8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible For Indoor Power Distribution Systems

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible For Indoor Power Distribution Systems

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZR-YJV 5*25mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
10000 meters per month

Product Summary

5 Core 25mm² ZR-YJV Flame Retardant Copper Cable for Indoor Power Distribution Systems Cable Designation & Meaning Code Meaning ZR Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). YJ XLPE (cross-linked polyethylene) insulation V PVC outer ...

Product Details

Highlight:

8.2mm25mm 5 core armoured cable

,

8.6mm 25mm 5 core armoured cable

,

Indoor Power Distribution sheathed flexible cable

Conductor (×5):
Bare Annealed Copper, Class 2 Stranded, 7×∅2.14 Mm, Conductor Ø ≈ 6.4–6.8 Mm Depending On Compaction
Conductor nominal area (per core):
25 Mm²
Number of cores:
5
Conductor construction:
Class 2, 7×∅2.14 Mm,IEC 60228 / GB/T 3956, Min. 7 Wires
Conductor diameter (approx.):
6.4–6.8 Mm
Insulation (×5):
XLPE
Insulation thickness:
0.9 Mm (25 Mm² Class)
Diameter over insulated core:
8.2–8.6 Mm,conductor + 2×0.9
8.2–8.6 mm conductor + 2×0.9:
FR PP Filler + FR Tape
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.5 Mm (GB/T 12706 Multi-core 5-core 16–35 Mm² Range)
Overall cable diameter:
17.5 – 21.0 Mm
Design outer diameter:
≈ 19.0 Mm
Approx. weight:
520 – 660 Kg/km
Design weight:
≈ 580 Kg/km
Cable shape:
Round

Product Description

5 Core 25mm² ZR-YJV Flame Retardant Copper Cable for Indoor Power Distribution Systems

 

Cable Designation & Meaning

 

Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

5×25 mm²

Five cores, nominal copper conductor area 25 mm² per core

 

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems

ZR-YJV 5×25 mm² — Cable Specification & Engineering Data 

1. Overview & Ratings. ZR-YJV 5×25 — flame-retarding five-core cable, five 25 mm² Cu conductors, XLPE insulation, one ST2 PVC sheath, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; built and proof-tested per GB/T 12706.1 / IEC 60502-1, stranding per GB/T 3956, ZC fire class per GB/T 19666. ≈ 26.6 mm, ≈ 1503 kg/km (Al ≈ 697.4), 100 m coils/drums.

 

2. Construction Stack. Conductor → outer sheath:

Layer Build Wall Diameter
Conductor (×5) Annealed Cu, Class 2, 7 × 2.14 mm (1+6) each — ≈ 6.4 mm
Insulation (×5) XLPE 1.2 mm ≈ 8.8 mm
Lay-up Five cores (pentagonal ring) + filler + binder tape — ≈ 23.0 mm (calc.)
Sheath Flame-retarded PVC, ST2, black 1.8 mm ≈ 26.6 mm (Mingda five-core)

 

3. Electrical Ratings. R ≤ 0.727 Ω/km @ 20 °C; routine 3.5 kV / 5 min; insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km. Reference ampacity (five cores loaded) ≈ 105 A air / 125 A buried @ 25 °C — Mingda five-core unarmored table.

 

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.727 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.946 Ω/km

per core

Current rating in air (30 °C, single circuit, 5-core)

≈ 80–92 A

common catalogue value

Current rating in air (design)

≈ 85 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 92–105 A

common catalogue 95–102 A

Design buried rating

≈ 98 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 2.5 kA

reference

Frequency

50/60 Hz AC

—

 

4.Cable Parameters and Test Parameters

 

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems

 

ZR-YJV 5×25 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.727 Ω/km @ 20 °C (per core) Every production length
Routine Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor-to-earth/water
Routine Construction check GB/T 2951 Ins. ≥ 1.2 mm; sheath ≥ 1.8 mm; OD within tolerance Thickness & diameter
Sample Hot set test — XLPE GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking degree
Sample Conductor construction & diameter GB/T 3956 Class 2; 7 × 2.14 mm; Ø ≈ 6.4 mm Per batch
Type Single-cable flame test GB/T 18380.12 No flame spread to top reference ZR property
Type Bunched flame test — class C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m ZC class
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core rule
Post-install DC withstand test Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown New installations
Optional Insulation resistance @ 20 °C Factory method ≥ 36.7 MΩ·km Not routine in GB/T 12706.1
Optional XLPE volume resistivity Material test ≥ 1 × 10¹² Ω·cm Material reference

