify tinned copper variant.

2. Construction Stack (Inner → Outer, expanded)

Layer / Feature Build Function
Conductor (×3) Pure annealed Cu, Class 5, 84×0.40 mm per core R ≤ 1.91 Ω/km, heavy feeder-grade current
Insulation PVC ≈ 1.0 mm per core 300/500 V dielectric, 3-phase coding
Inner sheath PVC + filler ≈ 1.2 mm Round bedding for triangular core lay
Braid shield Pure Cu, ≈ 85% coverage Low transfer impedance for heavy feeder circuits
Outer jacket PVC ≈ 1.5 mm Heavy-duty oil/abrasion protection

3. Electrical Characteristics

DC resistance ≤ 1.91 Ω/km at 20 °C per GB/T 3956 Class 5 pure copper — roughly 76% lower than 2.5 mm², making it suitable for heavy 3-phase feeder runs and large motor circuits. Rated voltage 300/500 V. Estimated ampacity ≈ 55–70 A in free air at 30 °C. Insulation resistance ≥ 20 MΩ·km. Routine AC withstand test at 2000 V for 5 minutes. Typical capacitance ≈ 250 pF/m at 1 kHz. The pure copper braid provides ≈ 60–70 dB shielding at 30–1000 MHz. Voltage drop ≈ 0.19 V per 100 m at 10 A — suitable for heavy 3-phase feeder runs up to 50 m.

Insulation & Sheath Data

Property

Value

Insulation material

PVC (Type TI2)

Outer sheath material

PVC (Type TM2)

Shield material

Tinned copper braid

Long-term service temp.

70 °C (continuous)

Max. conductor temp. (normal)

70 °C

Short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Test voltage AC (5 min)

2.0 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹² Ω·cm

Shield

 Pure copper braid, ≥ 80% coverage (EMI/RFI protection)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

300 / 300 V

GB/T 5023.5 (control/signal)

Max. system voltage

350 V AC / 500 V DC

—

Test voltage AC (5 min)

2.0 kV

Routine test

DC resistance @20 °C

≤ 1.91 Ω/km per core

GB/T 3956 Class 5 Cu max (10.0 mm²)

AC resistance @70 °C (est.)

≈ 2.39 Ω/km per core

—

Current rating in air (30 °C)

Control/low-power: 52 A per core​ (recommended max.)

conservative control rating

Current rating in tray (30 °C)

Control/low-power: 58 A per core​

—

DC current capacity

52 A​ per core

—

Short-circuit current (1 s, Cu, 160 °C)

≈ 1,100 A per core

—

Capacitance (core-to-core, approx.)

≈ 0.18 µF/km

PVC

Capacitance (core-to-shield, approx.)

≈ 0.28 µF/km

PVC

Inductive reactance (approx.)

≈ 0.09 Ω/km

at 50 Hz

Frequency

DC / up to 100 MHz (signal)

—

Characteristic impedance (approx.)

50 – 70 Ω

signal reference

Attenuation (at 1 MHz, approx.)

≈ 0.3 dB/100 m

—


Reference values: RVVP 3×10.0 at 52 A per core, 24 V DC → max load ≈ 1,248 W​ per core (low-power device supply). At 230 V AC → max load ≈ 11,960 VA​ per core (light power use).

4. Thermal & Flame Behaviour

Operating range -15 to +70 °C continuous. Short-circuit withstand up to 160 °C for ≤ 5 seconds. PVC insulation and jacket are flame-retardant per IEC 60332-1. The cable is halogen-containing (PVC), emitting HCl gas on burning — avoid in enclosed switchrooms. For public or enclosed spaces, specify LSZH alternatives. The 1.5 mm Type ST jacket is oil- and abrasion-resistant for heavy machinery and plant wiring. Note: bare pure copper oxidizes in humid environments — install in dry indoor or conduit-protected locations. UV resistance is limited.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

70 °C (continuous)

Max. short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Min. installation ambient temp.

