RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control
RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control
제품 요약
RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 3×10.0 mm² Three cores of 10.0 mm² copper conductor Construction : Three 10.0 mm² fine...
제품 세부정보
Conductor (×3):
구리, 유연성(클래스 5), 공칭 80×∅0.40mm(10.0mm²), 코어당 도체 Ø ∅5.2mm
Insulation:
PVC(TI2 유형), 공칭 두께 1.0mm, 최소 두께 0.78mm
Lay-up:
3개의 절연 코어가 함께 꼬여 있음
Shield:
순수 구리 브레이드, 적용 범위 ≥ 80%, 공칭 16×10/0.10mm
Outer sheath:
PVC(유형 TM2), 공칭 두께 1.4mm, 최소 두께 1.08mm
Conductor nominal area:
10.0mm²(Cu) × 3
Number of cores:
3
Conductor material:
구리 (Cu)
Conductor class:
클래스 5 유연성
Conductor construction:
코어당 80×∅0.40mm
Conductor diameter:
≒ 코어당 5.2mm
Insulation thickness (nom.):
1.0mm
Insulation thickness (min.):
0.78 mm
Shield coverage:
≥ 80%
Outer sheath thickness (nom.):
1.4 밀리미터
Outer sheath thickness (min.):
1.08 mm
Overall cable diameter:
15.5 – 18.0mm
Design outer diameter:
≒ 16.8mm
Approx. weight:
500 – 620kg/km
Design weight:
≒ 560kg/km
Cable shape:
둥근
제품 설명
RVVP 3x10mm² Shielded Control Cable Flexible Copper Cable for Heavy Industrial Equipment Control Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 3×10.0 mm² Three cores of 10.0 mm² copper conductor Construction : Three 10.0 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥80% coverage) over the laid-up cores, PVC outer sheath. Applicable Standards GB/T