RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V

RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
RVVP 2x6.0mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 2×6.0 mm² Two cores of 6.0 mm² copper conductor Construction: Two 6.0 mm² fine...

Product Details

Highlight:

RVVP 2x6.0mm² shielded power cable

,

braided copper control cable 300/500V

,

2 core heavy duty flexible cable

Conductor (×2):
Copper, Flexible (Class 5), Nominal 84×∅0.30 Mm (6.0 Mm²), Conductor Ø ≈ 3.9 Mm Per Core
Insulation:
PVC (Type TI2), Nominal Thickness 0.8 Mm, Min. Thickness 0.62 Mm
Lay-up:
Two Insulated Cores Twisted Together
Shield:
Pure Copper Braid, Coverage ≥ 80%, Nominal 16×8/0.10 Mm
Outer sheath:
PVC (Type TM2), Nominal Thickness 1.2 Mm, Min. Thickness 0.92 Mm
Conductor nominal area:
6.0 Mm² (Cu) × 2
Number of cores:
2
Conductor material:
Copper (Cu)
Conductor class:
Class 5 Flexible
Conductor construction:
84×∅0.30 Mm Per Core
Conductor diameter:
≈ 3.9 Mm Per Core
Insulation thickness (nom.):
0.8 Mm
Insulation thickness (min.):
0.62 Mm
Shield coverage:
≥ 80%
Outer sheath thickness (nom.):
1.2 Mm
Outer sheath thickness (min.):
0.92 Mm
Overall cable diameter:
11.8 – 13.5 Mm
Design outer diameter:
≈ 12.6 Mm
Approx. weight:
250 – 310 Kg/km
Design weight:
≈ 280 Kg/km
Cable shape:
Round

Product Description

RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V

Cable Designation & Meaning

Code

Meaning

R

Flexible cord 

V

PVC insulation 

V

PVC sheath 

P

Copper braid shield 

2×6.0 mm²

Two cores of 6.0 mm² copper conductor


Construction: Two 6.0 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥80% coverage) over the laid-up cores, PVC outer sheath.

Applicable Standards

  • GB/T 5023.5-2008 / IEC 60227-5 — Polyvinyl chloride insulated cables — Flexible cables (cords)
  • GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables (Class 5 flexible)
  • GB/T 18380.3 / IEC 60332-3 — Flame retardant (Category A/B/C as specified)
  • GB/T 5023.2-2008 / IEC 60227-2 — Test methods

RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V

RVVP 2×6.0 mm² — Flexible Shielded Feeder Cable — Specification 

1. Overview & Ratings

RVVP 2×6.0 is the largest 2-core RVVP size — a shielded feeder cable rated 450/750 V. It uses pure annealed bare copper (not tinned) for both the conductor and braid, maximizing conductivity. Two 6.0 mm² cores carry 37–48 A for main power feeds on large machines, transformer secondary runs, and large motor supplies. The heavy-duty braid suppresses EMI/RFI so power runs stay clean. OD ≈ 13.5 mm, ≈ 185 kg/km (est.). Max conductor temperature 70 °C, -15 to +70 °C. Intended for dry indoor feeder applications; for damp or outdoor duty, specify tinned copper variant. Not for mains distribution or direct burial.

2. Construction Stack (Inner → Outer, expanded)

Layer / Feature Build Function
Conductor (×2) Pure annealed Cu, Class 5, 84×0.30 mm per core R ≤ 3.08 Ω/km, feeder-grade current
Insulation PVC ≈ 1.0 mm per core 450/750 V dielectric, colour-coded
Inner sheath PVC + filler ≈ 0.8 mm Round bedding, braid substrate
Braid shield Pure Cu, heavy-duty, ≈ 85% coverage Low transfer impedance, high fault capacity
Outer jacket PVC ≈ 1.4 mm Extra-heavy-duty oil/abrasion protection

3. Electrical Characteristics

DC resistance ≤ 3.08 Ω/km at 20 °C per GB/T 3956 — roughly 33% lower than the 4.0 mm² variant, cutting voltage drop to ≈ 0.31 V per 100 m at 10 A. Rated voltage 450/750 V. Estimated ampacity ≈ 37–48 A in free air at 30 °C. Insulation resistance ≥ 25 MΩ·km. Routine AC withstand test at 2500 V for 5 minutes. Typical capacitance ≈ 210 pF/m at 1 kHz. The pure copper braid is sized for heavy earth-fault energy expected on feeder circuits. Suitable for main power feeds and large motor supplies up to 50 m.

