RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control
Product Summary
Product Details
Product Description
RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
R |
Flexible cord |
|
V |
PVC insulation |
|
V |
PVC sheath |
|
P |
Copper braid shield |
|
3×10.0 mm² |
Three cores of 10.0 mm² copper conductor |
Construction: Three 10.0 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥80% coverage) over the laid-up cores, PVC outer sheath.
Applicable Standards
- GB/T 5023.5-2008 / IEC 60227-5 — Polyvinyl chloride insulated cables — Flexible cables (cords)
- GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables (Class 5 flexible)
- GB/T 18380.3 / IEC 60332-3 — Flame retardant (Category A/B/C as specified)
- GB/T 5023.2-2008 / IEC 60227-2 — Test methods
RVVP 3×10.0 mm² — Flexible Shielded Heavy Feeder Cable — Specification
1. Overview & Ratings
RVVP 3×10.0 is the largest 3-core RVVP size — a shielded heavy feeder cable rated 300/500 V. It uses pure annealed bare copper (not tinned) for both the conductor and braid, maximizing conductivity. The three 10.0 mm² cores are laid up in a triangular formation and handle 3-phase main feeder runs, large motor feeds, and heavy-duty power distribution near the power cable territory. The braid suppresses EMI/RFI from nearby VFDs and servo drives. OD ≈ 20.0 mm, ≈ 380 kg/km (est.), ≈ 55–70 A. Max conductor temperature 70 °C, -15 to +70 °C. Intended for dry indoor heavy feeder circuits; for damp or outdoor duty, specify tinned copper variant.
2. Construction Stack (Inner → Outer, expanded)
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor (×3) | Pure annealed Cu, Class 5, 84×0.40 mm per core | R ≤ 1.91 Ω/km, heavy feeder-grade current |
| Insulation | PVC ≈ 1.0 mm per core | 300/500 V dielectric, 3-phase coding |
| Inner sheath | PVC + filler ≈ 1.2 mm | Round bedding for triangular core lay |
| Braid shield | Pure Cu, ≈ 85% coverage | Low transfer impedance for heavy feeder circuits |
| Outer jacket | PVC ≈ 1.5 mm | Heavy-duty oil/abrasion protection |
3. Electrical Characteristics
DC resistance ≤ 1.91 Ω/km at 20 °C per GB/T 3956 Class 5 pure copper — roughly 76% lower than 2.5 mm², making it suitable for heavy 3-phase feeder runs and large motor circuits. Rated voltage 300/500 V. Estimated ampacity ≈ 55–70 A in free air at 30 °C. Insulation resistance ≥ 20 MΩ·km. Routine AC withstand test at 2000 V for 5 minutes. Typical capacitance ≈ 250 pF/m at 1 kHz. The pure copper braid provides ≈ 60–70 dB shielding at 30–1000 MHz. Voltage drop ≈ 0.19 V per 100 m at 10 A — suitable for heavy 3-phase feeder runs up to 50 m.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
PVC (Type TI2) |
|
Outer sheath material |
PVC (Type TM2) |
|
Shield material |
Tinned copper braid |
|
Long-term service temp. |
70 °C (continuous) |
|
Max. conductor temp. (normal) |
70 °C |
|
Short-circuit temp. (≤5 s) |
160 °C |
|
Emergency overload temp. |
100 °C (≤1 h) |
|
Test voltage AC (5 min) |
2.0 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹² Ω·cm |
|
Shield |
Pure copper braid, ≥ 80% coverage (EMI/RFI protection) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
300 / 300 V |
GB/T 5023.5 (control/signal) |
|
Max. system voltage |
350 V AC / 500 V DC |
— |
|
Test voltage AC (5 min) |
2.0 kV |
Routine test |
|
DC resistance @20 °C |
≤ 1.91 Ω/km per core |
GB/T 3956 Class 5 Cu max (10.0 mm²) |
|
AC resistance @70 °C (est.) |
≈ 2.39 Ω/km per core |
— |
|
Current rating in air (30 °C) |
Control/low-power: 52 A per core (recommended max.) |
conservative control rating |
|
Current rating in tray (30 °C) |
Control/low-power: 58 A per core |
— |
|
DC current capacity |
52 A per core |
— |
|
Short-circuit current (1 s, Cu, 160 °C) |
≈ 1,100 A per core |
— |
|
Capacitance (core-to-core, approx.) |
≈ 0.18 µF/km |
PVC |
|
Capacitance (core-to-shield, approx.) |
≈ 0.28 µF/km |
PVC |
|
Inductive reactance (approx.) |
≈ 0.09 Ω/km |
at 50 Hz |
|
Frequency |
DC / up to 100 MHz (signal) |
— |
|
Characteristic impedance (approx.) |
50 – 70 Ω |
signal reference |
|
Attenuation (at 1 MHz, approx.) |
≈ 0.3 dB/100 m |
— |
Reference values: RVVP 3×10.0 at 52 A per core, 24 V DC → max load ≈ 1,248 W per core (low-power device supply). At 230 V AC → max load ≈ 11,960 VA per core (light power use).
