RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V

RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
RVVP 2x1.5mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 2×1.5 mm² Two cores of 1.5 mm² copper conductor Construction: Two 1.5 mm² fine-stranded ...

Product Details

Highlight:

RVVP 2x1.5mm² shielded control cable

,

braided shielded PLC cable 300/500V

,

2 core anti-interference automation cable

Conductor (×2):
Copper, Flexible (Class 5), Nominal 30×∅0.25 Mm (1.5 Mm²), Conductor Ø ≈ 2.0 Mm Per Core
Insulation:
PVC (Type TI2), Nominal Thickness 0.7 Mm, Min. Thickness 0.53 Mm
Lay-up:
Two Insulated Cores Twisted Together
Shield:
Pure Copper Braid, Coverage ≥ 80%, Nominal 16×5/0.10 Mm
Outer sheath:
PVC (Type TM2), Nominal Thickness 0.9 Mm, Min. Thickness 0.68 Mm
Conductor nominal area:
1.5 Mm² (Cu) × 2
Number of cores:
2
Conductor material:
Copper (Cu)
Conductor class:
Class 5 Flexible
Conductor construction:
32×∅0.25 Mm Per Core
Conductor diameter:
≈ 2.0 Mm Per Core
Insulation thickness (nom.):
0.7 Mm
Insulation thickness (min.):
0.53 Mm
Shield coverage:
≥ 80%
Outer sheath thickness (nom.):
0.9 Mm
Outer sheath thickness (min.):
0.68 Mm
Overall cable diameter:
7.5 – 8.5 Mm
Design outer diameter:
≈ 8.0 Mm
Approx. weight:
85 – 105 Kg/km
Design weight:
≈ 95 Kg/km
Cable shape:
Round

Product Description

RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V

Cable Designation & Meaning

Code

Meaning

R

Flexible cord 

V

PVC insulation 

V

PVC sheath 

P

Copper braid shield 

2×1.5 mm²

Two cores of 1.5 mm² copper conductor


Construction: Two 1.5 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥85% coverage) over the laid-up cores, PVC outer sheath.

Applicable Standards

  • GB/T 5023.5-2008 / IEC 60227-5 — Polyvinyl chloride insulated cables — Flexible cables (cords)
  • GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables (Class 5 flexible)
  • GB/T 18380.3 / IEC 60332-3 — Flame retardant (Category A/B/C as specified)
  • GB/T 5023.2-2008 / IEC 60227-2 — Test methods

RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V

RVVP 2×1.5 mm² — Flexible Shielded Control Cable — Specification 

1. Overview & Ratings

RVVP 2×1.5 is a medium-current shielded control cable rated 450/750 V, one step up from the 0.75 and 1.0 mm² variants. R = flexible tinned copper conductor, V = PVC insulation, V = PVC outer sheath, P = braided copper shield. OD ≈ 7.8 mm, ≈ 68 kg/km (est.), ≈ 12–15 A. The tinned copper braid at ≈ 85% coverage blocks EMI/RFI from nearby VFDs, servo drives and welders. The larger conductor reduces voltage drop on longer control runs, making it the preferred choice for machine tool wiring, remote PLC I/O and 24 V DC control loops. Max conductor temperature 70 °C, operating range -15 to +70 °C. Not for outdoor UV exposure or mains power.

2. Construction Stack (Inner → Outer, expanded)

Layer / Feature Build Function
Conductor (×2) Tinned Cu, Class 5, 30×0.25 mm per core R ≤ 13.3 Ω/km, medium-current, solderable
Insulation PVC ≈ 0.7 mm per core 450/750 V dielectric, colour-coded
Inner sheath PVC + filler ≈ 0.6 mm Round bedding, braid substrate
Braid shield Tinned Cu, ≈ 85% coverage EMI/RFI shielding, earth-fault return
Outer jacket PVC ≈ 0.8 mm Oil/abrasion protection, printed markings