Insulation & Sheath Data

Property

Value

Insulation material

PVC (Type TI2)

Outer sheath material

PVC (Type TM2)

Shield material

Tinned copper braid

Long-term service temp.

70 °C (continuous)

Max. conductor temp. (normal)

70 °C

Short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Test voltage AC (5 min)

2.0 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹² Ω·cm

Shield

Pure copper braid, ≥ 80% coverage (EMI/RFI protection)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

300 / 300 V

GB/T 5023.5 (control/signal)

Max. system voltage

350 V AC / 500 V DC

—

Test voltage AC (5 min)

2.0 kV

Routine test

DC resistance @20 °C

≤ 3.08 Ω/km per core

GB/T 3956 Class 5 Cu max (6.0 mm²)

AC resistance @70 °C (est.)

≈ 3.85 Ω/km per core

—

Current rating in air (30 °C)

Control/medium-power: 34 A per core​ (recommended max.)

conservative rating

Current rating in tray (30 °C)

Control/medium-power: 38 A per core​

—

DC current capacity

34 A​ per core

—

Short-circuit current (1 s, Cu, 160 °C)

≈ 660 A per core

—

Capacitance (core-to-core, approx.)

≈ 0.17 µF/km

PVC

Capacitance (core-to-shield, approx.)

≈ 0.28 µF/km

PVC

Inductive reactance (approx.)

≈ 0.09 Ω/km

at 50 Hz

Frequency

DC / up to 100 MHz (signal)

—

Characteristic impedance (approx.)

50 – 70 Ω

signal reference

Attenuation (at 1 MHz, approx.)

≈ 0.35 dB/100 m

—


Reference values: RVVP 2×6.0 at 34 A per core, 24 V DC → max load ≈ 816 W​ per core (medium-power device supply). At 230 V AC → max load ≈ 7,820 VA​ per core (power use).

4. Thermal & Flame Behaviour

Operating range -15 to +70 °C continuous. Short-circuit withstand up to 160 °C for ≤ 5 seconds. PVC insulation and jacket are flame-retardant per IEC 60332-1. The cable is halogen-containing (PVC), emitting HCl gas on burning — avoid in enclosed switchrooms. For public or enclosed spaces, specify LSZH alternatives. The extra-heavy 1.4 mm Type ST jacket provides robust oil and abrasion resistance for heavy machinery, presses and industrial plants. Note: bare pure copper oxidizes in humid environments — install in dry indoor or conduit-protected locations. UV resistance is limited.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

70 °C (continuous)

Max. short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Min. installation ambient temp.

−15 °C

Service ambient range

−15 °C to +70 °C

Flexing temp. range

−5 °C to +70 °C


Fire Performance (RVVP — PVC, Non-Low-Smoke)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 / IEC 60332-3​ (Category A/B/C as specified)

Halogen content

Contains halogen​ (PVC)

Smoke density

Not low-smoke​ (IEC 61034-2 not applicable)

Corrosivity

Corrosive​ (HCl emission from PVC)

Toxicity

Toxic fumes​ when burned (CO, HCl)

EMI shielding

Excellent​ (tinned copper braid, ≥85% coverage)

UV resistance

Poor​ (PVC degrades outdoors, use conduit or UV-resistant)

Water resistance

Limited​ (PVC sheath)