4. Thermal & Flame Behaviour
Operating range -15 to +70 °C continuous. Short-circuit withstand up to 160 °C for ≤ 5 seconds. PVC insulation and jacket are flame-retardant per IEC 60332-1. The cable is halogen-containing (PVC), emitting HCl gas on burning — avoid in enclosed switchrooms. For public or enclosed spaces, specify LSZH alternatives. The 1.5 mm Type ST jacket is oil- and abrasion-resistant for heavy machinery and plant wiring. Note: bare pure copper oxidizes in humid environments — install in dry indoor or conduit-protected locations. UV resistance is limited.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
70 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
160 °C |
|
Emergency overload temp. |
100 °C (≤1 h) |
|
Min. installation ambient temp. |
−15 °C |
|
Service ambient range |
−15 °C to +70 °C |
|
Flexing temp. range |
−5 °C to +70 °C |
Fire Performance (RVVP — PVC, Non-Low-Smoke)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.3 / IEC 60332-3 (Category A/B/C as specified) |
|
Halogen content |
Contains halogen (PVC) |
|
Smoke density |
Not low-smoke (IEC 61034-2 not applicable) |
|
Corrosivity |
Corrosive (HCl emission from PVC) |
|
Toxicity |
Toxic fumes when burned (CO, HCl) |
|
EMI shielding |
Excellent (tinned copper braid, ≥85% coverage) |
|
UV resistance |
Poor (PVC degrades outdoors, use conduit or UV-resistant) |
|
Water resistance |
Limited (PVC sheath) |
5. Installation Practice & Handling
Minimum bending radius ≥ 6×OD ≈ 120 mm for fixed installation; 12×OD ≈ 240 mm for drag-chain applications. The 20.0 mm OD and 380 kg/km make this the bulkiest and heaviest 3-core RVVP — plan cable trays, lifting and bending allowance carefully. When terminating, connect the braid shield to earth at a robust shield gland or drain wire, as heavy feeder circuits carry high fault energy. Use heavy-duty ferrules on the 84-strand conductors. Route the cable away from high-power motor cables by at least 300 mm. After installation, verify insulation resistance, shield continuity and 3-phase polarity before energizing.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 6 × OD → ≈ 101 mm at Ø16.8 mm |
flexible cable |
|
Max. pulling tension |
150 N per core (10.0 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Not recommended (PVC, non-UV, water ingress) |
— |
|
Surface mounting |
Cable tray, conduit, trunking, DIN rail |
— |
|
Conduit ID |
≥ 63 mm |
— |
|
Fixing |
cable ties, clamps, clips |
— |
|
Impact resistance |
Low (PVC) |
— |
|
Water resistance |
Limited (PVC sheath) |
— |
|
UV resistance |
Poor (indoor/conduit only) |
— |
|
Flex life |
Excellent (Class 5 fine-stranded) |
flexible routing |
|
Termination note |
Compression lugs (10.0 mm²), crimp terminals, lug terminals |
— |
6. Typical Service Applications
3-phase main feeder runs from distribution panel to large machines, transformer secondary runs to load centers, large motor power feeds (up to ~15 HP), heavy-duty solenoid valve and actuator power, and interconnection between main switchgear and field distribution. The 10.0 mm² cross-section is the upper limit of RVVP 3-core size — the sweet spot for heavy feeder runs up to 30–50 m where current demand is 55–70 A and EMI protection is required. Not for: mains AC power distribution, high-speed fieldbus, direct burial, or outdoor UV-exposed runs.