−15 °C

Service ambient range

−15 °C to +70 °C

Flexing temp. range

−5 °C to +70 °C


Fire Performance (RVVP — PVC, Non-Low-Smoke)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 / IEC 60332-3​ (Category A/B/C as specified)

Halogen content

Contains halogen​ (PVC)

Smoke density

Not low-smoke​ (IEC 61034-2 not applicable)

Corrosivity

Corrosive​ (HCl emission from PVC)

Toxicity

Toxic fumes​ when burned (CO, HCl)

EMI shielding

Excellent​ (tinned copper braid, ≥85% coverage)

UV resistance

Poor​ (PVC degrades outdoors, use conduit or UV-resistant)

Water resistance

Limited​ (PVC sheath)

5. Installation Practice & Handling

Minimum bending radius ≥ 6×OD ≈ 120 mm for fixed installation; 12×OD ≈ 240 mm for drag-chain applications. The 20.0 mm OD and 380 kg/km make this the bulkiest and heaviest 3-core RVVP — plan cable trays, lifting and bending allowance carefully. When terminating, connect the braid shield to earth at a robust shield gland or drain wire, as heavy feeder circuits carry high fault energy. Use heavy-duty ferrules on the 84-strand conductors. Route the cable away from high-power motor cables by at least 300 mm. After installation, verify insulation resistance, shield continuity and 3-phase polarity before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 6 × OD → ≈ 101 mm at Ø16.8 mm

flexible cable

Max. pulling tension

150 N per core (10.0 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Not recommended​ (PVC, non-UV, water ingress)

—

Surface mounting

Cable tray, conduit, trunking, DIN rail

—

Conduit ID

≥ 63 mm

—

Fixing

cable ties, clamps, clips

—

Impact resistance

Low (PVC)

—

Water resistance

Limited​ (PVC sheath)

—

UV resistance

Poor​ (indoor/conduit only)

—

Flex life

Excellent​ (Class 5 fine-stranded)

flexible routing

Termination note

Compression lugs (10.0 mm²), crimp terminals, lug terminals

—


6. Typical Service Applications

3-phase main feeder runs from distribution panel to large machines, transformer secondary runs to load centers, large motor power feeds (up to ~15 HP), heavy-duty solenoid valve and actuator power, and interconnection between main switchgear and field distribution. The 10.0 mm² cross-section is the upper limit of RVVP 3-core size — the sweet spot for heavy feeder runs up to 30–50 m where current demand is 55–70 A and EMI protection is required. Not for: mains AC power distribution, high-speed fieldbus, direct burial, or outdoor UV-exposed runs.


RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

7. Testing & Quality Assurance Regime

Routine tests (100% production): DC resistance, AC voltage withstand (2000 V/5 min), insulation resistance, conductor construction, wall thickness, dimensional check, print legibility, mass per length, visual appearance, and packing. Type tests (per batch / material change): shield coverage, heat aging (100 °C/7 days), cold bend (-15 °C), jacket tensile, flame retardancy, and shielding effectiveness. Every coil ships with mill test certificate, ROHS and REACH declarations. The 300/500 V rating uses a 2000 V withstand test.


Cable Parameters


RVVP 3×10.0 mm² — Full Parameter Sheet
Shielded flexible heavy feeder cable · 300/500 V · pure annealed Cu Class 5 · PVC insulation/jacket · pure Cu braid ≈ 85% · 3-core triangular lay-up · GB/T 9330 / IEC 60227
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type RVVP — Flexible pure Cu, PVC ins., PVC jacket, braid shield

Rated voltage (U0/U) 300/500 V Heavy feeder / main power / large motor feeds

Number of cores 3 — 3 cores, triangular lay-up, colour-coded

Nominal cross-section 10.0 mm² Per core, Class 5 flexible

Conductor material Pure annealed copper (bare) — Class 5 per GB/T 3956, not tinned

Insulation material PVC (Type SP) — 70 °C rated, 1.0 mm wall

Shield Pure copper braid — ≈ 85% coverage, low transfer impedance

Outer jacket material PVC (Type ST) — Oil/abrasion resistant, 1.5 mm

Standard reference GB/T 9330 / IEC 60227 / UL 2464 — Harmonized control cable
02 · Conductor