5. Installation Practice & Handling

Minimum bending radius ≥ 6×OD ≈ 81 mm for fixed installation; 12×OD ≈ 162 mm for drag-chain applications. At 13.5 mm OD and 185 kg/km, this is the bulkiest and heaviest RVVP 2-core variant — plan cable trays, lifting and bending allowance carefully. Terminate the braid shield to earth via a robust shield gland or drain wire, as feeder circuits carry higher fault energy. Use heavy-duty ferrules on the 84-strand conductor. Route at least 300 mm away from motor and VFD power cables. After installation, verify insulation resistance, shield continuity and polarity before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 6 × OD → ≈ 76 mm at Ø12.6 mm

flexible cable

Max. pulling tension

90 N per core (6.0 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Not recommended​ (PVC, non-UV, water ingress)

—

Surface mounting

Cable tray, conduit, trunking, DIN rail

—

Conduit ID

≥ 40 mm

—

Fixing

cable ties, clamps, clips

—

Impact resistance

Low (PVC)

—

Water resistance

Limited​ (PVC sheath)

—

UV resistance

Poor​ (indoor/conduit only)

—

Flex life

Excellent​ (Class 5 fine-stranded)

flexible routing

Termination note

Screw terminals, compression lugs (6 mm²), crimp terminals

—

6. Typical Service Applications

Main power feeds from distribution panel to large machines and production lines, transformer secondary runs to load centers, large motor supply wiring between drive and motor, power to heavy solenoid valves and actuators in industrial plants, and interconnection between main switchgear and field distribution. The 6.0 mm² cross-section is the upper limit of RVVP 2-core size — the sweet spot for runs up to 30–50 m where current demand is 30–48 A and EMI protection is required. Not for: mains AC distribution, high-speed fieldbus, direct burial, outdoor UV exposure, or damp environments.

RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V

7. Testing & Quality Assurance Regime

Routine tests (100% production): DC resistance, AC voltage withstand (2500 V/5 min), insulation resistance, conductor construction, wall thickness, dimensional check, print legibility, mass per length, visual appearance, and packing. Type tests (per batch): shield coverage plus heavy fault-current withstand, heat aging (100 °C/7 days), cold bend (-15 °C), jacket tensile, flame retardancy, and shielding effectiveness. Every heavy drum ships with mill test certificate, ROHS and REACH declarations. The heavy fault-current test is standard for feeder-grade RVVP.


Cable Parameters


RVVP 2×6.0 mm² — Full Parameter Sheet
Shielded flexible feeder cable · 450/750 V · pure annealed Cu Class 5 · PVC insulation/jacket · pure Cu braid ≈ 85% · GB/T 9330 / IEC 60227
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type RVVP — Flexible pure Cu, PVC ins., PVC jacket, braid shield

Rated voltage (U0/U) 450/750 V Feeder / main power / large motor

Number of cores 2 — 2 cores, colour-coded

Nominal cross-section 6.0 mm² Per core, Class 5 flexible, upper RVVP size

Conductor material Pure annealed copper (bare) — Class 5 per GB/T 3956, not tinned

Insulation material PVC (Type SP) — 70 °C rated, 1.0 mm wall

Shield Pure copper braid, heavy-duty — ≈ 85% coverage, high fault energy

Outer jacket material PVC (Type ST) — Oil/abrasion resistant, 1.4 mm extra-heavy

Standard reference GB/T 9330 / IEC 60227 / UL 2464 — Harmonized power-control cable
02 · Conductor

Stranding 84 × 0.30 mm — Class 5 pure copper per core

Conductor diameter ≈ 3.0 mm Per core, compacted lay

DC resistance @ 20 °C ≤ 3.08 Ω/km Maximum per GB/T 3956 (pure Cu)

Conductor surface Bare pure copper — Not tinned; for dry indoor use
03 · Insulation