7. Testing & Quality Assurance Regime
Routine tests (100% production): DC resistance, AC voltage withstand (2000 V/5 min), insulation resistance, conductor construction, wall thickness, dimensional check, print legibility, mass per length, visual appearance, and packing. Type tests (per batch / material change): shield coverage, heat aging (100 °C/7 days), cold bend (-15 °C), jacket tensile, flame retardancy, and shielding effectiveness. Every coil ships with mill test certificate, ROHS and REACH declarations. The 300/500 V rating uses a 2000 V withstand test.
Cable Parameters
| RVVP 3×10.0 mm² — Full Parameter Sheet | ||||
| Shielded flexible heavy feeder cable · 300/500 V · pure annealed Cu Class 5 · PVC insulation/jacket · pure Cu braid ≈ 85% · 3-core triangular lay-up · GB/T 9330 / IEC 60227 | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | RVVP | — | Flexible pure Cu, PVC ins., PVC jacket, braid shield | |
| Rated voltage (U0/U) | 300/500 | V | Heavy feeder / main power / large motor feeds | |
| Number of cores | 3 | — | 3 cores, triangular lay-up, colour-coded | |
| Nominal cross-section | 10.0 | mm² | Per core, Class 5 flexible | |
| Conductor material | Pure annealed copper (bare) | — | Class 5 per GB/T 3956, not tinned | |
| Insulation material | PVC (Type SP) | — | 70 °C rated, 1.0 mm wall | |
| Shield | Pure copper braid | — | ≈ 85% coverage, low transfer impedance | |
| Outer jacket material | PVC (Type ST) | — | Oil/abrasion resistant, 1.5 mm | |
| Standard reference | GB/T 9330 / IEC 60227 / UL 2464 | — | Harmonized control cable | |
| 02 · Conductor | ||||
| Stranding | 84 × 0.40 mm | — | Class 5 pure copper per core | |
| Conductor diameter | ≈ 4.0 | mm | Per core, strand-lay | |
| DC resistance @ 20 °C | ≤ 1.91 | Ω/km | Maximum per GB/T 3956 (pure Cu) | |
| Conductor surface | Bare pure copper | — | Not tinned; for dry indoor use | |
| 03 · Insulation | ||||
| Insulation type | PVC (Type SP) | — | Soft PVC, 70 °C | |
| Insulation thickness | ≈ 1.0 | mm | Nominal | |
| Insulated core Ø | ≈ 6.0 | mm | Per core | |
| Insulation resistance | ≥ 20 | MΩ·km | At 20 °C | |
| 04 · Shield & Inner Sheath | ||||
| Inner sheath material | PVC + polyester filler | — | Bedding over triangular core lay | |
| Inner sheath thickness | ≈ 1.2 | mm | Nominal | |
| Shield type | Pure Cu braid | — | Woven over inner sheath | |
| Shield coverage | ≈ 85 | % | Typical | |
| Shielding effectiveness | ≈ 60–70 | dB | At 30–1000 MHz | |
| 05 · Outer Jacket | ||||
| Jacket material | PVC (Type ST) | — | Oil/abrasion resistant | |
| Jacket thickness | ≈ 1.5 | mm | Nominal | |
| Overall finished diameter | ≈ 20.0 | mm | 3-core shielded heavy feeder cable | |
| Approximate cable mass | ≈ 380 | kg/km | Pure Cu + PVC + braid | |
| Mass per 100 m | ≈ 38.0 | kg/100 m | For coil / drum loading | |
| 06 · Electrical | ||||
| Rated voltage | 300/500 | V | Heavy feeder / main power | |
| Test voltage (AC) | 2000 | V AC | 5 min routine | |
| DC resistance @ 20 °C | ≤ 1.91 | Ω/km | Per GB/T 3956 (pure Cu) | |
| Ampacity (free air) | ≈ 55–70 | A | 10.0 mm², 70 °C | |
| Voltage drop @ 10 A / 100 m | ≈ 0.19 | V | I × R | |
| Capacitance (core-core) | ≈ 250 | pF/m | At 1 kHz | |
| 07 · Thermal & Mechanical | ||||
| Max continuous conductor temp. | 70 | °C | Normal service | |
| Short-circuit temp. (≤5 s) | 160 | °C | Copper limit | |
| Min. ambient temp. | -15 | °C | Fixed installation | |
