RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V

RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
RVVP 2x2.5mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 2×2.5 mm² Two cores of 2.5 mm² copper conductor Construction: Two 2.5 mm² fine-stranded ...

Product Details

Highlight:

RVVP 2x2.5mm² shielded control cable

,

braided copper shielded VFD cable

,

2 core flexible shielded cable 300/500V

Conductor (×2):
Copper, Flexible (Class 5), Nominal 49×∅0.25 Mm (2.5 Mm²), Conductor Ø ≈ 2.6 Mm Per Core
Insulation:
PVC (Type TI2), Nominal Thickness 0.8 Mm, Min. Thickness 0.62 Mm
Lay-up:
Two Insulated Cores Twisted Together
Shield:
Pure Copper Braid, Coverage ≥ 80%, Nominal 16×5/0.10 Mm
Outer sheath:
PVC (Type TM2), Nominal Thickness 0.9 Mm, Min. Thickness 0.68 Mm
Conductor nominal area:
2.5 Mm² (Cu) × 2
Number of cores:
2
Conductor material:
Copper (Cu)
Conductor class:
Class 5 Flexible
Conductor construction:
49×∅0.25 Mm Per Core
Conductor diameter:
≈ 2.6 Mm Per Core
Insulation thickness (nom.):
0.8 Mm
Insulation thickness (min.):
0.62 Mm
Shield coverage:
≥ 80%
Outer sheath thickness (nom.):
1.0 Mm
Outer sheath thickness (min.):
0.76 Mm
Overall cable diameter:
8.8 – 10.0 Mm
Design outer diameter:
≈ 9.4 Mm
Approx. weight:
120 – 150 Kg/km
Design weight:
≈ 138 Kg/km
Cable shape:
Round

Product Description

RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V

Cable Designation & Meaning

Code

Meaning

R

Flexible cord 

V

PVC insulation 

V

PVC sheath 

P

Copper braid shield 

2×2.5 mm²

Two cores of 2.5 mm² copper conductor


Construction: Two 2.5 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥80% coverage) over the laid-up cores, PVC outer sheath.

Applicable Standards

  • GB/T 5023.5-2008 / IEC 60227-5 — Polyvinyl chloride insulated cables — Flexible cables (cords)
  • GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables (Class 5 flexible)
  • GB/T 18380.3 / IEC 60332-3 — Flame retardant (Category A/B/C as specified)
  • GB/T 5023.2-2008 / IEC 60227-2 — Test methods

RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V

RVVP 2×2.5 mm² — Flexible Shielded Power-Control Cable — Specification

1. Overview & Ratings

RVVP 2×2.5 is a shielded power-control cable rated 450/750 V — the largest 2-core RVVP size, bridging signal-grade shielded cable and small power cable. R = flexible tinned copper, V = PVC insulation, V = PVC jacket, P = braided shield. OD ≈ 9.2 mm, ≈ 95 kg/km (est.), ≈ 20–25 A. Two 2.5 mm² tinned copper cores carry real motor and actuator current while the 85% braid suppresses EMI/RFI. Designed for motor control wiring, solenoid and actuator power, and auxiliary power runs near sensitive electronics. Max conductor temperature 70 °C, -15 to +70 °C. Not for outdoor UV exposure or mains distribution.

2. Construction Stack (Inner → Outer, expanded)

Layer / Feature Build Function
Conductor (×2) Tinned Cu, Class 5, 50×0.25 mm per core R ≤ 7.41 Ω/km, power-level current
Insulation PVC ≈ 0.8 mm per core 450/750 V dielectric, colour-coded
Inner sheath PVC + filler ≈ 0.7 mm Round bedding, braid substrate
Braid shield Tinned Cu, ≈ 85% coverage EMI/RFI + higher fault-current path
Outer jacket PVC ≈ 1.0 mm Heavy oil/abrasion protection

3. Electrical Characteristics

DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956 — roughly 44% lower than the 1.5 mm² variant, cutting voltage drop to ≈ 0.74 V per 100 m at 10 A. Rated voltage 450/750 V. Estimated ampacity ≈ 20–25 A in free air at 30 °C. Insulation resistance ≥ 25 MΩ·km. Routine AC withstand test at 2500 V for 5 minutes. Typical capacitance ≈ 170 pF/m at 1 kHz. The braid provides ≈ 60–70 dB shielding at 30–1000 MHz. Suitable for 24 V DC and 110/220 V AC auxiliary power runs up to 20–50 m.

Insulation & Sheath Data

Property

Value

Insulation material

PVC (Type TI2)

Outer sheath material

PVC (Type TM2)

Shield material

Tinned copper braid

Long-term service temp.