3. Electrical Characteristics

DC resistance ≤ 13.3 Ω/km at 20 °C per GB/T 3956 — roughly 30% lower than the 1.0 mm² variant, cutting voltage drop to ≈ 1.33 V per 100 m at 10 A. Rated voltage 450/750 V. Estimated ampacity ≈ 12–15 A in free air at 30 °C. Insulation resistance ≥ 25 MΩ·km. Routine AC withstand test at 2500 V for 5 minutes. Typical capacitance ≈ 150 pF/m at 1 kHz. The braid provides ≈ 60–70 dB shielding at 30–1000 MHz. Suitable for 24 V DC and 110 V AC control loops over longer distances.


Insulation & Sheath Data

Property

Value

Insulation material

PVC (Type TI2)

Outer sheath material

PVC (Type TM2)

Shield material

Tinned copper braid

Long-term service temp.

70 °C (continuous)

Max. conductor temp. (normal)

70 °C

Short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Test voltage AC (5 min)

2.0 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹² Ω·cm

Shield

Tinned copper braid, ≥ 85% coverage (EMI/RFI protection)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

300 / 300 V

GB/T 5023.5 (control/signal)

Max. system voltage

350 V AC / 500 V DC

—

Test voltage AC (5 min)

2.0 kV

Routine test

DC resistance @20 °C

≤ 13.3 Ω/km per core

GB/T 3956 Class 5 Cu max (1.5 mm²)

AC resistance @70 °C (est.)

≈ 16.6 Ω/km per core

—

Current rating in air (30 °C)

Control: 10 A per core​ (recommended max.)

conservative control rating

Current rating in tray (30 °C)

Control: 12 A per core​

—

DC current capacity

10 A​ per core

—

Short-circuit current (1 s, Cu, 160 °C)

≈ 165 A per core

—

Capacitance (core-to-core, approx.)

≈ 0.14 µF/km

PVC

Capacitance (core-to-shield, approx.)

≈ 0.22 µF/km

PVC

Inductive reactance (approx.)

≈ 0.07 Ω/km

at 50 Hz

Frequency

DC / up to 100 MHz (signal)

—

Characteristic impedance (approx.)

50 – 70 Ω

signal reference

Attenuation (at 1 MHz, approx.)

≈ 0.6 dB/100 m

—


Reference values: RVVP 2×1.5 at 10 A per core, 24 V DC → max load ≈ 240 W​ per core (control/signal use). At 230 V AC → max load ≈ 2,300 VA​ per core (not recommended for power).

4. Thermal & Flame Behaviour

Operating range -15 to +70 °C continuous. Short-circuit withstand up to 160 °C for ≤ 5 seconds. PVC insulation and jacket are flame-retardant per IEC 60332-1. The cable is halogen-containing (PVC), emitting HCl gas on burning — avoid in enclosed switchrooms where corrosive fume is a concern. For public or enclosed spaces, specify LSZH alternatives. The thicker 0.8 mm Type ST jacket offers improved oil resistance for machine tool and press applications. UV resistance is limited; install indoors or in UV-protected conduits only.


Temperature Characteristics

Property

Value

Max. conductor operating temp.

70 °C (continuous)

Max. short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Min. installation ambient temp.

−15 °C

Service ambient range

−15 °C to +70 °C

Flexing temp. range

−5 °C to +70 °C


Fire Performance (RVVP — PVC, Non-Low-Smoke)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 / IEC 60332-3​ (Category A/B/C as specified)

Halogen content

Contains halogen​ (PVC)

Smoke density

Not low-smoke​ (IEC 61034-2 not applicable)

Corrosivity

Corrosive​ (HCl emission from PVC)

Toxicity

Toxic fumes​ when burned (CO, HCl)

EMI shielding

Excellent​ (tinned copper braid, ≥85% coverage)

UV resistance

Poor​ (PVC degrades outdoors, use conduit or UV-resistant)

Water resistance

Limited​ (PVC sheath)