| Min. bending radius | ≥ 6 × OD ≈ 120 | mm | Fixed; 12× for moving | |
| Halogen content | Halogen-containing | — | PVC compound | |
| 08 · Flame & Environment | ||||
| Flame retardancy | IEC 60332-1 | — | Single vertical flame | |
| Oil resistance | Good | — | Type ST PVC | |
| UV resistance | Limited | — | Indoor / conduit use | |
| Corrosion resistance | Limited (bare Cu) | — | Dry indoor only; use tinned for damp/outdoor | |
| ROHS / REACH | Compliant | — | EU 2011/65/EU | |
Cable Test Parameters
| Test Parameters — RVVP 3×10.0 mm² | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 1.91 Ω/km | Routine |
| 2 | AC voltage withstand | 2000 V AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | 500 V megohmmeter | ≥ 20 MΩ·km | Routine |
| 4 | Conductor construction | Visual + strand count | 84 × 0.40 mm pure Cu per core | Routine |
| 5 | Wall thickness | Micrometer cross-section | Ins. ≈ 1.0 mm; jacket ≈ 1.5 mm | Routine |
| 6 | Dimensional check | Caliper | OD ≈ 20.0 mm | Routine |
| 7 | Print legibility | Visual + rubbing | Marks legible | Routine |
| 8 | Mass per unit length | Weighing | ≈ 380 kg/km | Routine |
| 9 | Appearance | Visual | Smooth, no blisters | Routine |
| 10 | Packing | Visual | Coil, sealed ends, labelled | Routine |
| 11 | Shield coverage | Unwrap + count | ≥ 80% (≈ 85%) | Type |
| 12 | Heat aging test | 7 days at 100 °C | Retention ≥ 70% | Type |
| 13 | Cold bend test | -15 °C, 4 h mandrel | No cracking | Type |
| 14 | Jacket tensile test | Universal tester | Meets GB/T 9330 min. | Type |
| 15 | Flame retardancy | IEC 60332-1 | Self-extinguish | Type |
| 16 | Shielding effectiveness | Triaxial / open-field | ≥ 60 dB at 30–1000 MHz | Type |
Cable Cross Section Structure

| RVVP 3×10.0 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| Layered build-up: pure copper Class 5 conductors (3 cores) → PVC insulation → inner PVC sheath → pure copper braid shield → PVC outer jacket · 300/500 V shielded heavy feeder cable · 3-phase main feeder / large motor feeds / heavy-duty power · EMI/RFI protection · -15~+70 °C | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (×3) | Pure annealed copper, Class 5 flexible — 84 × 0.40 mm strands per core | — | ≈ 4.0 (per core) | Heavy feeder; R ≤ 1.91 Ω/km; bare pure copper for high conductivity |
| 2 | Insulation (per core) | PVC compound (Type SP), extruded over each conductor, colour-coded | ≈ 1.0 | ≈ 6.0 (per insulated core) | Electrical insulation; 300/500 V rated; colour-coded for 3-phase identification |
| 3 | Inner sheath | PVC compound, extruded over the three laid-up cores, round filler | ≈ 1.2 | ≈ 15.0 (before braid) | Round and bed the triangular core lay; mechanical protection; bedding for braid |
| 4 | Braid shield | Pure copper wire braid, ≈ 85% coverage, laid over inner sheath | ≈ 0.7 (effective) | ≈ 17.0 | EMI/RFI shielding; low transfer impedance for heavy feeder circuits |
| 5 | Outer jacket | PVC compound (Type ST), black or grey, extruded over braid | ≈ 1.5 | ≈ 20.0 (finished) | Outer mechanical protection; oil-, abrasion-resistant; printed markings |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 20.0 | mm | 3-core shielded heavy feeder cable (est.) | ||
| Approximate cable mass | ≈ 380 | kg/km | Pure Cu + PVC + braid build-up | ||
| Nominal voltage rating | 300/500 | V | Heavy feeder / main power / large motor feeds | ||
