8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible For Indoor Power Distribution Systems

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible For Indoor Power Distribution Systems

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
ZR-YJV 5*25mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

5 Core 25mm² ZR-YJV Flame Retardant Copper Cable for Indoor Power Distribution Systems Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer ...

Product Details

Highlight:

8.2mm25mm 5 core armoured cable

,

8.6mm 25mm 5 core armoured cable

,

Indoor Power Distribution sheathed flexible cable

Conductor (×5):
Bare Annealed Copper, Class 2 Stranded, 7×∅2.14 Mm, Conductor Ø ≈ 6.4–6.8 Mm Depending On Compaction
Conductor nominal area (per core):
25 Mm²
Number of cores:
5
Conductor construction:
Class 2, 7×∅2.14 Mm,IEC 60228 / GB/T 3956, Min. 7 Wires
Conductor diameter (approx.):
6.4–6.8 Mm
Insulation (×5):
XLPE
Insulation thickness:
0.9 Mm (25 Mm² Class)
Diameter over insulated core:
8.2–8.6 Mm,conductor + 2×0.9
8.2–8.6 mm conductor + 2×0.9:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.5 Mm (GB/T 12706 Multi-core 5-core 16–35 Mm² Range)
Overall cable diameter:
17.5 – 21.0 Mm
Design outer diameter:
≈ 19.0 Mm
Approx. weight:
520 – 660 Kg/km
Design weight:
≈ 580 Kg/km
Cable shape:
Round

Product Description

5 Core 25mm² ZR-YJV Flame Retardant Copper Cable for Indoor Power Distribution Systems


Cable Designation & Meaning


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

5×25 mm²

Five cores, nominal copper conductor area 25 mm² per core


Construction: Five 25 mm² copper conductors (3 phase + 1 neutral + 1 earth), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems


ZC-YJV 5×25 mm² — LV Flame-Retardant Five-Core (TN-S) Small Branch Cable — Specification

1. Overview & Ratings. ZC-YJV 5×25 is a five-core TN-S LV small-branch cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C PVC sheath: five equal 25 mm² compacted copper cores (L1/L2/L3/N plus dedicated PE), dry-cured XLPE, unarmored. OD ≈ 18 mm, ≈ 1500 kg/km (est.), ≈ 78 A per core free air at 30 °C (est.). Scope: lighting/socket branches, fan feeds, small feeders and circuits needing a separate earth — not 950°C fire duty.


2. Construction Stack (Inner → Outer, expanded).


Layer / Feature Build Function
Cores L1/L2/L3 3×25 compacted Cu, Class 2, ≈7 strands Phase load current
Neutral N 1×25 compacted Cu, equal size Balanced return
Protective earth PE 1×25 compacted Cu, dedicated Separate TN-S earth path
Strand compaction Concentric layers rolled compact per core Compact round bundle, clean lugs
XLPE insulation Dry-cured PE, ≈1.2 mm Uniform 90°C dielectric
Five-core laying Equal cores around bundle center Round five-core bundle
PVC ZC sheath Class C, ≈1.6 mm overall Self-extinguishes, prints clear


3. Electrical Characteristics. Core R ≤ 0.741 Ω/km @20 °C on all five cores. Test 3.5 kV AC / 5 min; ≈ 78 A per core (est., air 30 °C); short-circuit ≈ 3.3 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance; dedicated low-R PE continuity.

Insulation & Sheath Data

Property

Value

Insulation material

XLPE (cross-linked polyethylene)

Outer sheath material

PVC (ST₂)

Long-term service temp.

90 °C (continuous)

Max. conductor temp. (normal)

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Test voltage AC (5 min)

3.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹⁴ Ω·cm

Shield

None as standard (can be added)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage

1.2 kV AC

—

Test voltage AC (5 min)

3.5 kV

Routine test

DC resistance @20 °C

≤ 0.727 Ω/km per core

GB/T 3956 Class 2 Cu max (25 mm²)

AC resistance @90 °C (est.)

≈ 0.932 Ω/km per core

—

Current rating in air (30 °C)

3-phase: 95 A​

5×25, touching, in free air

Current rating in tray (30 °C)

3-phase: 105 A​

5×25, spaced 2×OD

Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W)

3-phase: 100 A​

direct buried

Current rating in conduit (30 °C)

3-phase: 85 A​

—

Short-circuit current (1 s, Cu, 250 °C)

≈ 2.75 kA (2,750 A) per core

—

Capacitance (core-to-sheath, approx.)

≈ 0.18 µF/km

XLPE

Inductive reactance (approx.)