Stranding 84 × 0.40 mm — Class 5 pure copper per core

Conductor diameter ≈ 4.0 mm Per core, strand-lay

DC resistance @ 20 °C ≤ 1.91 Ω/km Maximum per GB/T 3956 (pure Cu)

Conductor surface Bare pure copper — Not tinned; for dry indoor use
03 · Insulation

Insulation type PVC (Type SP) — Soft PVC, 70 °C

Insulation thickness ≈ 1.0 mm Nominal

Insulated core Ø ≈ 6.0 mm Per core

Insulation resistance ≥ 20 MΩ·km At 20 °C
04 · Shield & Inner Sheath

Inner sheath material PVC + polyester filler — Bedding over triangular core lay

Inner sheath thickness ≈ 1.2 mm Nominal

Shield type Pure Cu braid — Woven over inner sheath

Shield coverage ≈ 85 % Typical

Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
05 · Outer Jacket

Jacket material PVC (Type ST) — Oil/abrasion resistant

Jacket thickness ≈ 1.5 mm Nominal

Overall finished diameter ≈ 20.0 mm 3-core shielded heavy feeder cable

Approximate cable mass ≈ 380 kg/km Pure Cu + PVC + braid

Mass per 100 m ≈ 38.0 kg/100 m For coil / drum loading
06 · Electrical

Rated voltage 300/500 V Heavy feeder / main power

Test voltage (AC) 2000 V AC 5 min routine

DC resistance @ 20 °C ≤ 1.91 Ω/km Per GB/T 3956 (pure Cu)

Ampacity (free air) ≈ 55–70 A 10.0 mm², 70 °C

Voltage drop @ 10 A / 100 m ≈ 0.19 V I × R

Capacitance (core-core) ≈ 250 pF/m At 1 kHz
07 · Thermal & Mechanical

Max continuous conductor temp. 70 °C Normal service

Short-circuit temp. (≤5 s) 160 °C Copper limit

Min. ambient temp. -15 °C Fixed installation

Min. bending radius ≥ 6 × OD ≈ 120 mm Fixed; 12× for moving

Halogen content Halogen-containing — PVC compound
08 · Flame & Environment

Flame retardancy IEC 60332-1 — Single vertical flame

Oil resistance Good — Type ST PVC

UV resistance Limited — Indoor / conduit use

Corrosion resistance Limited (bare Cu) — Dry indoor only; use tinned for damp/outdoor

ROHS / REACH Compliant — EU 2011/65/EU


Cable Test Parameters


Test Parameters — RVVP 3×10.0 mm²
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 1.91 Ω/km Routine
2 AC voltage withstand 2000 V AC, 5 min No breakdown Routine
3 Insulation resistance 500 V megohmmeter ≥ 20 MΩ·km Routine
4 Conductor construction Visual + strand count 84 × 0.40 mm pure Cu per core Routine
5 Wall thickness Micrometer cross-section Ins. ≈ 1.0 mm; jacket ≈ 1.5 mm Routine
6 Dimensional check Caliper OD ≈ 20.0 mm Routine
7 Print legibility Visual + rubbing Marks legible Routine
8 Mass per unit length Weighing ≈ 380 kg/km Routine
9 Appearance Visual Smooth, no blisters Routine
10 Packing Visual Coil, sealed ends, labelled Routine
11 Shield coverage Unwrap + count ≥ 80% (≈ 85%) Type
12 Heat aging test 7 days at 100 °C Retention ≥ 70% Type
13 Cold bend test -15 °C, 4 h mandrel No cracking Type
14 Jacket tensile test Universal tester Meets GB/T 9330 min. Type
15 Flame retardancy IEC 60332-1 Self-extinguish Type
16 Shielding effectiveness Triaxial / open-field ≥ 60 dB at 30–1000 MHz Type