| Max continuous conductor temp. | 70 | °C | Normal service | ||
| Min. ambient / installation temp. | -15 | °C | Fixed installation | ||
| DC resistance @ 20 °C | ≤ 1.91 | Ω/km | Class 5 pure copper, GB/T 3956 | ||
| Core count × cross-section | 3 × 10.0 | mm² | 3 cores, triangular lay-up | ||
| Shield coverage | ≈ 85 | % | Pure copper braid | ||
| Insulation resistance | ≥ 20 | MΩ·km | PVC at 20 °C | ||
| Test voltage (AC) | 2000 V AC / 5 min | — | Routine withstand test | ||
| Flame retardancy | IEC 60332-1 | — | Single vertical flame | ||
| Shielding effectiveness | ≈ 60–70 | dB | At 30–1000 MHz | ||
| Jacket colour | Black / grey / custom | — | Standard: black | ||
| Mass per 100 m | ≈ 38.0 | kg/100 m | For coil / drum loading | ||
| Reference standard | GB/T 9330 / IEC 60227 / UL 2464 | — | Harmonized control cable | ||
| Schematic — not to exact scale. Finished Ø ≈ 20.0 mm and weight ≈ 380 kg/km from cross-referenced industry samples; conductor stranding 84/0.40 mm per core, 3-core triangular lay-up, and braid coverage ≈ 85%. Pure copper (not tinned) for maximum conductivity. Est. values confirmed against factory type certificate. | |||||
Construction Description
| Construction Description — RVVP 3×10.0 mm² | |||
| Layer-by-layer build-up narrative · 300/500 V shielded heavy feeder cable · GB/T 9330 / IEC 60227 · pure annealed copper / PVC insulation / pure copper braid shield / PVC outer jacket | |||
| 1. Product Identity & Ratings | |||
| RVVP 3×10.0 is the largest 3-core RVVP size — a shielded heavy feeder cable rated 300/500 V. It uses pure annealed copper (not tinned) for both the conductor and braid, maximizing conductivity. The three 10.0 mm² cores are laid up in a triangular formation and handle 3-phase main feeder runs, large motor feeds, and heavy-duty power distribution near the power cable territory. OD ≈ 20.0 mm, ≈ 380 kg/km. Max 70 °C, -15 to +70 °C. For dry indoor use; specify tinned variant for damp/outdoor. | |||
| 2. Pure Copper Conductor (×3) | |||
| Each 10.0 mm² core is stranded from 84 pure annealed copper wires of 0.40 mm in a Class 5 flexible lay-up. Pure copper (bare, not tinned) delivers the highest conductivity: DC resistance ≤ 1.91 Ω/km at 20 °C — roughly 76% lower than 2.5 mm², making it suitable for heavy 3-phase feeder runs and large motor circuits. The 84-wire stranding keeps the cable flexible despite the large cross-section. | |||
| 3. PVC Insulation | |||
| Each conductor receives a 1.0 mm Type SP PVC extrusion, colour-coded for 3-phase identification — typically brown/black/grey (L1/L2/L3) or red/white/blue. The 1.0 mm wall provides extra dielectric margin for heavy feeder circuits. Insulation resistance ≥ 20 MΩ·km at 20 °C. | |||
| 4. Inner Sheath + Braid Shield | |||
| The three insulated cores are laid up in a triangular formation with round fillers to keep the cable round, then bedded with a 1.2 mm PVC inner sheath. Over this, a pure copper braid is woven at ≈ 85% coverage. The braid provides EMI/RFI shielding for heavy feeder circuits, diverting interference to ground through the shield drain — critical for large motor and VFD circuits. | |||
| 5. Outer PVC Jacket | |||
| A 1.5 mm Type ST PVC jacket completes the build, yielding an OD of ≈ 20.0 mm — the largest 3-core RVVP size, built for heavy-duty power distribution. The jacket is oil- and abrasion-resistant, flame-retardant per IEC 60332-1, and printed with product type, cross-section, voltage, metre mark and manufacturer. For drag-chain duty, specify RVVSP variant. |