5. Installation Practice & Handling

Minimum bending radius ≥ 6×OD ≈ 47 mm for fixed installation; 12×OD ≈ 94 mm for drag-chain or moving applications. The thicker 1.5 mm² core feels stiffer than 0.75/1.0, so use proper cable management. Terminate the braid shield to earth via a shield gland or drain wire at one end (or both ends per system grounding strategy). Use appropriate ferrules on the 30-strand conductor. Route the cable at least 200 mm away from motor and VFD power cables. After installation, verify insulation resistance, shield continuity and polarity before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 6 × OD → ≈ 48 mm at Ø8.0 mm

flexible cable

Max. pulling tension

22.5 N per core (1.5 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Not recommended​ (PVC, non-UV, water ingress)

—

Surface mounting

Cable tray, conduit, trunking, DIN rail

—

Conduit ID

≥ 20 mm

—

Fixing

cable ties, clamps, clips

—

Impact resistance

Low (PVC)

—

Water resistance

Limited​ (PVC sheath)

—

UV resistance

Poor​ (indoor/conduit only)

—

Flex life

Excellent​ (Class 5 fine-stranded)

flexible routing

Termination note

Screw terminals, IDC connectors, D-sub, RJ45 (via adapter)

—


6. Typical Service Applications

Machine tool control wiring, PLC remote I/O drops, 24 V DC control loops, relay and contactor control circuits, sensor and transducer interconnection on larger machines, and low-voltage alarm circuits. The 1.5 mm² cross-section is the sweet spot for longer runs (20–50 m) where smaller cables would show noticeable voltage drop, or where auxiliary loads such as small solenoid valves demand a bit more current. Particularly valuable near variable-frequency drives, servo motors and robotic cells. Not for: mains AC power distribution, high-speed fieldbus, direct burial, or outdoor UV-exposed runs.

RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V

7. Testing & Quality Assurance Regime

Routine tests (100% production): DC resistance, AC voltage withstand (2500 V/5 min), insulation resistance, conductor construction, wall thickness, dimensional check, print legibility, mass per length, visual appearance, and packing. Type tests (per batch / material change): shield coverage, heat aging (100 °C/7 days), cold bend (-15 °C), jacket tensile, flame retardancy, and shielding effectiveness. Every coil ships with mill test certificate, ROHS and REACH declarations. The 450/750 V rating adds a higher withstand test voltage than 300/500 V cables.


Cable Parameters


RVVP 2×1.5 mm² — Full Parameter Sheet
Shielded flexible control cable · 450/750 V · tinned Cu Class 5 · PVC insulation/jacket · tinned Cu braid ≈ 85% · GB/T 9330 / IEC 60227
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type RVVP — Flexible tinned Cu, PVC ins., PVC jacket, braid shield

Rated voltage (U0/U) 450/750 V Medium-current control / signal

Number of cores 2 — 2 cores, colour-coded

Nominal cross-section 1.5 mm² Per core, Class 5 flexible

Conductor material Tinned annealed copper — Class 5 per GB/T 3956 / IEC 60228

Insulation material PVC (Type SP) — 70 °C rated, 0.7 mm wall

Shield Tinned copper braid — ≈ 85% coverage

Outer jacket material PVC (Type ST) — Oil/abrasion resistant, 0.8 mm

Standard reference GB/T 9330 / IEC 60227 / UL 2464 — Harmonized control cable
02 · Conductor

Stranding 30 × 0.25 mm — Class 5 tinned copper per core

Conductor diameter ≈ 1.55 mm Per core, compacted lay

DC resistance @ 20 °C ≤ 13.3 Ω/km Maximum per GB/T 3956

Conductor surface Tinned — Anti-corrosion, solderable
03 · Insulation

Insulation type PVC (Type SP) — Soft PVC, 70 °C

Insulation thickness ≈ 0.7 mm Nominal (thicker than 1.0 mm²)