70 °C (continuous)

Max. conductor temp. (normal)

70 °C

Short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Test voltage AC (5 min)

2.0 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹² Ω·cm

Shield

Tinned copper braid, ≥ 80% coverage (EMI/RFI protection)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

300 / 300 V

GB/T 5023.5 (control/signal)

Max. system voltage

350 V AC / 500 V DC

—

Test voltage AC (5 min)

2.0 kV

Routine test

DC resistance @20 °C

≤ 7.98 Ω/km per core

GB/T 3956 Class 5 Cu max (2.5 mm²)

AC resistance @70 °C (est.)

≈ 10.0 Ω/km per core

—

Current rating in air (30 °C)

Control/low-power: 16 A per core​ (recommended max.)

conservative rating

Current rating in tray (30 °C)

Control/low-power: 18 A per core​

—

DC current capacity

16 A​ per core

—

Short-circuit current (1 s, Cu, 160 °C)

≈ 275 A per core

—

Capacitance (core-to-core, approx.)

≈ 0.15 µF/km

PVC

Capacitance (core-to-shield, approx.)

≈ 0.24 µF/km

PVC

Inductive reactance (approx.)

≈ 0.08 Ω/km

at 50 Hz

Frequency

DC / up to 100 MHz (signal)

—

Characteristic impedance (approx.)

50 – 70 Ω

signal reference

Attenuation (at 1 MHz, approx.)

≈ 0.5 dB/100 m

—


Reference values: RVVP 2×2.5 at 16 A per core, 24 V DC → max load ≈ 384 W​ per core (low-power device supply). At 230 V AC → max load ≈ 3,680 VA​ per core (light power use).

4. Thermal & Flame Behaviour

Operating range -15 to +70 °C continuous. Short-circuit withstand up to 160 °C for ≤ 5 seconds. PVC insulation and jacket are flame-retardant per IEC 60332-1. The cable is halogen-containing (PVC), emitting HCl gas on burning — avoid in enclosed switchrooms where corrosive fume is a concern. For public or enclosed spaces, specify LSZH alternatives. The thicker 0.8 mm Type ST jacket offers improved oil resistance for machine tool and press applications. UV resistance is limited; install indoors or in UV-protected conduits only.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

70 °C (continuous)

Max. short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Min. installation ambient temp.

−15 °C

Service ambient range

−15 °C to +70 °C

Flexing temp. range

−5 °C to +70 °C




Fire Performance (RVVP — PVC, Non-Low-Smoke)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 / IEC 60332-3​ (Category A/B/C as specified)

Halogen content

Contains halogen​ (PVC)

Smoke density

Not low-smoke​ (IEC 61034-2 not applicable)

Corrosivity

Corrosive​ (HCl emission from PVC)

Toxicity

Toxic fumes​ when burned (CO, HCl)

EMI shielding

Excellent​ (tinned copper braid, ≥85% coverage)

UV resistance

Poor​ (PVC degrades outdoors, use conduit or UV-resistant)

Water resistance

Limited​ (PVC sheath)

5. Installation Practice & Handling

Minimum bending radius ≥ 6×OD ≈ 55 mm for fixed installation; 12×OD ≈ 110 mm for drag-chain applications. The 2.5 mm² core is noticeably stiffer than 1.5 mm², so use proper cable trays and management. Terminate the braid shield to earth via a shield gland or drain wire — because the cable carries more power, shield grounding must be robust. Use heavy-duty ferrules on the 50-strand conductor. Route at least 250 mm away from motor and VFD power cables. After installation, verify insulation resistance, shield continuity and polarity before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 6 × OD → ≈ 56 mm at Ø9.4 mm

flexible cable

Max. pulling tension

37.5 N per core (2.5 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Not recommended​ (PVC, non-UV, water ingress)

—

Surface mounting

Cable tray, conduit, trunking, DIN rail

—

Conduit ID

≥ 25 mm

—

Fixing

cable ties, clamps, clips

—

Impact resistance

Low (PVC)

—

Water resistance

Limited​ (PVC sheath)

—

UV resistance

Poor​ (indoor/conduit only)

—

Flex life

Excellent​ (Class 5 fine-stranded)

flexible routing

Termination note

Screw terminals, compression lugs, IDC connectors

—



6. Typical Service Applications

Motor control wiring between contactor and motor terminal, solenoid valve and actuator power circuits, auxiliary 24 V DC and 110 V AC power runs on machines, PLC I/O power drops, and interconnection between control panels and field devices. The 2.5 mm² cross-section is the sweet spot for runs up to 20–50 m where current demand is 10–20 A and EMI protection matters — for example, wiring near servo drives, robot arms and welding equipment. Not for: mains AC power distribution, high-speed fieldbus, direct burial, or outdoor UV-exposed runs.

RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V

7. Testing & Quality Assurance Regime

Routine tests (100% production): DC resistance, AC voltage withstand (2500 V/5 min), insulation resistance, conductor construction, wall thickness, dimensional check, print legibility, mass per length, visual appearance, and packing. Type tests (per batch): shield coverage plus fault-current withstand, heat aging (100 °C/7 days), cold bend (-15 °C), jacket tensile, flame retardancy, and shielding effectiveness. Every coil ships with mill test certificate, ROHS and REACH declarations. The fault-current test is added for power-control duty.


Cable Parameters


RVVP 2×2.5 mm² — Full Parameter Sheet
Shielded flexible power-control cable · 450/750 V · tinned Cu Class 5 · PVC insulation/jacket · tinned Cu braid ≈ 85% · GB/T 9330 / IEC 60227
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type RVVP — Flexible tinned Cu, PVC ins., PVC jacket, braid shield

Rated voltage (U0/U) 450/750 V Power-control / auxiliary power

Number of cores 2 — 2 cores, colour-coded

Nominal cross-section 2.5 mm² Per core, Class 5 flexible

Conductor material Tinned annealed copper — Class 5 per GB/T 3956 / IEC 60228

Insulation material PVC (Type SP) — 70 °C rated, 0.8 mm wall

Shield Tinned copper braid — ≈ 85% coverage, higher fault energy

Outer jacket material PVC (Type ST) — Oil/abrasion resistant, 1.0 mm

Standard reference GB/T 9330 / IEC 60227 / UL 2464 — Harmonized control cable
02 · Conductor

Stranding 50 × 0.25 mm — Class 5 tinned copper per core

Conductor diameter ≈ 2.0 mm Per core, compacted lay

DC resistance @ 20 °C ≤ 7.41 Ω/km Maximum per GB/T 3956

Conductor surface Tinned — Anti-corrosion, solderable
03 · Insulation

Insulation type PVC (Type SP) — Soft PVC, 70 °C

Insulation thickness ≈ 0.8 mm Nominal (thicker than 1.5 mm²)