8. Factory Advantages
Pure annealed copper conductor at 84×0.40 mm stranding delivers maximum conductivity with Class 5 flexibility. Very low DC resistance (1.91 Ω/km) supports heavy 3-phase feeder runs and large motor circuits. 1.0 mm insulation and 1.5 mm heavy-duty jacket provide robust dielectric and mechanical protection. Pure copper braid at ≈ 85% coverage provides low transfer impedance. 3-core triangular lay-up combines 3-phase power in one shielded cable. Colour-coded cores prevent wiring errors. 100% routine electrical QA on every reel. Cut-to-length on coils with sealed ends. Full traceability with MTC and certification support for industrial plant tenders.

9. Packaging, Storage & Logistics
Cut to customer-specified length on export-grade coils, with both ends heat-sealed to prevent moisture ingress. Coils wrapped in waterproof film and corrugated cardboard, labelled with product type, core count, cross-section, length, weight, production date and reel number. Standard lengths 100/200/500/1000 m. Store dry indoor, -10 to +40 °C, below 75% RH, away from direct sunlight and chemical solvents. FOB Shanghai/Nanjing/Qingdao; CIF and DAP available. Sample lead time 5–7 days; bulk production 15–25 days.

10. Procurement Specification
State cable designation "RVVP 3×10.0 pure copper", required length per coil, and core colour preference (e.g. brown/black/grey for 3-phase). Request the routine AC withstand test record (2000 V) and shield coverage certificate for the specific batch. Note that this is a pure copper (bare) heavy feeder variant for dry indoor use — for damp or outdoor applications, specify the tinned copper variant. Specify any regional certification requirements (UL 2464, CE, etc.) at order time. Payment: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list.
11. Cable Industry FAQ
Q1: Why choose 10.0 mm² over 2.5 mm²? Much lower DC resistance (1.91 vs 7.98 Ω/km), higher ampacity (55–70 A vs 16–22 A), and enough current for heavy 3-phase feeder runs and large motor circuits.
Q2: Can it power large 3-phase motors? Yes — the 10.0 mm² core can carry 55–70 A, enough for 3-phase motors up to ~15 HP and heavy-duty solenoid valves.
Q3: How long can the heavy feeder run be? At 24 V DC and 10 A load, voltage drop is ≈ 0.19 V per 100 m — suitable for heavy feeder runs up to 50 m with acceptable voltage loss.
Q4: Is this the largest RVVP 3-core size? Yes — 10.0 mm² is the upper limit of the standard RVVP 3-core range. For larger cross-sections, switch to RVV or power cable.
Q5: What is the voltage rating? 300/500 V, suitable for low-voltage heavy feeder and power circuits.
Q6: Why pure copper instead of tinned? Bare pure copper has higher conductivity than tinned copper, ideal for heavy feeder circuits where every ohm matters.
Q7: Is it suitable for outdoor use? No — limited UV resistance and bare copper oxidize in humidity. Use indoors or in UV-protected conduits.
Q8: What is the bending radius? ≥ 6×OD ≈ 120 mm for fixed; 12× for moving applications.
Q9: What is the temperature range? -15 to +70 °C continuous.
Q10: What proof ships? Routine AC test record (2000 V) + shield coverage certificate + MTC.
Q11: When should I switch to a power cable? For cross-sections above 10.0 mm², higher voltage, or mains distribution, switch to RVV, YJV or other power cable types.