≈ 0.08 Ω/km

at 50 Hz

Frequency

50/60 Hz AC

—


Reference values: 5×25 at 95 A three-phase, 400 V → max load ≈ 57 kW​ (cos φ = 0.8). Suitable for light three-phase distribution with full neutral and earth (TN-S), small panels, and building branch circuits.


4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands branch cycling; indoor preferred, UV jacket optional.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Min. installation ambient temp.

0 °C (below 0 °C requires preheating)

Service ambient range

−20 °C to +90 °C

Flexing temp. range

0 °C to +90 °C

Fire Performance (ZC-YJV — Flame Retardant C)

Property

Value / Requirement

Flame retardant

GB/T 18380.12 / IEC 60332-1-2​ (single cable, self-extinguishing)

Flame retardant class

Class C​ (ZC) per GB/T 19666

Halogen content

Contains halogen (PVC sheath)

Smoke density

Not low-smoke (PVC)

Corrosivity

Corrosive (PVC)

Toxicity

Toxic fumes when burned (PVC)

EMI shielding

None (no metallic screen/armour)


5. Installation Practice & Handling. Hydraulic crimp 25 mm² lugs on all five cores, glands to ≈18 mm OD, torque per table; bend ≥ 15×OD ≈ 270 mm; apply conduit/tray derating; keep the bundle round; verify continuity of all five cores, phase sequence, neutral, dedicated PE and insulation before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 308 mm at Ø20.5 mm

five-core unarmoured

Max. pulling tension

375 N per core (25 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Suitable (with sand bedding)

—

Surface mounting

Cable tray, ladder, cleats

—

Conduit ID

≥ 40 mm

—

Fixing

cleats, cable ties

—

Impact resistance

Moderate

—

Water resistance

Good (PVC sheath)

—

UV resistance

Fair (PVC degrades outdoors, use UV-resistant PVC or conduit)

—

Flex life

Good (Class 2 stranded)

fixed installation

Termination note

Standard compression lugs or mechanical connectors

—


6. Typical Service Applications. TN-S lighting and socket branches, fan feeds, small feeders, lighting sub-panels, and equipment circuits requiring a separate protective earth.


8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems


7. Testing & QA Regime (16 items). Routine: core DC resistance on all five, 3.5 kV withstand, insulation resistance, continuity including dedicated PE, insulation and sheath thickness, dimensional check, strand construction, core color coding, eccentricity, print legibility, mass, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.