Insulation type PVC (Type SP) — Soft PVC, 70 °C

Insulation thickness ≈ 1.0 mm Nominal

Insulated core Ø ≈ 5.0 mm Per core

Insulation resistance ≥ 25 MΩ·km At 20 °C
04 · Shield & Inner Sheath

Inner sheath material PVC + polyester filler — Bedding over laid-up cores

Inner sheath thickness ≈ 0.8 mm Nominal

Shield type Pure Cu braid, heavy-duty — Woven over inner sheath

Shield coverage ≈ 85 % Typical

Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
05 · Outer Jacket

Jacket material PVC (Type ST) — Oil/abrasion resistant

Jacket thickness ≈ 1.4 mm Nominal, extra-heavy-duty

Overall finished diameter ≈ 13.5 mm 2-core shielded feeder

Approximate cable mass ≈ 185 kg/km Pure Cu + PVC + braid

Mass per 100 m ≈ 18.5 kg/100 m For heavy drum loading
06 · Electrical

Rated voltage 450/750 V Feeder / main power

Test voltage (AC) 2500 V AC 5 min routine

DC resistance @ 20 °C ≤ 3.08 Ω/km Per GB/T 3956 (pure Cu)

Ampacity (free air) ≈ 37–48 A 6.0 mm², 70 °C

Voltage drop @ 10 A / 100 m ≈ 0.31 V I × R

Capacitance (core-core) ≈ 210 pF/m At 1 kHz
07 · Thermal & Mechanical

Max continuous conductor temp. 70 °C Normal service

Short-circuit temp. (≤5 s) 160 °C Copper limit

Min. ambient temp. -15 °C Fixed installation

Min. bending radius ≥ 6 × OD ≈ 81 mm Fixed; 12× for moving

Halogen content Halogen-containing — PVC compound
08 · Flame & Environment

Flame retardancy IEC 60332-1 — Single vertical flame

Oil resistance Good — Type ST PVC, extra-heavy-duty

UV resistance Limited — Indoor / conduit use

Corrosion resistance Limited (bare Cu) — Dry indoor only; use tinned for damp/outdoor

ROHS / REACH Compliant — EU 2011/65/EU


Cable Test Parameters


Test Parameters — RVVP 2×6.0 mm²
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 3.08 Ω/km Routine
2 AC voltage withstand 2500 V AC, 5 min No breakdown Routine
3 Insulation resistance 500 V megohmmeter ≥ 25 MΩ·km Routine
4 Conductor construction Visual + strand count 84 × 0.30 mm pure Cu Routine
5 Wall thickness Micrometer cross-section Ins. ≈ 1.0 mm; jacket ≈ 1.4 mm Routine
6 Dimensional check Caliper OD ≈ 13.5 mm Routine
7 Print legibility Visual + rubbing Marks legible Routine
8 Mass per unit length Weighing ≈ 185 kg/km Routine
9 Appearance Visual Smooth, no blisters Routine
10 Packing Visual Heavy drum, sealed ends, labelled Routine
11 Shield coverage + heavy fault current Unwrap + short-circuit test ≥ 80% coverage; withstand heavy fault Type
12 Heat aging test 7 days at 100 °C Retention ≥ 70% Type
13 Cold bend test -15 °C, 4 h mandrel No cracking Type
14 Jacket tensile test Universal tester Meets GB/T 9330 min. Type
15 Flame retardancy IEC 60332-1 Self-extinguish Type
16 Shielding effectiveness Triaxial / open-field ≥ 60 dB at 30–1000 MHz Type


Cable Cross Section Structure

RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V

RVVP 2×6.0 mm² — Cross-Section Construction Diagram (Schematic)
Layered build-up: pure copper Class 5 conductors → PVC insulation → inner PVC sheath → pure copper braid shield → PVC outer jacket · 450/750 V shielded feeder cable · main power feed / large motor supply · EMI/RFI protection · -15~+70 °C
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (×2) Pure annealed copper, Class 5 flexible — 84 × 0.30 mm strands per core — ≈ 3.0 (per core) Feeder-level current; R ≤ 3.08 Ω/km; bare pure copper for maximum conductivity
2 Insulation (per core) PVC compound (Type SP), extruded over each conductor, colour-coded ≈ 1.0 ≈ 5.0 (per insulated core) Electrical insulation; 450/750 V rated; colour-coded (red/black, blue/white, etc.)
3 Inner sheath PVC compound, extruded over the two laid-up cores, round filler ≈ 0.8 ≈ 10.8 (before braid) Round and bed the cores; mechanical protection; bedding for braid
4 Braid shield Pure copper wire braid, ≈ 85% coverage, laid over inner sheath ≈ 0.6 (effective) ≈ 12.0 EMI/RFI shielding; heavy-duty earth-fault capacity for feeder circuits
5 Outer jacket PVC compound (Type ST), black or grey, extruded over braid ≈ 1.4 ≈ 13.5 (finished) Extra-heavy-duty outer protection; oil-, abrasion-resistant; printed markings






Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 13.5 mm 2-core shielded feeder cable (est.)
Approximate cable mass ≈ 185 kg/km Pure Cu + PVC + braid build-up
Nominal voltage rating 450/750 V Feeder / main power / large motor
Max continuous conductor temp. 70 °C Normal service
Min. ambient / installation temp. -15 °C Fixed installation
DC resistance @ 20 °C ≤ 3.08 Ω/km Class 5 pure copper, GB/T 3956
Core count × cross-section 2 × 6.0 mm² 2 cores, upper RVVP size
Shield coverage ≈ 85 % Pure copper braid, heavy-duty
Insulation resistance ≥ 25 MΩ·km PVC at 20 °C
Test voltage (AC) 2500 V AC / 5 min — Routine withstand test
Flame retardancy IEC 60332-1 — Single vertical flame
Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
Jacket colour Black / grey / custom — Standard: black
Mass per 100 m ≈ 18.5 kg/100 m For heavy drum loading
Reference standard GB/T 9330 / IEC 60227 / UL 2464 — Harmonized power-control cable
Schematic — not to exact scale. Finished Ø ≈ 13.5 mm and weight ≈ 185 kg/km from cross-referenced industry samples; conductor stranding 84/0.30 mm per core and braid coverage ≈ 85%. Pure copper (not tinned) for maximum conductivity. Est. values confirmed against factory type certificate.


Construction Description


Construction Description — RVVP 2×6.0 mm²
Layer-by-layer build-up narrative · 450/750 V shielded feeder cable · GB/T 9330 / IEC 60227 · pure annealed copper / PVC insulation / pure copper braid shield / PVC outer jacket
1. Product Identity & Ratings
RVVP 2×6.0 is the largest 2-core RVVP size — a shielded feeder cable rated 450/750 V. It uses pure annealed copper (not tinned) for both the conductor and braid, maximizing conductivity. Two 6.0 mm² cores carry 37–48 A for main power feeds on large machines, transformer secondary runs, and large motor supplies. The heavy-duty braid suppresses EMI/RFI so power runs stay clean. OD ≈ 13.5 mm, ≈ 185 kg/km. Max 70 °C, -15 to +70 °C range. For dry indoor use; specify tinned variant for damp/outdoor.
2. Pure Copper Conductor (×2)
Each 6.0 mm² core is stranded from 84 pure annealed copper wires of 0.30 mm in a Class 5 compacted lay-up. Pure copper (bare, not tinned) delivers the highest conductivity: DC resistance ≤ 3.08 Ω/km at 20 °C, roughly 33% lower than 4.0 mm². The 84-wire stranding keeps the cable flexible despite the large cross-section. Note: bare copper is intended for dry indoor environments where corrosion is not a concern; for outdoor or damp duty, specify tinned copper variant.
3. PVC Insulation
Each conductor receives a 1.0 mm Type SP PVC extrusion, matching the 4.0 mm² wall thickness but over a larger core. The insulation is colour-coded for polarity and circuit identification. Insulation resistance ≥ 25 MΩ·km. The wall provides the dielectric margin required for 450/750 V feeder service and carries the larger conductor's thermal load.
4. Inner Sheath + Braid Shield
The two insulated cores are laid up with polyester fillers to keep the cable round, then bedded with a 0.8 mm PVC inner sheath. Over this, a pure copper braid is woven at ≈ 85% coverage. The braid is sized for higher earth-fault energy expected on feeder circuits, where fault currents are larger. Pure copper braid has low transfer impedance, giving strong EMI shielding at higher frequencies.
5. Outer PVC Jacket
A 1.4 mm Type ST PVC jacket completes the build — the thickest in the RVVP 2-core range — yielding an OD of ≈ 13.5 mm. The extra-heavy jacket provides robust oil and abrasion resistance for heavy machinery, presses and industrial plants. Flame-retardant per IEC 60332-1. Printed markings show product type, cross-section, voltage, metre mark and manufacturer. For drag-chain duty, specify RVVSP.