Cable Cross Section Structure


RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

RVVP 3×10.0 mm² — Cross-Section Construction Diagram (Schematic)
Layered build-up: pure copper Class 5 conductors (3 cores) → PVC insulation → inner PVC sheath → pure copper braid shield → PVC outer jacket · 300/500 V shielded heavy feeder cable · 3-phase main feeder / large motor feeds / heavy-duty power · EMI/RFI protection · -15~+70 °C
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (×3) Pure annealed copper, Class 5 flexible — 84 × 0.40 mm strands per core — ≈ 4.0 (per core) Heavy feeder; R ≤ 1.91 Ω/km; bare pure copper for high conductivity
2 Insulation (per core) PVC compound (Type SP), extruded over each conductor, colour-coded ≈ 1.0 ≈ 6.0 (per insulated core) Electrical insulation; 300/500 V rated; colour-coded for 3-phase identification
3 Inner sheath PVC compound, extruded over the three laid-up cores, round filler ≈ 1.2 ≈ 15.0 (before braid) Round and bed the triangular core lay; mechanical protection; bedding for braid
4 Braid shield Pure copper wire braid, ≈ 85% coverage, laid over inner sheath ≈ 0.7 (effective) ≈ 17.0 EMI/RFI shielding; low transfer impedance for heavy feeder circuits
5 Outer jacket PVC compound (Type ST), black or grey, extruded over braid ≈ 1.5 ≈ 20.0 (finished) Outer mechanical protection; oil-, abrasion-resistant; printed markings






Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 20.0 mm 3-core shielded heavy feeder cable (est.)
Approximate cable mass ≈ 380 kg/km Pure Cu + PVC + braid build-up
Nominal voltage rating 300/500 V Heavy feeder / main power / large motor feeds
Max continuous conductor temp. 70 °C Normal service
Min. ambient / installation temp. -15 °C Fixed installation
DC resistance @ 20 °C ≤ 1.91 Ω/km Class 5 pure copper, GB/T 3956
Core count × cross-section 3 × 10.0 mm² 3 cores, triangular lay-up
Shield coverage ≈ 85 % Pure copper braid
Insulation resistance ≥ 20 MΩ·km PVC at 20 °C
Test voltage (AC) 2000 V AC / 5 min — Routine withstand test
Flame retardancy IEC 60332-1 — Single vertical flame
Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
Jacket colour Black / grey / custom — Standard: black
Mass per 100 m ≈ 38.0 kg/100 m For coil / drum loading
Reference standard GB/T 9330 / IEC 60227 / UL 2464 — Harmonized control cable
Schematic — not to exact scale. Finished Ø ≈ 20.0 mm and weight ≈ 380 kg/km from cross-referenced industry samples; conductor stranding 84/0.40 mm per core, 3-core triangular lay-up, and braid coverage ≈ 85%. Pure copper (not tinned) for maximum conductivity. Est. values confirmed against factory type certificate.


Construction Description


Construction Description — RVVP 3×10.0 mm²
Layer-by-layer build-up narrative · 300/500 V shielded heavy feeder cable · GB/T 9330 / IEC 60227 · pure annealed copper / PVC insulation / pure copper braid shield / PVC outer jacket
1. Product Identity & Ratings
RVVP 3×10.0 is the largest 3-core RVVP size — a shielded heavy feeder cable rated 300/500 V. It uses pure annealed copper (not tinned) for both the conductor and braid, maximizing conductivity. The three 10.0 mm² cores are laid up in a triangular formation and handle 3-phase main feeder runs, large motor feeds, and heavy-duty power distribution near the power cable territory. OD ≈ 20.0 mm, ≈ 380 kg/km. Max 70 °C, -15 to +70 °C. For dry indoor use; specify tinned variant for damp/outdoor.
2. Pure Copper Conductor (×3)
Each 10.0 mm² core is stranded from 84 pure annealed copper wires of 0.40 mm in a Class 5 flexible lay-up. Pure copper (bare, not tinned) delivers the highest conductivity: DC resistance ≤ 1.91 Ω/km at 20 °C — roughly 76% lower than 2.5 mm², making it suitable for heavy 3-phase feeder runs and large motor circuits. The 84-wire stranding keeps the cable flexible despite the large cross-section.
3. PVC Insulation
Each conductor receives a 1.0 mm Type SP PVC extrusion, colour-coded for 3-phase identification — typically brown/black/grey (L1/L2/L3) or red/white/blue. The 1.0 mm wall provides extra dielectric margin for heavy feeder circuits. Insulation resistance ≥ 20 MΩ·km at 20 °C.
4. Inner Sheath + Braid Shield
The three insulated cores are laid up in a triangular formation with round fillers to keep the cable round, then bedded with a 1.2 mm PVC inner sheath. Over this, a pure copper braid is woven at ≈ 85% coverage. The braid provides EMI/RFI shielding for heavy feeder circuits, diverting interference to ground through the shield drain — critical for large motor and VFD circuits.
5. Outer PVC Jacket
A 1.5 mm Type ST PVC jacket completes the build, yielding an OD of ≈ 20.0 mm — the largest 3-core RVVP size, built for heavy-duty power distribution. The jacket is oil- and abrasion-resistant, flame-retardant per IEC 60332-1, and printed with product type, cross-section, voltage, metre mark and manufacturer. For drag-chain duty, specify RVVSP variant.