Cable Parameters


ZR-YJV 5×25 mm² — Flame-Retardant Five-Core Power Cable (0.6/1 kV) · Product Parameters
CU / XLPE / PVC · 5 × 25 mm² · GB/T 12706.1, IEC 60502-1, GB/T 3956, GB/T 19666 · nominal values for reference
Code Parameter Value Unit Remarks
01 · Identification
Std: GB/T 12706.1 / IEC 60502-1; fire GB/T 19666; Um = 1.2 kV; 50 Hz
1-A Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable (five-core) — ZR-YJV; halogen-containing flame-retardant
1-B Model ZR-YJV 5×25 — 5 cores × 25 mm²; CU / XLPE / PVC
1-C Design standards GB/T 12706.1; IEC 60502-1 — Conductor GB/T 3956
1-D Rated voltage U0/U 0.6/1 kV Um = 1.2 kV; AC 50 Hz
1-E Core arrangement 5 cores (L1/L2/L3/N/PE) — Three phases + neutral + earth
1-F Nominal cross-section 25 mm² Per core, GB/T 3956
02 · Conductor
Std: GB/T 3956 / IEC 60228 Class 2 — 25 mm² = 7 wires (round)
2-A Material Plain annealed copper — High conductivity
2-B Class Class 2 (stranded) — GB/T 3956 / IEC 60228
2-C Stranding (per core) 7 × 2.14 mm (7/2.14) — 1+6 concentric rings
2-D Conductor diameter ≈ 6.4 mm Per core (7 × 2.14)
2-E Max. DC resistance @ 20 °C 0.727 Ω/km GB/T 3956 Class 2 Cu
03 · Insulation
Std: Mingda five-core unarmored table — 1.2 mm wall at 25 mm²
3-A Material Cross-linked polyethylene (XLPE) — Thermally cross-linked
3-B Nominal thickness 1.2 mm Mingda five-core table
3-C Diameter over insulation ≈ 8.8 mm Per core (calculated)
04 · Assembly
Std: pentagonal ring lay-up; filler takes the residual gap
4-A Core lay-up Five cores in a pentagonal ring + dry filler + binder tape — Round bundle
4-B Diameter over lay-up ≈ 23.0 mm Calculated (Ø 26.6 − 2 × 1.8)
05 · Sheath
Std: Mingda five-core unarmored table (Ø 26.6; 1503 / 697.4 kg/km)
5-A Material Flame-retardant PVC, ST2 — Black (or as ordered)
5-B Nominal thickness 1.8 mm Mingda five-core table
5-C Overall diameter ≈ 26.6 mm Mingda five-core unarmored
5-D Approx. cable weight ≈ 1503 kg/km Mingda 1503 (YJLV ≈ 697.4)
06 · Electrical
Std: Mingda five-core unarmored table (soil 125 / air 105 A Cu @ 25 °C)
6-A DC conductor resistance 0.727 Ω/km GB/T 3956 @ 20 °C, per core
6-B Routine voltage test 3.5 kV / 5 min — No breakdown; 50 Hz AC
6-C Insulation resistance ≥ 36.7 MΩ·km Finished cable @ 20 °C
6-D XLPE volume resistivity ≥ 1 × 10¹² Ω·cm Material level
6-E Capacitance (approx.) ≤ 0.45 μF/km Per core
6-F Ampacity — buried @ 25 °C (5 cores) ≈ 125 A Mingda basis (Cu)
6-G Ampacity — air @ 25 °C (5 cores) ≈ 105 A Mingda basis (Cu)
07 · Thermal
Std: XLPE class per GB/T 12706.1 / IEC 60502-1
7-A Continuous conductor temperature 90 °C XLPE class
7-B Short-circuit temperature (≤ 5 s) 250 °C GB/T 12706.1 / IEC 60502-1
7-C Ambient service range -20 to +45 °C Per datasheet family
7-D Min. laying temperature 0 °C Pre-heat below 0 °C
08 · Fire (ZR)
Std: GB/T 19666; GB/T 18380.12; GB/T 18380.35 (20 min, ≥ 1.5 L/m)
8-A Flame-retardant class ZC by default ("ZR") — Halogen-containing PVC
8-B Single-cable flame test Pass — GB/T 18380.12
8-C Bunched flame test — class C Char ≤ 2.5 m — GB/T 18380.35
8-D Halogen content Halogen-containing — LSZH needs WDZ-YJY
09 · Installation
Std: Q/GDW 13244.1-2018 for site test
9-A Min. bending radius (multi-core) ≥ 15 × OD — GB 50168 practice
9-B Laying methods Conduit, tray, trench, duct, trunking — Mechanical protection where buried
9-C Site test after installation DC 4U0 = 2.4 kV / 15 min — Q/GDW 13244.1-2018
10 · Packing
Std: custom lengths available; GB/T 6995 / project spec
10-A Standard delivery length 100 m per coil/drum — Custom lengths available
10-B Marking Model, voltage, maker, year, length marks — GB/T 6995 / project spec


Cable Test Parameters


ZR-YJV 5×25 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.727 Ω/km @ 20 °C (per core) Every production length
Routine Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor-to-earth/water
Routine Construction check GB/T 2951 Ins. ≥ 1.2 mm; sheath ≥ 1.8 mm; OD within tolerance Thickness & diameter
Sample Hot set test — XLPE GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking degree
Sample Conductor construction & diameter GB/T 3956 Class 2; 7 × 2.14 mm; Ø ≈ 6.4 mm Per batch
Type Single-cable flame test GB/T 18380.12 No flame spread to top reference ZR property
Type Bunched flame test — class C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m ZC class
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core rule
Post-install DC withstand test Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown New installations
Optional Insulation resistance @ 20 °C Factory method ≥ 36.7 MΩ·km Not routine in GB/T 12706.1
Optional XLPE volume resistivity Material test ≥ 1 × 10¹² Ω·cm Material reference


Cable Cross Section Structure

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems

ZR-YJV 5×25 mm² — Cable Cross-Section Structure (Schematic)
Five-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 5 Annealed copper, Class 2 stranded — 7 × 2.14 mm per core (7/2.14, 1+6), nominal 25 mm² per core — ≈ 6.4 (Ø per core) Current-carrying element; max DC resistance ≤ 0.727 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 5 Cross-linked polyethylene 1.2 ≈ 8.8 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Five insulated cores laid up in a pentagonal ring around dry filler; binder tape — ≈ 23.0 (Ø over lay-up, calc.) Round assembly; the 5th core is the PE (earthing) core
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.8 ≈ 26.6 (Ø overall, Mingda five-core) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666












Key Dimensions & Properties
Overall diameter ≈ 26.6 mm Mingda five-core unarmored table

Approx. cable weight ≈ 1503 kg/km Mingda 1503 (Al ≈ 697.4)

Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV

Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)

Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter

Flame-retardant class ZC (ZR) — GB/T 19666

Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.