 

5. Thermal & Fire. 90 °C continuous, 250 °C short-circuit (≤ 5 s); −20~+45 °C ambient, ≥ 0 °C laying; ZC per GB/T 19666 — GB/T 18380.12 single-burn + GB/T 18380.35 class-C bunched (char ≤ 2.5 m); PVC is halogen-bearing → WDZ-YJY for LSZH.

 

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems

 

6. Installation & Care. Bend ≥ 15 × OD; DC site test 4U0 = 2.4 kV / 15 min before energising (Q/GDW 13244.1-2018); pre-heat drums below 0 °C; de-rate 105/125 A for ambient, grouping, burial; lugs/glands for the 6.4 mm core and 26.6 mm sheath.

 

Insulation Test Data — ZR-YJV 5×25 mm²
ZR-YJV 5×25 mm²  (Cu / XLPE / FR-PVC)   ·   0.6/1 kV
1.  Cable Identification
Item Description Standard / Note
Designation ZR-YJV 5×25 mm² GB/T 12706.1-2020
Conductor Bare annealed copper, Class 2 stranded, 7ר2.14 mm GB/T 3956 / IEC 60228
Insulation XLPE (cross-linked polyethylene), 0.7 mm nominal GB/T 12706.1-2020
Insulator colours L1/L2/L3 = brown/black/grey; N = blue; PE = green-yellow IEC 60446
Outer sheath Flame-retardant PVC (ZR grade), 1.6 mm nominal, black GB/T 19666-2019
Rated voltage U₀/U 0.6 / 1 kV (Uₘ = 1.2 kV) IEC 60502-1
Number of cores 5 (L1+L2+L3+N+PE, equal sizes) —
2.  Insulation Design Data  (CORE)
Parameter Value Remarks
Insulation material XLPE (cross-linked polyethylene) —
Nominal thickness (eₙ) 0.7 mm 25 mm² class
Minimum allowable thickness (e_min) 0.54 mm eₙ − 0.16 mm (GB/T 12706.1-2020, Table 3)
Insulator colours L1/L2/L3 = brown/black/grey; N = blue; PE = green-yellow IEC 60446
Volume resistivity @ 90 °C ≥ 10¹² Ω·cm —
Dielectric loss factor (tan δ) @ 20 °C ≤ 1 × 10⁻³ reference
Relative permittivity (εᵣ) ≈ 2.3 – 2.5 reference
Long-term service temp. 90 °C GB/T 12706.1-2020
Short-circuit temp. (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 – 130 °C transient
Diameter over insulated core 7.8 mm conductor 6.4 + 2×0.7
3.  Thermal Characteristics
Property Value Remarks
Max. conductor operating temp. (normal) 90 °C long-term
Max. conductor temp. — short-circuit (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) —
Min. installation ambient temp. 0 °C (pre-heat below 0 °C) —
Service ambient range (PVC sheath) −15 °C to +90 °C —
Flame retardant class (sheath) Class C (ZR per GB/T 19666) —
4.  Insulation Test Schedule
Test Item Test Value / Condition Result
Routine withstand test (AC) 3.5 kV AC, 5 min — no breakdown PASS
Type test voltage 4.0 kV AC PASS (IEC 60502-1)
Partial discharge test ≤ 10 pC @ 1.73 U₀ (1.73 kV) PASS (XLPE)
Insulation resistance (IR) ≥ 10⁴ MΩ·km @ 20 °C (reference) PASS
Hot-set test (XLPE cross-linking) 200 °C, 15 min, load 0.2 N/mm² — elongation ≤ 175 %, permanent set ≤ 15 % PASS (IEC 60811-507)
Aging test (air oven) 135 °C, 168 h — tensile strength / elongation retained ≥ 80 % PASS
Tensile strength (insulation) ≥ 12.5 MPa (XLPE, before aging) PASS
Elongation at break (insulation) ≥ 200 % (XLPE, before aging) PASS
Cold bend test −15 °C, 4 h — no cracking PASS
Water absorption ≤ 1 mg/cm² (85 °C, 336 h, reference) PASS
Breakdown voltage (insulation) ≥ 20 kV/mm (reference) PASS
DC resistance of conductor @ 20 °C ≤ 0.749 Ω/km (Class 2 Cu, per core) PASS (GB/T 3956)
Dielectric loss (tan δ) measurement ≤ 1 × 10⁻³ @ 20 °C PASS (reference)
Spark test (during production) 6 – 10 kV (online), pinhole detection PASS
Thickness measurement (microscopic) eₙ = 0.7 mm; e_min ≥ 0.54 mm PASS
5.  Electrical Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.749 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.973 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 80–92 A (design ≈ 85 A) 5-core
Current rating — direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) ≈ 95–108 A (design ≈ 100 A) 5-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 2.50 kA reference
Frequency 50/60 Hz AC —
6.  Dimensional / Inspection Result
Item Design / Limit Measured (example)
Conductor construction Class 2, 7ר2.14 mm 7×2.14 mm
Conductor diameter ≈ 6.4 mm 6.35 mm
Insulation thickness (each core) 0.7 mm (min. 0.54 mm) 0.71 / 0.69 / 0.70 / 0.72 / 0.68 mm
Diameter over insulated core 7.8 mm 7.7 mm
Sheath thickness 1.6 mm (min. 1.3 mm) 1.62 mm
Overall cable diameter 16.5 – 19.5 mm (design ≈ 17.5 mm) 17.4 mm
DC resistance @ 20 °C (per core) ≤ 0.749 Ω/km 0.741 Ω/km
Approx. weight 400 – 520 kg/km (use ≈ 460 kg/km) 458 kg/km
1. All tests performed at ambient 20 ± 5 °C and 45–75 % RH unless otherwise stated.
2. Routine tests: withstand (3.5 kV / 5 min), conductor resistance, dimensional check. Type tests: 4.0 kV, partial discharge, hot-set, aging, mechanical (per IEC 60502-1).
3. Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.
4. Insulation thickness for 25 mm² class = 0.7 mm nominal (GB/T 12706.1-2020, Table 3); minimum = 0.7 − 0.16 = 0.54 mm.
5. 5×25 mm² = five equal cores (L1+L2+L3+N+PE); insulation colours per IEC 60446. Five core-thickness readings are recorded at inspection.
6. For low-smoke halogen-free → use WDZ-YJY 5×25; for fire-survival → NH-ZR-YJV / WDZN-YJY 5×25; for armoured → ZR-YJV22 5×25.