Insulated core Ø ≈ 2.95 mm Per core

Insulation resistance ≥ 25 MΩ·km At 20 °C
04 · Shield & Inner Sheath

Inner sheath material PVC + polyester filler — Bedding over laid-up cores

Inner sheath thickness ≈ 0.6 mm Nominal

Shield type Tinned Cu braid — Woven over inner sheath

Shield coverage ≈ 85 % Typical

Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
05 · Outer Jacket

Jacket material PVC (Type ST) — Oil/abrasion resistant

Jacket thickness ≈ 0.8 mm Nominal

Overall finished diameter ≈ 7.8 mm 2-core shielded

Approximate cable mass ≈ 68 kg/km Tinned Cu + PVC + braid

Mass per 100 m ≈ 6.8 kg/100 m For coil loading
06 · Electrical

Rated voltage 450/750 V Control / low-power

Test voltage (AC) 2500 V AC 5 min routine

DC resistance @ 20 °C ≤ 13.3 Ω/km Per GB/T 3956

Ampacity (free air) ≈ 12–15 A 1.5 mm², 70 °C

Voltage drop @ 10 A / 100 m ≈ 1.33 V I × R

Capacitance (core-core) ≈ 150 pF/m At 1 kHz
07 · Thermal & Mechanical

Max continuous conductor temp. 70 °C Normal service

Short-circuit temp. (≤5 s) 160 °C Copper limit

Min. ambient temp. -15 °C Fixed installation

Min. bending radius ≥ 6 × OD ≈ 47 mm Fixed; 12× for moving

Halogen content Halogen-containing — PVC compound
08 · Flame & Environment

Flame retardancy IEC 60332-1 — Single vertical flame

Oil resistance Good — Type ST PVC

UV resistance Limited — Indoor / conduit use

ROHS / REACH Compliant — EU 2011/65/EU


Cable Test Parameters


Test Parameters — RVVP 2×1.5 mm²
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 13.3 Ω/km Routine
2 AC voltage withstand 2500 V AC, 5 min No breakdown Routine
3 Insulation resistance 500 V megohmmeter ≥ 25 MΩ·km Routine
4 Conductor construction Visual + strand count 30 × 0.25 mm tinned Cu Routine
5 Wall thickness Micrometer cross-section Ins. ≈ 0.7 mm; jacket ≈ 0.8 mm Routine
6 Dimensional check Caliper OD ≈ 7.8 mm Routine
7 Print legibility Visual + rubbing Marks legible Routine
8 Mass per unit length Weighing ≈ 68 kg/km Routine
9 Appearance Visual Smooth, no blisters Routine
10 Packing Visual Coil/drum, sealed ends, labelled Routine
11 Shield coverage Unwrap + count ≥ 80% (≈ 85%) Type
12 Heat aging test 7 days at 100 °C Retention ≥ 70% Type
13 Cold bend test -15 °C, 4 h mandrel No cracking Type
14 Jacket tensile test Universal tester Meets GB/T 9330 min. Type
15 Flame retardancy IEC 60332-1 Self-extinguish Type
16 Shielding effectiveness Triaxial / open-field ≥ 60 dB at 30–1000 MHz Type


Cable Cross Section Structure


RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V


RVVP 2×1.5 mm² — Cross-Section Construction Diagram (Schematic)
Layered build-up: tinned Cu Class 5 conductors → PVC insulation → inner PVC sheath → tinned copper braid shield → PVC outer jacket · 450/750 V shielded control cable · medium-current signal & control · EMI/RFI protection · -15~+70 °C
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (×2) Tinned annealed copper, Class 5 flexible — 30 × 0.25 mm strands per core — ≈ 1.55 (per core) Medium-current signal/control; R ≤ 13.3 Ω/km; tinned for anti-corrosion and solderability
2 Insulation (per core) PVC compound (Type SP), extruded over each conductor, colour-coded ≈ 0.7 ≈ 2.95 (per insulated core) Electrical insulation; 450/750 V rated; colour-coded (red/black, blue/white, etc.)
3 Inner sheath PVC compound, extruded over the two laid-up cores, round filler ≈ 0.6 ≈ 6.1 (before braid) Round and bed the cores; mechanical protection; bedding for braid
4 Braid shield Tinned copper wire braid, ≈ 85% coverage, laid over inner sheath ≈ 0.4 (effective) ≈ 6.9 EMI/RFI shielding; drain path for fault currents; low transfer impedance
5 Outer jacket PVC compound (Type ST), black or grey, extruded over braid ≈ 0.8 ≈ 7.8 (finished) Outer mechanical protection; oil-, abrasion-resistant; printed markings






Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 7.8 mm 2-core shielded control cable (est.)
Approximate cable mass ≈ 68 kg/km Tinned Cu + PVC + braid build-up
Nominal voltage rating 450/750 V Control / signal / low-power circuits
Max continuous conductor temp. 70 °C Normal service
Min. ambient / installation temp. -15 °C Fixed installation
DC resistance @ 20 °C ≤ 13.3 Ω/km Class 5 tinned copper, GB/T 3956
Core count × cross-section 2 × 1.5 mm² 2 cores
Shield coverage ≈ 85 % Tinned copper braid
Insulation resistance ≥ 25 MΩ·km PVC at 20 °C
Test voltage (AC) 2500 V AC / 5 min — Routine withstand test
Flame retardancy IEC 60332-1 — Single vertical flame
Shielding effectiveness ≈ 60–70 dB At 30–1000 MHz
Jacket colour Black / grey / custom — Standard: black
Mass per 100 m ≈ 6.8 kg/100 m For coil / drum loading
Reference standard GB/T 9330 / IEC 60227 / UL 2464 — Harmonized control cable
Schematic — not to exact scale. Finished Ø ≈ 7.8 mm and weight ≈ 68 kg/km from cross-referenced industry samples; conductor stranding 30/0.25 mm per core and braid coverage ≈ 85%. Est. values confirmed against factory type certificate.


Construction Description


Construction Description — RVVP 2×1.5 mm²
Layer-by-layer build-up narrative · 450/750 V shielded control cable · GB/T 9330 / IEC 60227 · tinned copper / PVC insulation / tinned copper braid shield / PVC outer jacket
1. Product Identity & Ratings
RVVP 2×1.5 is a medium-current shielded control cable rated 450/750 V — one step up from 0.75 and 1.0 mm² variants. R = flexible tinned copper, V = PVC insulation, V = PVC jacket, P = braided shield. The two 1.5 mm² cores carry more current and support longer control runs with lower voltage drop. Target use: machine tool control wiring, PLC remote I/O, and 24 V DC control loops where distance or load demands a larger conductor. Max 70 °C, -15 to +70 °C range.
2. Tinned Copper Conductor (×2)
Each 1.5 mm² core is stranded from 30 tinned annealed copper wires of 0.25 mm in a Class 5 compacted lay-up. The thicker 0.25 mm wires give a bit more rigidity than the 0.20 mm stranding of smaller cross-sections, while remaining flexible enough for panel dressing. Tinning provides oxidation resistance and solderability. DC resistance is ≤ 13.3 Ω/km at 20 °C, roughly 30% lower than 1.0 mm², cutting voltage drop on longer runs.
3. PVC Insulation
Each conductor receives a 0.7 mm extrusion of Type SP PVC — slightly thicker than the 0.6 mm wall on smaller cores, to match the 450/750 V voltage rating. The insulation is colour-coded for polarity and circuit identification. Insulation resistance ≥ 25 MΩ·km at 20 °C. The thicker wall also improves dielectric margin and reduces capacitance over the 0.75/1.0 mm² variants, benefiting longer signal runs.
4. Inner Sheath + Braid Shield
The two insulated cores are laid up with polyester fillers to keep the cable round, then bedded with a 0.6 mm PVC inner sheath. Over this, a tinned copper braid is woven at ≈ 85% coverage. The braid handles both EMI shielding and the earth-fault return path. The thicker 1.5 mm² core also means the shield sees more fault energy, so the braid construction is verified per batch.
5. Outer PVC Jacket
A 0.8 mm Type ST PVC jacket completes the build, yielding an OD of ≈ 7.8 mm. The jacket is oil- and abrasion-resistant, flame-retardant per IEC 60332-1, and printed with product type, cross-section, voltage, metre mark and manufacturer. Black or grey standard; custom colours on request. For drag-chain or continuous-flex duty, specify RVVSP variant with enhanced braid.