8. Factory Advantages

Pure annealed copper conductor at 84×0.30 mm stranding delivers maximum conductivity (3.08 Ω/km) with Class 5 flexibility. 1.0 mm insulation and extra-heavy 1.4 mm jacket match the 450/750 V feeder rating. Pure copper braid at ≈ 85% coverage with high fault-energy capacity. Low DC resistance minimizes voltage drop on long feeder runs. Extra-heavy-duty oil-resistant Type ST jacket for heavy machinery and plant duty. 100% routine electrical QA on every drum. Cut-to-length on heavy wooden drums. Full traceability with MTC and certification support for industrial plant and machinery tenders.


9. Packaging, Storage & Logistics

Cut to customer-specified length on export-grade heavy-duty wooden drums, with both ends heat-sealed. At ≈ 185 kg/km, heavy drums are essential — a 500 m reel weighs nearly 93 kg, requiring forklift handling. Drums wrapped in waterproof film and corrugated cardboard, labelled with product type, core count, cross-section, length, weight, production date and drum number. Standard lengths 100/200/500/1000 m. Store dry indoor, -10 to +40 °C, below 75% RH, away from direct sunlight and chemical solvents. FOB Shanghai/Nanjing/Qingdao; CIF and DAP available. Sample lead time 5–7 days; bulk production 15–25 days.


RVVP 2x6.0mm² Extra High Current Shielded Heavy Duty Industrial Power Control Cable Braided Copper 300/500V

10. Procurement Specification

State cable designation "RVVP 2×6.0 pure copper", required length per heavy drum, and core colour preference. Request the routine AC withstand test record (2500 V), shield coverage certificate, and heavy fault-current test result. Note that this is a pure copper (bare) feeder variant for dry indoor use — for damp or outdoor applications, specify the tinned copper variant. Specify any regional certification requirements (UL 2464, CE, etc.) at order time. Payment: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list. For drag-chain duty, specify RVVSP variant.

11. Cable Industry FAQ

Q1: Why choose 6.0 mm² over 4.0 mm²? Lower DC resistance (3.08 vs 4.61 Ω/km), higher ampacity (37–48 A vs 28–35 A), and heavy-duty construction for feeder-level power distribution.

Q2: Is this the largest RVVP size? Yes — 6.0 mm² is the upper limit of the standard RVVP 2-core range. For larger cross-sections, switch to RVV or power cable.

Q3: Can it supply large motors? Yes — it is designed for main motor feeds and heavy-duty auxiliary power up to 48 A at 450/750 V.

Q4: What is the voltage drop at 10 A? ≈ 0.31 V per 100 m — roughly one-third the drop of 4.0 mm², ideal for long feeder runs.

Q5: Why is the jacket so thick (1.4 mm)? The extra-heavy Type ST jacket provides robust mechanical, oil and abrasion protection for heavy machinery and industrial plant duty.

Q6: How do you handle the weight? At 185 kg/km, heavy wooden drums are required — plan forklift or mechanical handling on site.

Q7: Is it suitable for drag chains? Not as standard — specify RVVSP (flexible braid) variant for continuous-flex applications.

Q8: What is the bending radius? ≥ 6×OD ≈ 81 mm for fixed; 12× for moving applications.

Q9: What is the temperature range? -15 to +70 °C continuous.

Q10: What proof ships? Routine AC test record (2500 V) + shield coverage + heavy fault-current test + MTC.

Q11: When should I step up from 6.0 to a power cable? For cross-sections above 6.0 mm², higher voltage, or mains distribution, switch to RVV, YJV or other power cable types.