Insulated core Ø ≈ 3.6 mm Per core

Insulation resistance ≥ 25 MΩ·km At 20 °C
04 · Shield & Inner Sheath

Inner sheath material PVC + polyester filler — Bedding over laid-up cores

Inner sheath thickness ≈ 0.7 mm Nominal

Shield type Tinned Cu braid — Woven over inner sheath

Shield coverage ≈ 85 % Typical

Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
05 · Outer Jacket

Jacket material PVC (Type ST) — Oil/abrasion resistant

Jacket thickness ≈ 1.0 mm Nominal

Overall finished diameter ≈ 9.2 mm 2-core shielded

Approximate cable mass ≈ 95 kg/km Tinned Cu + PVC + braid

Mass per 100 m ≈ 9.5 kg/100 m For coil loading
06 · Electrical

Rated voltage 450/750 V Power-control / auxiliary

Test voltage (AC) 2500 V AC 5 min routine

DC resistance @ 20 °C ≤ 7.41 Ω/km Per GB/T 3956

Ampacity (free air) ≈ 20–25 A 2.5 mm², 70 °C

Voltage drop @ 10 A / 100 m ≈ 0.74 V I × R

Capacitance (core-core) ≈ 170 pF/m At 1 kHz
07 · Thermal & Mechanical

Max continuous conductor temp. 70 °C Normal service

Short-circuit temp. (≤5 s) 160 °C Copper limit

Min. ambient temp. -15 °C Fixed installation

Min. bending radius ≥ 6 × OD ≈ 55 mm Fixed; 12× for moving

Halogen content Halogen-containing — PVC compound
08 · Flame & Environment

Flame retardancy IEC 60332-1 — Single vertical flame

Oil resistance Good — Type ST PVC

UV resistance Limited — Indoor / conduit use

ROHS / REACH Compliant — EU 2011/65/EU


Cable Test Parameters


Test Parameters — RVVP 2×2.5 mm²
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 7.41 Ω/km Routine
2 AC voltage withstand 2500 V AC, 5 min No breakdown Routine
3 Insulation resistance 500 V megohmmeter ≥ 25 MΩ·km Routine
4 Conductor construction Visual + strand count 50 × 0.25 mm tinned Cu Routine
5 Wall thickness Micrometer cross-section Ins. ≈ 0.8 mm; jacket ≈ 1.0 mm Routine
6 Dimensional check Caliper OD ≈ 9.2 mm Routine
7 Print legibility Visual + rubbing Marks legible Routine
8 Mass per unit length Weighing ≈ 95 kg/km Routine
9 Appearance Visual Smooth, no blisters Routine
10 Packing Visual Coil/drum, sealed ends, labelled Routine
11 Shield coverage + fault current Unwrap + short-circuit test ≥ 80% coverage; withstand rated fault Type
12 Heat aging test 7 days at 100 °C Retention ≥ 70% Type
13 Cold bend test -15 °C, 4 h mandrel No cracking Type
14 Jacket tensile test Universal tester Meets GB/T 9330 min. Type
15 Flame retardancy IEC 60332-1 Self-extinguish Type
16 Shielding effectiveness Triaxial / open-field ≥ 60 dB at 30–1000 MHz Type


Cable Cross Section Structure


RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V

RVVP 2×2.5 mm² — Cross-Section Construction Diagram (Schematic)
Layered build-up: tinned Cu Class 5 conductors → PVC insulation → inner PVC sheath → tinned copper braid shield → PVC outer jacket · 450/750 V shielded power-control cable · motor control / auxiliary power · EMI/RFI protection · -15~+70 °C
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (×2) Tinned annealed copper, Class 5 flexible — 50 × 0.25 mm strands per core — ≈ 2.0 (per core) Power-level control; R ≤ 7.41 Ω/km; tinned for anti-corrosion and solderability
2 Insulation (per core) PVC compound (Type SP), extruded over each conductor, colour-coded ≈ 0.8 ≈ 3.6 (per insulated core) Electrical insulation; 450/750 V rated; colour-coded (red/black, blue/white, etc.)
3 Inner sheath PVC compound, extruded over the two laid-up cores, round filler ≈ 0.7 ≈ 7.4 (before braid) Round and bed the cores; mechanical protection; bedding for braid
4 Braid shield Tinned copper wire braid, ≈ 85% coverage, laid over inner sheath ≈ 0.5 (effective) ≈ 8.4 EMI/RFI shielding; higher fault-current capacity for power-control circuits
5 Outer jacket PVC compound (Type ST), black or grey, extruded over braid ≈ 1.0 ≈ 9.2 (finished) Outer mechanical protection; oil-, abrasion-resistant; printed markings






Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 9.2 mm 2-core shielded power-control cable (est.)
Approximate cable mass ≈ 95 kg/km Tinned Cu + PVC + braid build-up
Nominal voltage rating 450/750 V Power-control / auxiliary power
Max continuous conductor temp. 70 °C Normal service
Min. ambient / installation temp. -15 °C Fixed installation
DC resistance @ 20 °C ≤ 7.41 Ω/km Class 5 tinned copper, GB/T 3956
Core count × cross-section 2 × 2.5 mm² 2 cores
Shield coverage ≈ 85 % Tinned copper braid
Insulation resistance ≥ 25 MΩ·km PVC at 20 °C
Test voltage (AC) 2500 V AC / 5 min — Routine withstand test
Flame retardancy IEC 60332-1 — Single vertical flame
Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
Jacket colour Black / grey / custom — Standard: black
Mass per 100 m ≈ 9.5 kg/100 m For coil / drum loading
Reference standard GB/T 9330 / IEC 60227 / UL 2464 — Harmonized control cable
Schematic — not to exact scale. Finished Ø ≈ 9.2 mm and weight ≈ 95 kg/km from cross-referenced industry samples; conductor stranding 50/0.25 mm per core and braid coverage ≈ 85%. Est. values confirmed against factory type certificate.