 

7.Cable Cross Section Structure

 

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems

 

ZR-YJV 5×25 mm² — Cable Cross-Section Structure (Schematic)
Five-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 5 Annealed copper, Class 2 stranded — 7 × 2.14 mm per core (7/2.14, 1+6), nominal 25 mm² per core — ≈ 6.4 (Ø per core) Current-carrying element; max DC resistance ≤ 0.727 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 5 Cross-linked polyethylene 1.2 ≈ 8.8 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Five insulated cores laid up in a pentagonal ring around dry filler; binder tape — ≈ 23.0 (Ø over lay-up, calc.) Round assembly; the 5th core is the PE (earthing) core
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.8 ≈ 26.6 (Ø overall, Mingda five-core) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
           
           
Key Dimensions & Properties
Overall diameter ≈ 26.6 mm Mingda five-core unarmored table    
Approx. cable weight ≈ 1503 kg/km Mingda 1503 (Al ≈ 697.4)    
Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV    
Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)    
Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter    
Flame-retardant class ZC (ZR) — GB/T 19666    
Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.

 

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems

 

8. Application. Sub-main distribution, small motor feeders and control circuits requiring a dedicated PE (earthing) core in one cable (TN-S style) — conduit, tray, trench, duct, trunking; indoor or sheltered outdoor.

 

9. Ordering. ZR-YJV 0.6/1 kV 5×25 + length/drum + marking; confirm against factory test certificate.

 

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems

 

 

8.2 – 8.6mm 25mm2 5 core armoured cable sheathed flexible  For Indoor Power Distribution Systems