Product Structure Introduction


Product Structure Introduction — ZR-YJV 5×25 mm² 
Five-core layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV
1. Overview & Ratings
ZR-YJV 5×25 is the third size of the flame-retarding five-core family: five 25 mm² copper conductors, XLPE insulation and one ST2 PVC jacket, rated 0.6/1 kV. Production and testing follow GB/T 12706.1 / IEC 60502-1, stranding follows GB/T 3956, and the ZR (ZC) fire class of GB/T 19666 is standard. Finished diameter ≈ 26.6 mm (Mingda five-core row), weight ≈ 1503 kg/km; 100 m coils or drums.
Five cores loaded, the cable is rated ≈ 105 A in air at 25 °C on the Mingda basis — sized for sub-main distribution, small motor feeders and circuits where a separate PE core is required.
2. Copper Stranded Conductor
Each 25 mm² core strands seven 2.14 mm annealed wires (7/2.14) in the 1+6 pack — the Class 2 pack for this section — to ≈ 6.4 mm Ø. DC resistance is capped at 0.727 Ω/km at 20 °C; the tight 1+6 arrangement yields a clean circular profile for the 1.2 mm insulation wall and compact terminations.
3. XLPE Dielectric Layer
XLPE is extruded at 1.2 mm — the wall Mingda's five-core table assigns to 25 mm², a step up from the 1.0 mm of the 16 mm² five-core size — giving ≈ 8.8 mm per core over the insulation. The dielectric is rated 90 °C continuously and 250 °C for five seconds, holds volume resistivity ≥ 1×10¹² Ω·cm and passes the 3.5 kV AC five-minute routine proof.
4. Cabling & PVC Sheath
Five insulated cores are cabled in a pentagonal ring with dry filler and binder tape into a ≈ 23.0 mm bundle, then sheathed in 1.8 mm of flame-retarded ST2 PVC to the published 26.6 mm finish. The jacket delivers ZC behaviour via GB/T 18380.12 and GB/T 18380.35; since PVC contains halogen, low-smoke orders move to WDZ-YJY.
5. Field Handling & Usage
• Respect the 15 × OD bending floor.  • Apply the DC 4U0 = 2.4 kV / 15 min site test before first energisation.  • Service ambient −20 to +45 °C; warm drums below 0 °C before pulling.  • Derate the 105 A (air) / 125 A (buried) reference for ambient, grouping and soil.  • Use lugs and glands sized for the 6.4 mm core and 26.6 mm sheath.


8. Factory Advantages.

  • TN-S five-core balance — dedicated PE core meets TN-S rules without sharing the neutral.
  • Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
  • Dosed ZC compound — self-extinguishing jacket protects lighting circuits and panel rooms.
  • Length-on-demand — cut to exact branch meter with sealed ends.
  • Uniform resistance log — all five 25 cores R recorded to lot for traceability.
  • Continuous print line — type, size, ZC, voltage and length readable along runs.
  • TN-S color coding — L1/L2/L3/N/PE colors reduce wiring errors.
  • Lightweight pack — light drum, easy ladder and ceiling handling.
  • Certified QA pack — routine + type test record shipped per batch.

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems


9. Packaging, Storage & Logistics. Cut to measured branch length on a light wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.


8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems


10. Procurement Specification. State "ZC-YJV 5×25", length, class C, TN-S colors; confirm the dedicated PE role; request the core resistance log and 16-item QA record. Est. values confirmed against the factory certificate.


11. Cable Industry FAQ.

  • Q1: How does 5×25 differ from 4×70? Five-wire TN-S with dedicated PE rather than four heavy cores: five 25 mm² cores vs four 70; core R 0.741 vs 0.268 Ω/km, core current ≈78 vs 175 A; aimed at lighting/socket branches and fan feeds rather than a heavy power branch.
  • Q2: What is the fifth core? A dedicated protective earth (PE) separate from the neutral per TN-S practice.
  • Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
  • Q4: DC resistance value? 25 cores ≤0.741 Ω/km at 20°C, identical on all five.
  • Q5: Screen or armor? Unscreened standard; add braid near VFD EMI; steel-tape armor for ground-crushing ducts.
  • Q6: Current per core? ≈78 A (est.) free air 30°C; derate in crowded conduit.
  • Q7: Bending? ≈270 mm (15×OD); small section bends easily in trunking.
  • Q8: Connectors? 25 mm² lugs on all five cores; gland to ≈18 mm OD.
  • Q9: Indoor or outdoor? Indoor preferred; specify UV-stabilized jacket for exposed runs.
  • Q10: Packing? Light wooden drum with moisture-sealed ends.
  • Q11: What proof ships? Core resistance log + 16-test record including PE continuity; est. values confirmed against certificate.