Construction Description


Construction Description — RVVP 2×2.5 mm²
Layer-by-layer build-up narrative · 450/750 V shielded power-control cable · GB/T 9330 / IEC 60227 · tinned copper / PVC insulation / tinned copper braid shield / PVC outer jacket
1. Product Identity & Ratings
RVVP 2×2.5 is a shielded power-control cable rated 450/750 V — the largest standard RVVP core size for 2-core variants. It bridges the gap between signal-grade shielded cable and small power cable: two 2.5 mm² tinned copper cores carry up to 20–25 A while the braid suppresses EMI/RFI. Typical uses include motor control wiring, solenoid and actuator power, and auxiliary power runs near sensitive electronics. Max 70 °C, -15 to +70 °C range.
2. Tinned Copper Conductor (×2)
Each 2.5 mm² core is stranded from 50 tinned annealed copper wires of 0.25 mm in a Class 5 compacted lay-up. The 50-wire stranding keeps the cable flexible despite the larger cross-section, so it still dresses in control panels. DC resistance ≤ 7.41 Ω/km at 20 °C — roughly 44% lower than 1.5 mm² — cutting voltage drop on 20–50 m power-control runs. Tinning provides oxidation resistance.
3. PVC Insulation
Each conductor receives a 0.8 mm Type SP PVC extrusion, thicker than the 0.7 mm wall on 1.5 mm² cores to match the power-level current and voltage rating. The insulation is colour-coded for polarity and circuit identification. Insulation resistance ≥ 25 MΩ·km. The thicker wall improves dielectric margin for 450/750 V service and reduces capacitance per unit length.
4. Inner Sheath + Braid Shield
The two insulated cores are laid up with polyester fillers to keep the cable round, then bedded with a 0.7 mm PVC inner sheath. Over this, a tinned copper braid is woven at ≈ 85% coverage. Because the 2.5 mm² core carries more current, the braid is also sized to handle higher earth-fault energy; shield continuity is verified per batch.
5. Outer PVC Jacket
A 1.0 mm Type ST PVC jacket completes the build, yielding an OD of ≈ 9.2 mm — noticeably bulkier than the 1.5 mm² variant. The jacket is oil- and abrasion-resistant, flame-retardant per IEC 60332-1, and printed with product type, cross-section, voltage, metre mark and manufacturer. Black or grey standard. For drag-chain or continuous-flex duty, specify RVVSP variant.

8. Factory Advantages

Pure copper conductor at 50×0.25 mm stranding balances flexibility and power capacity. Thicker 0.8 mm insulation and 1.0 mm jacket match the 450/750 V power-control rating. Tinned copper braid at ≈ 85% coverage handles both EMI shielding and higher earth-fault energy. Low DC resistance (7.41 Ω/km) minimizes voltage drop on longer power runs. Heavy-duty oil-resistant Type ST jacket for press and machine tool duty. 100% routine electrical QA on every reel. Cut-to-length coils or drums. Full traceability with MTC and certification support for machinery and industrial tenders.


9. Packaging, Storage & Logistics

Cut to customer-specified length on export-grade coils or wooden drums, with both ends heat-sealed. Due to the ≈ 95 kg/km weight, drums are recommended for lengths over 200 m to avoid coil distortion. Coils/drums wrapped in waterproof film and corrugated cardboard, labelled with product type, core count, cross-section, length, weight, production date and reel number. Standard lengths 100/200/500/1000 m. Store dry indoor, -10 to +40 °C, below 75% RH. FOB Shanghai/Nanjing/Qingdao; CIF and DAP available. Sample lead time 5–7 days; bulk production 15–25 days.


RVVP 2x2.5mm² Braided Copper Shielded Control Cable Protection for Variable Frequency Drive 300/500V

10. Procurement Specification

State cable designation "RVVP 2×1.5", required length per coil/drum, and core colour preference. Request the routine AC withstand test record (2500 V) and shield coverage certificate for the specific batch. Note that the voltage rating is 450/750 V — higher than the 300/500 V of smaller cross-sections. Specify any regional certification requirements (UL 2464, CE, etc.) at order time. Payment: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list. For drag-chain duty, specify RVVSP variant with enhanced flexible braid.

11. Cable Industry FAQ

Q1: Why choose 2.5 mm² over 1.5 mm²? Lower DC resistance (7.41 vs 13.3 Ω/km), higher ampacity (20–25 A vs 12–15 A), and heavier construction for motor control and actuator power circuits.

Q2: Can it power small motors? Yes — it is designed for motor control and solenoid/actuator power up to 20–25 A at 450/750 V.

Q3: What is the voltage rating? 450/750 V, suitable for 110 V AC and 220 V AC auxiliary control circuits.

Q4: How does the braid handle fault current? The 85% tinned copper braid is sized to handle higher earth-fault energy, verified per batch by a fault-current test.

Q5: Is it suitable for drag chains? Not as standard — specify RVVSP (flexible braid) variant for continuous-flex applications.

Q6: Can it be used outdoors? No — limited UV resistance; install indoors or in UV-protected conduits.

Q7: Is it halogen-free? No — PVC is halogen-containing. Use LSZH for enclosed or public spaces.

Q8: What is the bending radius? ≥ 6×OD ≈ 55 mm for fixed; 12× for moving applications.

Q9: What is the temperature range? -15 to +70 °C continuous.

Q10: What proof ships? Routine AC test record (2500 V) + shield coverage + fault-current test + MTC.

Q11: What is the voltage drop at 10 A? ≈ 0.74 V per 100 m — roughly half the drop of 1.5 mm², making it ideal for longer power-control runs.