8. Factory Advantages

Pure annealed copper conductor at 84×0.40 mm stranding delivers maximum conductivity with Class 5 flexibility. Very low DC resistance (1.91 Ω/km) supports heavy 3-phase feeder runs and large motor circuits. 1.0 mm insulation and 1.5 mm heavy-duty jacket provide robust dielectric and mechanical protection. Pure copper braid at ≈ 85% coverage provides low transfer impedance. 3-core triangular lay-up combines 3-phase power in one shielded cable. Colour-coded cores prevent wiring errors. 100% routine electrical QA on every reel. Cut-to-length on coils with sealed ends. Full traceability with MTC and certification support for industrial plant tenders.


RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

9. Packaging, Storage & Logistics

Cut to customer-specified length on export-grade coils, with both ends heat-sealed to prevent moisture ingress. Coils wrapped in waterproof film and corrugated cardboard, labelled with product type, core count, cross-section, length, weight, production date and reel number. Standard lengths 100/200/500/1000 m. Store dry indoor, -10 to +40 °C, below 75% RH, away from direct sunlight and chemical solvents. FOB Shanghai/Nanjing/Qingdao; CIF and DAP available. Sample lead time 5–7 days; bulk production 15–25 days.


RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control

10. Procurement Specification

State cable designation "RVVP 3×10.0 pure copper", required length per coil, and core colour preference (e.g. brown/black/grey for 3-phase). Request the routine AC withstand test record (2000 V) and shield coverage certificate for the specific batch. Note that this is a pure copper (bare) heavy feeder variant for dry indoor use — for damp or outdoor applications, specify the tinned copper variant. Specify any regional certification requirements (UL 2464, CE, etc.) at order time. Payment: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list.

11. Cable Industry FAQ

Q1: Why choose 10.0 mm² over 2.5 mm²? Much lower DC resistance (1.91 vs 7.98 Ω/km), higher ampacity (55–70 A vs 16–22 A), and enough current for heavy 3-phase feeder runs and large motor circuits.

Q2: Can it power large 3-phase motors? Yes — the 10.0 mm² core can carry 55–70 A, enough for 3-phase motors up to ~15 HP and heavy-duty solenoid valves.

Q3: How long can the heavy feeder run be? At 24 V DC and 10 A load, voltage drop is ≈ 0.19 V per 100 m — suitable for heavy feeder runs up to 50 m with acceptable voltage loss.

Q4: Is this the largest RVVP 3-core size? Yes — 10.0 mm² is the upper limit of the standard RVVP 3-core range. For larger cross-sections, switch to RVV or power cable.

Q5: What is the voltage rating? 300/500 V, suitable for low-voltage heavy feeder and power circuits.

Q6: Why pure copper instead of tinned? Bare pure copper has higher conductivity than tinned copper, ideal for heavy feeder circuits where every ohm matters.

Q7: Is it suitable for outdoor use? No — limited UV resistance and bare copper oxidize in humidity. Use indoors or in UV-protected conduits.

Q8: What is the bending radius? ≥ 6×OD ≈ 120 mm for fixed; 12× for moving applications.

Q9: What is the temperature range? -15 to +70 °C continuous.

Q10: What proof ships? Routine AC test record (2000 V) + shield coverage certificate + MTC.

Q11: When should I switch to a power cable? For cross-sections above 10.0 mm², higher voltage, or mains distribution, switch to RVV, YJV or other power cable types.