8. Factory Advantages

Pure copper conductor at 30×0.25 mm stranding balances flexibility and current capacity. Thicker 0.7 mm insulation and 0.8 mm jacket match the 450/750 V rating for extra dielectric margin. Tinned copper braid at ≈ 85% coverage provides reliable EMI shielding for industrial noise environments. Lower DC resistance (13.3 Ω/km) supports longer control runs. Oil-resistant Type ST jacket for machine tool duty. 100% routine electrical QA on every reel. Cut-to-length coils with sealed ends. Lightweight ≈ 68 kg/km. Full traceability with MTC and certification support for industrial and machinery tenders.


9. Packaging, Storage & Logistics

Cut to customer-specified length on export-grade coils or wooden drums, with both ends heat-sealed. Coils wrapped in waterproof film and corrugated cardboard, labelled with product type, core count, cross-section, length, weight, production date and reel number. Standard lengths 100/200/500/1000 m. Store dry indoor, -10 to +40 °C, below 75% RH, away from direct sunlight and chemical solvents. FOB Shanghai/Nanjing/Qingdao; CIF and DAP available. Sample lead time 5–7 days; bulk production 15–25 days. Wooden drums recommended for lengths over 500 m.


RVVP 2x1.5mm² Braided Shielded Industrial PLC Control Cable Anti-Interference Field Automation 300/500V

10. Procurement Specification

State cable designation "RVVP 2×1.5", required length per coil/drum, and core colour preference. Request the routine AC withstand test record (2500 V) and shield coverage certificate for the specific batch. Note that the voltage rating is 450/750 V — higher than the 300/500 V of smaller cross-sections. Specify any regional certification requirements (UL 2464, CE, etc.) at order time. Payment: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list. For drag-chain duty, specify RVVSP variant with enhanced flexible braid.

11. Cable Industry FAQ

Q1: Why choose 1.5 mm² over 1.0 mm²? Lower DC resistance (13.3 vs 19.5 Ω/km), higher ampacity (12–15 A vs 8–10 A), and a higher 450/750 V rating for longer control runs.

Q2: What voltage is it rated for? 450/750 V, suitable for machine tool control and 110 V AC control circuits.

Q3: How does the braid shield work? The tinned copper braid at ≈ 85% coverage diverts EMI/RFI currents to earth through the shield drain, giving ≈ 60–70 dB attenuation.

Q4: Is it suitable for drag chains? Not as standard — specify RVVSP (flexible braid) variant for continuous-flex applications.

Q5: Can it be used outdoors? No — limited UV resistance; install indoors or in UV-protected conduits.

Q6: Is it halogen-free? No — PVC is halogen-containing. Use LSZH for enclosed or public spaces.

Q7: How do I ground the shield? Connect braid to earth at one end (or both ends per system design) using a shield gland or drain wire.

Q8: What is the bending radius? ≥ 6×OD ≈ 47 mm for fixed; 12× for moving applications.

Q9: What is the temperature range? -15 to +70 °C continuous.

Q10: What proof ships? Routine AC test record (2500 V) + shield coverage certificate + MTC.

Q11: Can it carry 24 V DC signals? Yes — 1.5 mm² is well suited for 24 V DC control loops over longer distances with minimal voltage drop.